DC Inverter Type (Wall-mounted) trouble shooting guide

Outdoor
No. Problems Indoor Error Code Solution
Display
1、Check whether there is short circuit or open circuit .
Indoor room 2、If the sensor is right, then check whether the sensor is in the right position and connected to PCB board properly.
1 temperature sensor E1 on-flash-on 3、Check whether there is any water or damp on sensor.
fault 4、If there is no standard sensor on hand, change the sensor with the neibouring sensor to see whether the fault is disappears or not, if it
disappears, the sensor needs to be replaced, if it remains, then change the PCB board.
1、Check whether there is short circuit or open circuit .
2、If the sensor is right, then check whether the sensor is in the right position and connected to PCB board properly.
Outdoor pipe 3、Check whether there is any water or damp on sensor.
2 temperature sensor E2 on-flash-flash 4、If there is no standard sensor on hand, change the sensor with the neibouring sensor to see whether the fault is disappears or not, if it
fault disappears, the sensor needs to be replaced, if it remains, then change the PCB board.
5、If E2 still occur after replacing the PCB and sensor, then it may be lack of gas, try vacuumizing the system and refill the gas.
6、If E2 still occur after refilling the gas, there may be some obstruction in the capillary, try replacing a new capillary and then refill the gas.
1、Check whether there is short circuit or open circuit .
Indoor pipe 2、If the sensor is right, then check whether the sensor is in the right position and connected to PCB board properly.
3 temperature sensor E3 on-flash-off 3、Check whether there is any water or damp on sensor.
fault 4、If there is no standard sensor on hand, change the sensor with the neibouring sensor to see whether the fault is disappears or not, if it
disappears, the sensor needs to be replaced, if it remains, then change the PCB board.
1、Observe wether the fan motor can run for a while before the error code, if so,mechanical jamming can be excluded;
indoor fan motor
4 E4 off-flash-on 2、Check wether the plug of the motor is well connected or not.
feedback fault
3、Changed a new PG motor,if the error code E4 remains,then change the PCB board .
1、Firstly, the IDU and the ODU should be connected properly.
2、Observe the ODU main PCB board, turn on the air conditioner, three lights are all lighted up then off and the relay pulls in. If not, it is power
indoor & outdoor
supply problem.
5 communication E5/5E flash-on-on
3.Connect the black signal line S to terminal N of ODU. Turn on the air conditioner, if "5E" is still be reported, the main PCB board of ODU need
fault
to be replaced.
4.Check the IDU main PCB board,replace it.
1. The three compressor wires should be red to U, blue to V, black to W, or it will lead to reversal of compressor. Reverse any two phases to see
whether the problem can be solved.
2. The voltage between L and N on the terminal board of the ODU must be within 10% tolerance of the rated voltage. Check the pressure of the
system.
6 IPM modular fault F1 flash-flash-on 3. Check whether the module board is well fixed on the radiator, whether the condensor and the evaporator are clean enough.
4. If the error code F1 is reported immediately after turn on the air conditioner, you should observe whether there is any damage around the
module board.Mrasure the resistance between each two wires of compressor,it should be same and very small. Then check the insulation of
three compressor wire to the ground wire. Check the reactor.
5. Change a new module board instead,if the fault code disappears,it's the problem of the module board.
1、 test whether the power supply voltage is fluctuate wildly or the voltage is too low (less than alternating current 135 v);
2、 reactor is one of the core parts in PFC, please check whether there is any damage to the reactor itself, whether the connecting wire of reactor
well connected which causes the malfunction of PFC. Reactor can not be removed and replaced by short circuit directly;
3、if "PFC protection fault" is reported immediately after the start up of the air conditioner, it can be basically defined as a substantive fault which
has nothing to do with the power supply voltage and the system pressure.Please observed whether there is obvious lighting damaged device
around PFC board;
4、Test whether the power supply of 15 V, 5 V (3.3 V) on PFC board is stable to eliminate the problem of supply of external main control board
7 PFC modular fault F2 flash-flash-off which causes the malfunction of PFC fault;
5、 Normal PFC board can be used to replace the original one for testing. If the test is normal after replacing the PFC board, it indicateds that the
original PFC board is damanged;
6、There exists probability that there are problems in power supply of 15V or 5V of module board that leads to the malfunction of the control
power of PFC board
7、 Some module board integrates PFC function and compressor driving function together, then the intergrated module board can be changed
directly;

Compressor
8 F3 flash-on-flash Refer to F1 fault
operation fault
Exhaust
1.lack or excess refrigerant may lead this problem.
9 Temperature F4 flash-off-flash
2.Check whether the exhaust tem sensor is short circuit or open circuit.
sensor fault
Compressor shell
10 F5 off-on-off The test points are the same as that of common sensors.
temperature
Outdoor ambient
11 F6 off-flash-flash The test points are the same as that of common sensors.
temp sensor fault
1、check the power voltage, it must be within 10% tolerance of the rated voltage.
Over/under voltage 2、The voltage between P-N on module board is above 280VDC. If the voltage is lower, the PFC circuit is damaged;
12 F7 off-off-on
protection 3、 If "F7" is reported once the air conditioning is powered on and the power voltage is not lower than 150 V measured by multi-meter, it may be
the problem of main PCB of ODU.
1.Ccheck whether the communication connecting wire ( mostly 4 core) between module board and main control board is loose or the cable is
Outdoor modular
loose.
communication
2. use a multi-meter to measure whether the power supply introduced from main control board is normal, especially whether the power of 5V has
fault (only available
13 F8 flash-on-off been led to module board. Find "5V" and "GND" on the module board and test whether the voltage of 5V on the module is normal;
for outdoor main
3、 Use normal module board to replace the module board on the malfunctioned air conditioning board. When the external machine is powered
controller with 2 or
on, if communication failure disappears, it indicates that the problem is on the original module board, if there still exists communication failure,
3 boards)
the external main control board should be replaced;
Outdoor E²PROM EEPROM chips are usually welded with the external main control board together. If "external machine EEPROM fault" is reported,replace the
14 F9 flash-off-on
fault main control board directly can fix it;
1.DC motor usually runs softly. Observe whether the speed of fan is accelerated to the highest speed when started, if so, the speed feedback
Outdoor DC Fan signal has not been received by main controller board;
15 F0 flash-off-off
motor fault 2 .Check the connection between the DC motor and terminal board.
3.change a new motor, if fault is still reported, then replace the main PCB board.
1、check if the condensing pressure is too high.
Anti-overload
2、If the pressure is normal, then the outdoor pipe temperature sensor may be broken, replace a new sensor.
16 protection in P4 on-off-on
3、If the pressure is too high, check if the condenser is gathered with much dust; check if any obstruction in condenser ventilation; check if
cooling mode
outdoor fan motor is running normally; check if any obstruction in the gas circulation system.
1、check if the compressor discharge pipe is very hot. If not, then discharge temperature sensor may be broken, replace a new sensor.
Compressor
17 P5 / 2、 if the compressor discharge pipe is very hot, then check if outdoor fan motor is running normally; if any obstruction in condenser;check if any
Exhaust protection
gas leakage; check if any obstruction in the gas circulation system or the air is not completely expelled.
Indoor anti- 1、check if the condensing pressure is too high (normally more than 39bar)
overheating 2、If the pressure is normal, then the indoor pipe temperature sensor may be broken, replace a new sensor.
18 P6 off-on-on
protection in 3、If the pressure is too high,then check if the indoor fan motor is running normally; check if any obstruction in air-inlet;check if too much dust
heating mode gathered on the filter; check if any obstruction in the gas circulation system.
Indoor anti-freeze 1、check if the resistance of indoor pipe temperature is normal.
19 protection in P7 on-off-off 2, check if the indoor fan motor is running normally; check if any obstruction in air-inlet;check if too much dust gathered on the filter; check if any
cooling mode obstruction in the gas circulation system or any gas leakage.
1、check if the compressor running current is too high; if the current is normal, then outdoor control board may be broken, replace a new one.
Outdoor over-
20 P8 off-off-flash 2、check if the system pressure is too high; if the compressor is running normally; if any obstruction in the condenser; if indoor/outdoor fan motor
current protection
is running normally.