Document ID QA723
Summary
ControlLogix 1757-SRM Redundancy Quick Start
Question
How to troubleshoot redundancy with 1757-SRM?
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/42750 1/6
11/30/2020 ControlLogix 1757-SRM Redundancy Quick Start
Answer
This Redundancy Quick Start checklist is not meant to replace the ControlLogix Redundancy System User
Manual, but to supplement it with general guidelines on how to successfully bring a redundancy system online.
Hardware
The ControlLogix Redundancy System consists of one pair of identical chassis and associated hardware, each
comprised of:
1 1756-Ax Chassis
1 1756-Px Power Supply
1 to 2 1756-L55Mxx or 1 - 1756-L6x Processor ( V15.57)
1 - 1757-SRM Redundancy Module
1 to 3 1756-CNB(R)/D/E ControlNet Communication modules ( V15.57) or
1 to 7 1756-CNB(R)/D/E ControlNet Communication modules ( V15.60) *
1 to 2 Optional 1756-ENBT or 1756-EWEB Ethernet Communications Modules. ( V15.57)
* No I/O or other modules permitted in local chassis.
Hardware Placement
Identical Hardware
The 1756-L55Mxx/1756-L6x, 1757-SRM, 1756-CNB(R)/D/E and 1756-ENBT/1756-EWEB pairs MUST have the same
Model, Series and Firmware Revision levels.
Firmware Updated
Insure that the firmware for ALL modules is at the latest for the Redundancy version
being implemented, V11, V13 or V15. The latest revision kits and associated Release Notes
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/42750 2/6
11/30/2020 ControlLogix 1757-SRM Redundancy Quick Start
are available for download from www.ab.com > Technical Support > Downloads >
Firmware Updates > Control Hardware >1756-Lxx Redundancy Bundle > Select V11,
V13 or V15 Release Note &Firmware Kit.
ControlNet Set-Up
You MUST set each pair of Ethernet/IP modules to the same IP address (i.e. 10.10.10.10)
You MUST reserve the next IP address (i.e. 10.10.10.11) Ethernet/IP modules may not be
used to control I/O.
On the Controller Properties Redundancy Tab ensure that the Redundancy Enabled check
box is checked.
Power Up Check
. Power up one of the redundancy chassis (1-3 minutes).
. Check all of the module health LEDs.
. The 1757-SRM module should display PRIM.
. Check the CNB module display for the node address.
. Check the Ethernet/IP module display for the Ethernet IP address.
. Power down that chassis and power up the other, repeating the process.
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/42750 3/6
11/30/2020 ControlLogix 1757-SRM Redundancy Quick Start
Synchronization Check
With one redundancy chassis powered up and the 1757-SRM displaying PRIM, power up
the partner (secondary) chassis (1-3 minutes). The secondary chassis should display
SYNC. The system is synchronized.
Synchronization Troubleshooting
Make sure that the Auto-Synchronization option of the 1757-SRM is set to Always. (See
Chapter 4. of the User Manual.) If the secondary does not SYNC, then observe the
secondary CNB display:
Ensure all ControlNet taps, connections, connectors and terminators are installed.
Switchover
With a PRIM redundancy chassis and a secondary chassis in SYNC, shut off power to the
primary chassis. The secondary chassis should become the PRIM chassis. The CNBs in
the Primary chassis should display PwDS (Primary with Disqualified Secondary). Turn
power back on the new secondary chassis. The CNBs in the new primary chassis will
follow this sequence: PwNS > PwDS > PwOg > PwQs (no secondary > disqualified
secondary > synchronizing secondary > qualified secondary After a few minutes, the
secondary SRM should display SYNC and the CNB modules should display PwQS (Primary
with Qualified Secondary).
Switchover Troubleshooting
If, after initiating a switchover, the primary 1756-CNB modules do not display PwQS:
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/42750 4/6
11/30/2020 ControlLogix 1757-SRM Redundancy Quick Start
If the secondary CNBs display PwNS (Primary with No Secondary) then check
secondary chassis power.
Power = Check for Red led secondary comms module > Cycle power;
Replace and check 1757-SRCx cable.
No power = Restore power
If the secondary CNBs do not display PwNS (Primary with No Secondary) then
check secondary chassis:
SRM = Green OK
Secondary PLC Flashing Red OK = Clear Major Fault
Secondary PLC Solid Red OK = Cycle power > Replace PLC
Secondary CNB NET ERR = Check ControlNet media
SRM - Red OK = Cycle power > Contact Tech Support
RATE CONTENT
Recently Viewed
Replacing 1757-SRM
Using 440G-LZ Safety
1757-SRM: Configuring with 1756-RM2 in
Switch with 1734 Point
the ControlLogix ControlLogix
Guard I/O and 1732ES
Redundancy Redundancy without
Armour Block
downtime
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/42750 5/6
11/30/2020 ControlLogix 1757-SRM Redundancy Quick Start
DISCLAIMER
This knowledge base web site is intended to provide general technical information on a particular subject or subjects
and is not an exhaustive treatment of such subjects. Accordingly, the information in this web site is not intended to
constitute application, design, software or other professional engineering advice or services. Before making any
decision or taking any action, which might affect your equipment, you should consult a qualified professional
advisor.
ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR ACCURACY OF ANY OF THE
DATA CONTAINED IN THIS WEB SITE AND MAY MAKE CHANGES THERETO AT ANY TIME IN ITS SOLE DISCRETION
WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS "AS IS." IN NO EVENT
SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT, INCIDENTAL,
CONSEQUENTIAL, LOSS PROFIT OR DAMAGE, EVEN IF ROCKWELL AUTOMATION HAVE BEEN ADVISED ON THE
POSSIBILITY OF SUCH DAMAGES.
ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN RESPECT OF THE
INFORMATION (INCLUDING SOFTWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR
A PARTICULAR PURPOSE, MERCHANTABILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not
countenance the exclusion of implied warranties; thus, this disclaimer may not apply to you.
www.rockwellautomation.com
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/42750 6/6