Data Sheet: Tempower 2 Acb: Types: AR208S, AR212S, AR216S, AR220S
Data Sheet: Tempower 2 Acb: Types: AR208S, AR212S, AR216S, AR220S
Data Sheet: Tempower 2 Acb: Types: AR208S, AR212S, AR216S, AR220S
6
AR2 AR212S AR216S AR220S
Standard Standard Standard Standard
AMPERE RATING(A) 800 1250 1600 2000
RATED CURRENT (max) [In](A) JIS 12 ,IEC, EN, AS 800 1250 1600 2000
1 2 NEMA, ANSI 800 1250 1540 2000
Marine 800 1250 1600 2000
NEUTRAL POLE AMPERES FRAME (A) 800 1250 1600 2000
NUMBER OF POLES 3 4 3 4 3 4 3 4 3 4
RATED PRIMARY CURRENT OF OVER–CURRENT 200 400 400 400
RELEASE [ICT](A) 400 800 800 800
• for general feeder circuit use 800 1000 1250 1250
1250 1600 1600
2000
RATED CURRENT OF OVER–CURRENT RELEASE(A) = In <
100 < = 200 200 <
= In <
= 400 = In <
200 < = 400 = In <
200 < = 400
• for generator protection use 200 < In <
= 400 400 < In <
= 800 400 < In <
= 800 400 < In <
= 800
[In] is generator rated current. 400 < In <
= 800 630 < In <
= 1250 630 < In <
= 1250 630 < In <
= 1250
AC RATED INSULATION VOLTAGE 800 < In < 1600 800 < In <
= 1600
1000 < In <
= 2000
AC RATED INSULATION VOLTAGE [Ui](V. 50/60Hz) 1000 1000 1000 1000
RATED OPERATIONAL VOLTAGE [Ue](V. 50/60Hz) 690 690 690 690
AC RATED INSULATION VOLTAGE [kA sym rms] /MAKING CAP [kA peak]
JIS 12 , IEC, EN, AS AC 690V 5 50/105 50/105 50/105 50/105
[Ics= Icu] 440V 65/143 6 65/143 6 65/143 6 65/143 6
NEMA AC 635V 42/96.6 42/96.6 42/96.6 42/96.6
ANSI 508V 50/115 50/115 50/115 50/115
254V 65/149.5 65/149.5 65/149.5 65/149.5
7 DC 600V 8 40/40 40/40 40/40 40/40
250V 40/40 40/40 40/40 40/40
NK 9 AC 690V 50/115 50/115 50/115 50/115
450V 65/153 6 65/153 6 65/153 6 65/153 6
LR, AB, 9 AC 690V 50/115 50/115 50/115 50/115
GL, BV 450V 65/153 6 65/153 6 65/153 6 65/153 6
1 : Values in open air at 40°C (45°C for marine applications). 9 : Applicable to only 3 pole ACBs.
2 : Values of AR208S, AR212S, AR216S for draw-out type with horizontal ter- 10 : For vertical terminals or horizontal terminals.
minals, Values of the other ACBs for draw-out type with vertical terminals. 11 : These weights are based on normal specifications with the OCR and
3 : For 2 pole ACBs use outside poles of 3 pole ACB. standard accessories
4 : 4poles ACBs without Neutral phases protection can not apply IT earthing 12 : Comply with JIS C 8201-2-1 Ann.1 Ann.2
system.
5 : Contact TERASAKI for the details.
6 : For 500V AC. # : Contact TERASAKI for the ratings.
7 : AGR OCRs can not be used for DC. Please contact TERASAKI for DC Note: When the INST trip function is set to NON, the MCR function should be
application. enabled, otherwise, the rated breaking capacity is reduced to the rated
8 : A special version of the ACB is required above 250V DC. Contact latching current.
Terasaki for details.
Page 1 of 7
DATA SHEET: TEMPOWER2 ACB
Types: AR208S, AR212S, AR216S, AR220S,
L-characteristic for general feeder circuits (Type AGR-11BL, 21BL, 31BL)
Specifications
Setting range of protection functions
Protection functions Setting range
Adjustable long time-delay trip characteristics
LT
Pick-up current [IR] (A) [In]~(0.8 – 0.85 – 0.9 – 0.95 – 1.0 – NON) ; 6 graduations
• Non tripping when load current Ö ([IR]~1.05). • Tripping when ([IR]~1.05) É load current Ö ([IR]~1.2)
Time-delay [tR] (s) (0.5 – 1.25 – 2.5 – 5 – 10 – 15 – 20 – 25 – 30) at 600% of [IR]; 9 graduations
Time-delay setting tolerance (%) ±15% +150ms – 0ms
Adjustable short time-delay trip characteristics
ST
Pick-up current [Isd] (A) [In]~(1 – 1.5 – 2 – 2.5 – 3 – 4 – 6 – 8 – 10 – NON) ; 10 graduations
Current setting tolerance (%) ±15%
Time-delay [tsd] (ms) Relay time 50 100 200 400 600 800 ; 6 graduations
Resettable time (ms) 25 75 175 375 575 775
Max. total clearing time (ms) 120 170 270 470 670 870
Adjustable instantaneous trip characteristics
INST or MCR (For AGR-11B, INST only)
Pick-up current [I i] (A) [In]~(2 – 4 – 6 – 8 – 10 – 12 – 14 – 16 – NON) ; 9 graduations
Current setting tolerance (%) ±20%
Adjustable pre-trip alarm characteristics
PTA
Pick-up current [IP1] (A) [In]~(0.75 – 0.8 – 0.85 – 0.9 – 0.95 – 1.0) ; 6 graduations
Current setting tolerance (%) ±7.5%
Time-delay [tP1] (s) (5 – 10 – 15 – 20 – 40 – 60 – 80 – 120 – 160 – 200) at [I P1] or more; 10 graduations
Time-delay setting tolerance (%) ±15% +100ms – 0ms
Adjustable ground fault trip characteristics
GF Note: Set [Ig] to 1200A or less.
Pick-up current [Ig] (A) [ICT]~(0.1 – 0.2 – 0.3 – 0.4 – 0.6 – 0.8 – 1.0 – NON) ; 8 graduations
Current setting tolerance (%) ±20%
Time-delay [tg] (ms) Relay time 100 200 300 500 1000 2000 ; 6 graduations
Resettable time (ms) 75 175 275 475 975 1975
Max. total clearing time (ms) 170 270 370 570 1070 2070
Ground fault trip characteristics on line side
REF (AGR-21B, 31B only)
Pick-up current [IREF] (A) [ICT]~(0.1 – 0.2 – 0.3 – 0.4 – 0.6 – 0.8 – 1.0 – NON) ; 8 graduations
current setting tolerance (%) ±20%
Time-delay (s) Inst
N-phase protection characteristics
NP
Pick-up current [IN] (A) [ICT]~(0.4 – 0.5 – 0.63 – 0.8 – 1.0) ; Factory set to a user-specified value for AGR-11BL.
• Non tripping when load current Ö ([IN]~1.05). • Tripping when ([IN]~1.05) É load current Ö ([IN]~1.2)
Time-delay [tN] (s) Tripping at 600% of [IN] with LT time-delay [tR]
Time-delay setting tolerance (%) ±15% +150ms – 0ms
Phase rotation protection characteristics
NS (AGR-21B, 31B only)
Pick-up current [INS] (A) [In]~(0.2 – 0.3 – 0.4 – 0.5 – 0.6 – 0.7 – 0.8 – 0.9 – 1.0) ; 9 graduations
current setting tolerance (%) ±10%
Time-delay [tNS] (s) (0.4 – 0.8 – 1.2 – 1.6 – 2 – 2.4 – 2.8 – 3.2 – 3.6 – 4) at 150% of [INS] ; 10 graduations
Time-delay setting tolerance (%) ±20% +150ms – 0ms
Adjustable earth leakage trip characteristics
ELT (AGR-31B only)
Pick-up current [IΔR] (A) 0.2 – 0.3 – 0.5 (Medium sensitivity) or 1 – 2 – 3 – 5 – 10 (Low sensitivity)
Current setting tolerance Non operate below 70% of [IΔR], Operate between 70% and 100% of [IΔR].
Time-delay [tΔR] (ms) Relay time 100 150 300 500 800 1500 3000 ; 7 graduations
Resettable time (ms) 50 100 250 450 750 1450 2950
Max. total clearing time (ms) 250 300 450 650 950 1650 3150
Undervoltage alarm characteristics
UV (AGR-31B only)
Recovery setting voltage (V) [Vn]~(0.8 – 0.85 – 0.9 – 0.95) ; 4 graduations
Recovery voltage setting tolerance (%) ±5%
Setting voltage (V) [Vn]~(0.4 – 0.6 – 0.8) ; 3 graduations
Voltage setting tolerance (%) ±5%
Time-delay (s) 0.1 – 0.5 – 1 – 2 – 5 – 10 – 15 – 20 – 30 – 36 ; 10 graduations
Time-delay setting tolerance (%) ±15% +100ms–0ms
Control power AC100 – 120V ⎞ DC100 – 125V ⎞ DC24V ⎞
Common Common Common
AC200 – 240V ⎠ DC200 – 250V ⎠ DC48V ⎠
Power consumption: 5 VA
__ : Default setting
Page 2 of 7
DATA SHEET: TEMPOWER2 ACB
Types: AR208S, AR212S, AR216S, AR220S,
PROTECTION CHARACTERISTICS
3
N-phase protection LT current setting range
hour
2
current setting range
PTA current setting range
1
40
ST current setting range
20
GF current setting range
INST current setting range
10
minute
6
4
1
40
Operating time
20
Max
10
6
4
2
second
1
800ms
0.6
0.4 400ms
0.02
0.01
0.006
7
8
9
10
15
20
30
40
50
60
70
80
90
100
150
200
60
70
80
90
100
125
150
200
250
300
400
500
600
700
800
900
1000
1500
2000
2500
3000
Page 3 of 7
DATA SHEET: TEMPOWER2 ACB
Types: AR208S, AR212S, AR216S, AR220S,
P
C : ACB Front cover center line
Terminal size
Type t1 t2 t3 W
AR208S 10 10 15 17.5
AR212S 10 10 15 17.5
AR216S 20 15 25 22.5
AR220S 20 15 25 ——
CP
Maintenance
rear panel cut 158.5 158.5(3P) space
243.5(4P)
front panel cut
CP
N
335 ¶2
405
329
460
490
500
R
11
6
50
42.5
33
20
30
250
Mounting holes
Page 4 of 7
DATA SHEET: TEMPOWER2 ACB
Types: AR208S, AR212S, AR216S, AR220S,
P
C
N
15
35
35
Front connections
515
35
15
t3
318 25
380 50
2-ø11
CONNECTED position
TEST position Control circuit terminal cover
(optional)
ISOLA
TED position
2-ø20 AR208S
14 21 AR212S
Lifting AR220S,
AR216S N
hole 35 35 conductor overlap. max 85 85 85
17 199
15 15
18
ON-OFF u
btton cover 2-ø11
15.5
W
2525
12
25
42.5
Vertical terminals
14.5 14.5
W
9 32
149
W
M8 screw
earth ter minal
25
2525
150.5
W
32
15.5
40
3-ø11 7
t2
27
94 141 110 21
9 345 40 29
265 385 140(3P) ¶ 1
225(4P)
35 conductor overlap. max
15
N
52
25
85 85 85
2-ø11
t1
174
Horizontal terminals
138
Draw-out arm
385 (comes out when breaker is drawn out)
Page 5 of 7
DATA SHEET: TEMPOWER2 ACB
Types: AR208S, AR212S, AR216S, AR220S,
CP
P
C : ACB Front cover center line
27
305.5
208.5 (3P)
208.5 293.5 (4P)
CP
CP 175(3P)
240 240(3P) 175
325(4P) 260(4P)
460
490
335 ¶2
329
33
238
30
250
100
180 180(3P)
Maintenance space 265(4P)
82
Panel cutout
165
Terminal size
Type t1 t2 t3 W
AR208S 10 10 15 17.5
AR212S 10 10 15 17.5
AR216S 20 15 25 22.5
AR220S 20 15 25 —— 165 165(3P) 4-ø14
250(4P)
Mounting holes
¶2: Panel cut should be 339 mm not 335 mm when the door flange
is used. Refer to page 41.
• N represents the neutral pole of 4-pole ACBs.
The neutral pole is positioned to the right as standard when viewed from the front of the
ACB. However, the neutral pole can be customized so that it is positioned to the left.
• For the outline drawing for the version with earth leakage tripping, contact us.
Page 6 of 7
DATA SHEET: TEMPOWER2 ACB
Types: AR208S, AR212S, AR216S, AR220S,
15
35
mounting
hole ø14 2-ø11
Front connections
580
227 6
515
305.5
10.5
65
25 25
12
25
Vertical terminals
14.5 14.5
W
149
W
17
329
2525
25
9
t2
W
150.5
15.5
35
33
35
2-ø11 3-ø11
M8 screw
earth terminal
Panel
82 165 118
365
15
52
25
2-ø11
N
85 85 85
t1
Horizontal terminals
174
138
82 165 118
365
Page 7 of 7