Transformer Bushings, Type GOB: Technical Guide
Transformer Bushings, Type GOB: Technical Guide
Transformer Bushings, Type GOB: Technical Guide
The information provided in this document is intended to be general and does not
cover all possible applications. Any specific application not covered should be
referred directly to ABB, or its authorized representative.
This document must not be copied without our written permission, and the contents
thereof must not be imparted to a third party nor be used for any unauthorized
purpose. Contravention will be prosecuted.
Content
Content........................................................................................................................... 3
Design............................................................................................................................. 4
Features and benefits................................................................................................. 4
Shed profile, GOB 52 - 170 kV.................................................................................. 5
Shed profile, GOB 300 kV.......................................................................................... 5
General specifications................................................................................................ 5
Testing............................................................................................................................. 6
Test tap...................................................................................................................... 6
Test tap adapter......................................................................................................... 6
Electrical data.................................................................................................................. 7
Conductor loading........................................................................................................... 8
Overloading of bushings............................................................................................ 8
Short-time current...................................................................................................... 8
Dimensions...................................................................................................................... 9
Bushings without oil level gauge................................................................................ 11
Bushings with oil level gauge..................................................................................... 13
Ordering particulars......................................................................................................... 14
Bushings without oil level gauge................................................................................ 14
Bushings with oil level gauge..................................................................................... 16
Connection details........................................................................................................... 18
Inner terminal............................................................................................................. 18
Solid rod conductor................................................................................................... 18
Outer terminal............................................................................................................ 19
Separate terminal plate with bolts.............................................................................. 19
Arcing horns.............................................................................................................. 19
Type GOB 1050............................................................................................................... 20
Dimensions................................................................................................................ 20
Ordering particulars................................................................................................... 21
Recommendations for positioning................................................................................... 22
Design
The mounting flange, the top housing and the top washer
are protected by painting with a two-component primer and Fig. 1. Transformer bushing type GOB.
a grey-blue finishing coat of paint. The standard colour is
Munsell 5.5B 55/1.25.
Features and benefits
The bushings are delivered oil-filled and ready for use. –– A complete range and outstanding operational experience
from the most demanding applications for more than 40
If the bushing is mounted with an inclination of more than years.
45° from the vertical, special measures have to be taken to –– 3D models makes it easy to incorporate the bushing in its
ensure the condenser body is fully immersed in oil. Further context.
information can be obtained on request. –– We use a sealing system proven since 50 years around the
world.
–– Our test criteria and margins exceeding international stan-
dards.
70
R10
52.5 R4.5
General specifications
Application: Transformers
Classification: Oil impregnated paper, capacitance graded, outdoor-immersed bushing
Ambient temperature: +40 to -40 °C, minimum value as per temperature class 2 of IEC 60137
(-60 °C according to GOST 10693-81 item 2.26)
Altitude of site: < 1 000 m
Level of rain and humidity: 1-2 mm rain/min horizontally and vertically, as per IEC 60060-1
Pollution level: According to specified creepage distance and IEC 60815
Type of immersion medium: Transformer oil. Maximum daily mean oil temperature 90 °C. Maximum temporary oil temperature 115 °C
Oil level below bushing flange: Maximum 30 mm
Max. pressure of medium: 100 kPa overpressure
Markings: Conforming to IEC/ IEEE
During the manufacture and on its completion the bushing is GOB 1050 is also routine tested with a dry lightning impulse
subjected to a number of routine tests, in compliance with voltage withstand test.
IEC 60137. A tightness test is carried out on the assembled
bushing after the final drying and impregnation. The test Type tests have been carried out according to IEC 60137 and
is made with an oil overpressure of 180 kPa (1.8 bar) for IEEE. Type test reports are available on request.
12 hours at ambient temperature. No sign of leakage is
allowed. Test tap
The outer conducting layer of the condenser body is
Each bushing is subjected to a final electrical routine test. connected to an insulated test tap on the flange. During
The test is made at room temperature with the bushing operation the test tap cover must be screwed on, in order to
submerged in oil. Capacitance and tan δ are measured in earth the bushing. The max. test voltage of the tap is 2 kV,
steps up to the power frequency withstand voltage, which is 50 Hz for 1 minute. Max. service voltage is 600 V.
maintained for one minute. Capacitance and tan δ are also
measured at decreasing voltage at the same voltage levels as Test tap adapter
before the one minute test. For permanent connection of the test tap to measuring
circuits, a test tap adapter is required. Catalogue number
Measurements for detection of internal partial discharge 1ZSC003881-AAC.
(PD measurements) are also made. These measurements
are carried out at the same time as the power frequency
withstand test. PD measurements are made in steps up to
the full test voltage and down. It is always demonstrated that
the PD value is max. 5 pC at test voltage equal to the rated
system voltage.
Overloading of bushings
If the conductor for the bushing is selected with 120 % of the
rated current of the transformer, the bushing is considered
to be able to withstand the overload conditions stated in
IEC 60354 without further clarifications or tests, according to
IEC 60137.
Short-time current
The rated thermal short-time current (Ith) is calculated
according to IEC 60137.
Conductor Rated current Area mm2 Short-time current (Ith) Dynamic current (I d)
A 1s 2s kA, peak
kA, RMS kA, RMS
Solid rod 800 - 30 21 52
Solid rod 1100/1250 - 70 50 125
Stranded draw-lead 365 100 9.6 6.8 17
Draw
lead
length = Fig. 6.2. Top design. Fig. 6.3 Top design.
Fig. 6.4
1)
The bushings can be provided with a
n1 Holes longer shield L9 + 50 mm, in which
D = 16 case dimensions L, L1 and L5 also
increase by 50 mm.
Draw
lead
length =
Fig. 7.2. Top design. Fig. 7.3. Top design.
Fig. 7.4
n1 Holes
D = 16
1)
The bushings can be provided with a
longer shield L9 + 50 mm, in which
case dimensions L, L1 and L5 also
increase by 50 mm.
250 800 LF 123 013- - 30 6.2 998 240 590 65 555 60 - 480 70 13
015- 300 32 6.2 1258 500 590 555 260
083- 500 36 6.3 1558 700 690 655 460
250 1250 LF 123 017- - 31 6.2 1063 255 605 65 580 75 - 480 70 25
019- 300 36 6.2 1323 515 605 580 260
085- 500 37 6.3 1623 715 705 680 460
325 800 LF 123 025- - 35 6.2 1198 295 735 93 700 60 - 625 70 13
027- 300 40 6.2 1458 555 735 700 260
089- 500 45 6.3 1758 755 835 800 460
380 800 LF 123 037- - 35 6.2 1303 345 790 98 755 60 - 680 70 13
039- 300 39 6.2 1543 585 790 755 240
095- 500 41 6.3 1843 785 890 855 440
380 1250 LF 123 041- - 48 6.2 1368 360 805 98 780 75 - 680 70 25
043- 300 51 6.2 1608 600 805 780 240
097- 500 56 6.3 1908 800 905 880 440
450 800 LF 123 049- - 47 6.2 1473 345 960 98 925 60 - 850 70 13
051- 300 52 6.2 1713 585 960 925 240
053- 500 55 6.3 2013 785 1060 1025 440
550 800 LF 123 061- 100 85 6.2 1823 495 1160 60 1125 90 95 1050 60 25
063- 300 89 6.2 2108 680 1260 1225 280
107- 500 92 6.3 2308 880 1260 1225 480
550 1250 LF 123 065- 100 108 6.2 1868 495 1170 68 1145 100 95 1050 60 30
067- 300 113 6.2 2153 680 1270 1245 280
109- 500 119 6.3 2353 880 1270 1245 480
650 1250 LF 123 073- 150 125 6.2 2153 580 1370 60 1345 100 120 1250 60 30
075- 300 133 6.2 2413 740 1470 1445 280
113- 500 133 6.3 2613 940 1470 1445 480
750 1250 LF 123 077- 200 231 6.2 2468 685 1580 70 1555 100 165 1460 60 30
078- 300 232 6.2 2683 800 1680 1655 280
079- 500 244 6.3 2883 1000 1680 1655 480
101 34 112 120 101 250 290 245 70 8 12 10 16 1500±50 3000 2500
112 34 112 120 112 250 290 245 70 8 12 10 16 2500±70 2900 2500
126 22 118 145 150 250 290 280 50 8 12 12 18 3890±100 1300 1600
160 34 140 175 200 290 335 300 70 12 15 15 20 3430±100 2400 3100
160 34 140 175 200 290 335 305 70 12 15 15 20 4600±110 2600 3200
180 34 140 230 184 290 335 350 70 12 15 15 20 5420±140 2600 3200
250 800 LF 123 171- - 32 7.2 1138 240 730 65 695 60 - 480 70 15
173- 300 35 1398 500 260
175- 500 37 1598 700 460
250 1250 LF 123 167- - 33 7.2 1203 255 745 65 720 75 - 480 70 25
168- 300 36 1463 515 260
169- 500 38 1663 715 460
325 800 LF 123 177- - 36 7.2 1338 295 875 93 840 60 - 625 70 15
179- 300 41 1598 555 260
181- 500 47 1798 755 460
380 800 LF 123 183- - 36 7.2 1443 345 930 98 895 60 - 680 70 15
185- 300 40 1683 585 240
187- 500 42 1883 785 440
380 1250 LF 123 101- - 50 7.2 1508 360 945 98 920 75 - 680 70 25
102- 300 53 1748 600 240
103- 500 57 1948 800 440
450 800 LF 123 145- - 48 7.2 1613 345 1100 98 1065 60 - 850 70 15
147- 300 56 1853 585 240
149- 500 56 2053 785 440
550 800 LF 123 189- 100 86 7.2 1963 495 1300 60 1265 90 95 1050 60 25
190- 300 89 2148 680 280
191- 500 98 2348 880 480
550 1250 LF 123 142- 100 110 7.2 2008 495 1310 68 1285 100 95 1050 60 30
143- 300 114 2193 680 280
144- 500 120 2393 880 480
650 1250 LF 123 192- 150 129 7.2 2293 580 1510 60 1485 100 120 1250 60 30
193- 300 135 2453 740 280
194- 500 146 2653 940 480
750 1250 LF 123 104- 200 237 7.3 2718 685 1830 70 1805 100 165 1460 60 30
105- 300 240 2833 800 280
106- 500 243 3033 1000 480
101 34 112 140 101 250 290 245 70 8 12 10 16 1500±50 3000 2500
112 34 112 140 112 250 290 245 70 8 12 10 16 2500±70 2900 2500
126 22 118 200 150 250 290 280 50 8 12 12 18 3890±100 1300 1600
160 34 140 265 200 290 335 300 70 12 15 15 20 3430±100 2400 3100
160 34 140 265 200 290 335 305 70 12 15 15 20 4600±110 2600 3200
180 34 140 265 184 290 335 350 70 12 15 15 20 5420±140 2600 3200
Stud with O-ring and locking pin Separate terminal plate with bolts
Aluminium Copper alloy Aluminium Nickel-plated copper Alt. 1 Alt. 2 Mass kg
001-A 002-A 014-A 021-A 019 -A 019 - 2.6 004 -A
-D -B 3.3 -A
-E -C 4.2 -B
001-B 002-B 014-A 021-A 052 -A 052 - 6.8 004 -A
-D -B 8.4 -A
-E -C 10.6 -B
001-A 002-A 014-A 021-A 019 -F 019 - 3.1 004 -A
-K -G 3.9 -A
-L -H 4.7 -B
001-A 002-A 014-A 021-A 019 -M 019 - 3.5 004 -A
-R -N 4.2 -A
-S -P 5.0 -B
001-B 002-B 014-A 021-A 052 -V 052 - 8.6 004 -B
-Z -X 10.4 -B
-AA -Y 12.7 -B
001-A 002-A 014-A 021-A 019 -BL 019 - 4.0 004 -B
-BM -BN 4.7 -B
-BP -BR 5.5 -C
001-A 002-A 014-A 021-A 019 -T 019 - 4.9 004 -B
-X -U 5.7 -C
-Y -V 6.3 -C
001-B 002-B 014-A 021-A 052 -AM 052 - 12.0 004 -B
-AN -AP 14.1 -C
-AR -AS 15.5 -C
001-B 002-B 014-A 021-A 052 -F 052 - 14.0 005 -A
-K -G 15.9 -B
-L -H 17.5 -B
001-B 002-B 014-A 021-A 052 -M 052 - 16.3 005 -B
-R -N 18.0 -E
-S -P 19.5 -E
Stud with O-ring and locking pin Separate terminal plate with bolts
Aluminium Copper alloy Aluminium Tin-plated copper Alt. 1 Alt. 2 Mass kg
001-A 002-A 014-A 021-A 019 -AM 019 - 3.0 004 -B
-AS -AT 3.7 -B
-BB -BC 4.3 -B
001-B 002-B 014-A 021-A 052 -BC 052 - 7.7 004 -B
-BF -BD 9.3 -B
-BG -BE 10.8 -B
001-A 002-A 014-A 021-A 019 -AN 019 - 3.5 004 -B
-AU -AV 4.3 -B
-BD -BE 4.8 -B
001-A 002-A 014-A 021-A 019 -AP 019 - 3.9 004 -B
-AX -AY 4.6 -B
-BF -BG 5.1 -B
001-B 002-B 014-A 021-A 052 -BK 052 - 9.6 004 -B
-BN -BL 11.4 -B
-BP -BM 12.6 -B
001-A 002-A 014-A 021-A 019 -BS 019 - 4.4 004 -C
-BT -BU 5.1 -C
-BV -BX 5.6 -C
001-A 002-A 014-A 021-A 019 -AR 019 - 5.3 004 -C
-AZ -BA 5.8 -C
-BH -BK 6.4 -C
001-B 002-B 014-A 021-A 052 -AT 052 - 13.0 004 -C
-AU -AX 14.4 -C
-AV -AY 15.8 -C
001-B 002-B 014-A 021-A 052 -AD 052 - 14.9 005 -B
-AE -AF 16.1 -B
-AG -AH 17.7 -B
001-B 002-B 014-A 021-A 052 -AZ 052 - 18.0 005 -F
-BA -BB 19.0 -F
-AK -AL 20.5 -F
Inner terminal
Stud made of copper for connection of draw lead. The inner
terminal must be provided with an outer terminal.
Arcing horns
Arcing horns of galvanised steel can be mounted on the bushing.
The lower rod is fastened onto the flange with one of the
fixing screws and the upper rod by means of a bracket on the
outer terminal.
The gap distances for standard arcing horns are shown in the
table. Other gap distances on request.
Type GOB K C H
mm mm mm
250 230–440 315 112
325 320–580 315 112
380 400–620 315 112 Fig. 12. Gap distances.
450 400–780 315 112
550 620–960 315 114
650 700–1080 380 224
750 820–1290 380 224
1050 950–1840 420 410
Dimensions
When ordering, please state:
D=265
L2
L7
L4
Note:
L
The catalogue number should have one of the following letters
added to it, to indicate the type of insulator and oil end shield:
-K Brown porcelain
-L Light grey porcelain
180
D=200
L6
20
L1
L3
D=34
D=450
D=400
12 holes
D=23
M8 M8
D=7
D=7
20
D=32 L4
Alt. 1 - 3
Fig. 14. Inner terminal.
D=30
66
205
D=32
28
D=28
D=176
transformer (kV)
Distance to
250–800 170–70 65 uninsulated detail
Distance to flat sur-
250–95 75 face e.g. tank or core
250–1250 170–70 75 clamp
250–95 85
325–800 250–95 75 Fig. 18.
325–140 100
380–800 325–140 100
380–150 105
380–1250 325–140 105
380–150 110 ABB Ludvika, Sweden
2011
450–800 380–150 105 GOB 250 LF 123 013-K
ABB AB
© Copyright 2015 ABB, All rights reserved. 1ZSE 2750-102 en, Rev. 9, 2015-06-15
Components
SE-771 80 Ludvika, Sweden
Phone: +46 240 78 20 00
Fax: +46 240 121 57
E-Mail: [email protected]
www.abb.com/electricalcomponents