BMD4064 Input/Output Module Application
BMD4064 Input/Output Module Application
064-01-EN
Application
The input/output module BMD4064 with 64 digital inputs
or outputs receives System 4000 binary signals and
activates binary control functions.
The function of the 64 inputs or outputs can be individ-
ually software configured and defined for each
connection.
The first 8 inputs can be used as pulse counter inputs up
to 80 Hz.
Content Page
Important Information Regarding Product Safety ..................................................................................................2
Item........................................................................................................................................................................3
Technical Data.....................................................................................................................................................3
Accessories (not included in delivery) .................................................................................................................3
Dimensions ..........................................................................................................................................................3
Installation..............................................................................................................................................................4
Connection...........................................................................................................................................................5
Mounting ................................................................................................................................................................6
Removal...............................................................................................................................................................6
Commissioning ......................................................................................................................................................7
Setting the Switch Cabinet Bus Address .............................................................................................................7
LED Indicators .....................................................................................................................................................8
Änderungen vorbehalten - Contents subject to change - Sous réserve de modifications - Reservado el derecho a modificación - Wijzigingen
voorbehouden - Con riserva di modifiche - Innehåll som skall ändras - Změny vyhrazeny - Zmiany zastrzeżone - Возможны изменения -
A változtatások jogát fenntartjuk - ֱ⬭㒣䗮ⶹ㗠ᬍࡼⱘᴗ
A
Kieback&Peter GmbH & Co. KG
Tempelhofer Weg 50, 12347 Berlin/Germany
Telefon: +49 30 60095-0, Telefax: +49 30 60095-164
www.kieback-peter.de, [email protected]
Datasheet 2.60-70.064-01-EN Issue 2016-03-15
Safety Instructions
This data sheet contains information on installing and commissioning the product "BMD4064". Each
person who carries out work on this product must have read and understood this data sheet. If you
have any questions that are not resolved by this data sheet, you can obtain further information from
the supplier or manufacturer.
If the product is not used in accordance with this data sheet, the protection provided will be impaired.
Applicable regulations must be observed when installing and using the device. Within the EU, these
include regulations regarding occupational safety and accident prevention as well as those from the
VDE (Association for Electrical, Electronic & Information Technologies). If the device is used in other
countries, it is the responsibility of the system installer or operator to comply with local regulations.
Mounting, installation and commissioning work on the devices may only be carried out by qualified
technicians. Qualified technicians are persons who are familiar with the described product and who
can assess given tasks and recognize possible dangers due to technical training, knowledge and
experience as well as knowledge of the appropriate regulations.
Legend
WARNING
Indicates a hazard of medium risk which can result in death or severe bodily injury if it is not avoided.
CAUTION
Indicates a hazard of low risk which can result in minor or medium bodily injury if it is not avoided.
CAUTION
! Indicates a hazard of medium risk which can result in material damage or malfunctions if it is not
avoided.
NOTE
Indicates additional information that can simplify the work with the product for you.
Notes on Disposal
For disposal, the product is considered waste from electrical and electronic equipment (electronic
waste) and must not be disposed of as household waste. Special treatment for specific components
may be legally binding or ecologically sensible. The local and currently applicable legislation must be
observed.
A Page 2 / 8
Issue 2016-03-15 Datasheet 2.60-70.064-01-EN
Item
BMD4064 Input/output module
Technical Data
Cascade plug Z179 Different fieldbus or switch cabinet bus modules can be connected using
the cascade plug. Modules are supplied even when there are inactive
modules within the chain.
Connected lines: all supply voltages, CAN bus (+, -, GND)
A maximum of 5 modules can be connected in cascade.
Dimensions
90,0
44,7
143,5 60,0
A
Page 3 / 8
Datasheet 2.60-70.064-01-EN Issue 2016-03-15
Installation
CAUTION
! This product description describes specific settings and functions of the BMD4064. In addition to
these instructions, observe the product descriptions of other system components, such as DDC
controller DDC4000, BMR or DDC420.
CAUTION
! Switching on the power supply of unparameterized products can lead to unforeseen consequences
such as malfunctions or material damage.
Switch on the power only after the device has been configured by the commissioning technician.
A Page 4 / 8
Issue 2016-03-15 Datasheet 2.60-70.064-01-EN
Connection
CAUTION
! Deviating GND wiring may lead to malfunction.
BMD4064 BMD4064
GND 1
CAN238 CAN1 18 k39 K39
39 + 53
19 2 27 24V
DDC4000 40 DDC4000 20 - 24V~ 54 k40 K40
3 28 0V k41 K41
55
K1 k1 k21 K21 k42 K42
4 29 56 k43 K43
K2 k2 k22 K22
5 30 57 k44 K44
K3 k3 k23 K23
6 31 58 k45 K45
K4 k4 k24 K24
7 32 59 k46 K46
K5 k5 k25 K25
8 33 60 k47 K47
K6 k6 k26 K26
9 34 61 k48 K48
K7 k7 k27 K27
10 35 62 k49 K49
K8 k8 k28 K28
11 36 63 k50 K50
K9 k9 k29 K29
12 37 64 k51 K51
K10 k10 k30 K30
13 38 65 k52 K52
K11 k11 k31 K31
14 39 66 k53 K53
K12 k12 k32 K32
15 40 67 k54 K54
K13 k13 k33 K33
16 41 68
K14 k14 k34 K34 k55 K55
17 42 69
K15 k15 k35 K35 k56 K56
18 43 70 k57 K57
K16 k16 k36 K36
19 44 71 k58 K58
K17 k17 k37 K37 72
20 45 k59 K59
K18 k18 k38 K38 73
21 46 k60 K60
K19 k19 74
22 47 k61 K61
K20 k20 75
23 48 51 k62 K62
24 49 76
k63 K63
25 50 77
51 26 + 78
k64 K64
51 24V=
52 -
47 51
Z179 ..
50
A
Page 5 / 8
Datasheet 2.60-70.064-01-EN Issue 2016-03-15
Mounting
WARNING
Contact with live parts of electrical domestic installation can cause death due to electric shock.
Mounting/removal may only be carried out when power is switched off.
1 2 3 4
Installation with Z179 cascade plug accessory (not included in the scope of delivery)
1 2 3 4
5 6 7 8
Removal
WARNING
Contact with live parts of electrical domestic installation can cause death due to electric shock.
Mounting/removal may only be carried out when power is switched off.
1 2 3 4
A Page 6 / 8
Issue 2016-03-15 Datasheet 2.60-70.064-01-EN
Commissioning
CAUTION
! Commissioning by switching on the supply voltage may occur only after the commissioning
technician/engineer has finished configuring the DDC and has set the fieldbus address.
1 2 3 4
1 Transparent cover
2 Address switch
3 Green “BUS” LED
4 Red “Error” LED
Allowed range for the switch cabinet bus address: 01 to 16.
The rotary switches for setting the switch cabinet bus address are located under the Transparent
cover (1).
► Starting from the bottom corner on the side, use a screwdriver (blade width < 3 mm) to lift the
Transparent cover (1).
► Set the first digit of the switch cabinet bus address using the first Address
0 0
switch (2) and the second digit using the second Address switch (2). 1 9 1
2 8 2
The example shows the address “15”. 3 7 3
► With a little pressure, lock the Transparent cover (1) back into place. 6 5 4 6 5 4
x 10 x1
A
Page 7 / 8
Datasheet 2.60-70.064-01-EN Issue 2016-03-15
LED Indicators
A Page 8 / 8