Available Fault Current Calculation: Project Name Your Company Name
This document calculates the available fault current at a utility substation and service equipment. It determines the short circuit current (Isca) at the transformer to be 32,528 amperes based on the transformer rating. It then uses the point-to-point method to calculate the fault current at the service equipment, found to be 29,813 amperes line-to-line and 31,040 amperes line-to-neutral.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
64 views1 page
Available Fault Current Calculation: Project Name Your Company Name
This document calculates the available fault current at a utility substation and service equipment. It determines the short circuit current (Isca) at the transformer to be 32,528 amperes based on the transformer rating. It then uses the point-to-point method to calculate the fault current at the service equipment, found to be 29,813 amperes line-to-line and 31,040 amperes line-to-neutral.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1
Project Name
Your Company Name
Available Fault Current Calculation
by:John Sokolik Ver. 2017 Utility Fault Current amperes kVA = 1000 [email protected] E = 380 I = kVA x 1000 = trans. FLA trans. FLA = 1519 E x 1.732
Isca = trans. FLA x 100 x PF PF = 90%
transformer Z = Z = 5.19% Isca = ampere short-circuit current RMS symmetrical. Isca = 32,528 amperes
Point to Point Method
Length (distance) L = 20 1.732 x L x I (ASC) Isca = 32,528 'f ' factor = N x C x E L-N # conductors per phase N = 4 Phase conductor constant C = 26,706 Phase Conductor Volt Line to Line EL-L = 380 Volt f = 0.091 Neutral conductor constant C = 26,706 Neutral Conductor Multiplier Volt Line to Neutral EL-N = 220 Volt f = 0.048 M= 1 1+f Line to Line M = 0.917 Line to Neutral M = 0.954 Fault Current at Service Equipment
Isca x M = fault current at terminals of main disconnect L- L = 29,813 amperes
Isca x M = fault current at terminals of main disconnect L- N = 31,040 amperes