TEST REPORT
PRODUCT SPECIFICATIONS
System Voltage : 22 kV Rated Voltage : 22/√3 kV
Rated Current : 750 A Rated Resistance : 17Ω ; @20⁰C ±%5
Rated Time : 30sec Enc. Protection Class : IP55
LV Ter. Ins. Class : 1,2kV MV Ter. Ins. Class : 24kV
: 750/1A PX : 750/1A 5P20
Current Transformer - 1 Current Transformer - 2
2019/37834 2019/37839
ROUTINE TESTS
MEASUREMENT OF DC RESISTANCE VALUE
Ambient Temperature : 22°C Test Date :14.02.2020
Measured Value : 17Ω Acceptance Criteria : Rn±5%
: GW-INSTEK
Measurement Device Test Result :OK ☒ NOK ☐
MilliOhmMeter
PAINT AND GALVANIZATION THICKNESS MEASUREMENT
Ambient Temperature : 22°C Test Date :14.02.2020
Measured Value : 190 µm Acceptance Criteria : ≥50 µm
: ElektroPhysik
Test Result :OK ☒ NOK ☐ Measurement Device
Coating Thickness Gauge
Insulation Test
Applied Value :50,3kV, for 1 min at50Hz Acceptance Criteria : 50kV, for 1 min. at 50Hz
: MULTITEK
Test Result :OK ☒ NOK ☐ Measurement Device
AC High Voltage Tester
DC Impulse Test
Ambient Temperature : 22°C Test Date :14.02.2020
: 5kVDC, : 5kVDC,
Applied Value Acceptance Criteria
for 1 min. at 50Hz for 1 min. at 50Hz
Insulation Resistance : 6,52 GΩ Test Result :OK ☒ NOK ☐
Measurement Device : METREL TeraOhm 5 kV