Power System Protection (EE 703-N) : Chapter:1 INTRODUCTION
Power System Protection (EE 703-N) : Chapter:1 INTRODUCTION
(EE 703-N)
Chapter:1 INTRODUCTION
What is System Protection?
•Generators
•Transformers, Reactors
•Lines
•Buses
•Capacitors
Basics components used in protection
Currents and voltages to relays are supplied via CT’s and PT’s.
Current Transformer (CT)
A device which transforms the current on the power system from
large primary values to safe secondary values. The secondary
current will be proportional (as per the ratio) to the primary
current.
Potential Transformer (PT)
A device which transforms the
voltage on the power system
from primary values to safe
secondary values, in a ratio
proportional to the primary value.
Generator Protection
B. Rotor Problems
1. Loss of field
2. Field ground
a. First ground
b. Second ground
=TROUBLE
Generator Protection
Rotor
Generator Protection
1. Loss of Field
a. Impedance
Generator Protection
2. Field ground
a. DC voltage relay (64F)
The field ground relay is connected from the negative side
of the field to DC ground. Detects voltage from the field to
ground.
Generator Protection
C. Abnormal Conditions
1. Over/Under Frequency
2. Over Excitation
3. Reverse Power
4. Out of Step
5. Unbalance Current
XFMR Protection
Power transformers are expensive, and are a long lead-time item
(1 year or longer) so protection must be effective
Transformer Protection
● Winding-to-winding faults
● Winding-to-ground faults
● Bushing faults
Transformer Protection
Protection Methods
● Fuse
● Overcurrent
● Differential
Transformer Protection
Overcurrent Relays
Transformer Protection
Differential Protection:
What goes in must come out….. P-in = P-out
Transformer Protection
Microprocessor Relays
187T1-T
Wraps transformer
187T1-B
Wraps transformer and bus
Transformer Protection
187 T1-T
Zone of
Protection
Transformer Protection
187 T1-B
Zone of
Protection
Transmission Line Protection
Transmission Line Protection
Ice Storm
Faults
“Faults come uninvited and seldom go away voluntarily.”
Fault Types:
●Single line-to-ground
● Line-to-line
● Three Phase
● Line-to-line-to-ground
Transmission Line Protection
A. Overcurrent
B. Directional Overcurrent
C. Distance (Impedance)
D. Pilot
1. DCB (Directional Comparison Blocking
2. POTT (Permissive Overreaching Transfer Trip)
E. Line Current Differential
Transmission Line Protection
Distance Protection
A distance relay measures the impedance of a lineusing
the voltage applied to the relay and the current
applied to the relay.
Distance Relay
CT and PT
Connections
Transmission Line Protection
LINE DIFFERENTIAL
No fault or external fault, current at each end is balanced
The current going into the line is going out at other end
Bus Protection
Bus Differential:
Current into bus must equal current out of bus
Bus Protection
Bus Fault
Bus Protection
Double bus,
breaker-and-a-
half
Capacitor Protection
Purpose of capacitors:
A voltage relay detects the higher voltage and trips the breaker