Transformer Bushings, Type GOB: Technical Guide

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

1ZSE 2750-102 en, Rev.

Transformer bushings, type GOB


Technical guide
Original instruction

The information provided in this document is intended to be general and does not
cover all possible applications. Any specific application not covered should be
referred directly to ABB, or its authorized representative.

ABB makes no warranty or representation and assumes no liability for the


accuracy of the information in this document or for the use of such information. All
information in this document is subject to change without notice.

This document must not be copied without our written permission, and the contents
thereof must not be imparted to a third party nor be used for any unauthorized
purpose. Contravention will be prosecuted.
Content
Content........................................................................................................................... 3
Design............................................................................................................................. 4
Features and benefits................................................................................................. 4
Shed profile, GOB 52 - 170 kV.................................................................................. 5
Shed profile, GOB 300 kV.......................................................................................... 5
General specifications................................................................................................ 5
Testing............................................................................................................................. 6
Test tap...................................................................................................................... 6
Test tap adapter......................................................................................................... 6
Electrical data.................................................................................................................. 7
Conductor loading........................................................................................................... 8
Overloading of bushings............................................................................................ 8
Short-time current...................................................................................................... 8
Dimensions...................................................................................................................... 9
Bushings without oil level gauge................................................................................ 11
Bushings with oil level gauge..................................................................................... 13
Ordering particulars......................................................................................................... 14
Bushings without oil level gauge................................................................................ 14
Bushings with oil level gauge..................................................................................... 16
Connection details........................................................................................................... 18
Inner terminal............................................................................................................. 18
Solid rod conductor................................................................................................... 18
Outer terminal............................................................................................................ 19
Separate terminal plate with bolts.............................................................................. 19
Arcing horns.............................................................................................................. 19
Type GOB 1050............................................................................................................... 20
Dimensions................................................................................................................ 20
Ordering particulars................................................................................................... 21
Recommendations for positioning................................................................................... 22
Design

The bushing is built up around a centre tube on which the


condenser body is wound. The upper insulator, lower insulator
and mounting flange are held between the end plates by the
centre tube. Sealing is accomplished by oil-resistant rubber Outer terminal stud
gaskets in grooves.
Oil filling hole
with sealing plug Top
The annular space between the condenser body and the washer
Expansion space
porcelain is filled with transformer oil. A gas-filled expansion
space is left at the top. For GOB bushings without oil level Oil Top
gauge the oil level can be checked by means of a dipstick in housing

the oil filling hole.


Porcelain insulator
air side
The lower end is shielded by an epoxy resin insulated
aluminium shield. The shield is integrated for 52–170 kV, and
separate for 300 kV bushings.
Test tap

The inner terminal is attached to the centre tube by means


Mounting flange
of a through-going resilient pin which becomes locked when
the outer terminal is screwed on. This design, patented by
ABB, ensures effective electrical contact between the inner
Flange extension
and outer terminals. The inner terminal can be chosen for
connection to leads either by brazing or crimping. Top
Porcelain insulator housing
oil side
The outer terminal is available in aluminium or copper alloy Prism
Condenser body glass
and can be supplemented by terminal plates of corresponding
material.
Insulated shield Oil filling holes
(integrated or with sealing
The upper insulator is made in one piece of high quality separate) plug
electrical porcelain. The mounting flange is manufactured of
corrosion-resistant aluminium alloy.

The mounting flange, the top housing and the top washer
are protected by painting with a two-component primer and Fig. 1. Transformer bushing type GOB.
a grey-blue finishing coat of paint. The standard colour is
Munsell 5.5B 55/1.25.
Features and benefits
The bushings are delivered oil-filled and ready for use. –– A complete range and outstanding operational experience
from the most demanding applications for more than 40
If the bushing is mounted with an inclination of more than years.
45° from the vertical, special measures have to be taken to –– 3D models makes it easy to incorporate the bushing in its
ensure the condenser body is fully immersed in oil. Further context.
information can be obtained on request. –– We use a sealing system proven since 50 years around the
world.
–– Our test criteria and margins exceeding international stan-
dards.

4 Technical guide GOB | 1ZSE 2750-102 en, Rev. 9


Shed profile, GOB 52 - 170 kV
The shed profile is designed according to IEC 60815 and is of
alternating type with long and short sheds.

For special customer demands regarding creepage distance,


other shed forms may be used.

Fig. 2. Shed profile, GOB 52 – 170 kV.


To the right: long creepage shed profile for GOB 250/800, 325/800,
380/1250, 550/800, 650/1250 and 750/1250.

Shed profile, GOB 300 kV


The shed profile is designed according to IEC 60815 and is of 67.5
R8
alternating type with long and short sheds.

For special customer demands regarding creepage distance,


18°

other shed forms may be used. 31


10°

70

R10
52.5 R4.5

Fig. 3. Shed profile, GOB 300 kV.

General specifications
Application: Transformers
Classification: Oil impregnated paper, capacitance graded, outdoor-immersed bushing
Ambient temperature: +40 to -40 °C, minimum value as per temperature class 2 of IEC 60137
(-60 °C according to GOST 10693-81 item 2.26)
Altitude of site: < 1 000 m
Level of rain and humidity: 1-2 mm rain/min horizontally and vertically, as per IEC 60060-1
Pollution level: According to specified creepage distance and IEC 60815
Type of immersion medium: Transformer oil. Maximum daily mean oil temperature 90 °C. Maximum temporary oil temperature 115 °C
Oil level below bushing flange: Maximum 30 mm
Max. pressure of medium: 100 kPa overpressure
Markings: Conforming to IEC/ IEEE

1ZSE 2750-102 en, Rev. 9 | Technical guide GOB 5


Testing

During the manufacture and on its completion the bushing is GOB 1050 is also routine tested with a dry lightning impulse
subjected to a number of routine tests, in compliance with voltage withstand test.
IEC 60137. A tightness test is carried out on the assembled
bushing after the final drying and impregnation. The test Type tests have been carried out according to IEC 60137 and
is made with an oil overpressure of 180 kPa (1.8 bar) for IEEE. Type test reports are available on request.
12 hours at ambient temperature. No sign of leakage is
allowed. Test tap
The outer conducting layer of the condenser body is
Each bushing is subjected to a final electrical routine test. connected to an insulated test tap on the flange. During
The test is made at room temperature with the bushing operation the test tap cover must be screwed on, in order to
submerged in oil. Capacitance and tan δ are measured in earth the bushing. The max. test voltage of the tap is 2 kV,
steps up to the power frequency withstand voltage, which is 50 Hz for 1 minute. Max. service voltage is 600 V.
maintained for one minute. Capacitance and tan δ are also
measured at decreasing voltage at the same voltage levels as Test tap adapter
before the one minute test. For permanent connection of the test tap to measuring
circuits, a test tap adapter is required. Catalogue number
Measurements for detection of internal partial discharge 1ZSC003881-AAC.
(PD measurements) are also made. These measurements
are carried out at the same time as the power frequency
withstand test. PD measurements are made in steps up to
the full test voltage and down. It is always demonstrated that
the PD value is max. 5 pC at test voltage equal to the rated
system voltage.

Fig. 4. Test tap Fig. 5. Test tap adapter.

6 Technical guide GOB | 1ZSE 2750-102 en, Rev. 9


Electrical data

Type GOB Rating Routine test Design data


Highest voltage Phase-to-earth Dry lightning Wet power 1 min. dry Dry switching Wet switching
for equipment voltage impulse frequency AC 50 Hz impulse impulse
Um Uy kV, peak kV, RMS kV, RMS kV, peak kV, peak
kV, RMS kV, RMS
250-800 52 52 250 105 120 230 -
250-1250 52 52 250 105 120 230 -
325-800 72.5 72.5 350 140 160 300 -
380-800 100 72.5 380 150 165 330 -
380-1250 100 72.5 380 150 165 330 -
450-800 123 90 450 185 195 410 -
550-800 170 123 550 230 260 470 -
550-1250 170 123 550 230 260 470 -
650-1250 170 145 650 275 300 580 -
750-1250 170 170 750 325 365 670 -
1050-1100 300 173 1050 510 510 810 750

1ZSE 2750-102 en, Rev. 9 | Technical guide GOB 7


Conductor loading

The rated currents listed in this catalogue are the


standardised values according to IEC 60137 which, with the
largest possible conductor, fulfil the temperature rise test.

The GOB bushings fulfil the temperature rise test requirements


according to IEC 60137 and IEEE C57.19.00-1991.

Rated current Conductor 52 – 170 kV 300 kV


A Permissible current Permissible current
IEC, A IEEE, A IEC, A IEEE, A
800 Solid rod LF 170 019 800 730
1100, 1250 Solid rod LF 170 052 1250 1200 1100 1000
800, 1100, 1250 Stranded cable 50 mm2 165 150 155 130
800, 1100, 1250 Stranded cable 70 mm2 225 210 190 160
800, 1100, 1250 Stranded cable 95 mm2 300 285 240 195
800, 1100, 1250 Stranded cable 150 mm 2
475 415 330 275
1100, 1250 Stranded cable 185 mm2 530 460 380 320
1100, 1250 Stranded cable 285 mm2 665 570 540 450

Overloading of bushings
If the conductor for the bushing is selected with 120 % of the
rated current of the transformer, the bushing is considered
to be able to withstand the overload conditions stated in
IEC 60354 without further clarifications or tests, according to
IEC 60137.

Short-time current
The rated thermal short-time current (Ith) is calculated
according to IEC 60137.

For draw-lead of stranded copper, values are given for


100 mm2. For other areas the short-time current is directly
proportional to the area.

Conductor Rated current Area mm2 Short-time current (Ith) Dynamic current (I d)
A 1s 2s kA, peak
kA, RMS kA, RMS
Solid rod 800 - 30 21 52
Solid rod 1100/1250 - 70 50 125
Stranded draw-lead 365 100 9.6 6.8 17

8 Technical guide GOB | 1ZSE 2750-102 en, Rev. 9


Dimensions

Draw
lead
length = Fig. 6.2. Top design. Fig. 6.3 Top design.

Fig. 6.4

1)
The bushings can be provided with a
n1 Holes longer shield L9 + 50 mm, in which
D = 16 case dimensions L, L1 and L5 also
increase by 50 mm.

Fig. 6.1. Bushing design.

Fig. 6.1 - 6.4. GOB without oil level gauge, dimensions.

Draw
lead
length =
Fig. 7.2. Top design. Fig. 7.3. Top design.

Fig. 7.4

n1 Holes
D = 16
1)
The bushings can be provided with a
longer shield L9 + 50 mm, in which
case dimensions L, L1 and L5 also
increase by 50 mm.

Fig. 7.1. Bushing design.

Fig. 7.1 - 7.4. GOB with oil level gauge, dimensions.

1ZSE 2750-102 en, Rev. 9 | Technical guide GOB 9


Bushings without oil level gauge
Dimensions are subject to modification without notice.
Type Rated Cat. No. Space for Net Top Dimensions in mm
GOB current current mass design L1) L11) L2 L3 L4 L51) L6 L7 L8 L91)
A transformer kg acc. to
mm Fig.

250 800 LF 123 013- - 30 6.2 998 240 590 65 555 60 - 480 70 13
015- 300 32 6.2 1258 500 590 555 260
083- 500 36 6.3 1558 700 690 655 460
250 1250 LF 123 017- - 31 6.2 1063 255 605 65 580 75 - 480 70 25
019- 300 36 6.2 1323 515 605 580 260
085- 500 37 6.3 1623 715 705 680 460
325 800 LF 123 025- - 35 6.2 1198 295 735 93 700 60 - 625 70 13
027- 300 40 6.2 1458 555 735 700 260
089- 500 45 6.3 1758 755 835 800 460
380 800 LF 123 037- - 35 6.2 1303 345 790 98 755 60 - 680 70 13
039- 300 39 6.2 1543 585 790 755 240
095- 500 41 6.3 1843 785 890 855 440
380 1250 LF 123 041- - 48 6.2 1368 360 805 98 780 75 - 680 70 25
043- 300 51 6.2 1608 600 805 780 240
097- 500 56 6.3 1908 800 905 880 440
450 800 LF 123 049- - 47 6.2 1473 345 960 98 925 60 - 850 70 13
051- 300 52 6.2 1713 585 960 925 240
053- 500 55 6.3 2013 785 1060 1025 440
550 800 LF 123 061- 100 85 6.2 1823 495 1160 60 1125 90 95 1050 60 25
063- 300 89 6.2 2108 680 1260 1225 280
107- 500 92 6.3 2308 880 1260 1225 480
550 1250 LF 123 065- 100 108 6.2 1868 495 1170 68 1145 100 95 1050 60 30
067- 300 113 6.2 2153 680 1270 1245 280
109- 500 119 6.3 2353 880 1270 1245 480
650 1250 LF 123 073- 150 125 6.2 2153 580 1370 60 1345 100 120 1250 60 30
075- 300 133 6.2 2413 740 1470 1445 280
113- 500 133 6.3 2613 940 1470 1445 480
750 1250 LF 123 077- 200 231 6.2 2468 685 1580 70 1555 100 165 1460 60 30
078- 300 232 6.2 2683 800 1680 1655 280
079- 500 244 6.3 2883 1000 1680 1655 480

10 Technical guide GOB | 1ZSE 2750-102 en, Rev. 9


Creepage Cantilever load
D1 D2 D3 D4 D5 D6 D7 D8 D10 n1 R1 R2 T distance Max. permitted loading 60 s Test
mm perpendicular to the N
terminal
N
86 22 86 115 88 185 225 230 46 6 8 6 16 1690±50 1800 2000

101 34 112 120 101 250 290 245 70 8 12 10 16 1500±50 3000 2500

95 22 86 115 96 185 225 230 46 6 8 6 16 2240±50 1500 2000

95 22 86 115 96 185 225 240 46 6 8 6 16 2210±70 1400 1800

112 34 112 120 112 250 290 245 70 8 12 10 16 2500±70 2900 2500

95 22 86 115 96 185 225 245 46 6 8 6 16 2720±80 1150 1500

126 22 118 145 150 250 290 280 50 8 12 12 18 3890±100 1300 1600

160 34 140 175 200 290 335 300 70 12 15 15 20 3430±100 2400 3100

160 34 140 175 200 290 335 305 70 12 15 15 20 4600±110 2600 3200

180 34 140 230 184 290 335 350 70 12 15 15 20 5420±140 2600 3200

1ZSE 2750-102 en, Rev. 9 | Technical guide GOB 11


Bushings with oil level gauge
Dimensions are subject to modification without notice.
Type Rated Cat. No. Space for Net Top Dimensions in mm
GOB current current mass design L1) L11) L2 L3 L4 L51) L6 L7 L8 L91)
A transformer kg acc. to
mm Fig.

250 800 LF 123 171- - 32 7.2 1138 240 730 65 695 60 - 480 70 15
173- 300 35 1398 500 260
175- 500 37 1598 700 460
250 1250 LF 123 167- - 33 7.2 1203 255 745 65 720 75 - 480 70 25
168- 300 36 1463 515 260
169- 500 38 1663 715 460
325 800 LF 123 177- - 36 7.2 1338 295 875 93 840 60 - 625 70 15
179- 300 41 1598 555 260
181- 500 47 1798 755 460
380 800 LF 123 183- - 36 7.2 1443 345 930 98 895 60 - 680 70 15
185- 300 40 1683 585 240
187- 500 42 1883 785 440
380 1250 LF 123 101- - 50 7.2 1508 360 945 98 920 75 - 680 70 25
102- 300 53 1748 600 240
103- 500 57 1948 800 440
450 800 LF 123 145- - 48 7.2 1613 345 1100 98 1065 60 - 850 70 15
147- 300 56 1853 585 240
149- 500 56 2053 785 440
550 800 LF 123 189- 100 86 7.2 1963 495 1300 60 1265 90 95 1050 60 25
190- 300 89 2148 680 280
191- 500 98 2348 880 480
550 1250 LF 123 142- 100 110 7.2 2008 495 1310 68 1285 100 95 1050 60 30
143- 300 114 2193 680 280
144- 500 120 2393 880 480
650 1250 LF 123 192- 150 129 7.2 2293 580 1510 60 1485 100 120 1250 60 30
193- 300 135 2453 740 280
194- 500 146 2653 940 480
750 1250 LF 123 104- 200 237 7.3 2718 685 1830 70 1805 100 165 1460 60 30
105- 300 240 2833 800 280
106- 500 243 3033 1000 480

12 Technical guide GOB | 1ZSE 2750-102 en, Rev. 9


Creepage Cantilever load
D1 D2 D3 D4 D5 D6 D7 D8 D10 n1 R1 R2 T distance Max. permitted loading 60 s Test
mm perpendicular to the N
terminal
N
86 22 86 140 88 185 225 230 46 6 8 6 16 1690±50 1800 2000

101 34 112 140 101 250 290 245 70 8 12 10 16 1500±50 3000 2500

95 22 86 140 96 185 225 230 46 6 8 6 16 2240±50 1500 2000

95 22 86 140 96 185 225 240 46 6 8 6 16 2210±70 1400 1800

112 34 112 140 112 250 290 245 70 8 12 10 16 2500±70 2900 2500

95 22 86 140 96 185 225 245 46 6 8 6 16 2720±80 1150 1500

126 22 118 200 150 250 290 280 50 8 12 12 18 3890±100 1300 1600

160 34 140 265 200 290 335 300 70 12 15 15 20 3430±100 2400 3100

160 34 140 265 200 290 335 305 70 12 15 15 20 4600±110 2600 3200

180 34 140 265 184 290 335 350 70 12 15 15 20 5420±140 2600 3200

1ZSE 2750-102 en, Rev. 9 | Technical guide GOB 13


Ordering particulars

Bushings without oil level gauge Note:


When ordering, please state: The catalogue number should have one of the following letters
added to it, to indicate the type of insulator and oil end shield:
–– Type and catalogue number for bushings.
–– Catalogue number for inner and outer terminal assembly. -K Normal oil end shield, brown porcelain
–– Additional accessories or modifications. -L Normal oil end shield, light grey porcelain
–– Test required, in addition to the normal routine tests. -M Longer oil end shield, brown porcelain
–– Test tap adapter, if required. -N Longer oil end shield, light grey porcelain

Bushings Connection details, Cat. No. LF 170


Type Rated Cat. No. Space for Bushing tube Inner terminal stud
GOB current current (See Fig. 6.4) For crimping or brazing For brazing Undrilled
A transformer D2, mm Conductor area Conductor area with pilot
mm 50 mm2 70 mm2 95 mm 2 ≤150 mm2 ≤285 mm2 hole
250 800 LF 123 013- - 22 010-M 010-N 010-L 011-S - 011-U
015- 300
083- 500
250 1250 LF 123 017- - 34 - - - - 011-T 011-V
019- 300
085- 500
325 800 LF 123 025- - 22 010-M 010-N 010-L 011-S - 011-U
027- 300
089- 500
380 800 LF 123 037- - 22 010-M 010-N 010-L 011-S - 011-U
039- 300
095- 500
380 1250 LF 123 041- - 34 - - - - 011-T 011-V
043- 300
097- 500
450 800 LF 123 049- - 22 010-M 010-N 010-L 011-S - 011-U
051- 300
053- 500
550 800 LF 123 061- 100 22 010-M 010-N 010-L 011-S - 011-U
063- 300
107- 500
550 1250 LF 123 065- 100 34 - - - - 011-T 011-V
067- 300
109- 500
650 1250 LF 123 073- 150 34 - - - - 011-T 011-V
075- 300
113- 500
750 1250 LF 123 077- 200 34 - - - - 011-T 011-V
078- 300
079- 500

14 Technical guide GOB | 1ZSE 2750-102 en, Rev. 9


-HK Horizontal mounting, normal oil end shield, brown porcelain
-HL Horizontal mounting, normal oil end shield, light grey porcelain
-HM Horizontal mounting, longer oil end shield, brown porcelain
-HN Horizontal mounting, longer oil end shield, light grey porcelain

Outer terminal assembly Solid rod conductor Arcing horns

Stud with O-ring and locking pin Separate terminal plate with bolts
Aluminium Copper alloy Aluminium Nickel-plated copper Alt. 1 Alt. 2 Mass kg
001-A 002-A 014-A 021-A 019 -A 019 - 2.6 004 -A
-D -B 3.3 -A
-E -C 4.2 -B
001-B 002-B 014-A 021-A 052 -A 052 - 6.8 004 -A
-D -B 8.4 -A
-E -C 10.6 -B
001-A 002-A 014-A 021-A 019 -F 019 - 3.1 004 -A
-K -G 3.9 -A
-L -H 4.7 -B
001-A 002-A 014-A 021-A 019 -M 019 - 3.5 004 -A
-R -N 4.2 -A
-S -P 5.0 -B
001-B 002-B 014-A 021-A 052 -V 052 - 8.6 004 -B
-Z -X 10.4 -B
-AA -Y 12.7 -B
001-A 002-A 014-A 021-A 019 -BL 019 - 4.0 004 -B
-BM -BN 4.7 -B
-BP -BR 5.5 -C
001-A 002-A 014-A 021-A 019 -T 019 - 4.9 004 -B
-X -U 5.7 -C
-Y -V 6.3 -C
001-B 002-B 014-A 021-A 052 -AM 052 - 12.0 004 -B
-AN -AP 14.1 -C
-AR -AS 15.5 -C
001-B 002-B 014-A 021-A 052 -F 052 - 14.0 005 -A
-K -G 15.9 -B
-L -H 17.5 -B
001-B 002-B 014-A 021-A 052 -M 052 - 16.3 005 -B
-R -N 18.0 -E
-S -P 19.5 -E

1ZSE 2750-102 en, Rev. 9 | Technical guide GOB 15


Bushings with oil level gauge Note:
When ordering, please state: The catalogue number should have one of the following letters
added to it, to indicate the type of insulator and oil end shield:
–– Type and catalogue number for bushings.
–– Catalogue number for inner and outer terminal assembly. -K Normal oil end shield, brown porcelain
–– Additional accessories or modifications. -L Normal oil end shield, light grey porcelain
–– Test required, in addition to the normal routine tests. -M Longer oil end shield, brown porcelain
–– Test tap adapter, if required. -N Longer oil end shield, light grey porcelain

Bushings Connection details, Cat. No. LF 170


Type Rated Cat. No. Space for Bushing tube Inner terminal stud
GOB current current (See Fig. 7.4) For crimping or brazing For brazing Undrilled
A transformer D2, mm Conductor area Conductor area with pilot
mm 50 mm2 70 mm2 95 mm 2 ≤150 mm2 ≤285 mm2 hole
250 800 LF 123 171- - 22 010-M 010-N 010-L 011-S - 011-U
173- 300
175- 500
250 1250 LF 123 167- - 34 - - - - 011-T 011-V
168- 300
169- 500
325 800 LF 123 177- - 22 010-M 010-N 010-L 011-S - 011-U
179- 300
181- 500
380 800 LF 123 183- - 22 010-M 010-N 010-L 011-S - 011-U
185- 300
187- 500
380 1250 LF 123 101- - 34 - - - - 011-T 011-V
102- 300
103 500
450 800 LF 123 145- - 22 010-M 010-N 010-L 011-S - 011-U
147- 300
149- 500
550 800 LF 123 189- 100 22 010-M 010-N 010-L 011-S - 011-U
190- 300
191- 500
550 1250 LF 123 142- 100 34 - - - - 011-T 011-V
143- 300
144- 500
650 1250 LF 123 192- 150 34 - - - - 011-T 011-V
193- 300
194- 500
750 1250 LF 123 104- 200 34 - - - - 011-T 011-V
105- 300
106- 500

16 Technical guide GOB | 1ZSE 2750-102 en, Rev. 9


-HK Horizontal mounting, normal oil end shield, brown porcelain
-HL Horizontal mounting, normal oil end shield, light grey porcelain
-HM Horizontal mounting, longer oil end shield, brown porcelain
-HN Horizontal mounting, longer oil end shield, light grey porcelain

Outer terminal assembly Solid rod conductor Arcing horns

Stud with O-ring and locking pin Separate terminal plate with bolts
Aluminium Copper alloy Aluminium Tin-plated copper Alt. 1 Alt. 2 Mass kg
001-A 002-A 014-A 021-A 019 -AM 019 - 3.0 004 -B
-AS -AT 3.7 -B
-BB -BC 4.3 -B
001-B 002-B 014-A 021-A 052 -BC 052 - 7.7 004 -B
-BF -BD 9.3 -B
-BG -BE 10.8 -B
001-A 002-A 014-A 021-A 019 -AN 019 - 3.5 004 -B
-AU -AV 4.3 -B
-BD -BE 4.8 -B
001-A 002-A 014-A 021-A 019 -AP 019 - 3.9 004 -B
-AX -AY 4.6 -B
-BF -BG 5.1 -B
001-B 002-B 014-A 021-A 052 -BK 052 - 9.6 004 -B
-BN -BL 11.4 -B
-BP -BM 12.6 -B
001-A 002-A 014-A 021-A 019 -BS 019 - 4.4 004 -C
-BT -BU 5.1 -C
-BV -BX 5.6 -C
001-A 002-A 014-A 021-A 019 -AR 019 - 5.3 004 -C
-AZ -BA 5.8 -C
-BH -BK 6.4 -C
001-B 002-B 014-A 021-A 052 -AT 052 - 13.0 004 -C
-AU -AX 14.4 -C
-AV -AY 15.8 -C
001-B 002-B 014-A 021-A 052 -AD 052 - 14.9 005 -B
-AE -AF 16.1 -B
-AG -AH 17.7 -B
001-B 002-B 014-A 021-A 052 -AZ 052 - 18.0 005 -F
-BA -BB 19.0 -F
-AK -AL 20.5 -F

1ZSE 2750-102 en, Rev. 9 | Technical guide GOB 17


Connection details

Inner terminal
Stud made of copper for connection of draw lead. The inner
terminal must be provided with an outer terminal.

Material and Conductor Cat. No. Dimensions Mass


design area mm kg
mm2 D1 D2 L
Copper for 50 LF 170 010 -M 11 14.5 35 0.3
crimping or 70 -N 13 17 35 0.3
brazing 95 -L 15 20 35 0.3
Copper for ≤ 150 LF 170 011 -S 18 20 35 0.3
brazing only undrilled -U 5 20 35 0.3
≤ 285 -T 29 32 20 0.6
undrilled -V 5 32 20 0.6 Fig. 8. Inner terminal.

Solid rod conductor


The rod is produced from electrolytic copper and is divided
into two parts. For the 800 A conductor the two parts are
held together by a centre bolt with a resilient locking pin. For
the 1100/1250 A conductor the two parts are connected by
counter-sunk screws.

The lower part of the solid rod is designed to enable


connection by brazing.

The solid rod conductor can be divided either:

Alt. 1: 20 mm below the bushing flange, or

Alt. 2: 20 mm below the upper end of the bottom porcelain.

The solid rod conductor must be provided with an outer


terminal.

LF 170 019- LF 170 052-


800 A 1250 A

Fig. 9. Solid rod conductor.

18 Technical guide GOB | 1ZSE 2750-102 en, Rev. 9


Outer terminal
Stud made of copper alloy or aluminium with O-ring and
locking pin. Other types can be provided on request.

Material Cat. No. Dimensions Mass For bushings


mm kg with D2
D N mm
Aluminium LF 170 001 -A 30 55 0.5 22
Width across flats N
-B 30 66 0.8 34
Copper alloy LF 170 002 -A 30 55 1.2 22
-B 30 66 2.3 34 Fig. 10. Outer terminal assembly.

Separate terminal plate with bolts


The separate terminal plate is used for connecting the
bushing to the line conductor.

Material Cat. No.


Aluminium LF 170 014-A
Nickel-plated copper LF 170 021-A

Fig. 11. Separate terminal plate with bolts.

Arcing horns
Arcing horns of galvanised steel can be mounted on the bushing.

The lower rod is fastened onto the flange with one of the
fixing screws and the upper rod by means of a bracket on the
outer terminal.

The gap distances for standard arcing horns are shown in the
table. Other gap distances on request.

Type GOB K C H
mm mm mm
250 230–440 315 112
325 320–580 315 112
380 400–620 315 112 Fig. 12. Gap distances.
450 400–780 315 112
550 620–960 315 114
650 700–1080 380 224
750 820–1290 380 224
1050 950–1840 420 410

1ZSE 2750-102 en, Rev. 9 | Technical guide GOB 19


Type GOB 1050

Dimensions
When ordering, please state:
D=265

–– Type and catalogue number for bushings. D=355


–– Catalogue number for inner and outer terminal assembly.
–– Additional accessories or modifications.
–– Test required, in addition to the normal routine tests.
–– Test tap adapter, if required.

L2
L7

L4
Note:

L
The catalogue number should have one of the following letters
added to it, to indicate the type of insulator and oil end shield:

-K Brown porcelain
-L Light grey porcelain

180
D=200
L6
20
L1
L3

D=34

D=450
D=400

12 holes
D=23

Fig. 13. Dimensions, GOB 1050.

Dimensions are subject to modification without notice.


Rated Cat. No. Space for Net Dimensions in mm Creepage distance Cantilever load
current current mass L L1 L2 L3 L4 L6 L7 total protected Max Test
A transformer kg mm mm N N
mm
1100 LF 123 281- 300 335 3690 930 2555 49 2530 300 2066 7500 3200 1250 3200
LF 123 280- 600 350 3990 1230 2555 49 2530 600 2066 7500 3200 1250 3200

20 Technical guide GOB | 1ZSE 2750-102 en, Rev. 9


Ordering particulars
Cat. No. Inner terminal stud Solid rod conductor Oil end shield Arcing horns
For brazing Stud with O-ring and
locking pin
Conductor Undrilled Aluminium Copper Alt. 1 Alt. 2 Alt. 3 Epoxy Pressboard
area with pilot alloy insulated insulated
<285 mm2 hole
LF 123 281– 011-T 011-V 001-B 002-B 052 -FD 052 -FE 052 -FF 092-B 092-D 005-G
LF 123 280– -FA -FB -FC

M8 M8

D=7

D=7
20

D=32 L4

Alt. 1 - 3
Fig. 14. Inner terminal.

D=30

66
205

D=32

28

Fig. 15. Outer terminal.

D=28

156 R160 The solid rod can be divided:


107 Alt. 1: 20 mm below the bushing flange
Alt. 2: 20 mm below the upper end of the bottom porcelain
Alt. 3: 210 mm above the bottom end of the bushing
R1
5
D=105
R6

D=176

Fig. 16. Oil end shield. Fig. 17. Solid rod.

1ZSE 2750-102 en, Rev. 9 | Technical guide GOB 21


Recommendations for positioning

The maximum stresses in the oil at the surface of the shield


insulation must be limited to those values normal for insulated
conductors and similar components in the same transformer.

The adjacent recommendations are intended as guide lines


when complete calculations are not carried out.

Type GOB Internal insulation level of R (mm) Earthed layer

transformer (kV)
Distance to
250–800 170–70 65 uninsulated detail
Distance to flat sur-
250–95 75 face e.g. tank or core
250–1250 170–70 75 clamp
250–95 85
325–800 250–95 75 Fig. 18.
325–140 100
380–800 325–140 100
380–150 105
380–1250 325–140 105
380–150 110 ABB Ludvika, Sweden
2011
450–800 380–150 105 GOB 250 LF 123 013-K

450–185 125 No. 1ZSC 257 007


Um/Uy 52/52 kV Ir 800 A 50/60 Hz
550–800 450–185 130 LI / AC 250/120 kV
M 23 kg L 240 mm 0-90 °
550–230 155 C1 128 pF Tan δ 0.33 %
C2 80 pF Tan δ 0.45 %
550–1250 450–185 140
550–230 160
650–1250 550–230 160
650–275 185 Fig. 19. Nameplate with marking example.
750–1250 650–275 185
750–325 210
1050–1100 850–360 240
950–395 260
1050–460 300

22 Technical guide GOB | 1ZSE 2750-102 en, Rev. 9