CIVL4320 Assignment+2+Solution+-+2013
CIVL4320 Assignment+2+Solution+-+2013
Question 1
For column A, since both directions of column A are braced at the two ends, the effective
lengths in both directions are the same. Therefore, the orientation of the member can be
assigned in either ways as shown in the figure.
For column B, the orientation of the column should be set to maximize the flexural
buckling resistance of the member. It is advantageous to orientate the column with its
strong axis being aligned in the same plane of the diagonal braces as shown in the figure
such that the effective length for column buckling about its weak axis can be reduced
from 8 m to 4.5 m.
P
P
3.5m P
Beam
4.5m
Column A
Brace
Shear
wall
Column B
Brace
or
1
Solution to Problem Set 2 2013 Fall
2400 × 1000 1
Required gross area Ag = × = 145.5cm 3
165 100
Try 356 x 368 x 129 UC with Ag = 164 cm2
Section classification:
For 16 mm ≤ T = 17.5 mm ≤ 40 mm, Table 3.2
py = 265 N/mm2 where ε = 275 = 1.02
265
Effective Length LE
For pin ended in both axes:
LEx = LEy = 1.0 L = 8000 mm (in both x-x and y-y axes) Table 8.6
Slenderness l
λx = LEx/ rx = 8000/156 = 51.3 Clause 8.7.4
λy = LEy/ ry = 8000/94.3 = 84.8
Design strength pc
For rolled H-section and maximum thickness < 40 mm, Table 8.7
use Table 8.8(b) for strut curve (b) with buckling about x-x axis and
use Table 8.8(c) for strut curve (c) with buckling about y-y axis with
py = 265 N/mm2
With py = 265 N/mm2, and λx = 51.3, pcx = 227 N/mm2 Table 8.8 (b)
With py = 265 N/mm2, and λy = 84.8 pcy = 148 N/mm2 (control) Table 8.8 (c)
Compression resistance Pc
100 Clause 8.7.5
Pc = pc Ag = 164 × 148 × = 2427 kN > 2400 kN
1000
2
Solution to Problem Set 2 2013 Fall
2400 × 1000 1
Required gross area Ag = × = 129.4cm 3
185.5 100
Width B = 305.3 mm
Depth between fillets d = 246.7 mm
Flange thickness T = 15.4 mm
Web thickness t = 9.9 mm
Radius of gyration (x-x axis) rx = 13.4 cm
Radius of gyration (y-y axis) ry = 7.69 cm
Area of section A = 123 cm2
Section classification:
For T = 15.4 mm ≤ 16 mm, Table 3.2
275
py = 275 N/mm2 where ε = =1
275
Effective Length LE
For pin ended in both axes:
LEx = 8000 mm (in x-x axis) Table 8.6
LEy = 4500 mm (in y-y axis)
3
Solution to Problem Set 2 2013 Fall
Slenderness λ
λx = LEx/ rx = 8000/134 = 59.7 Clause 8.7.4
λy = LEy/ ry = 4500/76.9 = 58.5
Design strength pc
For rolled H-section and maximum thickness < 40 mm, Table 8.7
use Table 8.8(b) for strut curve (b) with buckling about x-x axis and
use Table 8.8(c) for strut curve (c) with buckling about y-y axis with
py = 275 N/mm2
2
With py = 275 N/mm , and λx = 59.7, pcx = 221 N/mm2 Table 8.8 (b)
With py = 275 N/mm2, and λy = 58.5 pcy = 204 N/mm2 (control) Table 8.8 (c)
Compression resistance Pc
100 Clause 8.7.5
Pc = pc Ag = 204 × 123 × = 2509 kN > 2400 kN
1000
4
Solution to Problem Set 2 2013 Fall
Question 2
1/F
3
4 5
Fg Fg
1.5m 1.5m
Only one-half of the gravity load on the central beam at the first floor is transmitted to
the pair of the braces at the first story.
1 5 15
Fg = ⋅ ( wg × 3) = wg
2 4 8
Fw Fw
The two bracing members at the first story have to carry cumulatively 6W of wind
loads from the upper 6 stories
1 5
Fw = ⋅ ( 6W ) = 5W
2 3
5
Solution to Problem Set 2 2013 Fall
Consider the following load combinations for the maximum factored compression load:
1) Dead Load + Imposed Load : 1.4D+1.6L
15 15
F= wg = (1.4 × 35 + 1.6 × 40) = 211.9 kN
8 8
2) Dead Load + Wind Load: 1.4D+1.4W
15 15
F= wg + 5W = (1.4 × 35) + 5 (1.4 × 50) = 441.9 kN
8 8
3) Dead Load + Imposed Load+Wind Load: 1.2D+1.2L+1.2W
15 15
F= wg + 5W = (1.2 × 35 + 1.2 × 40) + 5 (1.2 × 50) = 468.8kN
8 8
Therefore, the maximum factored design compression = 468.8 kN
468.8 × 1000 1
Required gross area Ag = × = 34.1 cm 2
137.5 100
Section classification:
For T = 11 mm ≤ 16 mm, Table 3.2
275
py = 275 N/mm2 where ε = =1
275
6
Solution to Problem Set 2 2013 Fall
B
= 8.13 < 15ε = 15
2T
For web:
d
= 19.0 < 40ε = 40
t
Thus, the section is not slender, and py = 275 N/mm2.
Also, compression resistance Pc = Ag pc Clause 8.7.5
Effective Length LE
For pin ended in both axes:
LEx = LEy = 1.0 L = 5000 mm (in both x-x and y-y axes) Table 8.6
Slenderness λ
λx = LEx/ rx = 5000/68.5 = 73.2 Clause 8.7.4
λy = LEy/ ry = 5000/38.7 = 129.2
Design strength pc
For rolled H-section and maximum thickness < 40 mm, Table 8.7
use Table 8.8(b) for strut curve (b) with buckling about x-x axis and
use Table 8.8(c) for strut curve (c) with buckling about y-y axis with
py = 275 N/mm2
With py = 275 N/mm2, and λx = 73.2, pcx = 196 N/mm2 Table 8.8 (b)
2
With py = 275 N/mm , and λy = 129.2 pcy = 87 N/mm2 (control) Table 8.8 (c)
Compression resistance Pc
100 Clause 8.7.5
Pc = pc Ag = 87 × 47.1 × = 409.8 kN < 468.8 kN
1000
The next available section 203 x 203 x 46 UC must then be used for
the bracing member. Since 203 x 203 x 46 UC provides a cross
sectional area of 58.7 cm2 which is about 25% greater than that of 152
x 152 x 37 UC, the section 203 x 203 x 46 UC is deemed adequate for
the bracing member.
7
Solution to Problem Set 2 2013 Fall
Question 3
Roof load:
8
Solution to Problem Set 2 2013 Fall
5411× 1000 1
Required gross area Ag = × = 340cm 3
159 100
Section classification:
For 16 mm ≤ T = 36.5 mm ≤ 40 mm, Table 3.2
275
py = 265 N/mm2 where ε = = 1.02
265
9
Solution to Problem Set 2 2013 Fall
Effective Length LE
For pin ended in both axes:
LEx = LEy = 1.0 L = 8000 mm (in both x-x and y-y axes) Table 8.6
Slenderness λ
λx = LEx/ rx = 8000/165 = 48.5 Clause 8.7.4
λy = LEy/ ry = 8000/103 = 77.7
Design strength pc
For rolled H-section and maximum thickness < 40 mm, Table 8.7
use Table 8.8(b) for strut curve (b) with buckling about x-x axis and
use Table 8.8(c) for strut curve (c) with buckling about y-y axis with
py = 265 N/mm2
2
With py = 265 N/mm , and λx = 48.5, pcx = 230 N/mm2 Table 8.8 (b)
With py = 265 N/mm2, and λy = 77.7, pcy = 161 N/mm2 (control) Table 8.8 (c)
Compression resistance Pc
100 Clause 8.7.5
Pc = pc Ag = 161 × 366 × = 5893 kN > 5411 kN
1000
10
Solution to Problem Set 2 2013 Fall
12 m 12 m
Beam B
Grider C
Beam B :
SECTION PROPERTIES
D = 454.6mm B = 255.8mm t = 8.1mm T = 13.3mm
I x = 25500cm 4 d = 407.6mm Z x = 1122cm 3 S x = 1287cm 3
SECTION CLASSIFICATION
Design strength, p y = 275kN / mm 2 for T ≤ 16mm (Table 3.2)
11
Solution to Problem Set 2 2013 Fall
275
ε= =1 (Table 7.1 Note b)
275
Plastic limiting value of d/t for web of an I-section with neutral axis at mid-depth is 80ε
d
= 50.32 < 80ε = 80 (Table 7.1)
t
Thus, the web is also plastic.
SHEAR CAPACITY
Shear area, Av = tD = 8.1× 454.6 = 3682mm 2 (Cl. 8.2.1)
p A
Shear capacity, Vc = y v = 584.64 kN > 111.36 kN (OK) (8.1)
3
MOMENT CAPACITY
Co-existing shear force V = 0kN ≤ 0.6Vc = 325.6kN (Cl. 8.2.2.1)
It is under low shear condition
As the floor slab provides full lateral restraints to the compression flange of the beam, it
is not necessary to check lateral-torsional buckling of the beam.
DEFLECTION
Unfactored uniform imposed load, ω = 3 × 2 = 6kN / m
Maximum deflection due to imposed load,
5 ωL4 L
δ= ≤
384 EI x 360
5 6 × 12000 4
= (OK) (Table 5.1)
384 205000 × 25500 × 10 4
12000
= 30.9mm < = 60mm
200
12
Solution to Problem Set 2 2013 Fall
Girder C :
Note that the total imposed load on the girder derived from a tributary area of 48 m2 may
be reduced by 5% in accordance with the Hong Kong Building Regulations. However, no
imposed load reduction has been considered in this solution for conservative reason.
SECTION PROPERTIES
D = 457mm B = 190.4mm t = 9mm T = 14.5mm
I x = 33320cm 4 d = 407.6mm Z x = 1458cm 3 S x = 1653cm 3
SECTION CLASSIFICATION
Design strength, p y = 275kN / mm 2 for T ≤ 16mm (Table 3.2)
275
ε= =1 (Table 7.1 Note b)
275
Plastic limiting value of d/t for web of an I-section with neutral axis at mid-depth is 80ε
d
= 45.29 < 80ε = 80 (Table 7.1)
t
Thus, the web is also plastic.
13
Solution to Problem Set 2 2013 Fall
SHEAR CAPACITY
Shear area, Av = tD = 9 × 457 = 4113mm 2 (Cl. 8.2.1)
p y Av
Shear capacity, Vc = = 653.0 kN > 222.7 kN (OK) (8.1)
3
MOMENT CAPACITY
Co-existing shear force V = 222.7 kN ≤ 0.6Vc = 391.8 kN (Cl. 8.2.2.1)
It is under low shear condition
As the floor slab provides a full lateral restraint to the compression flange of the girder, it
is not necessary to check lateral-torsional buckling of the girder.
DEFLECTION
Unfactored point load, P = 3 × 2 × 6 × 2 = 72 kN
12000
= 8.08mm < = 60mm
200
Assume that the secondary beams and primary girders are connected to their adjacent
members using typical shear connections in such a way that there is no local failure
caused by concentrated point loads. Checking of web bearing capacity and web buckling
resistance is not required.
Typical simple shear connections for beams and girders:
Question 5
Max moment at mid-span = 544 × 6.25 − 274 × 2.5 / 2 − 274 × 3.75 = 2030 kNm
SECTION PROPERTIES
D = 762.2mm, B = 266.7mm, t = 14.3mm, T = 21.6mm
I x = 205300cm 4 , d = 686mm, Z x = 5387cm3, S x = 6198cm 3
SECTION CLASSIFICATION
Design strength, p y = 345kN / mm 2 for 16mm < T < 40mm (Table 3.2)
275
ε= = 0.89
345 (Table 7.1 Note b)
Plastic limiting value of d/t for web of an I-section with neutral axis at mid-depth is 80
d
= 48.0 < 80ε = 71.2
t (Table 7.1)
Thus, the web is also plastic.
As the floor slab provides full lateral restraint to the compression flange of the girder, it is
not necessary to check lateral-torsional buckling of the girder.
16
Solution to Problem Set 2 2013 Fall
Since ae > 0.7d and assume that the bottom tension flange is allowed to move sideways
relative to the restrained compression flange (i.e. the effective length of the web LE=
1.2d)
0.7d 25εt
Web buckling resistance = Pxr = Pbw (Cl 8.4.10.6.1)
LE (b1 + nk)d
0.7 × 686 25 × 275 355 ×14.3
= × ×1982
1.2 × 686 (200 + 5 × 38.1) × 686
= 0.58 × 0.61×1982 = 701 kN
17