User Manual ALFA (NET) 31 DP - 10/+90 C Cool/Heat Thermostat.: Function

The document is a user manual for the ALFA(NET) 31 DP digital thermostat. It can be programmed for cooling or heating applications with a temperature range of -10/+90°C. The thermostat connects to a network via RS-485 and can be controlled using buttons to view and adjust the setpoint temperature. It also allows changing parameters for settings like temperature differential, sensor offset, and switching between cooling and heating modes.

Uploaded by

taupiq
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
163 views4 pages

User Manual ALFA (NET) 31 DP - 10/+90 C Cool/Heat Thermostat.: Function

The document is a user manual for the ALFA(NET) 31 DP digital thermostat. It can be programmed for cooling or heating applications with a temperature range of -10/+90°C. The thermostat connects to a network via RS-485 and can be controlled using buttons to view and adjust the setpoint temperature. It also allows changing parameters for settings like temperature differential, sensor offset, and switching between cooling and heating modes.

Uploaded by

taupiq
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

User manual

ALFA(NET) 31 DP -10/+90OC
Cool/Heat Thermostat.

VDH doc. 091112 Version: v1.0 Date: 16-11-2009


Software: ALFA(NET)31DP -10/+90C File: Do053809.wpd Range: -10/+90C per 0,1C

* Function.
The ALFA(NET) 31 DP is a digital thermostat for panel mounting. The function from the thermostat
can be programmed for cooling or heating.
The ALFANET 31 DP has a RS 485 network connection so it can be read out and adjusted on the
Alfanet.

* Installation.
On the topside of the ALFA(NET) 31 DP you can see how the sensor, power supply and relay have
to be connected.
After connecting the ALFA(NET) 31 DP to the power supply, a self test function is started. As this test
is finished, the measured temperature appears in the display.
When the relay is activated, the led 'on' will light-up in the display.

* Control.
The ALFA(NET) 31 DP thermostat can be controlled by three pushbuttons on the front. These keys
are;
SET - view / change the setpoint.
UP - increase the setpoint.
DOWN - decrease the setpoint.

* Viewing setpoint.
By pushing the SET key the setpoint appears in the display. The led 'set' starts blinking. A few
seconds after releasing the SET key the setpoint disappears and the measured temperature is shown
in the display.

* Changing setpoint.
Push the SET key and the setpoint appears in the display. Release the SET key. Now push the SET
key again and together with the UP or DOWN keys the setpoint can be changed. A few seconds after
releasing the keys the measured temperature shows again in the display.

1
* Setting internal parameters.
Next to the adjustment of the setpoint, some internal settings are possible like differential, sensor-
offset, setpoint range and the function cooling or heating.
By pushing the DOWN key for more than 10 seconds, you enter the 'internal programming menu'. In
the left display the upper and lower segment, are blinking. With the UP and DOWN keys the required
parameter can be selected (see the parameter table).
If the required parameter is selected, the value can be read-out by pushing the SET key. Pushing the
UP or DOWN keys, together with the SET key allows you to change the value of this parameter.
If no key is pushed for 20 seconds, the ALFA(NET) 31 DP changes to its normal operation mode.

* Adjustment sensor.
The sensor can be adjusted by using the Sensor Offset (parameter 04). Indicates the ALFA(NET) 31
DP e.g. 2C too much, the Sensor Offset has to de decreased by 2C.

* Error messages.
In the display of the ALFA(NET) 31 DP the following error messages can appear:

Er - Sensor broken. Solution:


- Check if the sensor is connected correctly.
- Check the sensor (1000 at 25C).
- Replace the sensor.

EE - Settings are lost. Solution:


- Reprogram the settings.

* Technical details.
Model : ALFA(NET) 31 DP
Range : -10/+40C, readout per 0,1C
Supply : 230Vac 50/60Hz (or else see productsticker), 3VA
Relay : SPDT 250V/16A(C-NO), 8A(C-NC) (cos phi=1)
Communication: RS 485 Network (2xtwisted pair shielded) only at ALFANET model.
Control : by pushbuttons on the front.
Front : Polycarbonate IP65
Sensor : SM 811/2m (1000 at 25C)
Sizes : 35 x 77 x 71,5mm (hwd)
Panel hole : 28 x 70mm (hw)

- Provided with memory protection during power failure.


- Connection with screw terminals on the back side.
- Equipped with self test function and sensor failure detection.
- Special versions are available upon request.

2
* Parameters ALFA(NET) 31 DP.

PARA- DESCRIPTION PARAMETER RANGE STANDARD


METER VALUE

01 Switching differential 1..15C 3


02 Minimum setpoint -10..+40C -10
03 Maximum setpoint -10..+40C +40
04 Offset temperature sensor -15..+15C 0
10 Startup delay after power failure 0..99 Minutes 0
11 Relays on at sensor failure 0 = No 0
1 = Yes

15 Function cooling or heating 0 = Cool 0


1 = Heat
16 Switch on delay relays 1) 0..99 0
17 Switch off delay relays 1) 0..99 0
18 Parameter 16/17 in seconds or minutes 0 = Seconds 0
1 = Minutes
19 Minimum on-time relays 0..99 Minutes 0
20 Minimum off-time relays 0..99 Minutes 0
90 Network number 1..250 1
95 Software version 0..255 -
96 Production year 00..99 -
97 Production week 1..52 -
98 Serial number (x1000) 0..255 -
99 Serial number (units) 0..999 -

1) On active delay led 'on' blinks.

* Function Diagram.

3
* Dimensions.

* Connection diagram.

If applicable

* Address.
VDH Products BV Tel: +31 (0)50 - 30 28 900
Produktieweg 1 Fax: +31 (0)50 - 30 28 980
9301 ZS Roden Email: [email protected]
The Netherlands Internet: www.vdhproducts.nl