0% found this document useful (0 votes)
219 views2 pages

KV-DN20 Datasheet

This document provides specifications for the KV-DN20 DeviceNetTM unit, including its communication protocol, transmission specifications, maximum cable lengths and number of nodes, master and slave modes, internal current consumption, weight, and dimensions.

Uploaded by

aman shah arbain
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
219 views2 pages

KV-DN20 Datasheet

This document provides specifications for the KV-DN20 DeviceNetTM unit, including its communication protocol, transmission specifications, maximum cable lengths and number of nodes, master and slave modes, internal current consumption, weight, and dimensions.

Uploaded by

aman shah arbain
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Data 

Sheet

KV­DN20
DeviceNet™ Unit

SPECIFICATIONS

Model KV­DN20

Type DeviceNetTM unit

Communication protocol Compliant with DeviceNetTM

Transmission specification Transmission rate 500 kbps, 250 kbps, 125 kbps

Transmission media 5 dedicated cables (2 for signal system, 2 for power, 1 for shield line)

Connection topology Multidrop method

Maximum cable length Thick main cable 500 m (Transmission speed 125 kbps), 250 m (Transmission speed 250 kbps), 100 m (Transmissio
n speed 500 kbps)
Thin main cable 100 m (All transmission speeds)

Maximum number of nodes 64 (including master, slave, configurator)

Master mode Connected pieces per network Max. 64

Type of communication I/O communication (Poll/Bit­Strobe/COS/Cyclic), Explicit message communication

Type and size of assigned devices Relay or data memory (indicated per block)
Max. size (per block) [For relaying: Input 64 ch, Output 64 ch, For data memory: Input 200 words, Output 200 words]
× 2 blocks

Assignment method of device Auto configuration (Fixed or assigned with front end) and manual assignment

Slave connection pieces per unit Max. 63

Maximum number of I/O per slave Input: 2048 points (128 words), Output: 2048 points (128 words)

Data length of message communication Sending: 106 bytes, receiving 110 bytes

Slave mode Connected pieces per network Max. 64

Type of communication I/O communication (Poll), Explicit message communication

Type and size of assigned devices Relaying or data memory
Max. size [For relay: Input 64 ch/Output 64 ch, For data memory: Input 128 words/Output 128 words

Internal current consumption Internal circuit: 24 VDC 45 mA or less (supplied by CPU unit)
Communication circuit: 24 VDC 25 mA or less (supplied by communication connector)

Weight Approx. 150 g

KEYENCE MALAYSIA 1­800­88­1358 https://www.keyence.com.my/ 2021/08/16 Page:1/2


Data Sheet

Dimensions

* Download CAD file or product manual for larger image/text and more detail.