Dry-Type Transformer: High Reliability Maintenance-Free Environmentally Friendly
Dry-Type Transformer: High Reliability Maintenance-Free Environmentally Friendly
Dry-Type Transformer: High Reliability Maintenance-Free Environmentally Friendly
High Reliability
Maintenance-free
Environmentally Friendly
Dry-type Transformer
Features of Products
1 2
1. Lifting lug 3
2. LV terminal
4
3. Core
4. HV terminal
5
5. HV winding
6
6. Tapping terminal
7
7. LV windings
8. Base
1
Technical Specifications
■■ Voltage Range: Up to 35kV(including dual voltages)
■■ Capacity: 30 to 40000kVA(AN)
■■ Taps: ±2x2.5% are standard (other options available)
■■ Frequency: 50Hz or 60Hz
■■ Phases: Single or Three-Phase
■■ Vector Group: Dyn11, Yyn0 or others
■■ Cooling: AN or AF
■■ Insulation Class: F or H
■■ Insulation Level:
■■ Voltage 6/10kV 20kV 35kV
■■ P.F.test 35kV 50kV 70kV
■■ B.I.L.test 75kV 125kV 170kV
■■ Protection Enclosure Grade: IP00, IP20, IP23 or as
required
■■ Service Condition: Altitude, not exceeding 1000m.
Ambient temperature, not exceeding 40℃
■■ Standards:
■■ GB1094《Power Transformer》
■■ IEC60076《Power Transformer》
■■ Customizable according to special customer demands.
S C B
High-voltage Level(kV)
Rated Capacity Level(kVA)
Code of performance level (Design code)
LV foil-type winding
Resin-insulated
dry-type transformer
Three-phase
2
Dry-type Transformer
Technical Data
Voltage class 10kV, 30 up to 2500 kVA
Voltage Power Uk P0 Pk at Lwa Length Width Height Total Weight Roller
Model Class [kVA] [%] [W] 120°C[W] [(db(A)] [mm] [mm] [mm] [kg] distance
(kV) IP00/IP20 IP00/IP20 IP00/IP20 IP00/IP20 [mm]
SC10-30/10 30 4 190 710 50 900/1650 760/1450 1000/2000 380/680 550
SC10-50/10 50 4 270 1000 55 1000/1650 760/1450 1100/2000 560/860 550
SC10-63/10 63 4 320 1170 55 1100/1650 760/1450 1100/2000 600/900 550
SC10-80/10 80 4 370 1380 55 1100/1650 760/1450 1100/2000 690/990 550
SCB10-100/10 100 4 400 1570 55 1100/1650 760/1450 1150/2000 780/1080 550
SCB10-125/10 11 125 4 470 1850 55 1200/1650 760/1450 1200/2000 1010/1310 550
SCB10-160/10 10.5 160 4 540 2130 58 1200/1650 760/1450 1200/2000 1120/1420 660
SCB10-200/10 10 200 4 620 2530 58 1300/1650 760/1450 1200/2000 1360/1660 660
SCB10-250/10 6.3 250 4 720 2760 58 1350/1950 760/1600 1250/2000 1480/1830 660
SCB10-315/10 6 315 4 880 3470 60 1350/1950 760/1600 1250/2000 1550/1900 660
SCB10-400/10 400 4 980 3990 60 1350/1950 760/1600 1250/2000 1680/2030 660
SCB10-500/10 500 4 1160 4880 60 1350/1950 760/1600 1250/2000 1900/2250 660
SCB10-630/10 630 4 1340 5880 62 1600/2350 850/1650 1400/2000 2740/3240 660
SCB10-630/10 630 6 1300 5960 62 1600/2350 850/1650 1400/2000 2400/2900 660
SCB10-800/10 800 6 1520 6960 64 1600/2350 850/1650 1500/2000 2950/3450 820
SCB10-1000/10 1000 6 1770 8130 64 1700/2350 850/1650 1550/2000 3320/3820 820
SCB10-1250/10 1250 6 2090 9690 65 1700/2350 850/1650 1650/2000 3770/4270 820
SCB10-1600/10 1600 6 2450 11730 66 1900/2650 850/1850 1750/2500 4680/5230 820
SCB10-2000/10 2000 6 3050 14450 66 1950/2650 1200/1850 1800/2500 5430/5980 820
SCB10-2500/10 2500 6 3600 17170 68 2100/2650 1200/1850 1950/2500 6580/7130 1070
3
Outline drawings
REAR VIEW (LV SIDE) LEFT SIDE VIEW FRONT VIEW (HV SIDE)
HV terminal
4
Dry-type Transformer
Manufacturing
CORE
5
Manufacturing
CORE
6
Dry-type Transformer
Manufacturing
WINDINGS
Computer-controlled HV automatic winding machines Eaton also produces LV copper-foil windings. The advantage
constant tension and automatic wire laying function were of foil winding is that the current density can distribute itself
imported from STOLLBERG, a German company. The freely along the width of the conductor and have strong short-
HV windings are made of copper electromagnetic wire circuit resistance. LV foil is closely through highly-purified
and insulated with fiberglass mats through segmented round-edge foil strip and insulating material pre-saturated in
cylindrical structure, and thus with a low voltage between epoxy resin. LV foil winding machine is the newest product
layers and strong over-voltage resistance. The winding of of STOLLBERG. Controlled by a computer module, the
larger capacity has a heat-radiating air passage to make a machine can maintain constant tension, wipe off any debur
good heat radiation. and rectify deviations automatically.
7
Manufacturing
CASTING
The winding is moved into the vacuum casting chamber cured in an oven to form strong solid coils under high
of epoxy resin vacuum casting equipment to dry after temperature.
preheating, the moisture/gas in the insulation are removed We adopt the casting equipment introduced from
in the vacuum casting procedure. Meanwhile, the imported HUBERS, a German company. It applies the patented
chemical materials (e.g. epoxy resin and hardener) are technologies (e.g. thin-film deaeration and static mixing).
continuously prepared in the separate vessels. After The static mixing technology is significantly superior to
the preparation process is finished, all of the materials dynamic one in the consistent physical/chemical property
are pumped into a static mixer at the ratio preset by the of material mixture (e.g. viscosity and chemical reaction
precise computer measuring system, and then cast into degree).
the molds. After the completion of casting, the coils are
8
Dry-type Transformer
Optional Accessories
Steel-plate protective enclosure
The steel-plate enclosure is processed from
high-quality cold-rolled steel plate through three
numerical control equipment (i.e. numerical
control cutter, numerical control puncher
and numerical control plate bender). The
surface of enclosure panel is treated through
phosphorization and plastic spraying, and thus
possesses a very high corrosion resistance. The
steel-plate enclosure has various advantages
(e.g. beautiful exquisite appearance, good
ventilation, simple fast installation, and
convenient transportation). Its assembled
structure has a high mechanical strength. It can
be easily assembled on the scene, and there are
access door and ventilating hole in its front and
at its back. The color of steel-plate enclosure
is computer gray (RAL7032) or customizable
according to customer demand.
9
Optional Accessories
Air-cooling system
The transformer can be cooled by two modes:
air natural cooling (AN) and air forced cooling
(AF). Forced-air AF output of the transformer is
up to 140% of the self-cooled rating, should be
used only for emergency non-recurring loads,
and but is not recommended for long-term
running.
Temperature Controller
The temperature is controlled by means of
sensor provided on each transformer. The
sensor (Pt100) are installed in the LV winding.
The digital controller shows the operating
temperature of each LV winding, sequentially.
The temperature controller performs the
following functions of three-phase winding
during transformer running: automatically switch
the cooling fans on at 100℃ and off at 80℃ , it
will send an over-temperature alarm at 130℃ ,
and will send emergency shutdown trip signal at
150℃ . and sensor fault alarm.
10
Dry-type Transformer
Quality Control
Eaton Electric quality control was carried out
according to ISO9001 quality management
standard and production standard, there are
many quality engineers working for IQC, PQC,
FQC and OQC. All product should be inspected
and tested by operator, auditor and inspector
according to the production standards and
requirements before it been transported to the
next production process, the failed product will
be rejected. The product's quality and reliability
are ensured by our strict management procedure,
serious working attitude and advanced testing
equipments.
Transformer Inspection and Test Center
Impulse Test System Transformer Load Loss Test System Micro-ohm Meter WR50-12
11
Customer Reference List
12
Eaton is a power management company with 2015 sales of $20.9
billion. Eaton provides energy-efficient solutions that help our customers
effectively manage electrical, hydraulic and mechanical power more
efficiently, safely and sustainably. Eaton has approximately 97,000
employees and sells products to customers in more than 175 countries.
For more information, visit www.eaton.com.cn