Legend, Features, Operation, and Accessories
Legend, Features, Operation, and Accessories
g ZENITH CONTROLS
SHED FEATURE TO PERMIT SHUNT TRIP OF DOWNSTREAM LOAD(S). ONCE ACTIVATED, GENERATOR CONTROL WILL CONTINUE TO SEND START SIGNAL TO GENERATOR TO
16 ENGINE >OPERATION--
AUTO LOAD SHED REQUIRES MANUAL/USER RESET VIA MENU RESET PUSHBUTTON OR COOLDOWN PERMIT UNLOADED RUNNING AND COOLDOWN OF GENSET
COOLDOWN >TIMERS
CONFIGURABLE AUTO LOAD SHED RESET INPUT.
GENERATOR CONTROL WILL REMOVE THE GENERATOR START SIGNAL AFTER
B, E,H, I, 17
CHICAGO ALARM/CTAP FUNCTION. INCLUDES AUDIBLE ALARM UPON CONNECTION TO STOP EXPIRATION OF COOLDOWN TIME DELAY IN #16 ABOVE
13 J, K, L, CTAP
NON-PREFERRED SOURCE.
OR M
C, F, I, J, CHICAGO, IL 60609 USA
13 K, M, N, P2 EXTENDED ENGINE START RELAY - ADJ 0.5 SEC TO 300 SEC
THIS DRAWING CONTAINS PROPRIETARY AND CONFIDENTIAL INFORMATION.
OR O REVISION: A ECN : S-8713 DUPLICATION, REPRODUCTION OR USE OF THIS DOCUMENT OR ITS CONTENTS IN ANY FORM
D, G, H, OTHER THAN AS EXPRESSLY PERMITTED BY ZENITH CONTROLS, INC. IS STRICTLY PROHIBITED.
INCLUDES (2) CT'S FOR SINGLE PHASE, (3) CT'S FOR 3PH/3W OR (4) CT'S FOR 3PH/4W SYSTEMS.
13 J, L, M, N MPQ
OR O
ADDS POWER QUALITY METERING.
DATE: 04/30/08 DRAFT: CE ENG: CE DRAWING NUMBER:
APPLICATION MX350
92A-2000 1 OF 9
REV:
A
DESCRIPTION : ESTABLISHED JOB / MODEL : ZTED (600-3000A)
ELECTRICAL SCHEMATIC DRAWINGS - GE ZENITH ZTED SERIES TRANSFER SWITCHES - DELAY TRANSITION TYPE - 600 TO 3000A
LEGEND, FEATURES, OPERATION, ACCESSORIES
THE FOLLOWING SETTINGS AND ADJUSTMENTS ARE AVAILABLE WITHIN THE ZTE TRANSFER SWITCH. REFER TO THE ZTE
OPERATIONS AND MAINTENANCE MANUAL FOR ADDITIONAL DETAILS.
12.0 DRAWING LEGEND
10.0 PROGRAMMABLE ENGINE EXERCISER
NOTE: SWITCH NOMINAL VOLTAGE AND FREQUENCY SETTINGS ARE INDICATED ON THE NAMEPLATE.
A PROGRAMMABLE ENGINE EXERCISER IS PROVIDED AS A STANDARD CONTROL FEATURE ON ALL ZTE TRANSFER SWITCHES. ITEM/SYMBOL DESCRIPTION
7. 0 NORMAL/PREFERRED
PARAMETER & EMERGENCY/ALTERNATE
RANGE OF SETTINGS
DEFAULTSOURCELOCATION
FAILURE SETTINGS
ON DISPLAY AC CONNECTION PLUG
SETTING (FOLLOW LISTED NAVIGATION) TWO (2) DIFFERENT TYPES OF EXERCISERS ARE CONFIGURABLE IN THE CONTROLLER: AUX CONNECTION PLUG
HOME>SETPOINT>OPERATION>S1 A3-1,2,3 SOURCE 2 POSITION CONTACT
UNDERVOLTAGE 75% TO 99% NOMINAL 80% - PERIODIC EXERCISER: IF ENABLED, THE ATS WILL PERFORM A TEST FUNCTION ON A PERIODIC BASIS, DEPENDING ON THE
SETTINGS (OR S2 SETTINGS) A4-1,2,3 SOURCE 1 POSTION CONTACT
UTIL: 59 HZ EXERCISER SETTING TYPE. CE SOURCE 2 MAIN TRANSFER OPRATOR
UNDERFREQUENCY 45.0 TO 59.9 HZ SAME AS ABOVE o PROGRAMMBLE TYPES: THE TYPE IS USER PROGRAMMABLE AS ‘DAILY’, ‘WEEKLY’, ’14 DAYS’, OR ’28 DAYS’
GEN: 54 HZ CEO SOURCE 2 OPEN MAIN TRANSFER OPRATOR
OVERVOLTAGE 105% TO 110% NOMINAL 110% SAME AS ABOVE o # PROGRAMABLE EVENTS: UP TO (7) SEPARATE TEST EVENTS MAY BE PROGRAMMED, EACH WITH START TIME,
CN SOURCE 1 MAIN TRANSFER OPRATOR
OVERFREQUENCY 50.1 TO 63.0 HZ OFF SAME AS ABOVE START DATE, AND RUN DURATION.
o OPERATION DESCRPTION: EACH TEST EVENT WILL AUTOMATICALLY RE-INITIATE EVERY DAY, WEEK, 14 DAYS, SEO SOURCE 1 OPEN MAIN TRANSFER OPRATOR
HOME>SETPOINT>CONTROL> CPU CENTRAL PROCESSING UNIT
VOLTAGE IMBALANCE 5% TO 20% PHASE-PHASE 10% OR 28 DAYS – IN ACCORDANCE WITH THE EXERCISER SETTING.
ALARMS CT1,2,3 CURRENT TRANSFORMER
o RANGES: ENGINE RUN DURATION RANGE IS 0 MIN: 1 SEC TO 59 MIN: 59 SEC
VOLTAGE IMBALANCE HOME>SETPOINT>CONTROL> CTTB CURRENT TRANSFORMER TERMINAL BLOCK
1 TO 60 SECONDS 30 SEC
TIME DELAY ALARMS CV CONTROL VOLTAGE
- CLOCK EXERCISER: IF ENABLED, THE ATS WILL PERFORM A TEST FUNCTION AT SPECIFIC DATES/TIMES SETUP IN THE
CONTROLLER BY THE USER/OPERATOR. DC CONNECTION PLUG
o PROGRAMMBLE TYPES: THE TYPE IS USER PROGRAMMABLE AS ‘365 DAYS’ DS DISCONNECT SWITCH
8.0 NORMAL/PREFERRED & EMERGENCY/ALTERNATE SOURCE RETURN SETTINGS o # PROGRAMABLE EVENTS: UP TO (24) SEPARATE TEST EVENTS MAY BE PROGRAMMED, EACH WITH START TIME, E1,2,3 SOURCE 2 EMERGENCY LINE
START DATE, AND RUN DURATION. EN SOURCE 2 EMERGENCY NEUTRAL LINE
DEFAULT LOCATION ON DISPLAY o OPERATION DESCRPTION: EACH TEST EVENT WILL BE INITIATED AT THE DATE/TIME SET FOR EACH EVENT.
PARAMETER RANGE OF SETTINGS K- CARD MX350 NON CONFIGURABLE INPUT/OUTPUT CARD
SETTING (FOLLOW LISTED NAVIGATION)
o RANGES: RUN DURATION RANGE IS 0 MIN: 1 SEC TO 59 MIN: 59 SEC L-CARD MX350 CONFIGURABLE INPUT/OUTPUT CARD
HOME>SETPOINT>OPERATION>S1
UNDERVOLTAGE 85% TO 100% NOMINAL 90% N1,2,3 SOURCE 1 EMERGENCY LINE
SETTINGS (OR S2 SETTINGS)
NN SOURCE 1 EMERGENCY NEUTRAL LINE
UNDERFREQUENCY 45.1 TO 60.0 HZ
UTIL: 59.5 HZ SAME AS ABOVE 11.0 STANDARD CONTROL SWITCHES OIP OPERATOR INTERFACE PANEL
GEN: 57 HZ
OVERVOLTAGE 103% TO 108% NOMINAL 105% SAME AS ABOVE PA3 CONNECTION PLUG
REMOTE PSU MX350 POWER SUPPLY MODULE
OVERFREQUENCY 50.0 TO 62.9 HZ OFF SAME AS ABOVE LOCATION OF FACT
SWITCH ACTIVATION Q2 REMOTE SYSTEM TEST CONTACT
HOME>SETPOINT>CONTROL> APPLICABLE CONTROL ADJUST ORY
VOLTAGE IMBALANCE * 5% TO 20% PHASE-PHASE 10% FUNCTION DESCRIPTION PERMITTED
ALARMS SETTINGS IN ZTE RANGE DEFAU RCE RECTIFIER CAPACITOR, EMERGENCY
(CODE) (CUSTOMER
VOLTAGE IMBALANCE HOME>SETPOINT>CONTROL> DISPLAY LT RCN RECTIFIER CAPACITOR, NORMAL
1 TO 60 SECONDS 30 SEC CONFIG INPUT)
TIME DELAY * ALARMS RSS SECONDARY SOLENOID RECTIFIER
PREFERRED HOME-->SETPOINT--
* AVAILABLE 3-PHASE UNITS ONLY SOURCE >CONTROL or GREEN SCR-E SILICON CONTROL RECTIFIER, COMMAND TO CLOSE SOURCE 2
PERMITS USER SELECTION OF THE PREFERRED SOURCE S1 OR S2 S1 YES SCR-EO SILICON CONTROL RECTIFIER, COMMAND TO OPEN SOURCE 2
SELECT 'CONTROL'
• SWITCH (S3) PUSHBUTTON SCR-N SILICON CONTROL RECTIFIER, COMMAND TO CLOSE SOURCE 1
9.0 TIME DELAY SETTINGS IF SET TO ENABLED/YES: CONTROL WILL CONNECT TO THE SCR-NO SILICON CONTROL RECTIFIER, COMMAND TO OPEN SOURCE 2
NON-PREFERRED SOURCE EVEN IF PREFERRED RETURNS SE SOURCE 2 LIMIT SWITCH (CLOSE WHEN ATS IS IN SOURCE 2 POSITION
LOCATION ON BEFORE EXPIRATION OF PREFERRED SOURCE FAILURE TIME SOURCE 2 LIMIT SWITCH (CLOSE WHEN ATS IS IN SOURCE 2 OPEN
DESCRIPTION DEFAULT DISPLAY HOME-->SETPOINT-- ENABLED SEO
EXTENDED DESCRIPION SETTING RANGE COMMIT DELAY DISAB POSITION)
ON DISPLAY SETTING (FOLLOW LISTED >CONTROL or GREEN (YES),
TRANSFER ELED YES SLE TRANSFER TO EMERGENCY RELAY
NAVIGATION) 'CONTROL' DISABLED
TO S2 (S13) IF SET TO DISABELED/NO: CONTROL WILL REMOVE START (NO) SLN TRANSFER TO NORMAL RELAY
DELAY FROM FAILURE OF PUSHBUTTON (NO)
DELAY FOR 0 TO 10 SEC SIGNAL AND STAY CONNECTED TO THE PREFERRED SOURCE SN SOURCE 1 LIMIT SWITCH (CLOSE WHEN ATS IS IN SOURCE 1 POSITION
PREFERRED SOURCE TO HOME>SETPOINT> IF PREFERRED RETURNS BEFORE EXPIRATION OF
GENERATOR (0 TO 259 MIN IF 120 VAC EXTERNAL POWER 3 SEC. SOURCE 1 LIMIT SWITCH (CLOSE WHEN ATS IS IN SOURCE 2 OPEN
SENDING OF START SUPPLY CONNECTED) OPERATION>TIMERS PREFERRED SOURCE FAILURE TIME DELAY SNO
START POSITION)
SIGNAL TO GENERATOR
HOME-->EXERSISER-- SOL-1 LIMIT SWITCH SOLENOID, SOURCE 1
DELAY - XFER DELAY ON TRANSFER TO >TEST-->FASTTEST or
TO NON- NON-PREFERRED SOURCE 0 SEC TO 259 MINUTES (15,540 SEC). FAST TEST INITIATES A TEST WITH LOAD, USING FIXED (SMALL) TIME SOL-2 LIMIT SWITCH SOLENOID, SOURCE 2
NOTE: BYPASS OF TIME DELAY PERMITTED 3 SEC. SAME AS ABOVE GREEN 'TEST' N/A N/A NO
PREFERRED AFTER SENSING THAT SWITCH DELAY SETTINGS SS SECONDARY SOLENOID
VIA PUSHBUTTON ON STATUS SCREEN PUSHBUTTON THEN
SRC SOURCE IS HEALTHY T1,2,3 LOAD LINES
'FASTTEST'
TIME PERIOD SWITCH TN LOAD NEUTRAL LINE
DELAY – HOME-->EXERSISER--
WILL REMAIN IN 0 SEC TO 10 MINUTES (600 SEC). >TEST-->XFERLOAD or UTA UNIVERSAL TRANSFORMER ASSEMBLY
NEUTRAL TO TEST WITH INITIATES A TEST WITH LOAD, USING SAME TIME DELAY
CENTER/OFF POSITION NOTE: BYPASS OF TIME DELAY PERMITTED 5 SEC. SAME AS ABOVE GREEN 'TEST' N/A N/A YES VT1 SOURCE 1 VOLTAGE SENSING CARD
NON- LOAD (TSL) SETTINGS AS THOSE FOR ACTUAL OUTAGE CONDITION
BEFORE CONNECTING TO VIA PUSHBUTTON ON STATUS SCREEN
PUSHBUTTON THEN VT2 SOURCE 2 VOLTAGE SENSING CARD
PREFERRED
NON-PREFERRED SOURCE 'XFERLOAD'
DELAY ON SENSING OF HOME-->EXERSISER--
ALTERNATE SOURCE 0 SEC TO 30 SEC. TEST NO >TEST-->NOXFER or
TIME DELAY INITIATES A STARTING OF GENERATOR BY ATS, BUT NO
FAILURE TO PERMIT NOTE: BYPASS OF TIME DELAY PERMITTED OFF/ 0 SEC. SAME AS ABOVE LOAD GREEN 'TEST' N/A N/A YES
FOR GEN SAG TRANSFER OF LOAD AWAY FROM PREFERRED SOURCE
GENSET TO RECOVER VIA PUSHBUTTON ON STATUS SCREEN
(TSNL) PUSHBUTTON THEN
FROM LOAD IMPACT 'NOXFER'
DELAY ON RE-TRANSFER IF SET TO "AUTO": SWITCH WILL AUTOMATICALY CONNECT
DELAY - XFER
TO PREFERRED SOURCE 0 SEC TO 259 MINUTES. TO THE SOURCES UPON EXPIRATION OF ASSOCIATED TIME
TO
TO ENSURE SOURCE IS NOTE: BYPASS OF TIME DELAY PERMITTED 30 MINUTES SAME AS ABOVE DELAYS
PREFERRED
HEALTHY AND 2ND VIA PUSHBUTTON ON STATUS SCREEN
SRC
FAILURE IS UNLIKELY IF SET TO "MANUAL S2 TO S1 ONLY (S5)" SWITCH WILL NOT
TIME PERIOD SWITCH AUTOMATICALLY RETURN TO PREFERRED SOURCE. SWITCH "AUTO",
DELAY – WILL REMAIN IN 0 SEC TO 10 MINUTES (600 SEC). WILL WAIT FOR OPERATOR TO GIVE PERMISSIVE [SOFT "MANUAL
NEUTRAL TO CENTER/OFF POSITION NOTE: BYPASS OF TIME DELAY PERMITTED 5 SEC. SAME AS ABOVE AUTO/
SWITCH ON STATUS SCREEN] OR RECEIPT OF USER HOME-->SETPOINT-- S1 TO S2, S2
PREFERRED BEFORE CONNECTING TO VIA PUSHBUTTON ON STATUS SCREEN MANUAL
CONFIGURABLE CUSTOMER INPUT CONFIGURED TO >CONTROL or GREEN TO S1
NON-PREFERRED SOURCE SELECT AUTO YES
"MANUAL XFER S2 TO S1 (S5)" FEATURE 'CONTROL' (S12)",
DELAY FOR DELAY TO PERMIT SWITCH
0 MIN:0 SEC TO 60MIN:0SEC. PUSHBUTTON "MANUAL
ENGINE UNLOADED RUNNING OF NOTE: BYPASS OF TIME DELAY PERMITTED 5 MINUTES SAME AS ABOVE (S5, S12)
IF SET TO "MANUAL S1 TO S2, S2 TO S1 (S12)" SWITCH WILL S2 TO S1
COOLDOWN GENSET FOR COOLDOWN VIA PUSHBUTTON ON STATUS SCREEN NOT AUTOMATICALLY CONNECT TO THE NON-PREFERRED ONLY (S5)"
SOURCE, OR RETURN TO PREFERRED SOURCE. SWITCH WILL
WAIT FOR OPERATOR TO GIVE PERMISSIVE [SOFT SWITCH ON
STATUS SCREEN] OR RECEIPT OF USER CONFIGURABLE
CUSTOMER INPUT CONFIGURED TO "MANUAL XFER S1 -2
AND S2-1 (S12)" FEATURE
Z1 0 A 2 S 1 A A 1 0 A X X X X XX CONFIGURATION OF THE I/O AT TIME OF FACTORY SHIPMENT IS SHOWN ON THE NAMEPLATE ADJACENT TO THE CUSTOMER CONNECTIONS TERMINAL STRIP AND
THE ATTACHED TABLE. NEW CONTROL FEATURES MAY BE ADDED IN FIELD BY SETTING THE CURRENT CONTROL FEATURE I/O ADDIGNEMENT TO “N/A” AND RE-
ALLOCATING THE I/O POINT TO A NEW FEATURE. SEE O&M MANUAL FOR COMPLETE PROCEDURE FOR I/O RE-ASSIGNMENT AND LIST OF AVAILABLE FEATURES.
FACTORY DEFAULT I/O CONFIGURATION
DIGIT #1, #2 PRODUCT TYPE
TYPE "A" "B" "C" "D" "M" RECORD
Z1 - ATS FEATURE EXTENDED DESCRIPTION (INPUT/
OPTION
4 IN/ 4 IN/ 8 IN/ 12 IN/ 4 IN/ SITE
CODE
Z2 - BYPASS ATS OUTPUT) 4 OUT 4 OUT 8 OUT 12 OUT 4 OUT SETTING
DIGIT #15 GROUND BUS OPTIONS CODE USER DIGITAL INPUTS (UP TO 10) FOR USER CONFIG ALARMS UP TO 10 ALARMS, ACTIVATED BY INPUTS & TIME DELAY
‘X’, OR 1-8. SEE O&M FOR DETAILS CONFIGURABLE &/OR FLEXLOGIC SETTING. INCLUDE USER-PROG MESSAGE DISPLAY INPUT CCDI-x N/A * * * N/A
DIGITAL ALARMS
USER CONFIG DIGITAL ALARMS OUTPUT CONTACT FOR PROGRAMMED DIGITAL ALARMS OUTPUT CCAD-x N/A * * * N/A
DIGIT #16 TVSS OPTIONS CODE
‘X’, OR ‘A-G’. SEE O&M FOR DETAILS
g
DIGIT #17 BATTERY CHARGER OPTION CODE
‘X’, OR ‘1-4’. SEE O&M FOR DETAILS