Resistance Thermometer Measuring Transducer - MINI MCR-RTD-UI-NC - 2902849
Resistance Thermometer Measuring Transducer - MINI MCR-RTD-UI-NC - 2902849
Resistance Thermometer Measuring Transducer - MINI MCR-RTD-UI-NC - 2902849
com/pi/products/2902849
Configurable temperature transducer for the connection of 2, 3, and 4-conductor resistance thermometers
and resistance-type sensors. Can be configured via DIP switches or, with extended functionality, using the
software. Screw connection, standard configuration.
Product Description
The configurable temperature transducer with 3-way isolation is suitable for the connection of resistance thermometers and remote resistance-type
sensors with 2, 3, and 4-conductor connection technology.
The measured values are converted into a linear current or voltage signal.
You can configure the device using one of the free software solutions. Default settings can also be made directly on the device by simply using the
DIP switches (see configuration table). The measuring transducer supports fault monitoring.
GTIN
GTIN 4046356689205
Technical data
Note
EMC: class A product, see manufacturer's declaration in the download
Utilization restriction
area
Dimensions
Width 6.2 mm
Height 93.1 mm
Depth 101.2 mm
Ambient conditions
Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Maximum altitude ≤ 2000 m
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
08/05/2021 Page 1 / 8
https://www.phoenixcontact.com/pi/products/2902849
Input data
Configurable/programmable Yes
Sensor types (RTD) that can be used Pt, Ni, Cu sensors
0 Ω ... 4000 Ω (Minimum measuring span: 10% of the selected
Linear resistance measuring range
measuring range)
Sensor input current approx. 200 µA
-200 °C ... 850 °C (Range depends on sensor type, range can be set
Temperature measuring range freely via software or in increments from -150°C to 850°C via DIP
switches)
Connection technology 2-, 3-, 4-conductor
Output data
Number of outputs 1
Configurable/programmable Yes
Voltage output signal 0 V ... 10 V
10 V ... 0 V
0 V ... 5 V
1 V ... 5 V
Current output signal 0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
Max. output voltage approx. 12.3 V
Max. output current 24.6 mA
Load/output load voltage output 10 kΩ
Load/output load current output 500 Ω (at 20 mA)
Ripple < 20 mVPP
< 20 mVPP (at 500 Ω)
Power supply
9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the
Supply voltage range
supply voltage. It can be snapped onto a 35 mm DIN rail according to
EN 60715))
Typical current consumption < 27 mA (at 24 V DC)
Power consumption ≤ 700 mW (at IOUT = 20 mA, 9.6 V DC, load 500 Ω)
Connection data
Connection method Screw connection
Stripping length 12 mm
08/05/2021 Page 2 / 8
https://www.phoenixcontact.com/pi/products/2902849
General
Transmission error resistance thermometer 0.1 % * 350 K / set measuring range; 0.1 % > 350 K (Pt/Ni)
0.3 % * 200 K / set measuring range; 0.3 % > 200 K (Cu)
Transmission error resistance-type sensor 2Ω
Maximum temperature coefficient 0.01 %/K
Status display LED red
Protective circuit Transient protection
Electrical isolation Basic insulation according to EN 61010
Overvoltage category II
Degree of pollution 2
Rated insulation voltage 50 V AC/DC
Test voltage, input/output/supply 1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
EN 61000-6-2 When being exposed to interference, there may be
Noise immunity
minimal deviations.
Color green
Housing material PBT
Mounting position any
The T connector can be used to bridge the supply voltage. It can be
Assembly instructions
snapped onto a 35 mm DIN rail according to EN 60715.
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
EMC data
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Typical deviation from the measuring range final value 0.04 %
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 0.1 %
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Typical deviation from the measuring range final value 0.02 %
Conformance/approvals
Designation CE
Certificate CE-compliant
Designation UL, USA/Canada
Identification UL 508 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC
Designation Shipbuilding approval
Certificate DNV GL TAA00002R0
Temperature B
Humidity B
Vibration B
EMC B
Required protection according to the Rules shall be provided upon
Enclosure
installation on board
Drawings
08/05/2021 Page 4 / 8
https://www.phoenixcontact.com/pi/products/2902849
S-Port
OUT U,I
1 1 5 + 5
active passive
GND 1
2 2 6 – 6
ϑ ϑ ϑ
+24V
3 3 7 +
IN U,I OUT
4 4 GND 2
8 –
FM
FM GND 2 +24V
POWER
Classifications
eCl@ss
ETIM
UNSPSC
08/05/2021 Page 5 / 8
https://www.phoenixcontact.com/pi/products/2902849
Approvals
Approvals
Approvals
Ex Approvals
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705
DNV GL
https://approvalfinder.dnvgl.com/ TAA00002R0
cULus Listed
Accessories
Accessories
DIN rail connector
08/05/2021 Page 6 / 8
https://www.phoenixcontact.com/pi/products/2902849
DIN rail connector for DIN rail mounting. Universal for TBUS housing. Gold-plated contacts, 5-pos.
Evaluation unit
The fault monitoring module is used to evaluate and report group errors from the fault monitoring system and to
monitor the supply voltages. The error is reported via an N/O contact. Screw connection, standard configuration.
Marking material
Fold up transparent cover for MINI MCR modules with additional labeling option using insert strips and flat Zack
marker strip 6.2 mm
Label for extended marking of MINI MCR modules in connection with the MINI MCR-DKL
Power module
The MINI MCR-SL-PTB-FM(-SP) power terminal block is used to supply the supply voltage to the DIN rail connector.
The FM power terminal block offers the additional function of monitoring in combination with the fault monitoring
module. Screw connection.
08/05/2021 Page 7 / 8
https://www.phoenixcontact.com/pi/products/2902849
MCR power terminal block for supplying several MINI Analog modules via the DIN rail connector, with screw
connection, maximum current consumption of up to 2 A
Power supply
Primary-switched MINI POWER supply for DIN rail mounting, input: 1-phase, output: 24 V DC/1.5 A
Programming adapter
Adapter - IFS-BT-PROG-ADAPTER - 2905872
Bluetooth adapter with micro USB and S-PORT interface for wireless communication with the MINI Analog,
MINI Analog Pro, MACX Analog, INTERFACE system gateways, and PLC logic device series.
Programming adapter - IFS-USB-PROG-ADAPTER - 2811271
Programming adapter with USB interface, for programming with software. The USB driver is included in the software
solutions for the products to be programmed, such as measuring transducers or motor managers.