Available Fault Current Calculation: Project Name Your Company Name

This document calculates the available fault current at a utility substation and service equipment. It determines the short circuit current (Isca) at the transformer to be 32,528 amperes based on the transformer rating. It then uses the point-to-point method to calculate the fault current at the service equipment, found to be 29,813 amperes line-to-line and 31,040 amperes line-to-neutral.

Uploaded by

JAY CASIBANG
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
64 views1 page

Available Fault Current Calculation: Project Name Your Company Name

This document calculates the available fault current at a utility substation and service equipment. It determines the short circuit current (Isca) at the transformer to be 32,528 amperes based on the transformer rating. It then uses the point-to-point method to calculate the fault current at the service equipment, found to be 29,813 amperes line-to-line and 31,040 amperes line-to-neutral.

Uploaded by

JAY CASIBANG
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Project Name

Your Company Name

Available Fault Current Calculation


by:John Sokolik Ver. 2017
Utility Fault Current amperes kVA = 1000 [email protected]
E = 380
I = kVA x 1000 = trans. FLA trans. FLA = 1519
E x 1.732

Isca = trans. FLA x 100 x PF PF = 90%


transformer Z = Z = 5.19%
Isca = ampere short-circuit current RMS symmetrical. Isca = 32,528 amperes

Point to Point Method


Length (distance) L = 20
1.732 x L x I (ASC) Isca = 32,528
'f ' factor =
N x C x E L-N # conductors per phase N = 4
Phase conductor constant C = 26,706 Phase Conductor
Volt Line to Line EL-L = 380 Volt
f = 0.091
Neutral conductor constant C = 26,706 Neutral Conductor
Multiplier Volt Line to Neutral EL-N = 220 Volt
f = 0.048
M= 1
1+f Line to Line M = 0.917
Line to Neutral M = 0.954
Fault Current at Service Equipment

Isca x M = fault current at terminals of main disconnect L- L = 29,813 amperes


Isca x M = fault current at terminals of main disconnect L- N = 31,040 amperes