Insulation Coordination
Insulation Coordination
Insulation Coordination:
“The process of bringing the insulation strengths of electrical equipment and buses into the
proper relationship with expected overvoltages and with the characteristics of the insulating
media and surge protective devices to obtain an acceptable risk of failure.”
In co-ordinating the system under consideration, we have to ensure that the equipment used
are protected, and that inadvertent interruptions are kept to a minimum.
The co-ordinating gap must be chosen so as to provide protection of the transformer under all
conditions. However, the line gaps protecting the line insulation can be set to a higher
characteristic to reduce unnecessary interruptions.
It is seen that the increase in the number of disc units is only slight for the 220 kV system,
with the increase in the overvoltage factor from 2.0 to 3.5 ,but that there is a rapid increase in the
750kV system.
Thus, while it may be economically feasible to protect the lower voltage lines up to an
overvoltage factor of 3.5 (say), it is definitely not economically feasible to have an overvoltage
factor of more than about 2.0 or 2.5 on the higher voltage lines.
Switching overvoltages is predominant in the higher voltage systems. However, these may
be controlled by proper design of switching devices.
The aim of statistical methods is to quantify the risk of failure of insulation through
numerical analysis of the statistical nature of the overvoltage magnitudes and of electrical
withstand strength of insulation.
Since we cannot find suitable insulation such that the withstand distribution does not
overlap with the overvoltage distribution, in the statistical method of analysis, the insulation is
selected such that the 2% overvoltage probability coincides with the 90% withstand probability
as shown.