Mantto Probabilidades
Mantto Probabilidades
Mantto Probabilidades
September 12-16,2004
1003
Authorized licensed use limited to: Jaime Quispe. Downloaded on March 30, 2009 at 19:11 from IEEE Xplore. Restrictions apply.
Adjust breaker-operating mechanism as described in processing techniques. The time-axes of reference Bequency
the manufacturer’s insfmction book. pattern and test frequency pattem are aligned to indicate any
Make sure all bolts, nuts, washers, cotter pins etc.are changes in the condition of the operating mechanism. The
properly tightened. presence of an abnormal event in the test signature will change
AAer servicing the circuit breaker, verify whether the the hquency, and the time at which this event occurs.
contacts can move to the fully opened and fully closed 3) Control Circuit Monitoring
positions or not. Portable test sets are generally used to monitor the control
2) Contacts circuit. The circuit breaker is forced into operation and the
Check the alignment and condition of the contacts and control circuit signals are recorded [I 11. The following are the
make adjustments according to the manufacturer’s typical control circuit signals that can be monitored in practice
instruction book [121.
Check if the contact wear and have1 time meet Tripcoilcurrent
specifications Close coil current
3) Insirlaring A4edirini and Arc Extinction DC Supply voltage
Check for leaks and remove any water content. Check A, B auxiliary contacts
govemor and compressor for required pressure X B Y Coils
Recondition oil by filtering Trip initiation
Close initiation
B. Replacenienr
B. Contacts
This includes the replacement of various components.
Arc chute and nozzle parts if damaged Inspections related to circuit breaker conhcts are mentioned
Govemon and compressors if wom or malfunctioning in this section.
I ) Contact Resistance Test
Contacts if badly worn or bumed
The resistance of the main contact can be measured with a
Oil if dielectric strength drops below an allowable limit
portable double bridge (Kelvin) or a “Ducter” [7]. A DC current
and if any arc products are found in the oil.
is injected in one phase of the breaker, and the breaker is forced
into operation. The current and voltage over the contact are
I v . INSPECTION TESTS
measured and the dynamic resistance curve is calculated. The
This section gives an idea about bow various inspections can condition of the contacts can be analyzed hy comparing the
be done, and what is the information that can be obtained h m measured resistance c w e with previous measurements 191.
those tests. Some of the possible inspection tests used in practice 2) Contact Tentperatrire Monitoring
for a circuit breaker are mentioned below [8]. The inspection Large changes in contact temperature may be due to broken
tests are grouped according to the order of components that are contact fingers, excessive burning of the main contacts, material
discussed in section 11. degradation, oxide formation, weak contact springs, improperly
A. Operating A4echanisni or not fully closed contacts etc. Optical sensors are used to
measure the temperature of the contacts [4].
Inspection tests, which give the performance of operating
mechanism either directly or indirectly, are presented in this C. Inspection ofoil
section. Oil sample can be taken and tested for its dielectric strength.
I ) Contact Travel Time Aleasrmnienl The following are the inspections that can be done in practice
The motion of the breaker contacts can be determined with [51.
contact travel time measurement. It is a plot of position Color and visual inspection
(distance) of contacts with respect to contact travel time, and Interfacial tension (soluble contaminants measurement)
can be obtained by a resistive transducer [9]. The transducer is Dissipation factor (measure of power lost as heat)
usually mounted on a moving part of the breaker. The contact
travel time measurements provide information about the D. Partial Discharge
operating components of the circuit breaker, which include Insulation failures of circuit breakers can be detected by
mechanical finks and interrupter contacts. Partial discharge monitoring [13]. The test procedure and
2) Vibration Analysis equipment for the partial discharge monitoring are discussed in
Mechanical malfunctions, excessive contact wears, detail in reference [14]. Various methods are reported in
maladjustments, other irregularities and failures can he detected literature so far hut the cost varies according to the test
through vibration pattems [IO]. Accelerometers mounted procedures and accuracy of results.
usually on the arcing chamber and operating mechanism, are
used lo record the vibrations. The recorded vibration pattems
are converted into timdfiequency patterns using signal-
1004
Authorized licensed use limited to: Jaime Quispe. Downloaded on March 30, 2009 at 19:11 from IEEE Xplore. Restrictions apply.
V. C0MPARISONBEl"A CIRCUITBREAKERAND
TRANSFORMER
Circuit breaker is an electrical device that operates on
command. Once the operating mechanism receives trip or close
signal from a control circuit, it starts working and opens or
closes the main contacts respectively. The overall performance
of the breaker depends on the operating mechanism, which
consists of various moving parts. Transformer is a device,
which while in service, is always in an energized state. The
insulating oil properties used in breaker and transformer are
different. Suggested limits for service-aged insulating oils for
both breaker and hansformer are given in table I [5]. Having an
idea ahout the similarities and differences between the two
devices, and knowing the maintenance model of the transformer
will help in developing the maintenance model for the circuit
breaker. Table 11 provides a comparison between the breaker
and transformer characteristics.
1005
Authorized licensed use limited to: Jaime Quispe. Downloaded on March 30, 2009 at 19:11 from IEEE Xplore. Restrictions apply.
The proposed criterion for assessment of the condition of Condition 3: excessive wear and need complete overhaul
operating mechanism is or replacement
Condition 1: satisfactoly, test results follow the reference curve 2) Control Circuit Monitoring
Condition 2: caution stage, test results deviate slightly and need The recorded control signals are analyzed to find any
more attention abnormalities in the breaker operation. A detailed analysis of
circuit breaker operations based on automated monitoring of
control circuit is discussed in reference [12]. Table 111 shows
some of the possible causes for the behavior of the measured
signals [16].
Figures 3,4,5 and 6 show the sluggish trip latch, defective
close coil, defective auxiliary switch and defective battery
respectively.
The proposed criterion for the condition of control circuit is
Fig. 2 Com~arisonof circuit brcaker contact mvel curves [4]
Condition 1: within specification and will not require
maintenance
1006
Authorized licensed use limited to: Jaime Quispe. Downloaded on March 30, 2009 at 19:11 from IEEE Xplore. Restrictions apply.
Condition 2 : caution stage; need more attention TABLE N
Condition 3: final stage; need major replacement SUGGESTED LLMTS FOR CONTWUEO USE OF SERVICE-AGED
CIRCUIT
BREAKER WSULATMG OILIS]
Test and mclhod S"gg&d limit
TART F 111
.._-_I
D i e l d e strength 25
ABNORMAL WAVEFORMS 1161
k V minimum
Signal Name Signal Behavior Figun Possible Cause
Tnp Coil Currenl Dip delayed Fig. 3 Binding or fndion Dielectric strength, kV minimum
Close Coil Excessive noise Fig. 4 Defective close mil I m gap' 20
current (distariion) 2 mm gap. 27
A&B Contacts Abnormal noise Fig. 5 Defective amiliay
on contacts switch Dissipation factor (power factor),
DC Voltages Dc Voltage Fig. 6 Defective substation 25 "C, %maximum 1.0
unstable batter).or high
impedance short hterfacid tensioa "im minimum 25
Condition 1: satisfactory
Condition 2: should be reconditioned for further use
Condition 3: poor condition; dispose
Suggested limits for oil in condition 1 are listed in table IV.
Fig. 3. Trip current dip delayed Criterion for recondition is .excessive carbon in oil and
reduced dielectric strength (dielectric strength drops below the
accepted limit).
A detailed analysis of inspection tests and the collected data
I/
,. .. .. ...... . . .. . .
is needed for implementation of the model, and will be
included in further work.
B. Invesligalion Process
Fig. 4. Closc current exassive noise Information out of the inspection tests can be used to
A ; determine the condition of the device followed by the
necessiuy maintenance action and rate of the next inspection.
C. Mainlenance Action
I ) Do nothing
The breaker is in satisfactory condition and no maintenance
Fig. 5. Noisy msition when opening is needed. The probability that the system is set back to same
stage is relatively high.
DC
2) Basic Mainrenonce
This maintenance action increases the probability of going
back to the previous stage.
3) Replacernenr
Fig. 6. X Voltage unstable Replacement of damaged components brings the system
back to its original stage i.e. beginning stage.
3) Contact Resislance Measurement
The possible causes for abnormal increase in contact
VII. CONCLUSION
resistance are deposition of foreign material in contacts, loose
contacts and loose bushing connections [7]. A probabilistic maintenance model for circuit breakers is
The proposed criterion for the condition of contacts is introduced. Information collected during inspection tests is
Condition 1: satisfactory analyzed and the condition of the breaker can he defined.
Condition 2 caution stage; need more attention Maintenance action is taken according to the condition of the
Condition 3: excessive wear and need complete overhaul breaker. Implementation of the model using Monte Carlo
4) Inspeclion of O i l simulation is in progress. Maintenance cost and time to failure
Service-aged oils are classified into the following three of each transformer and circuit breaker will be incorporated.
conditions P1.
1007
Authorized licensed use limited to: Jaime Quispe. Downloaded on March 30, 2009 at 19:11 from IEEE Xplore. Restrictions apply.
REFERENCES
[I] IEEEiPES Task Forcc on Impact of Maintenance Strategy on Reliability
of the Reliability, &sk and Probability Applications Subeo”iltee,
“The present status of maintwmce strategies and the impact of
maintenance on reliability”, IEEE Trans. P a v e r Sysrents, vol. 16, no. 4,
pp. 638- 616,November 2001
121 I. Endrenyi, and S. H.S i m Availability optimization for continuously
‘I
1008
Authorized licensed use limited to: Jaime Quispe. Downloaded on March 30, 2009 at 19:11 from IEEE Xplore. Restrictions apply.