ELECTRICAL SCHEMATIC DRAWING - GE ZENITH ZTED SERIES TRANSFER SWITCHES - DELAY TRANSITION TYPE - 600 TO 3000A

LEGEND, FEATURES, OPERATION, AND ACCESSORIES


1.0 CONTROL CONFIGURATION GROUPS 5.0 SEQUENCE OF OPERATIONS 6.0 STANDARD INDICATORS, PUSHBUTTONS, AND ANNUNCIATION
ZTE SWITCHES ARE CONFIGURED TO ONE (1) OF THE FOLLOWING FIVE (5) OPTION PACKAGES. NOTE: ATS CATALOG NUMBER NOTE: SEE O&M MANUAL FOR ADDITIONAL SEQUENCE OF OPERATION DETAILS AND DIAGNOSTICS.
SCHEME, DIGIT #9, INDICATES THE INSTALLED CONTROL PACKAGE
RELATED LOCATION OF
CONFIGURATION DESCRIPTION
STATE DESCRIPTION FUNCTION: USER SETTINGS IN
ZTE OPERATOR
STANDARD PACKAGE FOR AUTOMATIC ATS. INCLUDES FULL FUNCTION ATS CONTROL, DIAGNOSTICS, USER DISPLAY (DOOR
A SETTINGS MENU
CONTROL SWITCHES, (4) USER-CONFIGURABLE INPUTS, AND (4) USER-CONFIGURABLE OUTPUTS
ALL FEATURES IN "A" PLUS: USER-CONFIGURABLE ANALOG & DIGITAL ALARMS, 20-CHANNEL DATA CONNECTED TO SETTING OF
SETPOINT-- MOUNTED)
B STAY ON PREFERRED SOURCE UNTIL FAILURE IS DETECTED OR A TEST >OPERATION--
LOGGER, 10-CHANNEL WAVEFORM CAPTURE, AUTO LOAD SHED FEATURE 0 PREFERRED PREFERRED
WITH LOAD IS INITIATED. (NOTE: JUMP TO STEP #3 IF TEST WITH LOAD) >S1 (S2)
ALL FEATURES IN "B" PLUS: (4) ADDITIONAL USER-CONFIGURABLE INPUTS AND OUTPUTS (TOTAL 8 INPUTS, SOURCE SOURCE
C SETTINGS
8 OUTPUTS)
SETPOINT--
ALL FEATURES IN "C" PLUS: (4) ADDITIONAL USER-CONFIGURABLE INPUTS AND OUTPUTS (TOTAL 12 SOURCE
D PREFERRED >OPERATION--
INPUTS, 12 OUTPUTS), FLEXLOGIC USER-PROGRAMMABLE CUSTOM LOGIC EDITOR 1 CONTROL SENSES THE FAILURE OF THE DESIGNATED PREFERRED SOURCE FAILURE
SOURCE FAILURE >S1 (S2)
STANDARD PACKAGE FOR MANUAL ATS. INCLUDES FULL FUNCTION ATS CONTROL, DIAGNOSTICS, USER SETTINGS
SETTINGS
M CONTROL SWITCHES (SEE ITEM #4), (4) USER-CONFIGURABLE INPUTS, AND (4) USER-CONFIGURABLE
PREFERRED DELAY FOR SETPOINT--
OUTPUTS CONTROL INITIATES A TIME DELAY ON STARTING OF GENERATOR IN
2 SOURCE FAIL GENERATOR >OPERATION--
CASE OF FAST RETURN OF SOURCE
TIMER START >TIMERS

2.0 STANDARD CONTROL INTERFACE SIGNALS 3


START
CONTROL SENDS A START COMMAND TO THE GENERATOR ON INDICATOR DESCRIPTION
GENERATOR
EXPIRATION OF THE TIME DELAY (P) IN #2 ABOVE SOURCE AVAIL LED'S S1 (GREEN) AND S2 (RED) INDICATE SOURCE HEALTHY
ZTE SWITCHES SUPPORT THE FOLLOWING STANDARD INTERFACE SIGNALS. SEE CUSTOMER CONNECTION
DIAGRAM FOR TERMINAL LOCATIONS AND DETAILS SETPOINT-- SOURCE CONN LED'S S1 (GREEN) AND S2 (RED) INDICATE SOURCES CONNECTED TO LOAD
NON-PREFERRED SOURCE
>OPERATION-- RED LED, INDICATIES AN ACTIVE ALARM. SEE STATUS SCREEN (HOME--
4 SOURCE CONTROL DETECTS THAT THE NON-PREFERRED SOURCE IS AVAILABLE RETURN ALARM LED
SIGNAL (CODE) DESCRIPTION RATINGS >S1 (S2) >STATUS) FOR DETAILED ALARM MESSAGE
AVAILABLE SETTINGS
START SIGNAL FROM ATS TO GENSET IN EVENT OF LOSS OF PREFERRED FORM 'C' CONTACTS, SETTINGS RED LED, INDICATES CONTROLLER IS TIMING FOR NEXT ACTION. SEE
ENGINE START SIGNAL (E)
SOURCE 10A @ 28VDC/120VAC DELAY – TD ACTIVE STATUS SCREEN (HOME-->STATUS) FOR DESCRIPTION OF THE TIME
MAINTAINED CONTACT (CLOSE FOR TEST) FROM BUILDING CONTROL NON-PREFERRED XFER TO SETPOINT-- DELAY AND DISPLAY OF REMAINING TIME
FORM 'C' CONTACT, CONTROL INITIATES A TIME DELAY (W) TO PERMIT THE GENERATOR TO
SYSTEM TO SIMULATE AN OUTAGE CONDITION. SWITCH WILL START 5 SOURCE NON >OPERATION-- INDICATES ATS IS READY TO TRANSFER TO A SOURCE, BUT IS RECEIVING
REMOTE TEST SIGNAL (Q2) RATED FOR 28VDC, STABILIZE BEFORE TRANSFER OF THE LOAD.
GENERATOR AND TRANSFER LOAD. SWITCH WILL RETURN TO PREFERRED STABILITY TIMER PREFERRED >TIMERS AN INHIBIT TRANSFER SIGNAL. INHIBIT COMMAND MAY BE LOCAL
1A MINIMUM SRC XFER INHIBIT
SOURCE UPON REMOVAL OF TEST SIGNAL. DISCONNECT SWITCH (DS), LOCAL OR REMOTE AUTO/MANUAL SWITCH,
QTY (2) N/O IF (S13) IS SET TO "ENABLED" - CONTROL WILL INITIATE THE TRANSFER OR INHIBIT TRANSFER SIGNALS
SOURCE 1 CONNECTED TO HOME--
AUXILIARY CONTACT INDICATING LOAD IS CONNECTED TO ATS SOURCE #1 CONTACTS, 10A @ COMMIT SEQUENCE EVEN IF THE PREFERRED SOURCE RETURNS BEFORE ALARM RESET USED TO RESET LATCHED ALARM CONDITIONS.
LOAD (A4) >SETPOINT--
28VDC/120 VAC TRANSFER TO EXPIRATION OF TIME DELAY (W) IN #5 ABOVE. COMMIT TEST JUMP BUTTON TO TEST MENU.
>CONTROL
QTY (2) N/O 6 NON-PREFERRED XFER INFO JUMP BUTTON TO RUN REPORT.
SOURCE 2 CONNECTED TO or GREEN
AUXILIARY CONTACT INDICATING LOAD IS CONNECTED TO ATS SOURCE #2 CONTACTS, 10A @ SOURCE (S13) IF (S13) IS SET TO "DISABLED" AND PREFERRED SOURCE RETURNS BEFORE SWITCH (S13) CONTROL JUMP BUTTON TO CONTROL MENU.
LOAD (A3) 'CONTROL'
28VDC/120 VAC EXPIRATION OF TIME DELAY (W) IN #5 ABOVE, CONTROL REMOVES START
PUSHBUTTO HOME JUMP BUTTON TO HOME SCREEN
QTY (1) N/O SIGNAL AND STAYS CONNECTED TO PREFERRED SOURCE.
BYPASS MTS CONNECTED AUXILIARY CONTACT INDICATING THAT OPERATOR HAS MANUALLY UP/DOWN ARROW PERMITS UP/DOWN SCROLLING WITHIN SCREEN
CONTACT, 10A @ IF AUTO/MANUAL SWITCH SET TO "AUTO" OR "MANUAL S2 TO S1 ONLY
TO SOURCE 1 BYPASSED SOURCE 1 TO THE LOAD (BYPASS ATS ONLY) ESC' KEY BRINGS OPERATOR TO PREVIOUS SCREEN
28VDC/120 VAC (S5)" – ATS WILL AUTOMATICALL INITIATE THE TRANSFER SEQUENCE
HOME-- ENTER' KEY SELECTS ITEMS WITHIN MENU SYSTEM AND CONFIRMS OPERATIONS
QTY (1) N/O UPON EXPIRATION OF TIME DELAY (DW) IN #7 ABOVE.
BYPASS MTS CONNECTED AUXILIARY CONTACT INDICATING THAT OPERATOR HAS MANUALLY >SETPOINT-- HELP' KEY TRIGGERS MENU-DEPENDENT HELP POPUP MESSAGE
CONTACT, 10A @ AUTO/ MANUAL AUTO /MAN
TO SOURCE 2 BYPASSED SOURCE 2 TO THE LOAD (BYPASS ATS ONLY) >CONTROL PERMITS CALIBRATION UPLOAD/MODIFY/DOWNLOAD USING ENERVISTA
28VDC/120 VAC 7 SELECT SWITCH IF AUTO/MANUAL SELECTOR (S12 OR S5) IS SET TOAUTO – ATS WILL SELECT USB PORT
or GREEN SETUP ™ SOFTWARE.
PERMISSIVE (S5) AUTOMATICALLY INITIATE WAIT FOR A PERMISSIVE SIGNAL BEFORE SWITCH
'CONTROL' 5 x SOFT KEYS MENU-DEPENDENT PUSHBUTTONS. FUNCTION OF PUSHBUTTON IS
INITIATING THE TRANSFER SEQUENCE. PERMISSIVE SIGNAL IS EITHER AN
3.0 NETWORKING AND METERING OPTIONS OPERATOR PUSHBUTTON ON THE 'STATUS' SCREEN OR CUSTOMER INPUT
PUSHBUTTON (BLUE ARROWS) INDICATED ON GRAPHICAL SCREEN ABOVE BUTTON.
SIGNAL.
ZTE SWITCHES MAY BE CONFIGURED WITH BUILT-IN NETWORKING AND METRING OPTIONS. SEE TRANSFER SWTICH CATALOG
NUMBER DIGITS #13 AND #14 AND THE TABLE BELOW TO DETERMINE INSTALLED OPTIONS
TRANSFER TO DELAY – SETPOINT-- ELEMENT LOCATION IN MENU
CONTROL WILL OPEN PREFERRED SOURCE, AND NON-PRERFERRED
DIGIT #13 DESCRIPTION 8 MID/CENTER NEUTRAL TO >OPERATION-- LAST & NEXT EXERCISE TIME HOME SCREEN
SOURCE WILL REMAIN OPEN FOR A TIME DELAY PERIOD (DW)
INCLUDES POWER QUALITY METERING. POSITION NON >TIMERS LAST TRANSFER TIMES s1-->s2, AND s2-->S1 HOME SCREEN
D, G, H, J, L, M, N, OR O PREFERRED
INCLUDES (2) CT'S FOR SINGLE PHASE, (3) CT'S FOR 3PH/3W OR (4) CT'S FOR 3PH/4W SYSTEMS. SWITCH AMP, VOLT RATING AND TYPE HOME SCREEN
CONNECT TO CONTROL WILL CONNECT THE LOAD TO THE NON-PREFERRED SOURCE PREFERRED SOURCE SETTING HOME SCREEN
DIGIT #14 DESCRIPTION 9 NON-PREFERRED AFTER EXPIRATION OF TIME DELAY (DW) IN #7 ABOVE) OR RECIEPT OF SOURCE VOLTAGES, FREQUENCY HOME-->VALUES
X NO COMMUNICATIONS SOURCE PERMISSIVE SIGNAL (#8 ABOVE) LOAD AMPS, KW, KVAR, PF (REQUIRES
S INCLUDES BUILT-IN SERIAL (RS-485) MODBUS RTU COMMUNICATIONS GEN CONTROL WILL DELAY ACTIVATION OF SOURCE 2 FAILURE (UNDER TIME DELAY SETPOINT-- HOME-->VALUES
METERING OPTION)
INCLUDES BUILT-IN SERIAL (RS-485) MODBUS RTU COMMUNICATIONS AND ETHERNET/TCPIP 10 STABILIZATION VOLTS/FREQ) TO PERMIT GENERATOR SET TO STABILIZE AFTER FOR GEN >OPERATION-- ALARM STATUS, STATUS OF TIMERS HOME-->STATUS
E COMMUNICATIONS. TIMER CONNECTION OF LOAD SAG >TIMERS CURRENT CONFIGURATION / ASSIGNENT OF
NOTE: COMMUNICATION PORTS MAY BE USED SIMULTANEOUSLY. SETPOINT-- HOME-->STATUS-->INPUTS
PREFERRED CONTROL WILL SENSE THE RETURN OF THE DESIGNATED PREFERRED SOURCE CUSTOMER INPUTS
>OPERATION-- CURRENT CONFIGURATION / ASSIGNENT OF
11 SOURCE SOURCE, OR DETECT THAT THE TEST WITH LOAD OPERATION HAS BEEN RETURN HOME-->STATUS-->OUTPUTS
>S1 (S2) CUSTOMER OUTPUTS
4.0 NON-STANDARD CONTROL OPTIONS AVAILABLE CANCELLED. SETTINGS
SETTINGS
CURRENT CONFIGURATION OF LOAD
DELAY – CONTROL RELAYS (ELEVATOR, LOAD PRE- HOME-->SETPOINT-->CONFIG
T THE FOLLOWING OPTIONS MAY BE INSTALLED ON THE ATS. SEE TRANSFER SWITCH CATALOG PREFERRED SETPOINT--
CONTROL INITIATES A TIME DELAY (T) TO PERMIT UTILITY POWER TO XFER TO SIGNAL)
NUMBER DIGITS #9, #13, AND #14 AND THE TABLE BELOW TO DETERMINE INSTALLED OPTIONS 12 SOURCE RETURN >OPERATION--
STABILIZE. PREFERRED
TIMER >TIMERS S1 FAIL/RESTORE SETTINGS HOME-->SETPOINT-->OPERATION-->S1 SETTING
SRC
ORDER VALUE FEATURE FEATURE DESCRIPTION S2 FAIL/RESTORE SETTINGS HOME-->SETPOINT-->OPERATION-->S2 SETTING
IF AUTO/MANUAL SELECT SWITCH IS SET TO "AUTO" – ATS WILL
CODE TIME DELAY ADJUSTMENTS HOME-->SETPOINT-->OPERATION-->TIMERS
AUTOMATICALL INITIATE THE RE-TRANSFER SEQUENCE UPON
DIGIT EXPIRATION OF TIME DELAY (DT) IN #13. HOME-- EVENT LOG HOME-->DIAG
# AUTO/MANUAL AUTO /MAN STATISTICS HOME-->DIAG-->STATS
>SETPOINT--
PROVISIONS ON POWER PANEL TO PERMIT TRANSFER OF SWITCH FROM LIVE NON- 13 SELECT SWITCH SELECT HOME-->SETPOINT-->CONTROL OR GREEN
IF AUTO/MANUAL SWITCH IS SET TO "MANUAL S1 TO S2, S2 TO S1 (S12)" – >CONTROL CONTROL SWITCHES
PREFERRED SOURCE TO EITHER DEAD CENTER POSITION (DELAY-TYPE AND CLOSED TYPE PERMISSIVE (S5) SWITCH 'CONTROL' PUSHBUTTON
A, E, F, ATS WILL WAIT FOR PERMISSIVE SIGNAL BEFORE INITIATING THE or GREEN
REMOTE ATS ONLY) OR DE-ENERGIZED PREFERRED SOURCE. ACTIVATES ON REMOTE CONTACT RETRANSFER SEQUENCE. PERMISSIVE SIGNAL IS EITHER AN OPERATOR 'CONTROL' EXERCISER STATUS HOME-->EXERCISER
13 G, H, I, J,
LOAD SHED SIGNAL FROM BUILDING AUTOMATION OR PARALLELING SWITCHGEAR SYSTEM. SWITCH PUSHBUTTON ON THE 'STATUS' SCREEN OR CUSTOMER INPUT SIGNAL. PUSHBUTTON SET EXERCISER TYPE HOME-->EXERCISER-->SETUP-->ENTER
OR 0
DISCONNECTS THE LOAD IMMEDIATELY UPON RECEIPT OF THE LOAD SHED SIGNAL, AND HOME-->EXERCISER-->TEST OR GREEN 'TEST'
DELAY – TEST
RETURNS TO LIVE SOURCE AFTER REMOVAL OF LOAD SHED SIGNAL. TRANSFER TO CONTROL WILL OPEN NON-PREFERRED SOURCE, AND PRERFERRED SETPOINT-- PUSHBUTTON
NEUTRAL TO
CONTROL INCLUDES PROVISIONS FOR AUTOMATIC DISCONNECTION FROM NON-PREFERRED 14 MID/CENTER SOURCE WILL REMAIN OPEN FOR A TIME DELAY PERIOD (DT) >OPERATION--
NON-
SOURCE IN EVENT OF UNDERFREQUENCY, UNDERVOLTAGE, OR OVERPOWER/KW. EACH POSITION >TIMERS
PREFERRED
SETPOINT IS INDEPENDENTLY SETABLE, WITH INDIVIDUAL TIME DELAYS. IF SWITCH IS
RE-CONNECT TO ATS WILL RECONNECT LOAD TO THE PREFERRED SOURCE AFTER
CONFIGURED WITH LOAD SHED (DIGIT #13 ABOVE) SWITCH CAN BE CONFIGURED TO MOVE
B, C, OR AUTO 15 PREFERRED EXPIRATION OF TIME DELAY (DT) IN #13 ABOVE OR RECIEPT OF
9 TO CENTER OFF OR DE-ENERGIZED NON-PREFERRED SOURCE. IF SWITCH DOES NOT
D LOAD SHED SOURCE PERMISSIVE SIGNAL (#14 ABOVE)
INCLUDE LOAD SHED, A USER-CONFIGURABLE OUTPUT MAY BE ASSIGNED TO AUTO LOAD
DELAY FOR SETPOINT--

g ZENITH CONTROLS
SHED FEATURE TO PERMIT SHUNT TRIP OF DOWNSTREAM LOAD(S). ONCE ACTIVATED, GENERATOR CONTROL WILL CONTINUE TO SEND START SIGNAL TO GENERATOR TO
16 ENGINE >OPERATION--
AUTO LOAD SHED REQUIRES MANUAL/USER RESET VIA MENU RESET PUSHBUTTON OR COOLDOWN PERMIT UNLOADED RUNNING AND COOLDOWN OF GENSET
COOLDOWN >TIMERS
CONFIGURABLE AUTO LOAD SHED RESET INPUT.
GENERATOR CONTROL WILL REMOVE THE GENERATOR START SIGNAL AFTER
B, E,H, I, 17
CHICAGO ALARM/CTAP FUNCTION. INCLUDES AUDIBLE ALARM UPON CONNECTION TO STOP EXPIRATION OF COOLDOWN TIME DELAY IN #16 ABOVE
13 J, K, L, CTAP
NON-PREFERRED SOURCE.
OR M
C, F, I, J, CHICAGO, IL 60609 USA
13 K, M, N, P2 EXTENDED ENGINE START RELAY - ADJ 0.5 SEC TO 300 SEC
THIS DRAWING CONTAINS PROPRIETARY AND CONFIDENTIAL INFORMATION.
OR O REVISION: A ECN : S-8713 DUPLICATION, REPRODUCTION OR USE OF THIS DOCUMENT OR ITS CONTENTS IN ANY FORM
D, G, H, OTHER THAN AS EXPRESSLY PERMITTED BY ZENITH CONTROLS, INC. IS STRICTLY PROHIBITED.
INCLUDES (2) CT'S FOR SINGLE PHASE, (3) CT'S FOR 3PH/3W OR (4) CT'S FOR 3PH/4W SYSTEMS.
13 J, L, M, N MPQ
OR O
ADDS POWER QUALITY METERING.
DATE: 04/30/08 DRAFT: CE ENG: CE DRAWING NUMBER:
APPLICATION MX350
92A-2000 1 OF 9
REV:
A
DESCRIPTION : ESTABLISHED JOB / MODEL : ZTED (600-3000A)
ELECTRICAL SCHEMATIC DRAWINGS - GE ZENITH ZTED SERIES TRANSFER SWITCHES - DELAY TRANSITION TYPE - 600 TO 3000A
LEGEND, FEATURES, OPERATION, ACCESSORIES
THE FOLLOWING SETTINGS AND ADJUSTMENTS ARE AVAILABLE WITHIN THE ZTE TRANSFER SWITCH. REFER TO THE ZTE
OPERATIONS AND MAINTENANCE MANUAL FOR ADDITIONAL DETAILS.
12.0 DRAWING LEGEND
10.0 PROGRAMMABLE ENGINE EXERCISER
NOTE: SWITCH NOMINAL VOLTAGE AND FREQUENCY SETTINGS ARE INDICATED ON THE NAMEPLATE.
A PROGRAMMABLE ENGINE EXERCISER IS PROVIDED AS A STANDARD CONTROL FEATURE ON ALL ZTE TRANSFER SWITCHES. ITEM/SYMBOL DESCRIPTION
7. 0 NORMAL/PREFERRED
PARAMETER & EMERGENCY/ALTERNATE
RANGE OF SETTINGS
DEFAULTSOURCELOCATION
FAILURE SETTINGS
ON DISPLAY AC CONNECTION PLUG
SETTING (FOLLOW LISTED NAVIGATION) TWO (2) DIFFERENT TYPES OF EXERCISERS ARE CONFIGURABLE IN THE CONTROLLER: AUX CONNECTION PLUG
HOME>SETPOINT>OPERATION>S1 A3-1,2,3 SOURCE 2 POSITION CONTACT
UNDERVOLTAGE 75% TO 99% NOMINAL 80% - PERIODIC EXERCISER: IF ENABLED, THE ATS WILL PERFORM A TEST FUNCTION ON A PERIODIC BASIS, DEPENDING ON THE
SETTINGS (OR S2 SETTINGS) A4-1,2,3 SOURCE 1 POSTION CONTACT
UTIL: 59 HZ EXERCISER SETTING TYPE. CE SOURCE 2 MAIN TRANSFER OPRATOR
UNDERFREQUENCY 45.0 TO 59.9 HZ SAME AS ABOVE o PROGRAMMBLE TYPES: THE TYPE IS USER PROGRAMMABLE AS ‘DAILY’, ‘WEEKLY’, ’14 DAYS’, OR ’28 DAYS’
GEN: 54 HZ CEO SOURCE 2 OPEN MAIN TRANSFER OPRATOR
OVERVOLTAGE 105% TO 110% NOMINAL 110% SAME AS ABOVE o # PROGRAMABLE EVENTS: UP TO (7) SEPARATE TEST EVENTS MAY BE PROGRAMMED, EACH WITH START TIME,
CN SOURCE 1 MAIN TRANSFER OPRATOR
OVERFREQUENCY 50.1 TO 63.0 HZ OFF SAME AS ABOVE START DATE, AND RUN DURATION.
o OPERATION DESCRPTION: EACH TEST EVENT WILL AUTOMATICALLY RE-INITIATE EVERY DAY, WEEK, 14 DAYS, SEO SOURCE 1 OPEN MAIN TRANSFER OPRATOR
HOME>SETPOINT>CONTROL> CPU CENTRAL PROCESSING UNIT
VOLTAGE IMBALANCE 5% TO 20% PHASE-PHASE 10% OR 28 DAYS – IN ACCORDANCE WITH THE EXERCISER SETTING.
ALARMS CT1,2,3 CURRENT TRANSFORMER
o RANGES: ENGINE RUN DURATION RANGE IS 0 MIN: 1 SEC TO 59 MIN: 59 SEC
VOLTAGE IMBALANCE HOME>SETPOINT>CONTROL> CTTB CURRENT TRANSFORMER TERMINAL BLOCK
1 TO 60 SECONDS 30 SEC
TIME DELAY ALARMS CV CONTROL VOLTAGE
- CLOCK EXERCISER: IF ENABLED, THE ATS WILL PERFORM A TEST FUNCTION AT SPECIFIC DATES/TIMES SETUP IN THE
CONTROLLER BY THE USER/OPERATOR. DC CONNECTION PLUG
o PROGRAMMBLE TYPES: THE TYPE IS USER PROGRAMMABLE AS ‘365 DAYS’ DS DISCONNECT SWITCH
8.0 NORMAL/PREFERRED & EMERGENCY/ALTERNATE SOURCE RETURN SETTINGS o # PROGRAMABLE EVENTS: UP TO (24) SEPARATE TEST EVENTS MAY BE PROGRAMMED, EACH WITH START TIME, E1,2,3 SOURCE 2 EMERGENCY LINE
START DATE, AND RUN DURATION. EN SOURCE 2 EMERGENCY NEUTRAL LINE
DEFAULT LOCATION ON DISPLAY o OPERATION DESCRPTION: EACH TEST EVENT WILL BE INITIATED AT THE DATE/TIME SET FOR EACH EVENT.
PARAMETER RANGE OF SETTINGS K- CARD MX350 NON CONFIGURABLE INPUT/OUTPUT CARD
SETTING (FOLLOW LISTED NAVIGATION)
o RANGES: RUN DURATION RANGE IS 0 MIN: 1 SEC TO 59 MIN: 59 SEC L-CARD MX350 CONFIGURABLE INPUT/OUTPUT CARD
HOME>SETPOINT>OPERATION>S1
UNDERVOLTAGE 85% TO 100% NOMINAL 90% N1,2,3 SOURCE 1 EMERGENCY LINE
SETTINGS (OR S2 SETTINGS)
NN SOURCE 1 EMERGENCY NEUTRAL LINE
UNDERFREQUENCY 45.1 TO 60.0 HZ
UTIL: 59.5 HZ SAME AS ABOVE 11.0 STANDARD CONTROL SWITCHES OIP OPERATOR INTERFACE PANEL
GEN: 57 HZ
OVERVOLTAGE 103% TO 108% NOMINAL 105% SAME AS ABOVE PA3 CONNECTION PLUG
REMOTE PSU MX350 POWER SUPPLY MODULE
OVERFREQUENCY 50.0 TO 62.9 HZ OFF SAME AS ABOVE LOCATION OF FACT
SWITCH ACTIVATION Q2 REMOTE SYSTEM TEST CONTACT
HOME>SETPOINT>CONTROL> APPLICABLE CONTROL ADJUST ORY
VOLTAGE IMBALANCE * 5% TO 20% PHASE-PHASE 10% FUNCTION DESCRIPTION PERMITTED
ALARMS SETTINGS IN ZTE RANGE DEFAU RCE RECTIFIER CAPACITOR, EMERGENCY
(CODE) (CUSTOMER
VOLTAGE IMBALANCE HOME>SETPOINT>CONTROL> DISPLAY LT RCN RECTIFIER CAPACITOR, NORMAL
1 TO 60 SECONDS 30 SEC CONFIG INPUT)
TIME DELAY * ALARMS RSS SECONDARY SOLENOID RECTIFIER
PREFERRED HOME-->SETPOINT--
* AVAILABLE 3-PHASE UNITS ONLY SOURCE >CONTROL or GREEN SCR-E SILICON CONTROL RECTIFIER, COMMAND TO CLOSE SOURCE 2
PERMITS USER SELECTION OF THE PREFERRED SOURCE S1 OR S2 S1 YES SCR-EO SILICON CONTROL RECTIFIER, COMMAND TO OPEN SOURCE 2
SELECT 'CONTROL'
• SWITCH (S3) PUSHBUTTON SCR-N SILICON CONTROL RECTIFIER, COMMAND TO CLOSE SOURCE 1
9.0 TIME DELAY SETTINGS IF SET TO ENABLED/YES: CONTROL WILL CONNECT TO THE SCR-NO SILICON CONTROL RECTIFIER, COMMAND TO OPEN SOURCE 2
NON-PREFERRED SOURCE EVEN IF PREFERRED RETURNS SE SOURCE 2 LIMIT SWITCH (CLOSE WHEN ATS IS IN SOURCE 2 POSITION
LOCATION ON BEFORE EXPIRATION OF PREFERRED SOURCE FAILURE TIME SOURCE 2 LIMIT SWITCH (CLOSE WHEN ATS IS IN SOURCE 2 OPEN
DESCRIPTION DEFAULT DISPLAY HOME-->SETPOINT-- ENABLED SEO
EXTENDED DESCRIPION SETTING RANGE COMMIT DELAY DISAB POSITION)
ON DISPLAY SETTING (FOLLOW LISTED >CONTROL or GREEN (YES),
TRANSFER ELED YES SLE TRANSFER TO EMERGENCY RELAY
NAVIGATION) 'CONTROL' DISABLED
TO S2 (S13) IF SET TO DISABELED/NO: CONTROL WILL REMOVE START (NO) SLN TRANSFER TO NORMAL RELAY
DELAY FROM FAILURE OF PUSHBUTTON (NO)
DELAY FOR 0 TO 10 SEC SIGNAL AND STAY CONNECTED TO THE PREFERRED SOURCE SN SOURCE 1 LIMIT SWITCH (CLOSE WHEN ATS IS IN SOURCE 1 POSITION
PREFERRED SOURCE TO HOME>SETPOINT> IF PREFERRED RETURNS BEFORE EXPIRATION OF
GENERATOR (0 TO 259 MIN IF 120 VAC EXTERNAL POWER 3 SEC. SOURCE 1 LIMIT SWITCH (CLOSE WHEN ATS IS IN SOURCE 2 OPEN
SENDING OF START SUPPLY CONNECTED) OPERATION>TIMERS PREFERRED SOURCE FAILURE TIME DELAY SNO
START POSITION)
SIGNAL TO GENERATOR
HOME-->EXERSISER-- SOL-1 LIMIT SWITCH SOLENOID, SOURCE 1
DELAY - XFER DELAY ON TRANSFER TO >TEST-->FASTTEST or
TO NON- NON-PREFERRED SOURCE 0 SEC TO 259 MINUTES (15,540 SEC). FAST TEST INITIATES A TEST WITH LOAD, USING FIXED (SMALL) TIME SOL-2 LIMIT SWITCH SOLENOID, SOURCE 2
NOTE: BYPASS OF TIME DELAY PERMITTED 3 SEC. SAME AS ABOVE GREEN 'TEST' N/A N/A NO
PREFERRED AFTER SENSING THAT SWITCH DELAY SETTINGS SS SECONDARY SOLENOID
VIA PUSHBUTTON ON STATUS SCREEN PUSHBUTTON THEN
SRC SOURCE IS HEALTHY T1,2,3 LOAD LINES
'FASTTEST'
TIME PERIOD SWITCH TN LOAD NEUTRAL LINE
DELAY – HOME-->EXERSISER--
WILL REMAIN IN 0 SEC TO 10 MINUTES (600 SEC). >TEST-->XFERLOAD or UTA UNIVERSAL TRANSFORMER ASSEMBLY
NEUTRAL TO TEST WITH INITIATES A TEST WITH LOAD, USING SAME TIME DELAY
CENTER/OFF POSITION NOTE: BYPASS OF TIME DELAY PERMITTED 5 SEC. SAME AS ABOVE GREEN 'TEST' N/A N/A YES VT1 SOURCE 1 VOLTAGE SENSING CARD
NON- LOAD (TSL) SETTINGS AS THOSE FOR ACTUAL OUTAGE CONDITION
BEFORE CONNECTING TO VIA PUSHBUTTON ON STATUS SCREEN
PUSHBUTTON THEN VT2 SOURCE 2 VOLTAGE SENSING CARD
PREFERRED
NON-PREFERRED SOURCE 'XFERLOAD'
DELAY ON SENSING OF HOME-->EXERSISER--
ALTERNATE SOURCE 0 SEC TO 30 SEC. TEST NO >TEST-->NOXFER or
TIME DELAY INITIATES A STARTING OF GENERATOR BY ATS, BUT NO
FAILURE TO PERMIT NOTE: BYPASS OF TIME DELAY PERMITTED OFF/ 0 SEC. SAME AS ABOVE LOAD GREEN 'TEST' N/A N/A YES
FOR GEN SAG TRANSFER OF LOAD AWAY FROM PREFERRED SOURCE
GENSET TO RECOVER VIA PUSHBUTTON ON STATUS SCREEN
(TSNL) PUSHBUTTON THEN
FROM LOAD IMPACT 'NOXFER'
DELAY ON RE-TRANSFER IF SET TO "AUTO": SWITCH WILL AUTOMATICALY CONNECT
DELAY - XFER
TO PREFERRED SOURCE 0 SEC TO 259 MINUTES. TO THE SOURCES UPON EXPIRATION OF ASSOCIATED TIME
TO
TO ENSURE SOURCE IS NOTE: BYPASS OF TIME DELAY PERMITTED 30 MINUTES SAME AS ABOVE DELAYS
PREFERRED
HEALTHY AND 2ND VIA PUSHBUTTON ON STATUS SCREEN
SRC
FAILURE IS UNLIKELY IF SET TO "MANUAL S2 TO S1 ONLY (S5)" SWITCH WILL NOT
TIME PERIOD SWITCH AUTOMATICALLY RETURN TO PREFERRED SOURCE. SWITCH "AUTO",
DELAY – WILL REMAIN IN 0 SEC TO 10 MINUTES (600 SEC). WILL WAIT FOR OPERATOR TO GIVE PERMISSIVE [SOFT "MANUAL
NEUTRAL TO CENTER/OFF POSITION NOTE: BYPASS OF TIME DELAY PERMITTED 5 SEC. SAME AS ABOVE AUTO/
SWITCH ON STATUS SCREEN] OR RECEIPT OF USER HOME-->SETPOINT-- S1 TO S2, S2
PREFERRED BEFORE CONNECTING TO VIA PUSHBUTTON ON STATUS SCREEN MANUAL
CONFIGURABLE CUSTOMER INPUT CONFIGURED TO >CONTROL or GREEN TO S1
NON-PREFERRED SOURCE SELECT AUTO YES
"MANUAL XFER S2 TO S1 (S5)" FEATURE 'CONTROL' (S12)",
DELAY FOR DELAY TO PERMIT SWITCH
0 MIN:0 SEC TO 60MIN:0SEC. PUSHBUTTON "MANUAL
ENGINE UNLOADED RUNNING OF NOTE: BYPASS OF TIME DELAY PERMITTED 5 MINUTES SAME AS ABOVE (S5, S12)
IF SET TO "MANUAL S1 TO S2, S2 TO S1 (S12)" SWITCH WILL S2 TO S1
COOLDOWN GENSET FOR COOLDOWN VIA PUSHBUTTON ON STATUS SCREEN NOT AUTOMATICALLY CONNECT TO THE NON-PREFERRED ONLY (S5)"
SOURCE, OR RETURN TO PREFERRED SOURCE. SWITCH WILL
WAIT FOR OPERATOR TO GIVE PERMISSIVE [SOFT SWITCH ON
STATUS SCREEN] OR RECEIPT OF USER CONFIGURABLE
CUSTOMER INPUT CONFIGURED TO "MANUAL XFER S1 -2
AND S2-1 (S12)" FEATURE

g ZENITH CONTROLS CHICAGO, IL 60609 USA


THIS DRAWING CONTAINS PROPRIETARY AND CONFIDENTIAL INFORMATION.
REVISION: A ECN: S-8713 DUPLICATION, REPRODUCTION OR USE OF THIS DOCUMENT OR ITS CONTENTS IN ANY FORM
OTHER THAN AS EXPRESSLY PERMITTED BY ZENITH CONTROLS, INC. IS STRICTLY PROHIBITED.
DATE: 04/30/08 DRAFT: CE ENG: CE DRAWING NUMBER:
APPLICATION MX350
92A-2000 2 OF 9
REV:
A
DESCRIPTION: ESTABLISHED JOB/MODEL: ZTED (600-3000A)
GE ZENITH ZTED SERIES TRANSFER SWITCHES
ZTE SERIES CATALOG NUMBER SCHEME, USER CONFIGURABLE I/O

13.0 ATS CATALOG NUMBER SCHEME 14.0 USER CONFIGURABLE I/O


ZTE SWITCHES INCLUDE USER CONFIGURABLE INPUTS & OUTPUTS (I/O) THAT MAY BE FIELD-RECONFIGURED TO MEET SITE NEEDS. THE AMOUNT OF I/O DEPENDS ON
THE INSTALLED CONTROL CONFIGURATION GROUP (SEE TABLE BELOW)

Z1 0 A 2 S 1 A A 1 0 A X X X X XX CONFIGURATION OF THE I/O AT TIME OF FACTORY SHIPMENT IS SHOWN ON THE NAMEPLATE ADJACENT TO THE CUSTOMER CONNECTIONS TERMINAL STRIP AND
THE ATTACHED TABLE. NEW CONTROL FEATURES MAY BE ADDED IN FIELD BY SETTING THE CURRENT CONTROL FEATURE I/O ADDIGNEMENT TO “N/A” AND RE-
ALLOCATING THE I/O POINT TO A NEW FEATURE. SEE O&M MANUAL FOR COMPLETE PROCEDURE FOR I/O RE-ASSIGNMENT AND LIST OF AVAILABLE FEATURES.
FACTORY DEFAULT I/O CONFIGURATION
DIGIT #1, #2 PRODUCT TYPE
TYPE "A" "B" "C" "D" "M" RECORD
Z1 - ATS FEATURE EXTENDED DESCRIPTION (INPUT/
OPTION
4 IN/ 4 IN/ 8 IN/ 12 IN/ 4 IN/ SITE
CODE
Z2 - BYPASS ATS OUTPUT) 4 OUT 4 OUT 8 OUT 12 OUT 4 OUT SETTING

SOURCE 1 FAILURE OUTPUT A1 OUTPUT 1 OUTPUT 1 OUTPUT 1 OUTPUT 1 OUTPUT 1


DIGIT #3 OPERATION SOURCE STATUS
SOURCE 2 FAILURE OUTPUT A1E OUTPUT 2 OUTPUT 2 OUTPUT 2 OUTPUT 2 OUTPUT 2
O – OPEN TRANSITION
D – DELAYED TRANSITION SWITCH
CONNECTED TO SOURCE 1 OUTPUT A4 * * * OUTPUT 12 *
C – CLOSED TRANSITION POSITION CONNECTED TO SOURCE 2 OUTPUT A3 * * * OUTPUT 11 *
CONNECTED TO CENTER (DELAY TYPE ATS ONLY) OUTPUT A34N * * * * *
BYPASS ATS ON SOURCE 1 (BYPASS ATS ONLY) OUTPUT AB3, AB4 * * * * *
DIGIT #4 AMPERE RATING
A – 40A B - 80A C – 100A, D – 150A, F – 225A SWITCH EXERCISING OUTPUT ACTIVE WHEN SWITCH IN EXERCISE MODE OUTPUT EXC * * OUTPUT 6 OUTPUT 6 *
G- 260A, I – 400A, J-600A, K-800A, L-1000A ENGINE START SIGNAL ACTIVE OUTPUT ESS * * * * *
AUTO TRANSFER OCCURRED – S1ÆS2 OR S2ÆS1 OUTPUT ATS2, ATS1 * * * * N/A
M-1200A, N-1600A, O-2000A, Q-3000A, MANUAL TRANSFER TO S2 OCCURED OUTPUT MTS2S1 N/A N/A N/A N/A OUTPUT 3
R-4000A MANUAL TRANSFER TO S1 OCCURED OUTPUT MTS1S2 N/A N/A N/A N/A OUTPUT 4
SWITCH STATUS
& DIAGNOSTICS TRANSFER INHIBIT (S2 TO S1, OR S1 TO S2) ON OUTPUT TIS2S1, TIS1S2 * * * * N/A
DIGIT #5 # POLES COMMON ALARM (ANY ALARM ACTIVE) OUTPUT ALM * * OUTPUT 7 OUTPUT 7 *
FAIL TO TRANSFER TO SOURCE 1 ALARM POSTIVE INDICATION OF XFER NOT RECEIVED BY CONTROL OUTPUT FTS1 * * * OUTPUT 9 *
2 – 2 POLE, 3- 3 POLE, 4- 4 POLE
FAIL TO TRANSFER TO SOURCE 2 ALARM OUTPUT FTS2 OUTPUT 3 OUTPUT 3 OUTPUT 3 OUTPUT 3 *
ATS NOT IN AUTO SWITCH IS INIHIBITED FROM AUTO OPERATION OUTPUT NIA * * OUTPUT 8 OUTPUT 8 N/A
DIGIT #6 APPLICATION/SOURCE TYPES TRANSFER TO SOURCE 2 ALARM (CHICAGO/CTAP) OUTPUT CTAP * * * * *
S – UTILITY TO GENERATOR
REMOTE ENGINE START ATS WILL RESPOND WITH START SIGNAL TO GEN INPUT RES INPUT 4 INPUT 4 INPUT 4 INPUT 4 INPUT 4
U – UTILTY TO UTILITY
NO LOAD TEST ATS WILL START GEN, BUT NOT TRANSFER LOAD INPUT TSNL * * * * Input 3
G – GENERATOR TO GENERATOR BYPASS TIME DELAY ON TRANSFER TO SOURCE 1 WILL CAUSE IMMEDIATE CONNECTION TO SOURCE 1 INPUT BYPTR INPUT 1 INPUT 1 INPUT 1 INPUT 1 N/A
BYPASS TIME DELAY ON TRANSFER TO SOURCE 2 WILL CAUSE IMMEDIATE CONNECTION TO SOURCE 1 INPUT BYPWR * * INPUT 5 INPUT 5 N/A
DIGIT #7 1 REMOTE INHIBIT TRANSFER TO SOURCE 1 WILL IHHIBIT ATS FROM CONNECTING LOAD TO SOURCE 1 INPUT Q7 INPUT 3 INPUT 3 INPUT 3 INPUT 3 N/A
CONTROL/ INHIBIT TRANSFER TO SOURCE 2 WILL IHHIBIT ATS FROM CONNECTING LOAD TO SOURCE 2 INPUT Q3 INPUT 2 INPUT 2 INPUT 2 INPUT 2 N/A
BUILDING AUTO/MAN TRANSFER SELECT - SOURCE 2 TO SOURCE 1 REMOTE CONTROL OF AUTO/MAN SWITCH INPUT S5R * * * * N/A
DIGIT #8 ENCLOSURE TYPE INTERFACE MANUAL RE-TRANSFER TO SOURCE 1 PERMISSIVE SIGNAL TO TRANSFER IN MANUAL MODE INPUT YNR * * INPUT 8 INPUT 8 INPUT 2
X - OPEN (NONE), A – NEMA 1, B –NEMA 1A AUTO/MAN TRANSFER SELECT - SOURCE 2 TO SOURCE 1 REMOTE CONTROL OF AUTO/MAN SWITCH INPUT
C – NEMA 3R, D – NEMA 3R W/ HEATER AND SOURCE 1 TO SOURCE 2 S12R * * INPUT 6 INPUT 6 N/A
MANUAL RE-TRANSFER TO SOURCE 2 PERMISSIVE SIGNAL TO TRANSFER IN MANUAL MODE INPUT YER * * INPUT 7 INPUT 7 INPUT 2
E – NEMA 4, F – NEMA 12, G – NEMA 4X
PRIME SOURCE SELECTION REMOTE SELECTION OF PRIME SOURCE INPUT S3R * * * INPUT 12 N/A
COMMIT/NO COMMIT TO TRANSFER TO SOURCE 2 REMOTE SELECTION OF COMMIT/NO COMMIT XFER INPUT S13R * * * * N/A
DIGIT #9 CONTROL OPTION PACKAGE
A, B, C, OR D: SEE SHEET #1 FOR DESCRIPTION PROGRAMMABLE PROGRAMMABLE LOAD CONTROL RELAY #1 PROG. AS ELEVATOR PRE-SIGNAL OR LOAD DISC. OUTPUT LCE1, LCL1 OUTPUT 4 OUTPUT 4 OUTPUT 4 OUTPUT 4 *
LOAD CONTROL PROGRAMMABLE LOAD CONTROL RELAY #2 PROG. AS ELEVATOR PRE-SIGNAL OR LOAD DISC. OUTPUT LCE2, LCL2 * * OUTPUT 5 OUTPUT 5 *
RELAYS PROGRAMMABLE LOAD CONTROL RELAY #3-#6 PROG. AS ELEVATOR PRE-SIGNAL OR LOAD DISC. OUTPUT LCE3-6, LCL3-6 * * * * *
DIGIT #10,#11 VOLTAGE RATING
2-DIGIT FACTORY CODE. SEE ATS NAMEPLATE AUTO LOAD SHED – REMOTE RESET REMOTE RESET FOR LATCHED AUTO LOAD SHED OUTPUT ALS N/A * * OUTPUT 10 N/A
AUTO LOAD
FOR RATED VOLTAGE SHED
REMOTE SELECTION TO SHED ATS OR PICKUP CONTROL INPUT
AUTO LOAD SHED – LOCAL/REMOTE SELECT RELAY ON ACTIVATION OF AUTO LOAD SHED LS1R N/A * * INPUT 9 N/A
AUTO LOAD SHED – KW BYPASS ENABLE/DISABLE ALS PICKUP ON OVER KW INPUT LS1KW N/A * * INPUT 10 N/A
DIGIT #12 LUG OPTIONS
2-DIGIT FACTORY CODE. SEE O&M MANUAL SOURCE 1 (OR SOURCE 2) UNDERVOLTAGE UVS1, UVS2 N/A * * * N/A
FOR DETAILS SOURCE 1 (OR SOURCE 2) OVERVOLTAGE OUTPUT OVS1/2 N/A * * * N/A
SOURCE 1 (OR SOURCE 2) UNDERFREQUENCY UFS1, UFS2 N/A * * * N/A
USER SOURCE 1 (OR SOURCE 2) OVERFREQUENCY OUTPUT OFS1/2 N/A * * * N/A
DIGIT #13 METERING & ACCESSORIES CODE CONFIGURABLE LOW PF ALARM OUTPUT LLPFA N/A * * * N/A
‘A’ THRU ‘O” OR X. SEE SHEET #1 FOR ANALOG ALARMS OUTPUT VTHDS1,
FURTHER DETAILS SOURCE 1 (OR SOURCE 2) VOLTAGE THD% ALARM VTHDS2 N/A * * * N/A
LOAD CURRENT THD% ALARM OUTPUT CTA N/A * * * N/A
LOAD KW (OVERLOAD) ALARM OUTPUT LOKWA N/A * * * N/A
DIGIT #14 COMMUNICATIONS OPTIONS CODE OUTPUT OCAPA/B/C,
‘X’, ‘S’, OR ‘E’. SEE SHEET #1 FOR FURTHER OVERCURRENT ALARM (PHASE A, B, C, OR N) NOCA N/A * * * N/A
DETAILS SOURCE 1 (OR SOURCE 2) VOLTAGE IMBALANCE OUTPUT VIAS1, VIAS2 N/A * * * N/A
LOAD CURRENT UNBALANCE ALARM OUTPUT CIA N/A * * * N/A

DIGIT #15 GROUND BUS OPTIONS CODE USER DIGITAL INPUTS (UP TO 10) FOR USER CONFIG ALARMS UP TO 10 ALARMS, ACTIVATED BY INPUTS & TIME DELAY
‘X’, OR 1-8. SEE O&M FOR DETAILS CONFIGURABLE &/OR FLEXLOGIC SETTING. INCLUDE USER-PROG MESSAGE DISPLAY INPUT CCDI-x N/A * * * N/A
DIGITAL ALARMS
USER CONFIG DIGITAL ALARMS OUTPUT CONTACT FOR PROGRAMMED DIGITAL ALARMS OUTPUT CCAD-x N/A * * * N/A
DIGIT #16 TVSS OPTIONS CODE
‘X’, OR ‘A-G’. SEE O&M FOR DETAILS

g
DIGIT #17 BATTERY CHARGER OPTION CODE
‘X’, OR ‘1-4’. SEE O&M FOR DETAILS

DIGIT #18 ‘X’ ZENITH CONTROLS


CHICAGO, IL 60609 USA
ECN : S-8713 THIS DRAWING CONTAINS PROPRIETARY AND CONFIDENTIAL INFORMATION.
REVISION: A DUPLICATION, REPRODUCTION OR USE OF THIS DOCUMENT OR ITS CONTENTS IN ANY FORM
OTHER THAN AS EXPRESSLY PERMITTED BY ZENITH CONTROLS, INC. IS STRICTLY PROHIBITED.
DRAWING NUMBER:
DATE: 04/30/08 DRAFT: CE ENG: CE APPLICATION MX350
REV:
3 OF 9
DESCRIPTION : ESTABLISHED JOB/MODEL : ZTED (600-3000A)
92A-2000 A