This document provides settings for the overcurrent protection relay for the 500 KVA auxiliary transformer at a 12kV substation. It recommends a pickup setting of 0.5A based on a calculation of the expected secondary current of 0.36A at 120% overload. It also recommends a time multiplier setting of 0.08 seconds based on calculations to provide an operating time of 0.212 seconds for the transformer, using the relay's normal inverse time-current characteristic. The settings are summarized as a pickup of 1.25A and time dial of 0.08 seconds for the overcurrent protection, along with other relay parameter settings.

Uploaded by

raj
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
284 views1 page

Relay Settings

This document provides settings for the overcurrent protection relay for the 500 KVA auxiliary transformer at a 12kV substation. It recommends a pickup setting of 0.5A based on a calculation of the expected secondary current of 0.36A at 120% overload. It also recommends a time multiplier setting of 0.08 seconds based on calculations to provide an operating time of 0.212 seconds for the transformer, using the relay's normal inverse time-current characteristic. The settings are summarized as a pickup of 1.25A and time dial of 0.08 seconds for the overcurrent protection, along with other relay parameter settings.

Uploaded by

raj
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

SIEMENS

C.1 500 KVA Aux Transformer 12kV side Overcurrent Protection


Relay Type = 7SJ8031-5EB00-1FB0
CT Ratio = 800 / 400 / 5A

A. Plug Setting:
Considering 1.2 times overloading, the overcurrent plug setting of protected
object should be 120 % of rated current.
= 500kVA x 1.2 ÷ (√3 x 12 kV)

= 28.87 A
Corresponding secondary current = 28.87 A ÷ 400 ÷5
= 0.36 A
pickup setting = 0.36 A ≈ 7.2% x In
= 0.5 to 20 A (steps 0.01)
Recommneded Relay settings = 8.0% x In
pickup setting ≈ 0.40 A
Hence selected pickup setting ≈ 0.50 A
(Note:Due to limitation of relay range ,we propose to select Pick up value 0.5 instead of 0.4)
B. Time Multiplier Setting:
Fault Current contributed by = 500kVA x 1 ÷ (√3 x 12 kV x 0.046)

transformer = 522.96 A
Multiples of Fault Current = 523.0 ÷( 400 /5 x 0.50)
= 13.07 A
0.02
As per IEC Normal Inverse characteristic = 0.14 ÷ [(13.1) -1]
(Refer 7SJ80 manual page 384)
Operating time = 2.654 sec.
= 2.65 sec. at TMS = 1
Operating time for Auxiliary Trafo 12kV side = 0.200
Since, 2.65 x TMS = 0.200 sec.
TMS = 0.075
Available setting = 0.05 to 3.2s (steps 0.01s)
Hence the selected TMS ≈ 0.080
Operating time = 2.650 x 0.080 ≈ 0.212 sec.

C. Settings recommended :

General Data
Address Function Value
0214 Rated Frequency 50HZ
0209 Phase Sequence L1,L2,L3
0204 CT Rated Primary Current 400A
0205 CT Rated Secondary Current 5A
0217 IE-CT Rated Secondary Current 400A
0218 IE-CT Rated Secondary Current 5A

OverCurrent Protection
Address Function Value Range
1207 51 Pickup 1.25A 0.50 to 20A
1208 51 Time Dial 0.080 0.05 to 3.2 sec
1211 51 IEC Curve SI** Norm,Very,Ext,long
1202 50-2 Pickup 15A** 5.0A to 75A
1203 50-2 Delay 0 sec 0 to 60 sec
** Note:
Values has been modified as per site (GSM/GSP) recommendation.

SIEMENS Page 25 +
Energy Sector Projects/Engineering EM-TS PROJECTS /A5175/Relay Settings