Automatic Voltage Regulator (Avr) : General Description Technical Specification

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

MX321 AUTOMATIC VOLTAGE

REGULATOR (AVR)
SPECIFICATION, INSTALLATION AND ADJUSTMENTS

General description Technical specification


MX321 is a three phase sensed Automatic Voltage Regulator and
SENSING INPUT
forms part of the excitation system for a brush-less generator. Voltage Frequency 190-264V ac max, 2 or 3 phase
Excitation power is derived from a three-phase permanent magnet POWER INPUT (PMG) 50-60 Hz nominal
generator (PMG), to isolate the AVR control circuits from the effects Voltage
of nonlinear loads and to reduce radio frequency interference on the Current 170-220V ac max, 3 phase, 3 wire
Frequency 3A/phase
generator terminals. Sustained generator short circuit current is
another feature of the PMG system. OUTPUT
100-120 Hz nominal
Voltage
The AVR senses the voltage in the main generator winding and Current
max 120V dc
controls the excitation to maintain the generator output voltage within
continuous 3.7 A (see note 1)
the specified limits, compensating for load, speed, temperature and
Intermittent 6A for 10 secs.
power factor of the generator. Three phase RMS sensing is employed Resistance
15 ohms minimum
REGULATION
for superior voltage regulation.
+/- 0.5% RMS with 4% engine governing (see note 2)
Adjustable Soft start circuitry is included to provide a smooth THERMAL DRIFT
controlled build up of generator output voltage. 0.02% per deg. С change in AVR ambient (note 3) SOFT
START RAMP TIME 0.4 - 4 seconds TYPICAL SYSTEM
A frequency measuring circuit continually monitors the shaft speed of RESPONSE
the generator and provides under-speed protection of the excitation AVR response 10 ms
system by reducing the generator output voltage proportionally with Filed current to 90% 80 ms
Machine Volts to 97% 300 ms
speed below a pre-settable threshold. A further enhancement of this
EXTERNAL VOLTAGE ADJUSTMENT
feature is an adjustable volts per Hertz slope and voltage recovery
+/-10% with 5 к ohm 1 watt trimmer (see note 4) UNDER
time, to improve the response of turbo charged engines. FREQUENCY PROTECTION
Set point 95% Hz (see note 5)
Current limiting may be included to allow control over the amount of
Slope 100-300% down to 30 Hz
sustained short circuit current. Max. Dwell 20% volts/S recovery UNIT POWER
DISSIPATION 18 watts maximum ANALOGUE INPUT
Maximum excitation is limited to a safe period by internal shutdown of
Maximum input +/- 5 Vdc (see note 6)
the AVR output device. This condition remains latched until the
Sensitivity 1 v for 5% Generator Volts (adjustable) Input
generator has stopped. resistance 1k ohm QUADRATURE DROOP INPUT 10 ohms burden
Max. sensitivity: 0.22 A for 5% droop 0PF Max. input: 0.33 A
The AVR includes an over-voltage protection feature with internal
CURRENT LIMIT INPUT 10 ohms burden Sensitivity range: 0.5 - 1A
shutdown of the AVR output device, plus the ability to trip an optional OVER VOLTAGE DETECTOR INPUT
excitation circuit breaker if required. Set point: 300v. Time delay: 1 Sec (fixed)
CB trip coil volts: 10-30 vdc CB trip coil resistance: 20-60
Provision is made for the connection of a remote voltage trimmer, ohms OVER EXCITATION PROTECTION
allowing the user fine control of the generator's output.

An analogue input is provided allowing connection to a Newage


Power Factor controller or other external device with compatible
output.

The AVR has the facility for droop CT connection, to allow parallel
running with other similarly equipped generators.

Set point 75 Vdc


Time delay 8-15 seconds (fixed)
ENVIRONMENTAL
Vibration 2 50mm/sec
0-100 Hz 3.3g
100Hz-2kHz -40 to +70°C 95%
Operating temperature (see note 7) -55 to
Relative Humidity 0-70°C +80°C
Storage temperature

NOTES 4. Applies to Mod status E onwards. Generator de-rate may


1. Derate linearly from 3.7A at 50°C to 2.7A at 70°C apply. Check with factory.Factory set, semi-sealed,
2. The stated voltage regulation may not be maintained in the jumper selectable.
presence of certain transmitted radio signals. Any change in 5. Any device connected to the analogue input must be fully
regulation will fall within the limits in Criteria В of floating (galvanically isolated from ground), with an
BS.EN.61000-6-2 : 2001. insulation strength of 500V ac.
3. After 10 minutes. 6. Non condensing.

1 / 4 Page
2 / 4 Page
SUMMARY OF AVR CONTROLS
CONTROL FUNCTION DIRECTION

VOLTS TO ADJUST GENERATOR OUTPUT VOLTAGE TO CLOCKWISE INCREASES OUTPUT VOLTAGE CLOCKWISE
STABILITY PREVENT VOLTAGE HUNTING TO SET THE UFRO KNEE INCREASE THE DAMPING EFFECT CLOCKWISE REDUCES THE
UFRO POINT TO SET THE GENERATOR DROOP TO 5% AT KNEE POINT FREQUENCY CLOCKWISE INCREASES THE
DROOP OPF TO OPTIMISE ANALOGUE INPUT SENSITIVITY TO DROOP CLOCKWISE INCREASES THE GAIN OR SENSITIVITY
TRIM SET THE OVER EXCITATION TRIP LEVEL TO SET THE CLOCKWISE INCREASES THE TRIP LEVEL CLOCKWISE
EXC HZ RELATED VOLTAGE DIP TO SET THE HZ RELATED INCREASES THE DIP CLOCKWISE INCREASES THE RECOVERY
DIP RECOVERY TIME TO SET THE STATOR CURRENT LIMIT TIME CLOCKWISE INCREASES THE CURENT LIMIT
DWELL I LIMIT OVER V TO SET THE OVER VOLTAGE TRIP LEVEL TO SET THE CLOCKWISE INCREASES THE TRIP LEVEL CLOCKWISE
RAMP NO LOAD VOLTAGE RAMP UP TIME INCREASES THE VOLTAGE RAMP TIME

The main functions of the AVR are: The Circuit Breaker provides circuit isolation of the control system
Potential Divider and Rectifier takes a proportion of the generator in the event of an over excitation or over voltage condition.
output voltage and attenuates it. The potential divider is adjustable
The Over Excitation Detector continuously monitors the exciter
by the AVR Volts potentiometer and external hand trimmer (when
field voltage and turns off the power device if this rises above the
fitted). The output from the droop CT is also added to this signal. A
reference leve.l for greater than the stated time period. An
rectifier converts the a.c. input signal into a d.c. signal representing
external signal is also provided to trip the Circuit Breaker
generator voltage.
The Over Voltage Detector continuously monitors the generator
The DC Mixer adds the Analogue input signal the generator voltage
stator voltage and turns off the power device if this rises above the
signal.
reference level, for greater than the stated time period. An
The 3 Phase Rectifier converts the output of the current limit CT’s external signal is also provided to trip the Circuit Breaker
into a dc signal representing generator current.

The Amplifier (Amp) compares the generator voltage or current


ADJUSTMENT OF АVR CONTROLS
signals to the Reference Voltage and amplifies the difference (error) VOLTAGE ADJUSTMENT
to provide a controlling signal for the power devices. The Ramp The generator output voltage is set at the factory, but can be altered
Generator and Level Detector and Driver infinitely control the by careful adjustment of the VOLTS control on the AVR board, or by
conduction period of the Power Control Devices and hence provides the external hand trimmer if fitted. Terminals 1 and 2 on the AVR will
the excitation system with the required power to maintain the be fitted with a shorting link if no hand trimmer is required.
generator voltage within specified limits.
WARNING! Do not increase the voltage above the rated generator
The Stability Circuit provides adjustable negative ac feedback to voltage. If in doubt, refer to the rating plate mounted on the
ensure good steady state and transient performance of the control generator case.
system.
WARNING! Do not ground any of the hand trimmer terminals, as
The Power Supply provides the required voltages for the AVR these could be above earth potential. Failure to observe this could
circuitry. cause equipment damage.
The Low Hz Detector measures the period of each electrical cycle If a replacement AVR has been fitted or re-setting of the VOLTS
and causes the reference voltage to be reduced approximately adjustment is required, proceed as follows:
linearly with speed below a presettable threshold. The Dip and Dwell 1. Before running generator, turn the VOLTS control fully anti-
circuits provide adjustments for greater voltage roll off and recovery clockwise.
time. A Light Emitting Diode gives indication of underspeed running. 2. Turn remote volts trimmer (if fitted) to midway position.
3. Turn STABILITY control to midway position.
The Synchronising circuit is used to keep the Ramp Generator and 4. Connect a suitable voltmeter (0-300V ac) across line to neutral of
Low Hz Detector locked to the Permanent Magnet Generator the generator.
waveform period. 5. Start generator set, and run on no load at nominal frequency
e.g. 50-53Hz or 60-63Hz.
Power Control Devices vary the amount of exciter field current in
6. If the red Light Emitting Diode (LED) is illuminated, refer to the
response to the error signal produced by the Amplifier.
Under Frequency Roll Off (UFRO) adjustment. Continued

3 / 4 Page
FI I TING AND OPERATING (Refer to generator wiring diagram for connection details.)

7. Carefully turn VOLTS control clockwise until rated voltage TRIM ADJUSTMENT continued
is reached. The dc signal applied to this input adds to the AVR sensing circuit.
8. If instability is present at rated voltage, refer to stability A1 is connected to the AVR 0 volts. Positive on A2 increases
adjustment, then re-adjust voltage if necessary. excitation. Negative on A2 decreases excitation. The TRIM control
9. Voltage adjustment is now completed. allows the user to adjust the sensitivity of the input. With TRIM fully
STABILITY ADJUSTMENT anti-clockwise the externally applied signal has no effect. Clockwise
The AVR includes a stability or damping circuit to provide good it has maximum effect.
steady state and transient performance of the generator. Normal setting is fully clockwise when used with a Newage Power
A jumper link selector is provided to optimise the response of the Factor Controller.
stability circuit to various size generators. The link should be OVER EXCITATION (EXC) ADJUSTMENT
positioned as shown in the diagram according to the kW rating of This adjustment is set and sealed in the works and should not be
the generator. tampered with. An over excitation condition is indicated by the
The correct setting of the Stability adjustment can be found by illumination of the red LED which also indicates under-speed running
running the generator at no load and slowly turning the stability and over-volts.
control anti-clockwise until the generator voltage starts to become The generator must be stopped to reset an over-excitation trip.
unstable. The optimum or critically damped position is slightly DIP ADJUSTMENT
clockwise from this point (i.e. where the machine volts are stable This feature is mostly used when the generator is coupled to turbo
but close to the unstable region). charged engines with limited block load acceptance. The feature
UNDER FREQUENCY ROLL OFF (UFRO) works by increasing the V/Hz slope to give greater voltage roll off in
ADJUSTMENT proportion to speed. With the DIP control fully anti-clockwise, the
The AVR incorporates an underspeed protection circuit which gives generator voltage will follow the normal V/Hz line as the speed falls
a volts/Hz characteristic when the generator speed falls below a below nominal. Turning the DIP control clockwise provides greater
presettable threshold known as the "knee" point. The red Light voltage roll off aiding engine recovery.
Emitting Diode (LED) gives indication that the UFRO circuit is DWELL
operating. This feature is mostly used when the generator is coupled to turbo
The UFRO adjustment is preset and sealed and only requires the charged engines with limited block load acceptance. The feature
selection of 50 or 60Hz and 4 pole or 6 pole, using the jumper link works by introducing a delay between speed recovery and voltage
as shown in the diagram. recovery and allows a greater DIP setting without instability. With the
For optimum setting, the LED should illuminate as the frequency DWELL control fully anti-clockwise, the generator voltage will follow
falls just below nominal, i.e. 47Hz on a 50Hz system or 57Hz on a the V/Hz line. Turning the DWELL control clockwise increase the
60Hz system. delay time between speed recovery and voltage recovery.
DROOP ADJUSTMENT CURRENT LIMIT (I LIMIT) ADJUSTMENT
Generators intended for parallel operation are fitted with a This feature is mostly used to limit short circuit current or to provide a
quadrature droop C.T. which provides a power factor dependent current limit on motor starting. To use this feature, current limit CT's
signal for the AVR. The C.T. is connected to S1, S2 on the AVR, of the correct ratio need to be connected to the AVR S1 S2
(see generator wiring diagram for details). The DROOP adjustment terminals. There is an internal time limit of 10 seconds. Consult the
is normally preset in the works to give 5% voltage droop at full load factory before using this feature.
zero power factor. OVER VOLTAGE (OVER V) ADJUSTMENT
Clockwise increases the amount of C.T. signal injected into the This adjustment is set and sealed in the works and should not be
AVR and increases the droop with lagging power factor (cos 0). tampered with. An over voltage condition is indicated by the
With the control fully anti-clockwise there is no droop. illumination of the red LED which also indicates under-speed running
and over-excitation.
TRIM ADJUSTMENT The generator must be stopped to reset an over-voltage trip.
An analogue input (А1 A2) is provided to connect to the Newage RAMP
Power Factor Controller or other devices. It is designed to accept The AVR includes a soft start or voltage ramp-up circuit to control the
dc signals up to +/- 5 volts. rate of voltage build up, when the generator runs up to speed. This is
normally pre-set and sealed to give a voltage ramp-up time of
WARNING! Any devices connected to this input must be fully approximately 3 seconds. If required, this can be adjusted between
floating and galvanically isolated from ground, with an insulation the limits defined in the specification.
capability of 500V ac. Failure to observe this could result in
equipment damage.

4 / 4 Page

You might also like