Modbus Integration Guide en
Modbus Integration Guide en
POL6XX POL6XX
Climatix™
Modbus communication, slave mode
Integration guide
POL63x controller and POL902 communication module
VVS10
CB1J3960en_POL63x
2015-10-07 Building Technologies
Siemens Switzerland Ltd
Building Technologies Division
International Headquarters
Gubelstrasse 22
6301 Zug
Switzerland
Tel. +41 41-724 24 24 © Siemens Switzerland Ltd, 2015
www.siemens.com/buildingtechnologies Subject to change
2 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies 2015-10-07
Table of contents
3 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Table of contents 2015-10-07
4 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Table of contents 2015-10-07
1 About this document
1.1 Revision history
Version Date Changes Section Pages
1.0 01.03.2010 First edition
15.09.2010 Minor enhancements
02.12.2013 Product version VVS 9.0
07.02.2014 Minor enhancements
18.07.2014 Update for VVS10
07.10.2015 Minor enhancements
Product versions Description and functional scope of the products are based on the Climatix Valid
Version Set 10.0 or higher and application based on Siemens standard.
Further information The following documents contain additional information on the products described
in this manual:
Document Order no.
Data sheet "Communication module Modbus" CB1Q3934en
Basic documentation "Modbus communication module" CB1P3934en
Reference addresses "Modbus communication, slave mode" CB1Y3961en
Note! Uniqe documentation for each application field
Basic documentation "Climatix AHU application" CB1P3977en
Note! Uniqe documentation for each application field.
5 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies About this document 2015-10-07
1.4 Document conventions
Symbols used Below is an overview of all symbols used in this document denoting risks or
important information:
This symbol draws your attention to special safety notes and warnings. Failing to
observe these notes may result in injury and/or serious damages.
STOP This symbol denotes special information that, when failed to observe, may result in
faulty functionality or loss of data.
Notes with this symbol provide important information that requires appropriate
attention.
6 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies About this document 2015-10-07
1.5 Important information on safety
Field of application Use Modbus communication only for control and monitoring.
Intended use Trouble-free and safe product operation of the above products presupposes
transport, storage, mounting, installation, and commissioning as intended as well
as careful operation.
Fuses, switches, wiring and grounding must comply with local safety regulations for
Electrical
electrical installations.
installation
When wiring, strictly separate AC 230 V mains voltage from AC 24 V safety extra-
Wiring
low voltage (SELV) to protect against electrical shock!
Commissioning and Only qualified staff trained accordingly may prepare for use, commission, and
maintenance maintain Modbus communication modules.
Only authorized staff may diagnose and correct faults and recommission the plant.
Faults
This applies to working within the panel as well (e.g. testing or changing fuses).
Storage and transport Refer to the environmental conditions specified in the respective data sheets for
storage and transport.
If in doubt, contact your supplier.
Disposal Devices contain electrical and electronic components; do not dispose of them in
household garbage.
Observe all local and applicable laws.
7 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies About this document 2015-10-07
1.6 Trademarks and copyrights
Trademarks, legal The table below lists the third-party trademarks used in this document and their
owners legal owners. The use of trademarks is subject to international and domestic
provisions of the law.
All product names listed in the table are registered (®) or not registered (™)
trademarks of the owner listed in the table. We forgo the labeling (e.g. using the
symbols ® and ™) of trademarks for the purposes of legibility based on the
reference in this section.
Copyright This document may be duplicated and distributed only with the express permission
of Siemens, and may be passed on only to authorized persons or companies with
the required technical knowledge.
Request to the reader Before using our products, it is important that you read the documents supplied
with or ordered at the same time as the products (equipment, applications, tools
etc.) carefully and in full.
We assume that persons using our products and documents are authorized and
trained appropriately and have the technical knowledge required to use our
products as intended.
Exemption from liability Siemens assumes no liability to the extent allowed under the law for any losses
resulting from a failure to comply with the aforementioned points or for the improper
compliance of the same.
8 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies About this document 2015-10-07
2 Modbus networks
2.1 Modbus protocol
Modbus, general The following section provides only a brief overview of the Modbus protocol.
information For the full specification, see:
"Modicon Modbus Protocol Reference Guide PI MBUS 300 Rev. J".
Master/slave protocol The Modbus is a master/slave protocol. This, by definition, means that a Modbus
network contains only one master and at least one slave.
Transactions on The Modbus master uses a slave query to start transactions on the network. The
Modbus slave either responds positively with the requested service (response) or transmits
an "exception message".
Function codes The type of transaction is defined by the function code transmitted in the Modbus
telegrams. A function code defines the following:
Structure of the telegram, query and response.
Direction of data transmission (master → slave or slave → master).
Data format of data point.
Transmission modes The Modbus protocol defines two alternative serial transmission modes:
These modes have the following characteristics:
RTU (Remote Terminal Unit) mode
Binary-coded data.
Start and end of telegrams marked by timed pauses (a "silent interval") between
the characters transmitted.
Check sum algorithm: CRC (cyclical redundancy check).
ASCII mode
Data in hexadecimal notation.
Beginning and end of telegrams marked by start and end characters.
Check sum algorithm: LRC (longitudinal redundancy check).
Telegrams with multiple Certain types of Modbus transactions allow for transmission of a variable number
data points of Modbus data points in a single telegram.
Modbus TCP Ethernet A Modbus TCP/RTU gateway helps connect a Modbus/TCP master to one or
several Climatix controllers (slaves) if not a Climatix controller with internal TCP/IP
onboard is available:
P3934Z03
Slave Slave
9 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Modbus networks 2015-10-07
2.2 RS485 networks
RS485 definition RS485 is a balanced line, half-duplex transmission system that meets the
requirements for a truly multi-point communications network. The standard
specifies up to 32 drivers and 32 receivers on a single (3-wire) bus.
Half-duplex data transmission means that data can be transmitted in both
directions on a signal carrier, but not at the same time.
Unit loads of Climatix The following table outlines the Climatix devices that are using 3-wire RS-485
devices network interfaces.
Product Name Modbus Terminal Network Isolated
Protocol Usage Electrical RS485
Loading common
( unit load )
POL635 Master/Slave A+ B- REF 1/4 no
POL636 Master/Slave A+ B- REF 1/4 no
POL638 Master/Slave A+ B- REF 1/4 no
POL687 Master/Slave A+ B- REF 1/4 yes
POL902 2 x Slave A+ B- REF 1 yes
Topology An RS485-MODBUS configuration without repeater has one trunk cable, along
which devices are connected, directly (daisy chaining) or by short derivation
cables.
10 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Modbus networks 2015-10-07
2.3 Topologies
Introduction The RS485 standard is simple and well-proven. An important requirement however,
is the selection of the right topology.
Best: Individual line The best topology is a single line (line topology), with the bus cable connected
directly to the individual devices.
This type of connection has the least problems.
A+
A+
A+
REF
REF
REF
B-
B-
B-
RS485 RS485 RS485
Impairment due to Connecting network devices via intermediate terminals can result in reflections and
intermediate terminals harmonics of electrical signals. Long, not twisted intermediate lines obviously
increase the risk of interference.
A+
A+
A+
REF
REF
REF
B-
B-
B-
Error-prone: Star Avoid star topologies because errors/problems are hard to located and remove.
REF
REF
RS485 RS485
P3933Z17
REF
REF
RS485 RS485
11 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Modbus networks 2015-10-07
2.4 RS485, cable installation
Task of the third wire In order to provide higher noise immunity and high data reliability, Climatix Modbus
network interface is build as 3-wire connection RS-485 interfaces with a common
reference signal REF.
Depending on the manufacturer, the third wire on 3-wire network interfaces has
several names (for example: Common,Ground, Com. SC (Signal Common), R (for
Reference), GND, SG (Signal Ground) or REF (e.g. in Climatix)).
This connection is for a common reference signal. Voltage on lines Tx/Rx (or +/-)
are measured relative to the voltage level on the reference signal.
Risks due to missing You risk the following if you do not use a third wire:
third wire Destroyed RS485 inputs.
Unstable work.
New installation.
The risks are greater:
The higher the number of feeds to supply devices.
The greater the physical separation.
If fewer well grounded devices and feeds are used.
Screening not required You do not need screens. The twisted cable for Tx and Rx suppresses interference
more effectively than a screen.
The use of the shield as the third wire is prohibited.
An overall foil shield and drain wire provide additional noise protection.
Observe cabling Observe the following when running the bus cable:
Do not wind the bus cable around other cables or electric/magnetic sources (e.g.
around a motor cable).
Do not run the bus cable next to DC load switches (e.g. relay). These are the
main sources of interferences.
Frequency-controlled actuators are also source of high interference.
Protect bus cable against undesired moving (e.g. due to vibrations).
12 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Modbus networks 2015-10-07
RS485, cable installation, continued
Cable type The network cable recommended for use with the 3-wire (isolated RS-485
common) is a single twisted pair cable with third wire (1.5-pair) that is used to tie
the RS-485 reference (communication common) of all the nodes on the network
together.
Pay attention to the Each cable has its own impedance. Some cables are designed for impedance
impedance independent of length. Use this kind of cable. Nominal impedance is a start for
selection:
A cable is well suited if a number e.g. 100 Ohm is indicated.
The cable is not suited if impedance is indicated by meter/foot, as determination
of the value for terminating resistances requires measurements and calculations.
Thus, select a cable with the lowest possible capacity.
Cat5 cables? Yes, these cables are good. Use a twisted pair for Tx/Rx and a wire( 1.5-pair) or
the other pair( 2-pair) for the reference signal (REF)..
Cable length The end to end length of the trunk cable ( Bus ) must be limited. The maximum
length depends on the baud rate, the cable (Gauge, Capacitance or Characteristic
Impedance), the number of loads on the daisy chain, and the network
configuration.
For a 9600 Baud rate and AWG26 (or wider) gauge, the maximum length is
1000m.
The derivations must be short, never more than 20m. If a multi-port tap is used
with n derivations, each one must respect a maximum length of 40m divided
by n.
The higher the baud rate, the more important is the cable installation quality.
Issues such as twisted pair cable unfolded at each resistor gain importance.
13 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Modbus networks 2015-10-07
2.5 Wiring examples
Climatix devices with The following pictures show the correct wiring of Climatix POL63x controllers and
Modbus master POL902 communication modules with the Modbus master
Modbus master
Mains AC 24V
Enable internal
line termination network
Modbus master by operator unit
EARTH GROUND
POL63x
internally connected
0V / GND REF
(24V common) (RS485 common)
EARTH GROUND
Modbus slave Modbus slave Modbus slave
REF
REF
REF
A B A B A B
+ - + - + -
Shield
LT
120 Ω
Shield
Good daisy chain
shield connection
Climatix POL63x with Climatix POL63x with POL902 Modbus-Slave Modbus master
REF
A B
+ -
Mains AC 24V
EARTH GROUND
EARTH GROUND
Enable internal
line termination network
by operator unit
Shield
Modbus slave Modbus slave
The RS-485 common reference wire is referenced at one point (and only one point)
to earth ground.
An overall foil shield and drain wire provide additional noise protection.
14 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Modbus networks 2015-10-07
2.6 Line termination / polarization
Line Termination To minimize the reflections from the end of the RS485-cable it is required to place
a line termination near each of the 2 ends of the bus.
Line Polarization When there is no data activity on an RS-485 balanced pair, the lines are not driven
and, thus susceptible to external noise or interference. To insure that its receiver
stays in a constant state, when no data signal is present, some devices need line
polarization resistors ( pull up / pull down ) to bias the network. This will be done
typically in the Modbus Master device and must be done in one place only.
The line termination and at the same time the polarization can, in POL63x and
POl902, be enabled or disabled via the operator unit.
This means that a Climatix device can only enable the termination and polarization
at one end of the RS-485 line. On the other end the termination must be set
externally or with a device that can switch on the termination only (without
polarization).
Switchable by
operator unit
5V
Pull Up
680Ω
A+ 120Ω
Line
B- Termination
REF 1nF
Pull Down
680Ω
REF / Common
15 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Modbus networks 2015-10-07
2.7 TCP/IP networks
Modbus TCP port Modbus TCP in Climatix uses the TCP port 502. This port number is not
changeable.
IP address The IP address is assigned either dynamically via the DHCP server or set manually
via HMI. Normally is to use fixed IP address.
2.8 Tools
Modbus master Modbus slave devices e.g. Climatix controllers can be tested with several Modbus
simulation tools master simulation tools such as "Modbus Poll" or "ModScan" from a computer.
"Modbus Poll" can be downloaded from www.modbustools.com.
A RS485/RS232 converter or a Modbus RTU/TCP gateway may be needed to
connect to a computer.
16 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Modbus networks 2015-10-07
3 Commission instructions
3.1 General
Connection ways There are up to 3 ways to communicate with Modbus on a Climatix controller:
Internal RTU (POL63x)
Internal TCP (POL638)
External communication module POL902
Internal RTU A Modbus RTU, via RS485, interface is always available on the basic controller
(POL63x) POL63x.00/STD. It can be defined as the master or slave or switched off.
The internal Modbus interface is automatically set to master if any master function
is enabled in the controller.
Internal TCP A Modbus TCP interface is available on the POL638.00/STD controller via the
(POL638) standard Ethernet port. The internal Modbus TCP interface can be used for slave
mode and can be used for slave mode even if the RS485 port is used as master.
External communication Two extra Modbus RTU slave interface, is provided with the external Modbus
module POL902 communication module POL902. This is typically used when there is needed more
than one connection, example connection to both a BMS system and a Touch
panel. The module is also needed in case the internal RTU interface already is
used as a master interface.
17 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Commission instructions 2015-10-07
3.2 Commission internal Modbus RTU
Involved devices The picture shows the devices and connections involved in commissioning:
J3960Z02
POL63x
RS485 HMI-DM
Modbus RTU
Connection Proceed as follows to connect the Climatix controller to the Modbus line:
Step Action
1 Controller OFF.
2 Connect Modbus bus cable to the RS485 interface
(pins A+ and B-, Ref for GND).
3 Controller ON.
Configuration via Proceed as follows to configure the controller for internal Modbus RTU:
operator unit Step Action
1 Log in to HMI using the password for level 4 (Service), default 2000.
2 Go to Main Index > System overview > Communication > Modbus >
3 Select Device type (Internal mode):
Select the integrated Modbus interface RS485 to be used as slave.
Caution!
The integrated RS485 cannot be used as slave if already used as
master. This selection is blocked when a function require master.
4 Go to Internal settings for RS485 >
5 Select Internal Modbus slave address:
Enter the corresponding Modbus slave address (1…247).
6 Select Baudrate:
Enter the transmission rate as per the Modbus (2400, 4800, 9600,
19200 and 38400). All participants must have the same setting.
7 Select Stop bits:
One or two stop bits
All participants must have the same setting.
8 Select Parity:
None, even or odd parity.
All participants must have the same setting
9 Select Response delay:
Delays the response by n milliseconds.
- Resp.fail timeout:
Setting access time if used as master.
The master must undertake read access within this period, otherwise an
alarm is triggered. This has no influence for Modbus slave mode.
10 Select Termination:
The RS485 topology must always be ended using wave resistors.
They can be enabled or disabled here as described in section 2.6.
Only enable this when it is needed both termination and polarization,
otherwise use external line termination.
11 Select Reset required !!:
When done, restart controller using this command.
Extra Modbus comm is the alarm object and settings like alarm class etc for
Modbus faults can be changed here.
18 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Commission instructions 2015-10-07
Commission internal Modbus RTU, cont.
Configuration via After restart, the internal Modbus RTU is configured and ready to use.
operator unit, cont.
As a matter of principle, the controller must be restarted with "Reset required !!" or
power off/on the controller after changing any settings to assume the data.
Other setting than described above has nothing to do with Modbus RTU slave
mode and should not be changed.
19 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Commission instructions 2015-10-07
3.3 Commission internal Modbus TCP
Involved devices The picture shows the devices and connections involved in commissioning:
J3960Z 03
POL638
HMI-DM
Ethernet
Modbus TCP
Connection Connect the Climatix controller to the Ethernet (Modbus TCP) with a standard
network cable.
Configuration via Proceed as follows to configure the controller for internal Modbus TCP:
operator unit Step Action
1 Log in to HMI using the password for level 4 (Service), default 2000.
2 Go to Main Index > System overview > Communication > Modbus >
- Device type (Internal mode):
Selects if the integrated Modbus interface RS485 should be used as
master or slave. This has no influence for Modbus TCP.
3 Go to Internal settings for IP-Config. (TCP/IP) >
Note!
Settings for TCP/IP can also be displayed and changed in:
Main Index > System overview > Communication > IP-Config. >
- Take care to change TCP/IP setting if the controller is already connected
to Ethernet for other purpose.
4 Select functionality for DHCP:
Active means that the IP address is given from a DHCP server on the
network.
Passive means that a fixed IP address will be used as the settings
described below. Fixed IP address is preferred.
5 Select IP, Mask and Gateway:
The IP settings for the controller are used for a fixed IP address and are
only active if the DHCP parameter is set to Passive.
Note:
– End a line with #. Never use a “space” at the end.
After restart, the internal Modbus TCP is configured and ready to use.
As a matter of principle, the controller must be restarted with "Reset required !!" or
power off/on the controller after changing any settings to assume the data.
Other setting than described above has nothing to do with Modbus TCP slave
mode and should not be changed.
20 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Commission instructions 2015-10-07
3.4 The Modbus module
P3934Z02
1 6
T2
REF
RS485
SIEMENS SIEMENS
POL902.00/xxx
RS485
BSP BUS
REF
4
T1
3
2
Status LEDs The status LEDs "BSP" and "BUS" can light red, green and yellow during
operation.
"BSP" LED This LED informs on the status of the "Board Support Package" (BSP). Color and
flashing frequency of the LED:
Color Flashing frequency Meaning / Mode
Red / Green 1 s "on" / 1 s "off" BSP upgrade mode.
Green Steady "on" BSP operating and communication with
controller working.
Yellow Steady "on" BSP operating, but no communication with
controller.
Red Flashing at 2Hz BSP error (software error).
Red Steady "on" Hardware fault.
"BUS" LED This LED shows the status of external communication with the bus, not to the
controller. Color and flashing frequency of the LED:
Color Flashing frequency Meaning / Mode
Green Steady "on" All communication running, or if watchdog
is disabled.
Red Steady "on" All configured communications down.
Means no communication to the Master
within set timeout. In case the timeout is set
to zero the watchdog is disabled.
Yellow Steady "on" Startup, or one configured channel not
communicating to the master.
Power supply is outside the allowed range if both LEDs are dark.
21 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Commission instructions 2015-10-07
3.5 Commission Modbus modules
Modbus RTU
J3960Z04
POL902 / POL6XX
HMI-DM
Connect Modbus Proceed as follows to connect the Modbus module to the Modbus bus via RS485
module (see also description in section for the Modbus module):
Step Action
1 Controller OFF.
2 Connect Modbus module to controller using plug connection.
3 Connect Modbus bus cable to Modbus module (pins + and -, Ref for
GND).
Use the T1 interface if only one master/bus should be connected.
Use the T2 interface if an additionally master/bus should be connected.
4 Controller ON:
The module starts / initialization begins.
As soon as the two LEDs "BSP" and "BUS" are steady green,
communication with the controller and Modbus bus is active.
Caution!
The controller must be reset a second time to update HMI; prior to
parameterization.
Configuration via Proceed as follows to configure the Modbus module for Modbus RTU step by step:
operator unit Step Action
1 Log in to HMI-DM using the password for level 4 (Service), default 2000.
2 Go to Main Index > System overview > Communication > Modbus >
Module[x] Modbus >
or
Main Index > System overview > Communication > Comm module
overview > Module[x] Modbus >
Note! [x] is the position of the connected communication module. This is
only information used when more than one module is connected.
3 Go to Settings channel [y] >
Channel 1 / Channel 2. Displays as of this point the data for the first
Modbus channel (channel 1, terminal T1) and the second Modbus
channel (channel 2, terminal T2) of the module.
These are the corresponding parameters, with the exception of enable.
- Select Enable:
Only for channel 2. Set to active to enable channel 2 (T2)
Some applications use the name channel 0 for terminal 1 and channel 1 for
terminal 2 and other applications may use the same channel number as for the
terminal.
22 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Commission instructions 2015-10-07
Commission Modbus modules, cont.
Configuration via Step Action
operator unit, cont. 4 Select Slave address:
Enter the corresponding Modbus slave address (1…247).
Must be uniqe in the RS485 network
5 Select Baud rate:
Enter the transmission rate as per the Modbus (2400, 4800, 9600,
19200 and 38400). All participants must have the same setting.
6 Select Stop bits:
One or two stop bits
All participants must have the same setting.
7 Select Parity:
None, even or odd parity.
All participants must have the same setting.
8 Select Response delay:
Delays the response by n milliseconds.
9 Select Termination:
The RS485 topology must always be ended using wave resistors.
They can be enabled or disabled here as described in section 2.6.
Only enable this when it is needed both termination and polarization,
otherwise use external line termination.
10 Select Timeout comm:
Timeout for the communication watchdog. The BUS LED goes to red or
yellow if one or both of the interfaces/channels has no communication to
the master within the set time. In case the timeout is set to zero the
watchdog is disabled.
11 Select Reset required !!:
When done, restart controller using this command.
As a matter of principle, the controller must be restarted with "Reset required !!" or
power off/on the controller after changing any settings to assume the data.
Other settings than described above are only options and should normally not be
changed.
Parameter list The following table lists all other Modbus module parameters which are displayed
by the HMI in the "Module[x] Modbus" page:
Parameters Explanation
State Current status of the communication module
Comm failure Active = Communications error
Slave Displays whether the channel is used
Timeout Active = Indicates communication timeout
Software version Module BSP version
Advanced Go to Advanced settings -> see below
Eng.unit support Change dimensions to the imperial system
Communication Determines the objectnames, "Mapping", used for all
Comm mapping Modbus addresses. Normally “Mapping1” (16384) that is
(Language) the same as COM1. Normally hidden!
Use default Reset the module parameterization to default setting.
Module Com module type (name)
Device ID Module hardware ID
Trace Show if log files are available for export
23 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Commission instructions 2015-10-07
Blank page
24 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Commission instructions 2015-10-07
4 Integration
4.1 Map registers
Modbus data formats Modbus registers are organized into reference types identified by the leading
numeric character of the reference address:
The "x" following the leading character represents a four-digit reference address.
Leading character The leading character is generally determined by the function code followed by the
address specified for a given function. The leading character also identifies the I/O
data type.
Meaning The functions below are used to access the registers outlined in the register map of
the module for sending and receiving data.
25 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Integration 2015-10-07
4.3 Reference Modbus addresses
Register restrictions The internal Modbus onboard the controller has limited number of registers. Input
and holding registers are limited to max 1000 addresses..
Addresses used All reference addresses from 0001-1000 are generated and can be accessed even
if not listed. As a result, multiple coils/registers can be forced/reset even if there is
a gap between two reference addresses.
Do not read/write any addresses above 1000. Doing so causes an exception and
communication fails.
All address types start with 1, and due to that some Master devices start with 0 it is
in that case necessary to subtract all addresses in the reference list with 1.
Use the right document All available reference addresses are found in a separate document and are
for the actual application specific for the actual application. All different applications, and in some cases also
application versions, have different reference addresses. The specific document for
the actual application must be used to see what reference addresses that are
available.
The actual application name and version can be found using the HMI.
In some cases it is also good to check the BSP versions for Controller and Modbus
module. Latest BSP version for Modbus module should always be used.
Check actual versions Proceed as follows to see the actual application name and BSP versions:
1. Log in to HMI-DM using the password for level 4 (Service), default 2000.
2. Select Main Index > System overview > Versions >
Parameter Explanation / Example
+Application info
Application manufacturer/name e.g. Siemens
Application name/date e.g. STD_AHU_vX.XX
+BSP version Controller operating system.
Comm module 1 Communication module 1 operating system
Comm module 2 Communication module 2 operating system
Comm module 3 Communication module 3 operating system
Check actual versions Older application versions could have another HMI structure and same information
(Alternative) is found in a different place.
1. Select Main Index > System overview > Application info >
2. Select Main Index > System overview > Target > BSP version
26 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Integration 2015-10-07
5 Other information
5.1 Troubleshooting, tips
RS485 network Observe the following for RS485 network design and structure:
Baud rate, parity and stop bits must match network and master. All devices,
including other products, on the Modbus network must have the same settings.
The 3-wire bus is NOT interchangeable and must be connected correctly.
In case of long distance and/or high baud rate, consider end-of-line resistors like
120 Ohms on both sides (according to RS485 rules). In Climatix this can be
done via HMI.
The REF must be used and connected properly.
TCP/IP network Observe the following for TCP/IP network design and structure:
Check that the DHCP parameter is set to “Passive” if fixed IP address should be
used.
Try to ping the controller if the communication is not working. If the ping fails
something is wrong in the network or the IP settings.
Check that the defined TCP/UDP port is open in the firewall. For Modbus the
TCP port 502 is used.
27 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Other information 2015-10-07
5.2 FAQ on TCP/IP
Network: Ping the communication module using the IP address to test communications:
Disconnected Step Action
1 Select Start > Run on the Windows start bar:
The "Run" dialog box opens.
2 Enter CMD and click OK:
The "CMD.exe" DOS window opens.
3 Enter C:\>ping XXX.XXX.XXX.XXX and press Enter:
The ping result is displayed.
Note! (XXX.XXX.XXX.XXX is the set IP address)
You are dealing with a network or IP settings error if pinging does not work.
28 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Other information 2015-10-07
5.3 Upgrade application or BSP via SD card
Situation The Climatix POL6XX controller and/or the Modbus communication module
POL902 can in special cases be upgraded with new software. Direct upgrade from
VVS8 to VVS10 is not possible.
Modbus / Ethernet
J3960Z05
SD
All settings can be saved to the SD card before the upgrade and then loaded again
after the upgrade.
Upgrade procedure The upgrade procedure and how to save/load all settings are not described in this
manual. Contact your manufacturer to get instructions and necessary files.
29 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Other information 2015-10-07
5.4 Override I/Os via communication
Preamble Some inputs can be overridden via Modbus, see reference addresses. However
these inputs must first be setup for this before it works. Inputs can work, only via
hardware, only via communication or as a combination.
Prerequisite Input must first be enabled and hardware place selected in configuration.
30 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Other information 2015-10-07
Index
B R
Before you start ...................................................... 5 Revision history ....................................................... 5
RS485 cable installation ........................................12
C RS485 networks ....................................................10
Commission instructions ....................................... 17
Commission internal Modbus RTU ....................... 18 S
Commission internal Modbus TCP ....................... 20 Safety notes. ........................................................... 7
Commission Modbus modules ............................. 22 Status displays ......................................................21
Symbols in document .............................................. 6
D
Document use......................................................... 8 T
Document validity ................................................... 5 Target audience ....................................................... 5
Documents, other ................................................... 5 TCP/IP FAQ ...........................................................28
TCP/IP networks ...................................................16
F Tools ......................................................................16
Function codes ..................................................... 25 Topologies ............................................................. 11
Trademarks and copyrights ..................................... 8
I Troubleshooting, tips .............................................27
I/Os via communication ........................................ 30
U
L Upgrade via SD card .............................................29
Line termination / polarization ............................... 15
V
M Versions, BSP and application ..............................26
Map registers ........................................................ 25
Modbus module mechanical design ..................... 21 W
Modbus protocol ..................................................... 9 Wiring examples ....................................................14
Modbus reference addresses ............................... 26
31 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies Index 2015-10-07
Siemens Switzerland Ltd
Building Technologies Division
International Headquarters
Gubelstrasse 22
6301 Zug
Switzerland
Tel. +41 41-724 24 24 © Siemens Switzerland Ltd, 2015
www.siemens.com/buildingtechnologies Subject to change
32 / 32
Siemens Modbus communication, slave mode CB1J3960en_POL63x
Building Technologies 2015-10-07