Description J: Software: RK 4004-0003 F - ZG
Description J: Software: RK 4004-0003 F - ZG
1. Function 2
2. Type overview 7
3. Assembly 7
4. Installation 8
4.1 Terminal assignments X 1 to X 21 9
4.2 Setup operation 10
5. Parameters 13
5.1 Parameter list 13
5.2 Explanation of parameters 20
5.3 "Three position controller" upgrade 57
6. Setting values 59
7. Technical data 61
BEA--250482-EN-03
1. Function
1.1 Purpose Controller card RK 4004 is used to control a DC actuator with speed
and position feedback. For this purpose a current controller, speed
controller, position controller and motor output stage are integrated
on the card. Appropriate sensors may be attached via a CAN bus for
the position controlling of running webs and following-up of tools.
Operation is via a command device with text display and/or a digital
input-output card.
Keys:
Data memory
"Setup"
"Decrease value"
"Increase value"
Terminals
U Page 2
1.3 Operating principle The operating principle depends on the mode selected. The following
operating modes are possible:
Actuator manual:
In manual mode the actuator may moved to the left or right to a re-
quired position. The speed may be set in the appropriate parameter.
Automatic mode:
In automatic mode the web or tool is guided to the set position. Pre-
requisite to guiding is that guider lock is released.
Guider lock in automatic mode:
Guider inhibiting is only effective in automatic mode and may be acti-
vated on controller card RK 4... or via an interface.
Web offset:
A web offset may be set in automatic mode. A web offset means that
the set position value may be changed positively or negatively.
In the case of fixed sensors or a single motor support beam with two
positioning carriages, web offsetting is limited to 75 % of the sensor
measuring range. On the remaining applications with support beams
the web offset may be extended to include the entire support beam
position range.
Oscillation:
In automatic mode a oscillating set value is additionally added to the
set position value. The oscillating mode, period and path may be set
in the appropriate parameters or via a command station. In the case
of fixed sensors oscillation is only possbile within 75 % of the
measuring range.
Park sensor:
When using a support beam the positioning carriage along with the
sensor/tool located on it are moved (outwards) to the outer end posi-
tion.
U Page 3
1.4 Control structure with In a control structure for proportional actuators the web or tool actual
constant controlling for position value is compared with the required set position value and, in
proportional actuators the event of a deviation, it is transmitted to a P position controller as a
control difference. The resultant set speed value is compared with the
actual speed value and transmitted to the PI speed controller. The lat-
ter emits a pulse width-modulated signal at the output stage.
The following are available as proportional actuators:
DRS pivoting frame, VWS turning rod, SRS steering roller, WSS win-
ding station, SVS push roller SVS and VSS positioning and follow-up
controller.
U Page 4
1.5 Control structure with In a control structure for a support beam a set speed value is deter-
constant controlling for mined on the basis of the sensor signal via the P position controller
support beams that is transmitted to the speed controller. The resulting set speed va-
lue is compared to the actual speed value and transmitted to the PI
speed controller. The latter emits a pulse width-modulated signal at
the output stage. In "search for edge" or "hybrid" modes the sensor is
driven to follow-up the web edge.
Available as proportional actuator:
Support beam VSS
U Page 5
1.6 Control structure with con- In the case of a control structure for integral actuators the web actual
stant controlling for inte- position value is compared to the required web set position value
gral actuators and, in the event of a deviation, it is transmitted as a control diffe-
rence to a P position controller. The latter provides the necessary set
position value for the actuator. The current actual actuator position
value is compared to the required set position value and transmitted
as a control difference to the actuator position controller. The latter
generates the set speed value which is compared to the actual speed
value, the difference being fed to the PI speed controller which emits
a pulse width-modulated signal at the output stage.
Available integral actuators:
SWS segmented roller guider, VGA pivoting roller, BCS edge and
width spreader
U Page 6
U Page 7
X5 Right X6 Left
X 12 CAN connection
digital digital
without LED display
X 15 Fan sensor sensor
for internal device
networking
X7 CAN connection
with LED display
for CAN device
X 21 Supply voltage connector
for further E+L
X 11 SPI bus
modules
X9 serial bus
X 13 Supply voltage
for further E+L
modules X8 Analogue card
AK 4002
(only when ana-
logue sensors are
X1 Operating volta-
used)
ge
X 14 External configu-
ration adapter
X 10 Optical incre-
mental encoder
U Page 8
U Page 9
4.2 Setup operation The three keys and the displays are used as the setup control panel.
The key assignment (setup, decrease/increase value) is indicated in
the illustration opposite. The following applications are possible:
4.2.1 Setting the controller card device address
4.2.2 Current error display
4.2.3 Setting parameters
4.2.1 Set controller card Prior to commissioning the device address of controller card
device address RK 4004 must be checked and changed as necessary.
➜ Press both keys "decrease value" and "increase value" at the
same time. The group number is indicated via the "decrease value
" key and the device number via the "increase value" key. If both
keys are held down for longer than approx. 4 seconds the device
address will start to flash.
➜ If the device address deviates from the required address it may be
changed via the keys.
If none of the keys are actuated the device address will be saved
after approx. 20 seconds have elapsed and a software reset is
triggered.
U Page 10
4.2.2 Current error display In normal circumstances the display on the controller card indicates
only three dots. These three dots signal that no errors are present .
A flashing number signals an error. The number indicates the error
code. If several errors are present at the same time, the error with the
highest priority will be indicated. If this error is no longer present, the
display will indicate the next error.
Below is a list of possible errors:
4.2.3 Output X 20.4 In the case of certain errors (see table) output X 20.4 is switched to
"0". The internal switch on the controller card that furnishes a con-
nection to ground is opened.
The following circuit variants are recommended:
U Page 11
4.2.3 Parameter setting All parameters in the CAN network may be selected and changed by
the three keys. The following flow diagram illustrates basic operation
with the setup editor:
no
Select
further ja
parameters
no
Quit setup mode: select device number X.5, then
press and hold down the setup key and select +
parameter 3 by pressing the increase value key.
Release the setup key again and enter parameter
1 by pressing the increase or decrease value key. Quit setup mode
or
Press and hold down the setup key
and press the increase value key once. Release +
the setup key again.
U Page 12
5.1 Parameter list The parameter numbers are listed in the Number field of the table, in
the Name field the abbreviation. The Default field indicates the stan-
dard settings, Min and Max are the permissible limit values respec-
tively. The unit is indicated in the Unit field. The Description explains
the parameter function. If a dot (•) comes after the parameter number
this indicates that it is a display parameter, the value of which cannot
be changed.
..7. step width 0.10 0.01 10.00 mm Step width for web offset
U Page 13
.1.3. prop range +/- 10.0 -2000.0 2000.0 mm Guider proportional range
Web offset in mm at which the DC actuator
runs at maximum speed.
Decrease value in case of inaccurate guiding!
Increase value in case of uneven guiding!
.1.4. dual-rate width 30 10 90 % Window width in % in relation to the sensor scan range
This value is used to establish the switch point for
determing the dual rate characteristic curve.
.1.6. velocity auto 20 0 1000 mm/s Max. positioning velocity speed in automatic mode
.1.7. velocity pos 50 0 1000 mm/s Positioning velocity speed in positioning mode
.1.8. velocity jog 10 1 1000 mm/s Positioning velocity speed in jog mode
.1.9. velocity defect 1 1 1000 mm/s Positioning velocity when exceeding the set threshold
.2.0. • derated velocity 1000 mm/s Display of velocity limited by internal functions
(only active for selecting in parameter 1.1.8.)
.2.2. defect range ± 10.0 0.0 2000.0 mm range for detecting a web fault
if not attained switching to the set "velocity defect" speed
will be performed
.2.5. motion range total 0.0 0.0 3270.0 mm Total motor position range on calibration
AG positioning path must be entered prior to calibration
.2.8. alarm limit % 75 0 100 % Limit value for end position early warning
U Page 14
.3.3. • total resolution 0.0 0.0 3270.0 p/mm Motor gear constant
display only.
.3.6. linear gear 4.0 0.1 250.0 mm/rev Linear gear transmission
Entry of transmission ratio from
rotational to linear movement
.4.1. pos prop +/- 5.0 0.1 200.0 mm Position controller proportional range
.4.2. • act position 0.0 -3270.0 3270.0 mm Actual position (display only)
.4.3. • set position 0.0 -3270.0 3270.0 mm Set position (display only)
.4.5. prop stroke +/- 100 0 2000.0 mm Actuator correction path in the event of
a web fault of (.1.3. prop range +/-)
.4.6. • photo auto offset 0 -2000.0 2000.0 mm Actuator offset between set center and set operating
point during automatic mode
is set for <SETUP>+<AUTO>.
Only if function is activated via „Configuration SYS“.
.4.8. max. motor speed 1250 100 4000 rpm Motor speed characteristic value
Value is required for speed limiting
U Page 15
.5.6. cut-off current 8.0 0.0 10.0 A Cut-off current of motor output stage
.5.7. motorcurrent 1.0 0.0 7.0 A Max. permissible nominal motor current
.5.8. dyn. currentfactor 150 100 200 % Dynamic motor current rise
Motor is overloaded briefly by the variable factor
.5.9. therm. timeconst. 60 1 200 sec. Thermal time constant for brief motor current excess
o
.7.4. • temperature case xx C Heat sink temperature
U Page 16
o
.7.5. • temp. case max. xx C Maximal heat sink temperature reached
.9.5. CAN connector 0.0 0.0 7.F Address of the sensor at the right slot
Right
.9.6. CAN connector Left 0.0 0.0 7.F Address of the sensor at the left slot
U Page 17
1.0.1. delaytime 1 1.0 0.0 10.0 s Delay time 1 (for switching to emergency sensor)
1.0.2. delaytime 2 1.0 0.0 10.0 s Delay time 2 (for switching to main sensor)
1.1.0. calib. I-act 1.00 0.80 1.20 Motor current measurement calibration
U Page 18
1.1.9. • adaptive ratio 0 0 409,6 % Display of the current control loop amplification
1.2.0. max webspeed ratio 0 0 409,6 % Adaptive factor in % at maximum web speed
1.2.1. lim webspeed ratio 0 0 409,6 % Adaptive factor in % at web speed limit
1.2.8. testvalue 1 0 -100 100 % Test value 1 for service mode ! for service personnel only!
1.2.9. testvalue 2 0 -100 100 % Test value 2 for service mode ! for service personnel only!
1.3.0. testcycletime 0.01 0.01 10.00 s Test cycle time for service mode ! for ser. personnel only !
U Page 19
U Page 20
1 = Reset guider
In this reset all parameter values for the selected device are sa-
ved and a restart performed. Every time parameter values are
changed setup mode should always be quit via 1 to assure that
all changed parameter values are saved.
2 = Save parameters
Function 2 is identical to function 1, the only difference is that
no restart is performed for the selected device.
10 = Actuator initialisation run (with specification of the motion
path)
Prior to the initialisation run the actual positioning path must be
established and entered in parameter ".2.5. total motion range".
The actuator initialisation run is started by entering the value
10. Prior to starting the actuator should be located in its center
position for this start position is saved as the new center positi-
on. The latter may also be corrected manually at any time via
parameter ".3.1. center offset".
11 = Initialisation run-support beam
By entering value 11 the initialisation run for all support beams
featured in this group is performed.
12 = Initialisation run-actuator (with specification of motor and
gear data)
In this initialisation run by first entering the motor and gear data
(parameter .3.4./.3.5./.3.6. and .3.7.) the maximum positioning
path is established and entered in parameter ".2.5. total motion
range".
13 = Capture of guiding criterion photo
On follow-up control systems the position of the actuator/tool is
controlled according to the detected web position. In order to
calibrate the offset, a guiding criterion photo of the actuator
must be taken. To this end, the actuator is moved to the requi-
red location manually. While the actuator guiding criterion photo
is being taken, the offset is calculated on the basis of the cur-
rent actuator position and the web position and entered in para-
meter ".4.6. photo auto offset".
22= Save system parameters
The parameter values of certain parameters are additionally
stored and not deleted in the case of possible data memory de-
letion. The following parameters are saved: .8.2. / .8.3. / .8.4. /
.8.5. / .8.6. / .9.2. / .9.7. / .9.8. und .9.9. .
30 = general web guider basic parameter setting
31 = VS 35 .. support beam basic parameter setting
32 = 3 position controller basic parameter setting
33 = VS 50.. support beam basic parameter setting
The device-specific parameters are preset for the specified de-
vices by entering the appropriate value.
U Page 21
42 = Expanded setup-mode
In setup mode all existing parameters may be selected and the
parameter values viewed. Some of the parameter values may
be changed immediately. The protected parameters may only
be changed once value 42 has been entered. This entry furnis-
hes access to what is known as "expanded setup-mode". In ex-
panded setup mode all parameters that can be changed, may
be changed.
44 = Save customer settings
In this form of saving all parameter settings are stored in a
backup list. If necessary, all customer-specific settings may be
reloaded using parameter "..2. reset settings" .
98 = Delete error memory
This command should only be used by E+L service personnel.
The controller card can store up to 100 errors that have occur-
red. If the number of errors exceeds the 100 mark, the error
messages are pushed out at the back of the error memory and
are thus deleted.
99 = Delete data memory
This command should be used by E+L service personnel. The
entire data memory of the controller card is deleted. Once the
controller card is switched on the default values are automati-
cally loaded.
No commands are performed until a parameter change has
been executed!
U Page 22
U Page 23
Oscillation time tc
Path-dependent:
In path-dependent oscillation the oscillation period is determined by
path-dependent, external pulses. The oscillation period is divided up
into n-sections. The maximum number of pulses must not exceed 20
pulses per second.
The number of pulses to be set may be calculated as follows:
1. Establish path length per oscillation period
n-sections
web length s
U Page 24
U Page 25
Proportional actuator:
The smaller the set proportional range at a constant maximum posi-
tioning velocity (Parameter ".1.6. velocity auto") is, the greater the
amplification of the web guider will be.
A negative proportional range causes negative amplification, the
effective direction is thus inverted in automatic mode.
Velocity correction
Proportional range
.1.3. prop range ±
established correction 2,0 3,5
positioning velocity de-
pending on proportional
range 15 mm/s
8 mm/s
Control deviation
Positioning velocity
.1.6. velocity auto
20 mm/s
Set position
(sensor measuring range cen- Control deviation of
ter ) 1.5 mm
U Page 26
Example 1: Example 2:
1
G = 20/2 = 10 /s G = 20/3.5 = 5.71 1/s
VK = 1.5 mm * 10 1/s VK = 1.5 mm * 5.71 1/s
VK = 15 mm/s VK = 8.6 mm/s
U Page 27
Integral actuator:
The smaller the set proportional range is for the maximum correction
path of the actuator (parameter ".4.5. prop stroke ±"), the greater the
amplification of the web guider.
A negative proportional range causes negative amplification, the
effective direction in automatic mode is thus inverted.
Control deviation
Correction positioning
path
.4.5. prop stroke ±
25 mm
Set position
(Sensor measuring range
Control deviation of
center)
1.5 mm
U Page 28
Example 1: Example 2:
G = 25/2 = 12.5 G = 25/3.5 = 7.14
SK = 1.5 mm * 12.5 SK = 1.5 mm * 7.14
VK = 18.75 mm VK = 10.71 mm
Integral actuator optimisation:
Reduce the proportional range by small steps only. Following each
change of the parameter value the a web deviation should be produ-
ced manually in automatic mode so that oscillation may be detected
immediately.
Reduce the proportional range until the guider starts to oscillate. The
increase the proportional range again until no more oscillation may
be observed.
U Page 29
Set position
(Sensor measuring range Control deviation of
center ) 1.5 mm
U Page 30
Example 1: Example 2:
1
G = 15/2 = 7.5 /s G = 20/2 = 10.0 1/s
VK = 1.5 mm * 7.5 1/s VK = 1.5 mm * 10.0 1/s
VK = 11.25 mm/s VK = 15.0 mm/s
If the positioning velocity is too high the web guider will begin to oscil-
late.
The maximum positioning velocity must be set higher than the
maximum error velocity, yet must not exceed the nominal posi-
tioning velocity the DC actuator.
U Page 31
.2.1. reseved 21
Not assigned at present.
U Page 32
.2.6. positonrange +
.2.7. positionrange -
Via the position range limit the DC actuator drive is prevented from
reaching its mechanical spindle stop or the actuator its mechanical
stop.
On compact systems the maximum actuator positioning path (see
parameter ".2.5. total motion range") is shortened at the factory by
approx. 2 mm. In the case of on-site mounting of the DC actuator
drive the position range limit must be set by the customer.
Especially in the case of large moved masses, please ensure that the
actuator does not come to a standstill at once. The positioning range
must be reduced accordingly.
The set values are always in relation to the set center.
The positioning path must entered for both sides (right/left) of the
center position in parameter .2.6. and .2.7. of the positioning range.
These position range limits must not be used as safeguards for
persons or appliances. For the safety of persons or appliances the
end position limits must be fitted with additional limit switches or a
suitable mechanical stop.
U Page 33
Example:
Entered value in parameter .2.8. = 75 %
Entered value in parameter .2.6. / .2.7. = 15 mm
15 mm * 75 / 100 = 11.25 mm
If the positioning range of 11.25 mm is exceeded the end position ex-
ceeded message will be output.
.2.6. = 15 mm .2.7. = 15 mm
.2.9. reserved 29
Not assigned at present.
U Page 34
Center of
rotation
.3.4. .3.5. .3.6. .3.7.
encoder rotation linear mech.
resolution gear gear gear factor
S 2/S 1
U Page 35
U Page 36
.3.8. reserved 38
Not assigned at present.
.3.9. reserved 39
Not assigned at present.
Example:
A web set position deviation of 1 mm produces an actuator set positi-
Positioning velocity on of 15 mm based on the set values (parameter .1.3. und .4.5.).
The DC actuator drive covers the first 10 mm at maximum positioning
velocity as these values are outwith the grey range. Once the 10 mm
are passed, only 5 mm remain. These 5 mm lie within the grey range
Position
error and the velocity is thus reduced linearly to 0 until the 15 mm position
range is reached.
In the case of uneven edges (textile) this parameter may be
increased to dampen the DC actuator drive position controller. The
static precision of the web guider is hereby preserved.
Position con-
Maximum posi- troller propor-
The value of parameter .4.1. should amount at most to half of the
tioning velocity tional range sensor scanning range.
in automatic (Parameter
(parameter .4.1.)
.1.6.) .4.2. act position
The actual position of the actuator at the outfeed, in relation to the set
center, is displayed.
U Page 37
U Page 38
Correction path
Proportional range
established cor- .1.3. prop range ±
rection posi- 2,0
tioning path de-
pending on the
correction posi- 15 mm
tioning path 11 mm
Set position
(Sensor measuring Control deviation of
range center ) 1.5 mm
U Page 39
Center position
U Page 40
.5.3. I-PWM
The actual I-PWM value (pulse-width-modulated) is displayed. The
display is only of significance for internal tests.
.5.4. reserved 54
Not assigned at present.
U Page 41
Current
in mA Pos. 1 Pos. 2
internal cur-
rent limit
actual permissi-
ble motor cur-
rent
nom. motor current
motor current
Time
in s
If the motor current input is less than the nominal motor current the
permissible motor current will be increased within the set time (.5.9.
term. timeconst.) to the internal current limit. This actual permissible
motor current is displayed in parameter ".6.0. limited current".
If the motor current input (pos. 1) is greater than the nominal motor
current (.5.7. motor current) the permissible motor current will then
be reduced again within the set time (.5.9. term. timeconst.) to the
nominal motor current. As soon as the motor current is again drops
below the nominal motor current (pos. 2) increasing of the current li-
mit is resumed.
Once the operating voltage is supplied the permissible motor cur-
rent begins at the nominal motor current.
The current limit is upwardly limited by the maximum output stage
current (see technical data).
U Page 42
.6.5. reserved 65
Not assigned at present.
.6.6. reserved 66
Not assigned at present.
.6.7. reserved 67
Not assigned at present.
.6.8. diagnostics
Parameter block for displaying the system status.
U Page 43
.7.0. reserved 70
Not assigned at present.
.7.1. reserved 71
Not assigned at present.
.7.3. supplyvoltage 24 DC
The current supply voltage of the controllercard is displayed.
.7.6. reserved 76
Not assigned at present.
.7.7. reserved 77
Not assigned at present.
.7.8. mainloops/sec.
For internal evaluations only.
.8.1. reserved 81
Not assigned at present.
U Page 44
Example 1:
The positioning range is to be limited by two series-connected break
contacts.
The inputs X 4.4 (reference switch) and X 4.7 (end positions) should
be assigned as follows:
Input X 4.4 is assigned the value -3. The switching point is reached
via the positive motor direction of rotation.
Input X 4.7 is assigned the value -4 (break contact).
U Page 45
Example 2:
The positioning range is to be limited by two separate break contacts.
The inputs X 4.4 and X 4.7 should be assigned as follows:
Input X 4.4 is assigned the value -6. At signal 0 the negative motor
direction of rotation is stopped.
Input X 4.7 is assigned the value -5. At signal 0 the positive motor di-
rection of rotation is stopped.
If the circuit is set up with make contacts, value 5 or 6 must be set.
.8.7. reserved 87
Not assigned at present.
.8.8. reserved 88
Not assigned at present.
.8.9. reserved 89
Not assigned at present.
.9.0. reserved 90
Not assigned at present.
U Page 46
U Page 47
U Page 48
U Page 49
Example 2:
The "enable Photo" and "Sens. err.> Center" functions are required.
Sum value = 0040h + 0080h = 00A0h
Parameter value = A0
(*) no controller output 0000h None of the following 5 values is output via the CAN channel
( ) N-target -> CAN 0001h Output of the set speed value
( ) Delta N -> CAN 0002h Output of the speed difference
( ) Pos-target -> CAN 0003h Output of the set position value
( ) Delta Pos -> CAN 0004h Output of the position difference
( ) I-target -> CAN 0005h Output of the set current value
[ ] Disable I-Loop 0008h If no motor is connected to the controller card, this setting must be
used to switch off the current circuit.
[ ] Send targetpos. 0010h Instead of the DC actuator drive actual position the set position of the
DC actuator drive is transmitted as a CAN message. The following
losses with a follow-up controlling system are thus reduced.
[ ] lock webspeedlim 0020h If the set web speed fails to be reached (parameter 1.1.5.) automatic
mode is blocked.
[ ] Start AUTO slow 0040h If the web is outside of the proportional range when the operating
mode "automatic" is selected, the positioning speed will be reduced to
the positioning speed set for the manual mode. This reduction will be
made only once and it will be made after the "automatic" mode has
been selected.
U Page 50
Example :
The "I target-> CAN" and "Disable I Loop" functions are required.
Sum value = 0005h + 0008h = 000Dh
Parameter value = 000D
U Page 51
Example 1:
The "Auto: use all sens" and "force support free" functions are requi-
red.
Sum value = 0001h + 0004h = 0005h
Parameter value = 5
Example 2:
The "Sens sel. direct", "emergency sensor L" and "emergency sensor
R" functions are required.
Sum value = 0040h + 0080h + 0100h = 01A0h
Parameter value = 1A0
1.0.1. delaytime 1
1.0.2. delaytime 2
On the loss of the guiding criterion when a color line sensor an option
is available of switching to what is termed an emergency sensor.
Emergency guiding is activated in parameter ".9.9. operatorkey con-
fig". The periods after which switching-over takes place are set via the
two "delaytime" parameters.
Switching-over is performed according to the following principle:
Main sensor
(Color line sensor)
Emergency ensor
(Edge sensor)
Time
Status
Color line sensor valid invalid valid
.1.0.1 1.0.2.
Parameter delaytime delaytime
1 2
Operating mode automatic blocked automatic
U Page 52
➀ At this point the color line sensor loses its guiding criterion. The
web guider is blocked and the delay time set in parameter "1.0.1.
delaytime 1" started.
➁ On expiry of the set time switching to the emergency sensor takes
place and the web guider is enabled. Automatic mode is continued.
At the same time the controller card adopts the current actual web
position as the set position for the emergency sensor.
➂ The guiding criterion is available again and the delay time in para-
meter "1.0.2. delaytime 2" starts. Guiding is still performed by
emergency sensor.
➃ Once the set time has elapsed the system switches back to the
color line sensor.
1.0.7. calibration
Parameter block for calibrating the controller card.
U Page 53
1.1.5. 1.1.4.
1.1.5. = Entry of the minimum web speed
1.2.1. = Entry of the accompanying per cent value
Example 1:
The set proportional range (.1.3.) should be 200% at minimum web
speed and 50% at maximum web speed. The minimum web speed is
1.2.1. 15 m/min, the maximum web speed 60 m/min.
The corresponding per cent factor for the proportional range at a
1.2.0. specific web speed may be deduced from the characteristic curve
opposite.
1.1.5. 1.1.4.
U Page 54
Example 2:
The maximum positioning velocity in "automatic" mode (.1.6.) should
1.2.0. be 25% at minimum web speed and 100% at maximum web speed.
The minimum web speed is 5 m/min, the maximum web speed 20 m/
1.2.1. min.
The corresponding per cent factor for the positioning velocity at a
specific web speed may be deduced from the characteristic curve op-
1.1.5. 1.1.4. posite .
The reduction of the positioning velocity does not have any effect
on the sensitivity of the control loop.
1.2.5. !! Service !!
This parameter serves only as a parameter title for the following pa-
rameters that are grouped together due to their function. The para-
meter itself has no function.
1.2.8. testvalue 1
For E+L service personnel only.
1.2.9. testvalue 2
For E+L service personnel only.
1.3.0. testcycletime
For E+L service personnel only.
U Page 56
5.3 "Three position controller" For control card applications as a three position controller the va-
upgrade lue 32 must be entered in parameter "..3. start service" during
control card commissioning. This loads the three position control-
ler parameter record. The three position controller parameters that
differ from the norm are described below.
.1.3. puls range ± 2.0 0.0 2000.0 mm Switching threshold for transition
Stop at pulse output
.1.4. slow range ± 4.0 0.0 2000.0 mm Switching threshold for transition
Pulse output to permanent signal
.1.5. fast range ± 6.0 0.0 2000.0 mm Switching threshold for transition
Permanent signal to fast signal
.1.6. hysteresis 1.0 0.0 2000.0 mm Hysteresis of the individual switching thresholds
.1.7. pulse ON-time 1.0 0.0 10.0 sec Switch-on time of pulse signal
.1.8. pulse OFF-time 1.0 0.0 10.0 sec Switch-off time of pulse signal
.2.0. dig. I/O adress 0 0 7.F hex Address of digit. output card for the positioning signals
U Page 57
Switch-off duration
parameter .1.8.
U Page 58
6. Setting values
Type Mat. No. Pulse Trans- Spindle Watts Pos. Current Nominal Speed Speed Current Current
per rev mission pitch path speed
at 22 V P I P I
.3.4. .3.5. .3.6. .5.7. .4.8. .5.0. .5.1. .6.2. .6.3.
AG 2491 201444 8 8:1 4 20 12 0,86 3300 2,0 0,10 2,6 0,4
AG 2491 204474 8 8:1 4 20 25 0,86 3300 2,0 0,10 2,6 0,4
AG 2491 210667 8 8:1 4 20 50 0,86 3300 2,0 0,10 2,6 0,4
AG 2571 311963 8 8:1 5 40 25 2,9 2750 2,0 0,10 2,6 0,4
AG 2571 311941 8 20,25:1 5 40 25 2,9 2750 2,0 0,10 2,6 0,4
AG 2571 311964 8 8:1 5 40 50 2,9 2750 2,0 0,10 2,6 0,4
AG 2571 311942 8 20,25:1 5 40 50 2,9 2750 2,0 0,10 2,6 0,4
AG 2571 311965 8 8:1 5 40 75 2,9 2750 2,0 0,10 2,6 0,4
AG 2571 311966 8 20,25:1 5 40 75 2,9 2750 2,0 0,10 2,6 0,4
AG 2571 311804 8 8:1 5 40 100 2,9 2750 2,0 0,10 2,6 0,4
AG 2571 311943 8 20,25:1 5 40 100 2,9 2750 2,0 0,10 2,6 0,4
AG 2591 229159 8 8:1 5 40 15 2,9 2750 2,0 0,10 2,6 0,4
AG 2591 210896 8 8:1 5 40 25 2,9 2750 2,0 0,10 2,6 0,4
AG 2591 210897 8 8:1 5 40 50 2,9 2750 2,0 0,10 2,6 0,4
AG 2591 217908 8 20,25:1 5 40 50 2,9 2750 2,0 0,10 2,6 0,4
AG 2591 210898 8 8:1 5 40 75 2,9 2750 2,0 0,10 2,6 0,4
AG 2591 227057 8 20,25:1 5 40 75 2,9 2750 2,0 0,10 2,6 0,4
AG 2591 230119 8 20,25:1 5 40 100 2,9 2750 2,0 0,10 2,6 0,4
AG 2591 219860 8 8:1 5 40 100 2,9 2750 2,0 0,10 2,6 0,4
AG 2593 230661 8 1:1 4 120 12 2 1228 2,0 0,10 2,6 0,4
AG 2593 234536 8 1:1 4 120 50 2 1228 2,0 0,10 2,6 0,4
AG 2593 310696 8 1:1 5 120 75 2 1228 2,0 0,10 2,6 0,4
AG 2595 226921 8 8:1 5 40 24 2,9 2750 2,0 0,10 2,6 0,4
AG 2596 227183 8 8:1 5 40 40 2,9 2750 2,0 0,10 2,6 0,4
AG 2671 311967 8 16:1 5 80 25 4,9 3070 2,0 0,10 2,6 0,4
AG 2671 311946 8 28:1 5 80 25 4,9 3070 2,0 0,10 2,6 0,4
AG 2671 311944 8 16.1 5 80 50 4,9 3070 2,0 0,10 2,6 0,4
AG 2671 311947 8 28:1 5 80 50 4,9 3070 2,0 0,10 2,6 0,4
AG 2671 310208 8 16:1 5 80 75 4,9 3070 2,0 0,10 2,6 0,4
AG 2671 311948 8 28:1 5 80 75 4,9 3070 2,0 0,10 2,6 0,4
AG 2671 311945 8 16:1 5 80 100 4,9 3070 2,0 0,10 2,6 0,4
AG 2671 311949 8 28:1 5 80 100 4,9 3070 2,0 0,10 2,6 0,4
AG 2671 311807 8 16:1 5 80 150 4,9 3070 2,0 0,10 2,6 0,4
AG 2671 311950 8 28:1 5 80 150 4,9 3070 2,0 0,10 2,6 0,4
AG 2691 224526 8 4:1 5 80 50 4,9 3070 2,0 0,10 2,6 0,4
AG 2691 212610 8 16:1 5 80 50 4,9 3070 2,0 0,10 2,6 0,4
AG 2691 229098 8 28:1 5 80 50 4,9 3070 2,0 0,10 2,6 0,4
AG 2691 212609 8 16:1 5 80 75 4,9 3070 2,0 0,10 2,6 0,4
AG 2691 228765 8 28:1 5 80 75 4,9 3070 2,0 0,10 2,6 0,4
AG 2691 312204 8 34,5:1 5 80 100 7,5 2750 2,0 0,10 2,6 0,4
AG 2691 217808 8 16:1 5 80 100 4,9 3070 2,0 0,10 2,6 0,4
AG 2691 212325 8 28:1 5 80 100 4,9 3070 2,0 0,10 2,6 0,4
AG 2691 234946 8 4:1 5 80 175 4,9 3070 2,0 0,10 2,6 0,4
AG 2691 228283 8 28:1 5 80 175 4,9 3070 2,0 0,10 2,6 0,4
AG 2691 214554 8 16:1 5 80 175 4,9 3070 2,0 0,10 2,6 0,4
AG 4081 208615 8 6,25:1 2,5 9,5 25 0,71 2778 0,4 0,01 2,6 0,4
AG 4081 208616 8 6,25:1 2,5 9,5 6 0,71 2778 0,4 0,01 2,6 0,4
AG 4081 226862 8 6,25:1 2,5 9,5 50 0,71 2778 0,4 0,01 2,6 0,4
AG 4091 209822 8 6,25:1 2,5 9,5 6 0,71 2778 0,4 0,01 2,6 0,4
AG 4481 308422 500 1:1 2,5 9 12 0,9 1746 2,0 0,10 2,6 0,4
AG 4481 308498 500 1:1 2,5 20 30 0,9 1746 2,0 0,10 2,6 0,4
AG 4571 311968 8 8:1 5 40 25 2,9 2750 2,0 0,10 2,6 0,4
AG 4571 311952 8 20,25:1 5 40 25 2,9 2750 2,0 0,10 2,6 0,4
U Page 59
Type Mat. No. Pulse Trans- Spindle Watts Pos. Current Nominal Speed Speed Current Current
per rev mission pitch path speed
at 22 V P I P I
.3.4. .3.5. .3.6. .5.7. .4.8. .5.0. .5.1. .6.2. .6.3.
AG 4571 311805 8 8:1 5 40 50 2,9 2750 2,0 0,10 2,6 0,4
AG 4571 311953 8 20,25:1 5 40 50 2,9 2750 2,0 0,10 2,6 0,4
AG 4571 311951 8 8:1 5 40 75 2,9 2750 2,0 0,10 2,6 0,4
AG 4571 311954 8 20,25:1 5 40 75 2,9 2750 2,0 0,10 2,6 0,4
AG 4571 311806 8 8.1 5 40 100 2,9 2750 2,0 0,10 2,6 0,4
AG 4571 311955 8 20,25:1 5 40 100 2,9 2750 2,0 0,10 2,6 0,4
AG 4591 230566 8 8:1 5 40 25 2,9 2750 2,0 0,10 2,6 0,4
AG 4591 232466 8 20,25:1 5 40 25 2,9 2750 2,0 0,10 2,6 0,4
AG 4591 307757 8 20,25:1 5 40 50 2,9 2750 2,0 0,10 2,6 0,4
AG 4591 230657 8 8:1 5 40 50 2,9 2750 2,0 0,10 2,6 0,4
AG 4591 230568 8 8:1 5 40 75 2,9 2750 2,0 0,10 2,6 0,4
AG 4591 229330 8 20,25:1 5 40 75 2,9 2750 2,0 0,10 2,6 0,4
AG 4591 229329 8 8:1 5 40 100 2,9 2750 2,0 0,10 2,6 0,4
AG 4591 230136 8 20,25:1 5 40 100 2,9 2750 2,0 0,10 2,6 0,4
AG 4671 311969 8 11:1 5 80 25 4,9 3070 2,0 0,10 2,6 0,4
AG 4671 311958 8 25,14:1 5 80 25 4,9 3070 2,0 0,10 2,6 0,4
AG 4671 311956 8 11:1 5 80 50 4,9 3070 2,0 0,10 2,6 0,4
AG 4671 311959 8 25,14:1 5 80 50 4,9 3070 2,0 0,10 2,6 0,4
AG 4671 311808 8 11:1 5 80 75 4, 3070 2,0 0,10 2,6 0,4
AG 4671 311960 8 25,14:1 5 80 75 4,9 3070 2,0 0,10 2,6 0,4
AG 4671 311957 8 11:1 5 80 100 4,9 3070 2,0 0,10 2,6 0,4
AG 4671 311961 8 25,14:1 5 80 100 4,9 3070 2,0 0,10 2,6 0,4
AG 4671 311809 8 11:1 5 80 150 4,9 3070 2,0 0,10 2,6 0,4
AG 4671 311962 8 25,14:1 5 80 150 4,9 3070 2,0 0,10 2,6 0,4
AG 4691 230562 8 11:1 5 80 25 4,9 3070 2,0 0,10 2,6 0,4
AG 4691 230563 8 11:1 5 80 50 4,9 3070 2,0 0,10 2,6 0,4
AG 4691 230564 8 11:1 5 80 75 4,9 3070 2,0 0,10 2,6 0,4
AG 4691 230565 8 11:1 5 80 100 4,9 3070 2,0 0,10 2,6 0,4
AG 4691 230135 8 25,14:1 5 80 100 4,9 3070 2,0 0,10 2,6 0,4
AG 4699 309000 8 11:1 6 80 1090 4,9 3070 2,0 0,10 2,6 0,4
DR 1111 500 1:1 2,5 20 10 0,9 1746 1,0 0,02 2,6 0,4
DR 1272 500 1:1 2,5 20 10 0,9 1746 1,0 0,02 2,6 0,4
DR 2472 500 1:1 2 80 10 3,3 3475 2,0 0,10 2,6 0,4
DR 2472 500 1:1 2 80 15 3,3 3475 2,0 0,10 2,6 0,4
DR 2472 500 1:1 2 80 20 3,3 3475 2,0 0,10 2,6 0,4
VE 5016 8 8:1 5 40 350 2,9 2750 2,0 0,10 2,6 0,4
VE 5016 8 8:1 5 40 350 2,9 2750 2,0 0,10 2,6 0,4
VG 18 8 64:1 4 80 55 2,95 1897 2,0 0,10 2,6 0,4
DR 52 8 8:1 5 40 17-25 2,9 2750 2,0 0,10 2,6 0,4
VS 50 8 64:1 125 35 without 2,7 3300 2,0 0,10 2,6 0,4
VS 60 8 288:1 300 30 without 2,7 3300 2,0 0,10 2,6 0,4
VS 35 10 46:1 77 20 without 0,8 1870 2,0 0,10 2,6 0,4
VS 35 10 46:1 77 20 without 0,8 1870 2,0 0,10 2,6 0,4
VS 45 10 50:1 78 6 without 0,71 2778 2,0 0,10 7,0 0,1
VS 90 8 16:1 5 80 without 4,9 3070 2,0 0,10 2,6 0,4
BC 1103 8 8:1 5 40 19 2,9 2750 2,0 0,10 2,6 0,4
BT 25 8 16:1 100,0 80 without 4,9 3070 2,0 0,10 2,6 0,4
DR 2272 500 1:1 2,5 20 10 0,9 1746 2,0 0,10 2,6 0,4
U Page 60
Operating voltage
7. Technical Nominal value 24 V DC
data Nominal range 20 - 30 V DC
(including ripple)
Power input
without motor/sensors 4,8 W
with motor (maximum) 180 W
Current input
without motor/sensors 0,2 A
with motor (maximum) 7.2 A
Output voltage
at motor terminal ±22 V (PWM)
(PWM=pulse width-modulated)
Maximum output current 7A
Protection class IP 00
CAN bus
CAN bus level + 5 V (potential-free)
CAN baud rate 250 KBaud
U Page 61