EE8017 - HVDC - Unit 2
EE8017 - HVDC - Unit 2
d) 1.690
Answer: b)
3. The three phase voltage at the AC side terminals of the 6 pulse LCC is sinusoidal and
balanced, and there is a constant current source on the DC side. Which of the following
sentences is/are correct about following?
1) In a 6 pulse LCC, the 11th order harmonic component in the AC side currents is a
characteristic harmonic.
2) In a 6 pulse LCC, the 25th order harmonic component in the AC side currents is a non-
characteristic harmonic.
3) In a 6 pulse LCC, the 2nd order harmonic component in the AC side currents is a
characteristic harmonic.
4) In a 6 pulse LCC, the 4th order harmonic component in the AC side currents is a non-
EE8017- High Voltage Direct Current Transmission Page 2
ChettinadTech Dept of EEE
characteristic harmonic.
Options
a) 1 and 2
b)1 and 4
c) 2 and 3
d) 2 and 4
Answer: b)
4. The three phase voltage at the AC side terminals of the 12 pulse LCC is sinusoidal and
balanced, the transformers are ideal, and there is a constant current source on the DC side.
Which of the following sentences is/are correct about following?
1. In a 12 pulse LCC, the 17th order harmonic component in the AC side currents is a
characteristic harmonic.
2. In a 12 pulse LCC, the 19th order harmonic component in the AC side currents is a non-
characteristic harmonic.
3. In a 12 pulse LCC, the 35th order harmonic component in the AC side currents is a
characteristic harmonic.
4. In a 12 pulse LCC, the 47th order harmonic component in the AC side currents is a non-
characteristic harmonic.
Options
a) 1 and 2
b) 1 and 4
c) 2 and 3
d) 2 and 4
Answer: c)
8) In HVDC converter station equipment using thyristor it is necessary to use a large number of
thyristor in series because.
a) Current ratings of thyristor are low.
b)Voltage ratings of thyristor are low.
c) Thyristor always fail to an internal open circuit.
EE8017- High Voltage Direct Current Transmission Page 3
ChettinadTech Dept of EEE
9) In the HVDC system, the ac harmonics which get effectively eliminated with 12 pulse bridge
converters are..
a) Triplen harmonics
b) Triplen and 5th harmonics
c) Triplen, 5th and 7th harmonics
d)5th and 7th harmonics
Answer: d)
c) Vd = 0.5Vd0 Cosα
d) Vd = 3Vd0 Cosα
Answer: a)
23)If the firing angle becomes negative, then the rectifier begins to work as
a. A rectifier
b. An inverter
c. A chopper
d. A regulator
Answer: b)
24)Transformer utilization factor is a measure of the merit of a rectifier circuit. It is the ratio of
a. AC input power to the transformer volt – amp rating required by secondary
b. AC input power to the transformer volt – amp rating required by primary
c. DC output power to the transformer volt – amp rating required by secondary
d. DC output power to the transformer volt – amp rating required by primary
Answer: c)
27.To detect an over – current fault condition, the most reliable method is to connect a
a. Current sensor across IGBT
b. Voltage sensor across IGBT
c. Current sensor in series with IGBT
d. Voltage sensor in series with IGBT
Answer: c)
35)If pulse number = p, and k is an integer, voltage harmonic generated on the DC side is
(a) pk + 1
(b) pk – 1
(c) 2pk
(d) pk
Answer: d)
36)If pulse number is = p and k is an integer, the voltage harmonic generated on the AC side is
(a) pk
(b) 2pk
(c) pk ± 1
(d) 2pk ± 1
Answer: a)
37)In a 12-pulse converter, the phase difference between the two 6-pulse bridges is
(a) 0°
(b) 60°
(c) 30°
(d) 15°
Answer: c)
(c) 23
(d) 25
Answer: a)
40)In a 12-pulse bridge, if one transfers Y–Y has turns ratio 1:1, the other transformer Y–D will
have turns ratio
(a) 1:1
(b) 1: 3
(c) 3 :1
(d) 1: 2
Answer: b)
Answer: b)
49)The earth electrode in the ground return DC line is located from the converter station at a
distance of
(a) 1 km
(b) 3 to 5 km
(c) 10 km
(d) 8 to 20 km
Answer: d)