ekorsys units:
automation, control, protection, metering and
communications of the electric network
ekor.wtp
Multifunctional protection unit
for wind turbine generators
Reliable innovation. Personal solutions.
www.ormazabal.com
ekor.wtp ekorsys units:
Multifunctional protection unit automation, control, protection, metering and
for wind turbine generators communications of the electric network
Preface Design
The ekor.wtp dual power and self-powered The constantly increasing demands in wind
I II
protection, metering and control unit farms bring new requirements for both
12
combines a wide range of functionalities to the medium-voltage switchgear and the
make it a complete protection unit for wind associated protection functions.
turbines. The ekor.wtp range is designed to respond 8
1
to the changing demands of wind turbines, 7
throughout all stages of their life cycle.
2 9
Characteristics 4
6
11
10
In-cubicle integrated Manufacture 3
5
solution ● Solution fully assembled and factory tested
● Factory test reports
● Equipment installed, assembled and
tested at the factory Simplified commissioning
● Minimisation of wiring errors and ● Compact solution pre-tested at factory
commissioning time ● Factory-installed current transformers I. ekor.wtp
Modular functionality around bushing
● Self-powered protection features ● Fault and events records 1 Display 4 ESCAPE button
● Scalable automatisms Operation and maintenance
2 Menu keypad 5 Configuration
● Remote control and communications ● Operation and remote control port
Reliability ● Access via web server 3 SET key 6 Status LED
● Optimisation of mean time between ● Fault and events records
failures (MTBF) ● Disturbance recorder II. Switchgear
● Programmable vs. cabled automatisms ● Medium-voltage measuring
7 Circuit-breaker 10 Current
● Functional at low temperatures Interface transformers
Personal safety ● View system files as a file server 8 Earthing switch 11 MV cable voltage
● Three local or remote viewing modes: sensor (ekor.evt)
● Programmable automation
● Keypad-display 9 Voltage indicator:
12 MV busbar
● Alarms ekor.ivds
● Software ekor.soft-xml (ekor.wtp-100) voltage sensor
(ekor.evt)
Approach: wind turbine ● Webserver
● Non-proprietary configuration software
Functionality ● Configuration via web (ekor.wtp-200) or
● Wind turbine protection: xml file (ekor.wtp-100)
● Self-powered relay for protection in each
earthing system
● Tripping acceleration in the event of
internal fault
● High-reliability tripping
● Tripping block with starting current ANSI functions diagram
● Watchdog
ekor.wtp protection functions
● Efficiency in severe environments
● Scalable, compact solution
● Conformity with the grid code:
ekor.wtp-110
● Sequential reconnection
ekor.wtp-120 +
● Voltage dips ekor.wtp-210 + +
ekor.wtp-220 + + +
● Customised solutions:
Optional
● Disconnection / reconnection at low temp.
● Automation of events in extreme weather Measurements
conditions I E (P+, P-, Q1,…,Q4)
● Integration with other devices and V Phi (φ)
exchange of information P T
Q
ekorsys units: ekor.wtp
automation, control, protection, metering and Multifunctional protection unit
communications of the electric network for wind turbine generators
Technical characteristics
ekor.wtp ekor.wtp-110 ekor.wtp-120 ekor.wtp-210 ekor.wtp-220
General characteristics
Self-power/110-230 Vac ± 20%/
Dual power
24-125 Vdc ± 20 %
Current analog inputs 4 + Io (1)
4 + Io (1)
4 + Io (1)
4 + Io(1)
Voltage analog inputs VbusbarMV Vgenerator 3 + Vo (1)
3 + Vo (1)
3 + Vo + 3 + Vo
(1) (1)
3 + Vo(1) + 3 + Vo(1)
External fail safe trip inputs 2 (2)
2 (2)
2 (2)
2(2)
Configurable digital inputs/outputs 0/2 0/2 8/4 8/4
Settings groups 1 1 2 2
Protection functions
50-51[1]-51[2] 50N-51N[1]-51N[2] (2) (2) (2) (2)
50NS-51NS[1]-51NS[2] (2)
(2)
(2)
(2)
67 67N (2)
(2)
(2)
67NS (2)
(2)
(2)
49 46T-46I 46BC
27T-27I 59T-59I 59NT-59NI
Wind turbine applications
High-reliability alarms / trips 2 (fail-safe) 2 (fail-safe) 2 (fail-safe) 2 (fail-safe)
Watchdog (WD)
Trip blocked by 2nd harmonic (2) (2) (2) (2)
Trip acceleration (2) (2) (2)
Sequential reconnection automation
Voltage dips management (according to grid code)
Safety interlocking
Temperature automation
Measuring
Current
Voltage Active/reactive power
Energy P+, P-, Q1,…,Q4
Phi angle (φ)
Temperature
Control and supervision
Circuit breaker control & operation
Blocking by logic
Tripping coil supervision (TCS) Voltage presence/absence
Events records 4000 4000
Fault records 10 10 10 (advanced) 10 (advanced)
LED/ Configurable LED 4/0 4/0 8/2 8/2
Physical media
1 x micro-USB 1 x micro-USB
Front ports 1 x micro-USB 1 x micro-USB
1 x RJ-45 1 x RJ-45
Side ports 2 x RJ-45 2 x RJ-45
Serial communications(3) (side RS-485 x 1)
MODBUS-RTU
PROCOME-IEC 60870-5-103
DNP.3 Series
Ethernet communications (IP)(4) (Side Ethernet x1)(5)
MODBUS-TCP
DNP.3 TCP
IEC 60870-5-101
IEC 60870-5-104
IEC 61850
Notes: Configuration:
(1)
Calculated (3)
Check with Ormazabal other protocols (5)
Front port for local web access Standard
(2)
Self-powered (4)
Check with Ormazabal your IP protocol needs Optional
www.ormazabal.com
CA-212-EN-1903