Ney Furnace Manual Eng
Ney Furnace Manual Eng
Ney Furnace Manual Eng
SERVICE MANUAL
MODELS: 6-525
6-160A
6-1350A
6- 9363014 9014
TABLE OF CONTENTS
IV Features 4-1
V Specifications 5-1
Heating Curves 5-3
Cooling Curves 5-4
X Accessories 10-1
Please read and follow the safety precautions listed below. These are intended for
your safety and the safe operation of the equipment.
CAUTION
* DO NOT ATTEMPT TO SERVICE THE FURNACE UNTIL YOU HAVE READ AND UN-
DERSTOOD THE SERVICE INSTRUCTIONS INCLUDED IN THIS MANUAL.
* ALWAYS TURN OFF THE POWER AND REMOVE THE LINE CORD FROM THE WALL
OUTLET BEFORE SERVICING THE FURNACE.
WARNING
> This furnace is not designed for use in hazardous (Class I, II, or III) locations as
defined by the National Electric Code.
The furnace power cord is equipped with a three prong (grounding) plug for use with
wall receptacles to minimize the possibility of electric shock hazard from the furnace.
The wall receptacles and circuit should be checked by a qualified electrician to make
sure the receptacle is properly grounded.
1-1
Two prong wall receptacles must be replaced with three prong wall receitacles to
ensure proper operation and safety. Two to three prong adaptors are nqft considered
reliable, safe methods of electrical connection.
> This furnace must be connected to a properly sized power circuit with the correct
overcurrent protection for safe and reliable operation.
> As a routine working precaution, always wear safety glasses and protective
gloves when operating, loading and unloading the furnace. In addition wear respira-
tory protection when cleaning or servicing the muffle chamber.
At the time of publication of this manual, The J. M. Ney Company is actively studying
and performing test as to comply with the State of California law requiring that the
public be informed of products containing materials which in some circumstances are
carcinogenic in nature. At the conclusion of this analysis, additional information will
be provided in new product Operator Manuals. Should you desire a copy of the find-
ings, write The J. M. Ney Company, Yucaipa, CA, or call (714) 795-2461 Jnd ask for
Customer Service.
1-2
RECEIVING INFORMATION
UNPACKING
Carefully remove the furnace from the shipping carton. Save the carton and packing
materials. The carton serves as the best container for transporting the furnace.
- One furnace
LOSS OR DAMAGE
If there is any visible damage, do not attempt to operate the furnace. Note any exter-
nal evidence of loss or damage on the freight way bill or express receipt and have it
signed by the carrier's agent. Failure to adequately describe such external evidence
of loss or damage may result in the carrier's refusal to honor your damage claim. The
form required to file such a claim will be supplied by the carrier.
Concealed loss or damage means loss or damage which does not become apparent
until the merchandise has been unpacked and inspected. Should either occur, make
a written request for inspection by the carrier's agent within 15 days of the delivery
date. Then file a claim with the carrier since the damage is the carrier's responsibility.
6-525 MUFFLE
The 6-525 muffle (heating chamber) is constructed in one piece. It is considered nor-
mal for cracks to appear on the surface, along edges and in the corners. This will not
degrade or limit the performance or life of the muffle.
2-1
INSTALLATION
Remove all packing materials from inside and around the furnace. Select a benchtop
location within five feet (1.5 meters) of the power receptacle. The furnace should be
on a level surface at least 6 inches (16 cm) away from walls, other equipment, and
heat sensitive materials. Do not mount under shelves or other structures that will
restrict the flow of air. The furnace should be located under an exhaust hood if mate-
rial or chemical reactions will be taking place inside the furnace.
The power receptacle should have the following overcurrent protection as follows:
6-525 15 Amp fuse or circuit breaker
(100V units require 20 Amp)
6-160A, 6-1350 ...20 Amp fuse or circuit breaker with receptacle for
furnace only.
Firing trays are supplied with the furnace. Please place these in the muffle before the
first firing. These will prevent molten materials from flowing into the muffle.
6-160A and 6-1350A ONLY: The air exchange feature on these furnaces is accessible
from the rear of the furnace. If the integral fan is not to be used the rear damper
panel must be lowered. The compressed air fitting (1/8" female NPT) is then acces-
sible behind the damper panel.
If the top exhaust port is to be plugged, then it is recommended that the rear damper
panel be lowered. This will minimize the escape of hot air from around the door and
resulting discolored paint.
6-525 ONLY: The exhaust port along with mounting screws are packed in the top
packing insert. Locate the port and install it on top of the furnace.
3-1
FEATURES
GENERAL
> Six Stages (Segments) Of Temperature Control
> Four User Definable Stored Programs (Chainable Into 24 Stages Total)
6-52$
> Large Low Thermal Mass Fiber Muffle - Fast Heat and Cool Rates
6-16*>A
> Integral Fan for Forced Air Exchange
4-1
SPECIFICATIONS
ELECTRICAL:
6-525 6-1350A 6-160A
MECHANICAL:
5-1
OPERATIONAL:
Note: See following graphs for actual expected heat rate performance. 40°C(72°F)/
MIN is not possible at the maximum temperatures, air exchange, or withfnaximum
loads.
5-2
HEATING CURVES:
1100
1000
800..
T 6-1350A
E FAN OFF
M
P 6-1350A
E FAN HIGH
600
R
A 6-160A
T FAN HIGH
U
R
E
400..
200--
10 20 30 40 50 60 70 80 90 100 110
TIME (Minutes)
TEST CONDITIONS: Nominal Line Voltage; No Load In Muffle; Full Power Applied To Muffle; 6-160A
and 6-1350A with Internal Fan Set To 0 for OFF and 9 for MAX.
5-3
COOLING CURVES:
1100
1000__
800 _.
T
E
M
P
E 600
R
A
T FAN OFF
U 6-160A
R FAN HIGH .6-525
E 400
200--
0 0 10 20 30 40 50 60 70 80 90
TIME (Minutes)
TEST CONDITIONS: No Load In Muffle; No Power Applied To Muffle; 6-160A and 6-1 >0A with Internal
r
an Set To 0 for OFF and 9 for MAX.
5-4
FURNACE DESCRIPTION AND OPERATION:
6
"525: EXHAUST
'PORT
POWER
CORD
AUX1
OUTPUT
MUFFLE
THERMOCOUPLI
DOOR POWER
INSULA- CONTROL
SWITCH
TION PANEL
6-1
6-160A:
6-2
£:-:':£:::":::£::::::i&:&^
6-1350A:
6-3
CONTROL PANEL DESCRIPTION:
2.
IE*TAT C
/F
2 3
PROGRAM
1 0 BATT
SELECT 5 6
1 C3 C3 C3 L13
en
STAGE STAG£ SiPtib STAGE Sl«at: SiAafc
TIME,
2 nn 1 2 3 A 5 6
AUX1
8 9
HOLD
3 CD START RESU
START ENTER
4 RATE TEMP TIME
STOP
1.
NOTE: 1350A KEY LOCATIONS ARE SLIGHTLY DIFFERENT BUT PERFORM THE SAME OPERATIONS.
1. POWER SWITCH Turns main power on and off to furnace. Does rfot start
furnace operation.
4. DELAY START Turns the furnace on at a later time and runs the preselected
cycle. Also gives operator access to program ti e amount of
delay time desired. Pressing the DELAY START key causes
the DELAY START LED to flash and the current' alue to be
displayed. A new value can be programmed or he START/
STOP key can be pressed to start a cycle after a delay.
6-4
RATE refers to the desired temperature increase or de-
crease in tenths of a degree per minute (xx.x°/min). The
decrease in temperature or cooling is limited by the natural
cooling RATE of the furnace and its load. The control can
force it to be slower but not faster. See the heating and
cooling curves in Section 5.
9. TEMP / CYCLE TIME Resets the display to the current muffle temperature if para-
meters are being reviewed or programmed. Displays the
cycle time remaining in a TIME segment during operation.
6-5
10. START/STOP Starts the furnace. The cycle will operate as prdhrammed.
Stops the cycle if the furnace is operating. Restarting a
cycle that has been stopped with the START/STjpP key will
restart it from the beginning.
11. Digit or Numeric Keys Used to enter temperatures, times, and heat rates.
When entering a value, any incorrect entry can me changed
by reentering the correct value. The incorrect v|lue will dis-
appear off the left side of the display.
12. ENTER Confirms the Numeric Key entries and stores th|m in the
control's memory.
13. Parameter LED's LED's in the graph next to the switches are use|( to indicate
control status.
14. PROGRAM SELECT 1-4 Selects PROGRAM to be reviewed, programmed, or
run by the control. A new program can be seleited when-
ever the control is not running the current progfam.
15. STAGE 1-6 Selects the STAGE (segment) of the selected p gram to be
reviewed or programmed. The stages of the c rently se-
lected program can be reviewed at any time. T! e corre-
sponding LED lights with each key and goes o in seven
seconds if a parameter key (RATE, TEMP, TIM AUX) is not
pressed. Stage parameters can be reprogram led only
when the control is not running the current pro ram or when
the current program has been put on "HOLD".
All the STAGE LED's that are programmed light when the
furnace is started. They go out in sequence asfeach STAGE
is completed.
16. AUX1 Normally open electrical contact output that call be pro-
grammed to turned on and off as the furnace runs the
preprogrammed cycle. The AUX 1 output can i e pro-
grammed to be on or off independently for eacp segment of
a cycle. The IEC socket on the back of the furnace provides
a 5 amp max fused contact closure when turnei on.
6-6
17. AUX 2 NOTE: NOT APPLICABLE TO 6-525
The AUX 2 key controls the air exchange fan located on the
back of the furnace. The AUX 2 or air exchange fan can be
programmed to be on at a particular level or off independ-
ently for each stage of a cycle or program. The speed of the
fan (0 for OFF and 9 for MAX) which is related to the number
of air exchanges can also be programmed.
Auxiliary Output
Rear connection for AUX 1 described previously.
6-7
OPERATING THE FURNACE:
POWER ON:
Turning on the power switch activates the control. The control perf|rms a self-
test for approximately three seconds and displays the model numblr (ie. 525,
160A, or 1350A). At the end of the self-test the actual muffle tempei|jture is dis-
n played.
If an operating cycle is stopped with the START/STOP key, pressing the key a
second time will restart the cycle from the beginning. If the muffle is at an
elevated temperature, the control will use the programmed RATE 1||or the cool-
ing or heating to TEMP 1.
If the model number is not displayed or the display sequences throjigh all the
model numbers listed on the front cover; see BATTERY REPLACEMENT and
CONFIGURATION SETUP in Maintenance Section 7.
The furnace's operation can be changed in several ways by changing the "de-
fault settings". These are the preselected parameters the factory entered when
the unit was tested. For more information about these see CONFIGURATION
SETUP later in this section under programming.
6-8
STARTING THE FURNACE WITH A DELAY START:
A value for the DELAY START must be programmed first (The default value is
preprogrammed to zero). Press the DELAY START key followed by the digit
keys of the desire amount of delay in hours. The DELAY START LED will flash
and the programmed value will be displayed. Pressing the ENTER key will
store this value and turn off the DELAY START LED. Pressing the DELAY
START key again will activate the function, flash the LED, and display the delay
value in hours. Pressing the START/STOP key will start the delay followed by
the selected program. The DELAY START LED will be on during the delay.
FURNACE OPERATION:
During cycle operation all the indicating LED's (Program and Stage) for a cycle
will initially light and go out as that portion of the cycle is completed. The
RATE and TIME - TEMP LED's will alternately come on. If a DELAY START has
been selected, its LED will light first and when the delay is complete the rest of
the cycle LED's will light.
A flashing RATE LED indicates that the control is unable to maintain the pro-
grammed rate of change in temperature. The flashing is only an indication for
the operator; the furnace will continue the cycle uniterrupted. This condition
can be caused by programming the furnace with high programmed RATE,
large loads, or low power line voltages. Refer to the heating and cooling
curves in the SPECIFICATIONS section 5 for more information.
A power outage or turning off the power when the furnace is in the idle or off
mode does not cause a loss of the programs. The furnace will resume a delay
start cycle if a power interruption occurs during its operation. A power outage
when the furnace is heating will result in the resumption of the cycle when
power is reapplied, if the muffle temperature has dropped less than 50°C
(90°F). If the muffle temperature has dropped more than 50°C (90°F) the fur-
nace turns off. If power is interrupted or the power switch is turned off when
the furnace is operating at less than 100°C, the furnace will turn on when
power is reapplied.
HOLDING A TEMPERATURE:
The furnace can be stopped or held in the middle of a cycle indefinitedly by
pressing the HOLD/RESUME key. The muffle temperature, when the key is
pressed, will be maintained with the associated HOLD LED, STAGE LED, and
parameter LED on. Pressing the key a second time releases the control and it
resumes the cycle that is had been operating. The program parameters can be
reprogrammed when the control is put in the HOLD mode.
6-9
END OF CYCLE:
The default "End Of Cycle" maintains the last programmed temperature, dis-
plays "HOLD" and beeping every six minutes. Other "End Of Cycle! operations
available include maintaining the last programmed temperature without beep-
ing, turning off the muffle at the end of the cycle while displaying VEND", and
continuously repeating the cycle. The end of cycle default setting dan be
changed by following the directions outlined later in this section urfper CON-
FIGURATION SETUP.
DELAY START:
Pressing the DELAY START key displays the current programmed ialue and
flashes the associated LED. When the LED is flashing, the DELAY iTART value
can be reprogrammed by keying in a new value followed by the El ERkey. If
the value already stored for the delay start is acceptable, then eithi If the ENTER
key or the TEMP / CYCLE TIME key can be pressed to save the vaii e. If an
incorrect digit key is pressed while entering a parameter, the correl ;t parameter
should be reentered. The incorrect digit will shift off the display to| he left. An
alternate method to clear an incorrect entry is to press the DELAY TART key a
second time.
PROGRAMS:
Any one of the four programs can be selected for operation or programming
independently. Pressing a PROGRAM key activates that program and the
associated LED lights.
STAGES:
Once a program has been selected the individual stage RATE'S, TiMP's,
TIME'S, and AUX's can be programmed. A STAGE key has to be pressed before
the various parameters can be programmed. After the key is pressed the
STAGE LED will remain on for 7 seconds if no other keys are pressed. If one of
6-10
the parameter keys is pressed, it will remain on until the ENTER or TIME/TEMP
key is pressed. If the LED goes out, the STAGE key must be pressed again.
RATES:
The RATE key sets heat rate or temperature increase rate. Pressing the RATE
key displays the currrent value for the program and stage selected. The corre-
sponding RATE LED also flashes.
While the RATE LED is flashing, a new RATE can be entered on the keyboard.
If an incorrect digit key is pressed while entering a parameter, the correct pa-
rameter should be reentered. The incorrect digit will shift off the display to the
left. Once the correct value is displayed, save it by pressing the ENTER key. If
the ENTER key is not pressed, the original value will be retained and the new
value will be lost. After the ENTER key is pressed, the display returns to the
current muffle temperature.
Entering a 0 for any RATE (2 through 6) causes the cycle to end after the previ-
ous stage. (Example: RATE 4 = 0; Program ends after STAGE 3). Program-
ming RATE 1 to 0 causes the program to start with STAGE 2.
TEMPERATURES:
The TEMP key sets the muffle temperature. Pressing the TEMP key displays
the current value for the program and stage selected. The corresponding
TEMP LED also flashes.
TIMES:
The TIME key sets the length of the hold time at the programmed temperature.
Pressing the TIME key displays the current value for the program and stage
selected. The corresponding TIME LED also flashes.
While the TIME LED is flashing a new time can be entered for the selected
STAGE on the keyboard. If an incorrect digit key is pressed while entering a
parameter, the correct parameter should be reentered. The incorrect digit will
shift off the display to the left. Once the correct value is displayed, save it by
pressing the ENTER key. If the ENTER key is not pressed, the original value
6-11
will be retained and the new value will be lost. After the ENTER k / is pressed,
the display returns to the current muffle temperature.
Setting the last TIME to 0 causes the control to end the cycle and hut off. The
muffle temperature is not held. The last TIME can be TIME 6 or th TIME im-
meadiately before a RATE set equal to zero.
AUXILIARY OUTPUT # 1 :
The AUX 1 output is a normally open electrical contact accessible 0 the user in
the rear of the furnace close to the power cord. A adaptor plug is upplied in
the accessory kit to make the connections. The socket for AUX 1 1 fused at 5
amps with the fuses mounted in the socket.
The AUX 1 contacts can be independently closed (ON) or opened OFF) for
each STAGE of each PROGRAM. The AUX 1 is programmed to be ON (contacts
closed) by selecting a STAGE key of a program followed by the A X 1 key.
"AUX1 ON *" will be displayed if it was previously programmed to te off. Press-
ing the AUX 1 key a second time turns it off. "AUX1 OFF" is displa ed. "*"is
displayed in the far right character of the display when AUX 1 is o and the
cycle is running.
A fan symbol"-1 -" will appear in the far left character of the display, The two
bars in the display will rotate at a speed relative to that programmed. If 1 is
6-12
programmed they will rotate slow. If 9 is programmed they will rotate fast.
During cycle operation this symbol will appear when ever the fan is pro-
grammed to be on.
Compressed air or inert gas can also be ported into the furnace muffle via the
rear female 1/8"NPT fitting. This fitting is located behind the fan damper.
Lower the damper for access. The gas will be preheated by the bottom heating
plate and injected into the front of the furnace. The graph below gives an ap-
proximate relationship between changes per minute and gas pressure.
C •7
1
H
A
N c /
0
G
E /
'e-ieoA
5
S
P 4 /
E /
R I5-1350A
0 /
M
I /
£.
N
U
1
T
E
0
0
1
10 20 30 40 50 60
I 70 80 90 100 110
PRESSURE (PSI)
Note: Maximum Pressure Allowable is 120 PSI
6-13
CONFIGURATION SETUP:
The furnace has other features or operations that are only accessible whfen power is
applied (power up). These features are programmed by pressing the ENTER key
during the 3 seconds after power up when the furnace displays the modjl number.
"SELECT" will appear on the display to indicate configuration setup.
END OF CYCLE:
(1) Pressing the 1 key followed by the ENTER key will cause the cintrol to
continuous hold the last TEMP and beep every 6 minutes. 1HOLD
TEMP" is displayed. (This is the factory preset.)
(2) Pressing the 2 key followed by the ENTER key will cause the cintrol to
continuous hold the last TEMP without beeping. "HOLD TEMP" is dis-
played.
(3) Pressing the 3 key followed by the ENTER key will cause the c ntrol to end
the cycle and shut off the muffle after the last TIME. "END" 5 displayed
and the control beeps three times.
(4) Press the 4 key followed by the ENTER key will cause the cont||ol to con-
tinuously repeat the cycle that has been started.
The furnace will now shut down and display "Err3" if the nibffle tempera-
ture goes above the programmed High Limit Cutoff. The eiror is cleared
by turning off the furnace. Attempting to program a temperature higher
than the High Limit Cutoff will cause the control to beep anp display the
maximum temperature.
6-14
SYSTEM RESET: CAUTION!!!
(7) Press the 7 key followed by the ENTER key will cause the control to reset all
the parameters and settings in the control. "Reset" will be displayed.
This is for diagnostics and system checking.
To end the configuration setup routine press the 9 key followed by the ENTER
key. The control will go into normal operation displaying the current muffle
temperature.
6-15
EXAMPLE
SITUATION:
You wish to do a six stage temperature profile. The following heating ra. . !S, tempera-
tures and holding times are desired.
1. RATE=45°F/min TEMP=500°F TIME=.3 Hour
2. RATE=10°F/min TEMP=760°F TIME=.5Hour
3. RATE=5°F/min TEMP=1200°F TIME=1.7 Hours
4. RATE=10°F/min TEMP=1760°F TIME=3 Hours
5. RATE=-.5°F/min TEMP=1510°F TIME=.1 Hours
6. RATE=-10°F/min TEMP=1000°F TIME=30 Hours
6-16
22. TEMP Press key until the TEMP 3 LED flashes.
23. 1-2-0-0 1200°F
24. ENTER TEMP 3 is now programmed
25. TIME Press key until the TIME 3 LED flashes.
26. 1-7 1.7 Hours
27. ENTER TIME 3 is now programmed.
STAGE 3 IS NOW PROGRAMMED.
28. RATE Press key until the RATE 4 LED flashes.
29. 1-0-0 10.0°F/min
30. ENTER RATE 4 is now programmed.
31. TEMP Press key until the TEMP 4 LED flashes.
32. 1-7-6-0 1760°F
33. ENTER TEMP 4 is now programmed
34. TIME Press key until the TIME 4 LED flashes.
35. 3-0 3.0 Hours
36. ENTER TIME 4 is now programmed.
STAGE 4 IS NOW PROGRAMMED.
37. RATE Press key until the RATE 4 LED flashes.
38. 5 0.5 °F/min
39. ENTER RATE 5 is now programmed.
40. TEMP Press key until the TEMP 4 LED flashes.
41. 1-5-1-0 1510°F '
42. ENTER TEMP 5 is now programmed
43. TIME Press key until the TIME 4 LED flashes.
44. 1 0.1 Hour
45. ENTER TIME 5 is now programmed.
STAGE 5 IS NOW PROGRAMMED.
46. RATE Press key until the RATE 6 LED flashes.
47. 1-0-0 10.0°F/min
48. ENTER RATE 6 is now programmed.
49. TEMP Press key until the TEMP 6 LED flashes.
50. 1-0-0-0 1000°F
51. ENTER TEMP 6 is now programmed
52. TIME Press key until the TIME 6 LED flashes.
53. 3-0-0 30.0 Hours
54. ENTER TIME 6 is now programmed.
STAGE 6 IS NOW PROGRAMMED.
After TIME 6 the control will continue to hold the last temperature (TEMP 6) until
turned off while beeping every 6 minutes.
6-17
MAINTENANCE
CLEANING:
Vacuum (rather than blow) any muffle dust found in and around the furnace.
This will minimize the airborne dust.
Clean the control panel with a soft dry cloth. Do not use water, liquids or spray
cleaners on the panel or on the cloth. These cleaners can enter the switch
panel and cause damage.
Clean the furnace cabinet with any household non-abrasive cleaner and a soft
cloth.
CALIBRATION:
Under normal use the furnace will not require calibration. Situations where cali-
bration may be required include thermocouple damage and replacement, con-
trol/power pc board assembly replacement.
Once a measurement has been recorded, turn off the furnace and unplug its
power cord. Allow the furnace to cool to room temperature. Remove the con-
trol panel by following the directions under "Control Panel Removal" in section
8. The following directions apply once the control panel is opened.
The trimmer/potentiometer labeled R12 "SPAN ADJ" (see page 8-4) on the
computer/power printed circuit board assembly (horizontally mounted pcb) will
be adjusted to correct the calibration. If the muffle temperature measures
higher (positive difference in example above) than the furnace indicates, turn
7-1
the trimmer/potentiometer labeled R12 "SPAN ADJ" clockwise (CV|) to reduce
the display temperature. The potentiometer should be turned one lomplete
turn for every 10°C of difference. If the temperature measures lowlr (negative
difference) adjust the potentiometer counterclockwise (CCW) usin| the same
ratio.
BATTERY REPLACEMENT:
If the program contents are lost when the furnace power is turned | n and off,
then the battery is dead. In addition, if the "Low Batt" indicator flashes the
battery should be replaced. The battery in question is a small Lithfim coin type
battery (#2032).
CONFIGURATION SETUP:
When powered up for the first time after battery replacement, the control will
display a series of furnace model numbers (ie 525,160A, 1350A). fress the EN-
TER key when the correct model number of the furnace being worlled on ap-
pears. A pattern similar to "SELECT" will appear to indicate configuration
setup. Pressing the 9 key followed by the ENTER key will place the control in
the normal operating mode. See the CONFIGURATION SETUP in t | e program-
ming section 6 for details on possible operating mode changes.
MUFFLE REPAIR:
The 6-525 furnace muffle is constructed of a lightweight fiber insulltion. Exer-
cise caution to prevent punctures or tears in the muffle when loading and un-
loading the furnace. Punctures exposing the heating elements embedded in
the insulation may significantly shorten muffle life. The accessory peramic tray
provided with the furnace should be used to protect the muffle floe
Damage to the fiber insulation in the muffle or the door can be replired. A
bottle of "Fiber Harding Agent" has been included with your furnace shipment.
7-2
The "Fiber Harding Agent" is a binding solution with the viscosity of water. It
will harden the surface which was damaged. Directions for using this material
are listed below:
7-3
SERVICE
This section is provided as assistance to qualified service personnel. If you are quali-
fied to service the furnace, please read the entire manual before you attempt any
servicing.
IF YOU ARE NOT QUALIFIED TO SERVICE THE FURNACE, PLEASE READ THE
PARAGRAPH BELOW, AND FOLLOW THE DIRECTIONS SPECIFIED.
If the unit requires service, review pages 8-2 and 8-3 before contacting the service de-
partment at your dealer or The J. M. Ney Company, Yucaipa, CA. Describe the par-
ticular problem and give the model and serial numbers of the furnace. This informa-
tion is located on the data plate attached to back of the furnace. An RMA (Return
Material Authorization) number will be assigned to your unit as a control during the
repair period. The RMA number must appear on the shipping label so we can give
you fast and dependable service.
(714)795-2461
FAX: (714) 795-5268
8-1
TROUBLESHOOTING and ERROR CODES:
(See 5.0.0 Below for the "ERR" codes)
Review the following list of questions and suggestions before calling thefeervice
number listed on the previous page. Some of the answers may prove hefpful in help-
ing us solve the problem.
2.0.0 No operation - Furnace Dead - Display does not lightup , LED's do fiot come on,
and muffle does not heat.
2.1.0 Does the power receptacle have power? Test with another lo d (ie lamp or
radio.)
2.2.0 Does furnace beep when power is turned on? If yes, go to 2 ,0. If no, go
to 2.9.0.
2.3.0 Do any of the LED's on the control/power board light? Look fito rear back
vents of furnace. If yes, check pc board to pc board connections,
2.9.0 Please note the answers to the following questions before ca ing the
service telephone number listed on page 8-1.
What is model number and serial number of furnace? (List data plate
on back of furnace.)
Did furnace ever operate? For how long?
8-2
4.3.0 Cabinet around the door is discoloring. ("A" models only) Remove ex-
haust port ball plug if air exchange fan or compressed air fitting is being
used.
5.5.0 "DOOR" remains on display when door is closed. Check door switch con-
tinuity. Check door switch actuator tab by listening for switch click as
door closes.
8-3
6-525 SCHEMATIC:
AUX1 RECEPTACLE
5 Amn Fused
220 / 240V
RECEPTACLE
CONTROL
EARTH
GROUND
DOOR
SWITCH
THERMOCOUPLE
COMPUTER/POWER
PC BOARD
f \ r -\
MEMBRANE
SWITCH
\. J
8-4
6-160A and 6-1350A SCHEMATIC:
HEATING ELEMENTS
DOOR
SWITCH
THERMOCOUPLE
MUFFLE
CONNECTIONS
1350A SHOWN
R12
CALIBRATION
ADJUSTMENT ' 220/240V
RECEPTACI
COMPUTER/POWER
?C BOARD
CONTROL
EARTH
GROUND
ENCLOSURE
GROUND
AUX 1 SOCKET
(5 Amp Fused)
White
POWER
SWITCH Red
8-5
DISASSEMBLY INSTRUCTIONS:
Respiratory, eye, and hand protection should be worn during the followin|j proce-
dures.
The following tools are required for disassembly/reassembly work descr ed in this
section.
* Small blade screwdriver * Medium Phillips screwdriv
* Needle nose pliers * Regular pliers
6-525 SERVICE:
6-525 CONTROL PANEL REMOVAL:
(Access to pc boards, triac, power switch, door switch, thermocouple nd muffle
wiring connections)
1. Turn off the power to the furnace and remove the line cord from the \ia\\ recep-
tacle/outlet. Allow the furnace to cool to room temperature before tailing
service.
2. Remove 9 screws from around the top, sides, and bottom of the con rol panel.
Hanging the front of the furnace off of the counter by 2 inches (50n m) will aid
in removing the bottom screws.
3. The control panel can now be removed by pulling it out the front of t le furnace
while raising the panel up slightly. The control panel will slide out pproxi-
mately 6 inches (150mm).
4. With the control panel pulled out, various connections can be access ed. The pc
boards are replaceable along with the membrane switch panel with its mount-
ing plate with the drawer out. The control can be examined at this >oint along
with battery replacement and temperature calibration.
5. If the control panel is to be completely removed, the wiring connecti ns should
all be noted, labeled, or verified with the schematic included in this manual.
6. Reverse the steps above for reinstallation making sure that all electr cal connec-
tions are tight.
8-6
2. Remove Control Panel by following the instructions above.
3. Disconnect thermocouple red and yellow wires from the left-hand side of the
computer/power pc board. Disconnect the blue or blue/white muffle wires from
computer/power pc board and triac.
4. Remove the exhaust port by removing the 3 retaining screws.
5. Remove Front Panel from enclosure by removing 7 screws from top and sides.
6. The Front Panel with the muffle attached pulls out of the front of the enclosure.
7. The thermocouple can now be removed from the back of the muffle by pulling it
out.
8. Route the thermocouple through the bushing in the rear of the heatshield and
behind the door switch bracket.
9. Reverse steps 1-6 for reinstallation.( Note: The screws holding the front panel to
the cabinet must be installed prior to installing the control panel.
6-160A SERVICE:
6-160A CONTROL PANEL REMOVAL:
(Access to pc boards, triac, power switch, door switch, thermocouple and
muffle wiring connections)
1. Turn off the power to the furnace and remove the line cord from the wall recep-
tacle/outlet. Allow the furnace to cool to room temperature before starting
service.
2. Remove 9 screws from around the top and bottom of the control panel. Hanging
the front of the furnace over a counter by 2 inches (50mm) will aid in removing
8-7
the bottom screws.
3. The control panel can now be removed by pulling it out of the front the furnace
while raising the panel up slightly. The control panel will slide out pproxi-
mately 6 inches (150mm).
4. With the control panel pulled out, various connections can be acces ted. The RC
boards are replaceable along with the membrane switch panel wit [its mount-
Ing plate. The control can be examined at this point along with ba jry replace-
ment and temperature calibration.
5. If the control panel needs to be completely removed, the wiring con lections
should all be noted, labeled, or verified with the schematic include in this
manual.
6. Reverse the steps above for reinstallation making sure that all elect leal connec-
tions are tight.
8-8
6-1350A SERVICE:
6-1350A CONTROL PANEL REMOVAL
(Access to pc boards, triac, power switch, door switch, also thermocouple and
muffle wiring connections)
1. Turn off the power to the furnace and remove the line cord from the wall recep-
tacle/outlet. Allow the furnace to cool to room temperature before starting
service.
2. Remove the rear electrical panel (3 screws in lower left of furnace back, looking
from the rear.) and lay it to the side. The retaining screw for the control module
is located above and inside the furnace.
3. Push on this screw as it is removed. The control panel will slide out the front. The
control panel can be pulled out approximately 6 inches before any wires need
to be disconnected.
4. Refer to the schematic/wiring diagram (page 8-5) before removing any wires.
Calibration can be done in this position and most of the other possible service
requirements such as PC board replacement, triac replacement, and trou-
bleshooting.
5. To replace the control panel assembly, reverse the disassembly procedure.
1. Turn off the power to the furnace and remove the line cord from the wall recep-
tacle/outlet. Allow the furnace to cool to room temperature before starting
service.
2. Remove the furnace back by removing the back panel screws.
3. Remove the thermocouple from the muffle and push it back into the control
section.
4. Disconnect the power leads connecting the muffle to the control section. Discon-
nect all of the individual muffle plate connections from the terminal block.
5. Remove the 6 screws which hold the muffle back to the muffle, then remove the
aluminum back.
6. Remove the exhaust port tube by removing the 3 retaining screws.
7. Remove the rear fiber brick from the back of muffle. It will slide out the back
while the leads are fed through it. TAKE CARE NOT TO DAMAGE THE BRICK.
Note: Each plate supports the others. The sides or top plates will fall unless ade-
quate support is provided.
8. Slide the top plate out the back while supporting the others. Continue with the
sides and then the bottom plate.
9. The muffle can now be reassembled using the new part.
10. To reassemble, reverse the procedure and use the following precautions:
- Fiber rope used between top plate and top brick must be put back in place.
8-9
Fiber rope used between back brick and rear edges of plates must bp reinstalled
to prevent air from flowing into the chamber before preheating.
8-10
REPAIR PARTS
The furnace and its internal components and assemblies are delicate and need to be
packed properly for return shipment. Pack all parts or assemblies in a bag then foam
and seal them in suitable boxes. Use original packaging when it is available.
FURNACE 6-525
VOLTAGE
DESCRIPTION 100V 120V 220V 240V
Triac -—R9303015
Power Switch R9306021
Control/Power PC Board
Assembly —R9492572 R9492573
Display PC Board
Assembly . R9492703
Battery, Lithium
Panasonic Part Number Obtain Locally
BR2032
Radio Shack Number
CR2032
9-1
EXPLODED VIEW 6-525
MUFFLE
SPRING
DOOR + FRONT
PANEL
CONTROL
PANEL DIS1LAY
PC BOARD
SWlfTCH PLATE
MEMBRANE
SWITCH
CONTROL/
POWER
PC BOARD
POWER
SWITCH
9-2
FURNACE 6-1350A
The furnace and its internal components and assemblies are delicate and need to be
packed properly for return shipment. Pack all parts or assemblies in a bag then foam
and seal them in suitable boxes. Use original packaging when it is available.
VOLTAGE
DESCRIPTION 220V - 240V
Triac R9303015
Power Switch R9306021
Control/Power PC Board
Assembly R9492573
9-3
EXPLODED VIEW 6-1350A:
,CK PANEL
FAN, DUCT,
DAMPER ASSY
EAR ELECTRICAL
ANEL AND LINE CORD
CONTROL
PANEL
CONTROL/
POWER
PC BOARD
\DISPLAY
POWER .MEMBRANE PC BOARD
SWITCH SWITCH
9-4
EXPLODED VIEW 6-1350A MUFFLE:
Terminal
Block
9-5
FURNACE 6-160A
The furnace and its internal components and assemblies are delicate an i need to be
packed properly for return shipment. Pack all parts or assemblies a in I ag then foam
and seal them in suitable boxes. Use original packaging when it is avail ible.
VOLTAGE
DESCRIPTION 100V 120V 220V 240V
Thermocouple R9491747
Triac R9303015-—
Control/Power PC Board
Assembly —R9492570 R9492J 71 —
#
Display PC Board
Assembly R9492702
9-6
EXPLODED VIEW 6-160A:
BACK PANEL
DAMPER
THERMOCOUPLE
ASSEMBLY
DOOR + FRONT
PANEL
DISPLAY
PC BOARD
CONTROL
PANEL SWITCH PLATE
MEMBRANE
SWITCH
CONTROL/
POWER
PC BOARD
POWER
SWITCH TRIAC
9-7
ACCESSORIES
10-1
LIMITED WARRANTY and LIMITATION OF LIABILITY
1. WARRANTY: Except with respect to those components parts and uses which are
hereinafter described, The J.M. Ney Company warrants this furnace to be free from
defects in material and workmanship for a period of one year from the date of sale.
The J.M. Ney Company's liability under this warranty is limited solely to repairing or,
at Ney's option, replacing those products included within the warranty which are
returned to Ney within the applicable warranty period (with shipping charges pre-
paid), and which are determined by The J.M. Ney Company to be defective. This
warranty shall not apply to any product which has been subject to misuse; negli-
gence; or accident; or misapplied; or modified; or repaired by unauthorized per-
sons; or improperly installed.
3. INSPECTION: Buyer shall inspect the product upon receipt. The buyer shall
notify The J.M. Ney Company in writing of any claims of defects in material and
workmanship within thirty days after the buyer discovers or should have discovered
the facts upon which such a claim is based. Failure of the buyer to give written
notice of such a claim within this time period shall be deemed to be a waiver of such
claim.
4. DISCLAIMER: The provisions here-in stated The J.M. Ney Company's sole obli-
gation and exclude all other remedies or warranties, expressed or implied, including
those related to MERCHANTABILITY and FITNESS FOR A PARTICULAR PURPOSE.
6. LIMITATION OF ACTIONS: The buyer must initiate any action with respect to
claims under the warranty described in the first paragraph within one year after the
cause of action has accrued.
Corporate Offices: