0% found this document useful (0 votes)
329 views137 pages

Sample Specs

Uploaded by

prince francis
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
329 views137 pages

Sample Specs

Uploaded by

prince francis
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 137

SCOPE OF WORK & SUPPLY SECTION: C-1.

8
(Architecture) 6979-02-16-49-SC51 Rev.A
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 3 of 8
Strategic Storage Project, at Padur

1.1 GENERAL
The Scope of Work shall in general include all Architectural works for the below mentioned
Buildings/ Sheds for Strategic Storage of Crude Oil project at Padur (ISPRL).
Contractor shall develop the FEED to Approved for Construction (AFC) status, taking due
account of the detailed requirements of the buildings/ sheds, design basis, specifications and
standards for architectural works for the scope of work covered under this Contract.
CONTRACTOR shall not proceed with construction till those documents which are specifically
listed at “Review” category are reviewed by OWNER /PMC.
Scope of work by the Contractor shall consist of Architectural design & detail engineering
including preparation of Architectural drawings, construction including construction
supervision & supply of all materials, labour, tools & tackles etc., obtaining approvals from
statutory Authorities, supply of deliverables like drawings, documents, preparation of As-built
drawings etc and co-ordination with EIL & the Owner etc. all complete for the following
buildings and sheds:

1) Administration & Amenities Building


2) Control Room
3) Sub Station
4) Gate houses/Guard Rooms
5) Workshop & Warehouse
6) Car/ Scooter Parking Shed
7) Fire Water Pump House
8) Fire Station
9) Compressor House
10) D.G. Shed
11) Boiler House
12) Drinking Water Pump House
13) Raw Water Pump House
14) Shed for Metering Equipment
15) Watch Towers
16) Any other building or shed required from process or functional point of view
and specified elsewhere in the bid document.

1.2 DETAIL ENGINEERING


Detail Engineering shall be based on "Architectural design basis" and approved preliminary
drawings. The Contractor shall prepare construction drawings and submit the same to
Owner/PMC for review. The requirement of deliverables by the Contractor for detail
engineering is indicated elsewhere.

1.3 CONSTRUCTION
The Contractor in strict conformity with Owner/PMC reviewed construction drawings, using
materials as per Specifications, Standards & List of Approved Manufacturers as attached in
the Tender Documents shall carry out construction including construction supervision.
Construction shall include supply of all materials, labours, plants, tools & tackles by the
Contractor unless specifically mentioned elsewhere in the Tender Document.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


SCOPE OF WORK & SUPPLY SECTION: C-1.8
(Architecture) 6979-02-16-49-SC51 Rev.A
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 4 of 8
Strategic Storage Project, at Padur

1.4 STATUTORY APPROVALS


The Contractor shall obtain all necessary approvals from statutory authorities such as Factory
Inspector, Local Municipal or Development Authorities for the design and construction. The
Contractor shall also prepare all drawings, documents as required for obtaining such
approvals. Any changes/ modifications etc. in design/construction required for obtaining such
approvals shall also be done by the Contractor without any time & cost implication to the
Owner or PMC.

2.0 SCOPE OF SUPPLY

2.1 Owner’s Scope of Supply


NIL

2.2 Contractor’s Scope of Supply


All architectural materials, (consumables/ non-consumables), required for satisfactory
completion of the job, shall be supplied by the contractor.

3.0 DELIVERABLES BY THE CONTRACTOR


The Contractor shall submit a detailed schedule of submission of deliverables as indicated
herewith for review by Owner/PMC as per agreed schedule. Such a schedule shall be made
in line with the overall time schedule indicated elsewhere in the Tender Documents.
Submission of all deliverables shall be as per the said schedule as reviewed by Owner/PMC.
All deliverables shall be prepared using Computer software and shall be complete in all
respects including correct titles indicating Owner, Consultant, Contractor, Project name, PMC
Job No., Dates, Issues, Revisions and signatures of Performer, Checker & Approver of the
Contractor.
Incomplete, unsigned & unchecked Documents/ Drawings shall not be accepted and shall be
returned.
All revisions shall be clearly pointed out clouded for easy identification/ review.
All deliverables shall be submitted in requisite number of prints as per methodology
mentioned elsewhere in the Tender Documents.

Deliverables by the Contractor shall be as listed herewith.


1. Drawing/ Document Schedule:
The schedule shall include all Drawings/ Documents with Title, Number, Dates of
issues (scheduled & actual) & present review status etc. The schedule shall be
updated and submitted at regular intervals as mentioned elsewhere.
2. Drawings:
A. Preliminary Architectural Drawings of the buildings in accordance with bid
indicating Plans, Sections & Elevations & Architectural treatment. Such
preliminary drawings shall be prepared after finalisation of sizes & layout of the
required spaces/ areas/ rooms and review of the same by the originating
department of PMC.
B. Construction drawings of all the Buildings. Construction Drawings shall contain
the followings. These drawings shall be prepared incorporating comments etc.
on the preliminary Drawings.
1. Plan of all levels, Terrace Plan, Key Plan.
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
SCOPE OF WORK & SUPPLY SECTION: C-1.8
(Architecture) 6979-02-16-49-SC51 Rev.A
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 5 of 8
Strategic Storage Project, at Padur

2. Sections as required for complete understanding of the Design &


Construction.
3. Elevations of all sides.
4. Door/Window details.
5. False ceiling details & layouts.
6. Schedule of Architectural Finishes.
7. Architectural details as required.
8. Any other Drawing required for complete understanding of the Design &
Construction.
Drawings shall be prepared using AutoCAD software of latest (at the time of floating
the Tender) version.
Drawings shall be prepared in 1:100 or 1:50 scale. For Construction details, Door
Window Details, the scale shall be 1:20 to 25. For key plans larger but legible scale
may be used.
3. Specifications:
The Contractor shall prepare & submit specifications of materials etc., which are not
covered or attached in the Tender Documents for review by Owner/PMC.
4. Documents/ Drawings for Statutory Approval:
The Contractor shall prepare & submit Documents/Drawings for Statutory Approval in
accordance with the statutory requirement for Information/Record of Owner/PMC.
5. As Built Drawings:
The Contractor shall prepare & submit As-built drawings both in requisite no. of hard
prints as well as in form of computer files for Information/Record of Owner/PMC.
6. List of Sub- vendors/ authorised applicators for specialised items:
The Contractor shall submit list of all Sub- vendors/ authorised applicators to be
engaged for execution of various specialised items (like Waterproofing, Underdeck
Insulation, False ceiling, False Flooring etc.) for approval.

4.0 REVIEW OF THE CONTRACTOR'S DRAWINGS/ DOCUMENTS


Drawings/ Documents submitted by the Contractor shall be reviewed by Owner/PMC within
agreed upon time schedule.
It shall be Owner/ PMC's right to review any, all or none of the Drawings/ Documents
submitted by the Contractor.
Review by Owner/ PMC shall not relieve the Contractor of his responsibility for correct
Design, Engineering and Construction. The sole responsibility of the correctness of Design,
Engineering & Construction shall lie with the Contractor irrespective of the fact that the
Drawings/Documents submitted are reviewed or not reviewed by Owner/PMC. The Contractor
shall correct all faulty design & construction detected at any stage of work without any cost &
time implication to PMC or the Owner.
Following Parameters of Design & Drawings shall not be reviewed:
A. Adequacy of provisions (in terms of spaces, services & utilities) and space/ area/ Room
sizes for Plant Buildings or Plant Areas in other Buildings. The Contractor shall ensure
correctness of such provisions vis-à-vis Owner/ PMC reviewed G.A. drawings & submit
Architectural drgs. only after review of such provisions by concerned deptt. of PMC.
B. Correctness of Drawings in terms of dimensions, matching of Plan, Elevation, Section, etc.
These parameters may be reviewed at random only.
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
SCOPE OF WORK & SUPPLY SECTION: C-1.8
(Architecture) 6979-02-16-49-SC51 Rev.A
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 6 of 8
Strategic Storage Project, at Padur

C. The Contractor shall ensure correctness of Location, Co-ordinates, Orientation & Road/
Ground/ Pavement levels vis-à-vis EIL reviewed/approved G.A. drawings.

5.0 BUILDINGS REQUIREMENTS


Basic requirements of the buildings such as type of structure & basic functional spaces to be
accommodated within the buildings are indicated in the following clauses. However other than
these basic functional spaces indicated in the clauses, other circulation, utility & amenity
spaces shall also be provided. For details of these functional spaces or additional functional
spaces reference shall also be made to requirements mentioned elsewhere in the Bid
document for incorporation in design & construction.

5.1 Administration & Amenities Building


The Building shall be R.C.C. framed structure with RCC roof slab and 230 thick brick walls.
The building shall be designed as a double storied building with provision of approach to
terrace for maintenance purposes.
The building shall have the following minimum requirements:
Ground Floor
1) Amenities block
• Separate toilets and change rooms for workers and officers
• Dining room with pantry
• Recreation & games rooms
2) QA Laboratory
3) Server room with UPS and electrical racks

First Floor
Administration block shall include cabins for officers and officer-in-charge with PA, office
space for staff, utility spaces for printers, shredder machine, copiers, fax machines etc and
adequate record/store rooms, toilets and drinking water facilities.
The building shall be designed as an air conditioned building with window/ split a/c units as
per requirement. Provision for LAN networking with server shall be made. All workstations and
cabins shall have UPS, power points and LAN points. Any other requirements as desired by
Owner shall be taken care of during detail engineering.

5.2 Control Room


Control Room shall be a single storied building with RCC framed (RCC column, beam &
slab/roof) structure with brick walls.
The following are the minimum requirements to be housed in Control Room:-
• Rack Room (Air conditioned) - 20 mX 12 m
• Console Room (Air conditioned) - 20m X 10 m ( Including 5 X 10 m Engineering
console Room)
• Instrument Engineer Room (Air conditioned)
• UPS Room (Air conditioned) - 8mx12m
• Office Rooms for Shift-In-Charge & Shift Engineers (Air conditioned)
• Entrance Lobby/ Corridor
• Battery Room- 6mx8m
• Clean Agent Cylinder Room - 6mx9.5m
• Rest Room
• A.C. Plant/ A.H.U. Room - 6mx9.5m
• Locker/ Toilet/ Drinking water facilities.
• Any other as required during detail engineering.
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
SCOPE OF WORK & SUPPLY SECTION: C-1.8
(Architecture) 6979-02-16-49-SC51 Rev.A
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 7 of 8
Strategic Storage Project, at Padur

The building shall be centrally air conditioned. False ceiling with clear height of 3000mm shall
be provided in all areas except Battery Room & A.C. Plant/ A.H.U. Room.
False flooring shall be provided in Rack Room. Console room shall have partly false flooring
and partly solid flooring with trenches as per layout of consoles. UPS Room shall have
trenches in flooring. The trenches and false flooring shall be as per instrumentation &
electrical requirement.
Console room & Rack Room shall be separated by a perfect partition wall. Viewing windows
in this wall shall be 2hour fire rated.

5.3 Sub Station


Sub Station shall be double storied RCC structure (RCC column, beam & slab/roof)
structure with 230/345 thick brick walls. Substation shall be provided with two stairs,
each on either side i.e. one covered RCC stair to switchgear hall, loading/ unloading
platform and other upto roof.
The following are the minimum requirements to be housed in the Sub Station:-
• Cable cellar, Transformers - Ground floor
• Battery Room - Ground floor
• Pressurisation Room (Ground Floor-Double height)
• Switchgear Room (pressurised) - First floor
• HMI/ Operator Room (Air conditioned) - First floor
• Loading/ Unloading platform (RCC)
• Veranda/ Stairs
• Toilet & drinking water facilities
• Any other as required during detail engineering

5.4 Guard Room


Guard Room shall be a single storied building with RCC framed (RCC column, beam &
slab/roof) structure with brick walls.

5.5 Workshop/ Warehouse


Workshop/ Warehouse shall be a single storied building with RCC framed (RCC column,
beam & slab/roof) structure with brick walls.

5.6 Car/ Scooter Parking Shed


Car/ Scooter Parking Shed shall have tubular steel truss with pre-coated (Galvalume/
Zincalume) steel roof sheeting/ cladding.
5.7 Fire Water Pump House
Fire Water Pump House shall be a single storied building with RCC framed (RCC column,
beam & slab/roof) structure with brick walls.
5.8 Fire Station
Fire Station shall be a single storied building with RCC framed (RCC column, beam &
slab/roof) structure with brick walls.
The following are the minimum requirements to be housed in the Fire Station building:-
• Fire Tenders -2 nos.(open on front and side)
• Fire Officer/Fire Marshal room
• Control Room
• Battery Room
• Office
• Toilet & drinking water facilities
• Any other room as required during detail engineering
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
SCOPE OF WORK & SUPPLY SECTION: C-1.8
(Architecture) 6979-02-16-49-SC51 Rev.A
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 8 of 8
Strategic Storage Project, at Padur

5.9 Compressor House


Compressor House shed shall have RCC columns and steel truss with pre-coated
(Galvalume/ Zincalume) steel roof sheeting/ cladding.
5.10 D.G. Shed
DG Shed shall be a single storied building with RCC framed (RCC column, beam & slab/roof)
structure with brick walls.
5.11 Boiler House
Boiler House shall have RCC columns and steel truss with pre-coated (Galvalume/
Zincalume) steel roof sheeting/ cladding.
5.12 Drinking Water Pump House
Drinking Water Pump House shall be a single storied building with RCC framed (RCC column,
beam & slab/roof) structure with brick walls.
5.13 Service Water Pump House
Service Water Pump House shall be a single storied building with RCC framed (RCC column,
beam & slab/roof) structure with brick walls.
5.14 Watch Towers
Watch Towers shall have RCC framed (RCC column, beam & slab/roof) structure with RCC
stairs and brick walls for the enclosed cabin.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 3 of 40
Padur.

1.0 GENERAL

1.1 The design considerations given hereunder establish the minimum basic requirements
of reinforced cement concrete (RCC) structures, structural steel works and masonry
structures. All structures shall be designed for satisfactory performance and functions
for which the same are to be constructed.

a) All codes referred in this document pertain to BIS (Bureau of Indian Standards)
publications and bearing the prefix IS.

b) Whenever any reference to BIS code is made, the same shall be taken as the
latest revision (with all amendments issued there to) on the notified date of
submission of tender.

c) Apart from the BIS codes mentioned in particular in the various clauses of this
document, all other relevant codes related to the specific job under
consideration and/or referred to in the above-mentioned codes, shall be followed
wherever applicable. Reference to some of the codes in the various clauses of
this document does not limit or restrict the scope of applicability of other relevant
codes.

d) In case of any variation/contradiction between the provisions of BIS codes and


the requirements given hereunder, the provisions given in this document shall
have precedence over all others. In absence of relevant BIS codes, reference to
corresponding British/American codes may be made (in that order of
preference).

All designs, detailing and construction shall strictly conform to the enclosed
standards, specifications and ‘Specific Requirements’. Only if relevant
information is not available in this document, reference to relevant BIS code shall
be made.

1.2 The Contractor shall do the structural designing of all structures and prepare complete
set of civil and structural drawings needed for correct and accurate construction. The
design shall be strictly in accordance with ‘Design Criteria’ given herein.

1.3 Detailed list of drawings/documents including design calculations, design drawings, bar
bending schedules (for RCC works) and fabrication drawings (for structural steel works)
and structure-wise quantity statements (showing anticipated, released and balance
quantities of concrete & structural steel ) shall be prepared by the Contractor and
submitted monthly for review by Owner/Owner’s representative. This list shall also
indicate the document/drawing category (approval, review or information as applicable)
together with the scheduled and actual dates of submission of the documents.

1.4 Before proceeding with design and drawing preparation the Contractor shall submit
detailed general philosophy of design of various parts of (all) the structures and
equipment foundations along with explanatory sketches for review by Owner/Owner’s
representative. Only after the review and incorporation of comments on the general
philosophy, as offered during the review, the Contractor shall submit any design
document and/or drawing for review or information or issue the same for construction.
Design and detailing of the structures and foundations shall fulfill all functional
requirements for which the same is intended and it shall be ensured that adequate
accesses, clearances, clearing of interferences, provision of cutouts, etc. have been
provided to make the structure/foundation fully operational.
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 4 of 40
Padur.

1.5 The Design and Approved For Construction (AFC) drawings shall strictly adhere to the
reviewed design basis and architectural/structural general arrangement and shall
incorporate all the comments/ suggestions given by Owner/Owner’s representative
without any extra cost to the Owner and any implication of time-schedule for completion
of works.

1.6 Construction of units/structures identified for design/drawing review (as referred in


Specific Requirements attached in this document) by Owner/owner’s representative
shall not be taken up at the site till these documents are reviewed by Owner/owner’s
representative and comments/suggestions given by Owner/owner’s representative are
incorporated. For all other foundations and structures the Contractor shall directly
submit the AFC drawings to Engineer-in-Charge and construction of such works shall
be taken up immediately. Requisite number of prints of design and drawings for such
foundations/ structures shall also be simultaneously sent to Owner/owner’s
representative for their information and record. In the event Owner/owner’s
representative offers any comment on documents/drawings of Information category it
shall be ensured by the Contractor that these comments are duly incorporated in the
documents/ drawings and revised set of document/drawing is issued to site for
construction and simultaneously to Owner/owner’s representative for records.

Wherever review is carried out the same shall be restricted to following:

a) Conformance of general arrangement of the structure to already reviewed


design philosophy and design basis.

b) Overall framing of the building/conceptual foundation system.

c) Detailed design and drawings including input/ output of computer analysis and
design vis-à-vis actual drawing.

Irrespective of the identified structures requiring review, the Contractor shall


submit complete sets of design and drawings of all structures/foundation
systems.

1.7 (i) Structural design/drawings for any structure/foundation shall be submitted for
review only if referenced input (e.g. architectural drawing, piping GAD,
equipment data sheet, vendor drawing, etc.) have been reviewed by the
concerned Owner’s specialist in approval/review code-2 or 1.

(ii) To facilitate an overall systematic review the Contractor shall submit the design
and drawings for each independent building/structure, together with a copy of
the referenced reviewed input data, in one lot.

1.8 Submission of all identified documents including design calculations and drawings for
review and/or information/record to the Owner/Owner’s representative by the Contractor
shall be in requisite (as mentioned elsewhere) number of prints. To ensure accuracy,
correctness and completeness of documents before submission to Owner/Owner’s
representative, the Contractor shall ensure that all such submitted designs and
drawings are complete in all respects, thoroughly checked, stamped APPROVED FOR
CONSTRUCTION (AFC), and signed APPROVED by the Contractor's own responsible
Civil/structural graduate (minimum) engineer (irrespective of the fact that the same are
prepared in the Contractor's own design office or by an approved agency).

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 5 of 40
Padur.

Incomplete, unchecked, unsigned and unstamped documents/drawings and


designs shall not be accepted for review/construction and shall be returned
forthwith.

1.9 The accuracy/correctness of all designs and drawings shall be the sole responsibility of
the Contractor and any delay/loss/damage incurred by the Owner in respect of any
mistake/discrepancy/anomaly in such designs and drawings shall be entirely borne by
the Contractor.

1.10 Owner/Owner’s representative reserves the right to review any/all or none of the
designs and drawings. Review by Owner/Owner’s representative shall not relieve the
Contractor of his responsibility for correct design and execution of the works.

1.11 All revisions shall be clearly marked and clouded for easy identification. Subsequent
review of such revised documents shall be limited to revision as clouded.

1.12 All fabrication/erection drawings and bar bending schedules shall be prepared by the
Contractor and shall be directly issued for construction to his work site. Also, six copies
of such drawings together with design calculations for all splices, joints and gusset
plates shall simultaneously be submitted to Owner/owner’s representative at site
(Resident Construction Manager) for review. The Owner/owner’s representative at site
at his discretion may review all or some or none of these designs & drawings.

Wherever such review is carried out the same shall be restricted to the following:

a) Structural layouts, orientation, elevation of structural members.

b) Section/size of members.

c) Adequacy of few critical connections and joints for their required strength.

1.13 Internationally accepted commercial software viz. STAADPRO, COSMOS, GT


STRUDL, NISA only shall be permitted for analysis and design. STAADPRO shall not
be allowed for use in dynamic analysis of machine foundations.

In case software packages other than listed above are intended to be used for analysis
and design, the same shall be informed in writing to Owner/owner’s representative.
Calculations and relevant computer files containing input and detailed output (also refer
clause 1.14) shall be submitted by the Contractor for checking and validation of the
software package. Only after getting written approval from Owner/owner’s
representative, to this effect, such intended software be put to use for detailed analysis
and design.

1.14 Soft copies of all input files and the following documentation as hard copy shall be
submitted for computer aided analysis and design:

(i) Complete print out of input and output files.

(ii) Relevant sketches with node and member numbering, loading, etc.

(iii) Summary of member end forces, support reactions, stress ratio, deflections, etc.

Verification of the foundation loading data for all equipments/ structures/ stacks
etc., which form part of the comprehensive packages supplied by respective
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 6 of 40
Padur.

vendors, shall be entirely the responsibility of contractor. Contractor shall ensure


that wind/ seismic loadings are strictly in line with the basic wind pressure/ site
spectra curves.

Reviewing of designs/drawings is not obligatory on the part of Owner/Owner’s


representative and complete correctness/soundness of the designs/drawings and
their execution at the site shall be the sole responsibility of the Contractor
irrespective of the fact whether the same has been reviewed by Owner/Owner’s
representative or not. Any defect observed during construction or till the defect
liability period of works' shall be rectified and removed by the Contractor. The
Contractor shall carry out whatever modification or reconstruction is needed for
the purpose, to the entire satisfaction of the Engineer-in-Charge/Owner without
any extra cost and/or time implication to the Owner.

2.0 REFERENCED STANDARDS & PUBLICATIONS

Sl. No. CODES

1. Code of practice for plain & reinforce concrete IS: 456


2. Code of practice for general construction in steel IS: 800
3. Code of practice for use of cold-formed light gauge steel
structural members in general building construction IS: 801
4. Code of practice for use of structural steel in overhead
transmission line towers IS: 802
5. Code of practice for use of steel tubes in general building
construction IS: 806
6. Covered electrodes for manual metal arc welding
of carbon and carbon manganese steel IS: 814
7. Code of practice for use of metal arc welding for general
construction IS: 816
8. Code of practice for design loads IS: 875
9. Code of practice for construction of stone masonry IS: 1597
10. Fillers for expansion joints IS: 1838
11. Criteria for earthquake resistant design of structures IS: 1893 Part 1,4
12. Code of practice for structural use of unreinforced masonry IS: 1905
13. Recommended practice for hot dipped galvanizing on iron and
steel IS: 2629
14. Methods for testing uniformity of coating of zinc coated articles IS: 2633
15. Code of practice for design & construction of raft foundations IS: 2950
16. Code of practice for design & construction of machine foundations IS: 2974
17. Code of practice for concrete structures for storage of liquids IS: 3370
18. Code of practice for design and construction of foundation
for transmission line towers and poles IS: 4091
19. Code of practice for earthquake resistant design
and construction of buildings IS: 4326
20. Criteria for blast resistant design of structures for explosions
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 7 of 40
Padur.

above ground IS: 4991


21 Criteria for design of RC bins IS: 4995
22. Criteria for design of RCC chimneys IS: 4998
23. Code of practice for anti-termite measures in buildings IS: 6313
24. Code of practice for design & construction of steel chimney IS: 6533
25. Method for determination of mass of zinc coating IS: 6745
26. Chlorpyrifos emulsifiable concentrates IS: 8944
27. Criteria for design of steel bins for storage of bulk materials IS: 9178
28. Recommendations for metal arc welding of carbon and carbon
manganese steel IS: 9595
29. Two parts polysulphide based sealants IS: 12118
30. Code of practice for ductile detailing of reinforced concrete structures
subjected to seismic forces IS: 13920
31. Fire Proofing in Oil and Gas Industry
(A publication of Oil Industry Safety Directorate) OISD-STD-164
32. Code of practice for Design and construction of Pile foundations IS: 2911
33. Code of practice for structural safety of buildings - Shallow
foundations IS: 1904
34. Code of practice for determination of bearing capacity
of shallow foundations IS:6403
35. Code of practice for calculation of settlements of
foundations IS: 8009(Pt I, II)
36. Determination of dynamic properties of soil IS: 5249
37. Process Control Room Safety OISD-STD-163
38. Code of practice for cement and colored paints IS:5410

Note The above list is suggestive and not exhaustive. Apart from these basic codes any
other code referred-to in this document and/or any other related code shall also be
followed wherever required.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 8 of 40
Padur.

3.0 DESIGN CRITERIA - GENERAL

Offsite Pipe Rack shall be completely in structural steel construction with bolted
(machined holes) connections and subsequently welded. Unit pipe Rack shall have
RCC framed construction up to first deck level.

Fire proofing wherever required as per OISD-STD-164 shall be done for Two hours fire
rating.

Shed type structures like compressor house etc. shall completely be of steel
construction with pre-coated GI sheeting. Warehouse structure shall have RCC
columns with structural steel truss roofing arrangement. Technological structures
(structure provided to support vertical vessels and columns), shall be of concrete or
steel construction, based on the design/process requirement. All other buildings shall
be of RCC frame type construction with brick walls. (Refer Architectural scope of work,
specification and drawings enclosed elsewhere in the bid document for type and details
of the buildings.)

3.1 DESIGN LOADS

3.1.1 These loadings shall be applicable to all structures irrespective of the material
employed for construction.
a. Dead Loads
The weight of all permanent construction including walls, fire proofing, floors, roofs,
partitions, stairways and fixed service.

b. Equipment Loads
The empty weight of process equipment including all fixtures, platforms, and ladders
and attached piping but excluding contents shall be considered. If piping weight is
not indicated separately or included in the weight of the equipment, the same shall
be taken as 10% of the weight of the equipment.
c. Live Loads
Live loads shall, in general, be as per IS: 875. However, the following minimum live
loads shall be considered in the design of structures:
i. Process Building/Technological Structure
Operating area - 5.0 kN/m2
Maintenance area - 7.5 kN/m2

ii. Compressor House/TG house/Boiler house

Operating area - 7.5 kN/m2


Maintenance area - 7.5 kN/m2

iii. Service Platform

Vessel/Tower - 3.0 kN/m2


Isolated platform - 2.5 kN/m2
(for valve operation)

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 9 of 40
Padur.

Access way - 2.5 kN/m2


Cross over - 2.0 kN/m2
iv. Substation/Control Room
Panel floor - 10.0 kN/m2
Unknown partition1 - 1.0 kN/m2
v. Staircase
Process Building/
Technological Structure - 5.0 kN/m2
Office - 5.0 kN/m2
Substation/Control Room - 5.0 kN/m2
Laboratory - 3.0 kN/m2
Service platform - 2.5 kN/m2
In absence of any suitable provision for live loads for any particular type of floor or
structure as given above (or in BIS Codes), the assumed loading shall be got
approved by the Owner/owner representative.

Live load on various types of roofs shall be as per the requirements given in IS:875.

d. Operating Loads

Operating loads shall include maximum design loads sustained by the equipments
during plant operation.

e. Wind Loads

Wind loads shall generally be as per IS:875 except for switch yard structures &
transmission towers for which IS:802 shall be applicable.

The basic wind speed of the site is taken as 39 m/s.


Values of coefficients k1, k2, k3 shall be as per IS 875.

The design life span of all structures shall be taken as 60 years.

To account for surface area of piping, platforms and other attachments fixed to the
equipment the surface area of the equipment (vessel/column) exposed to wind shall
be increased by 20% or as specified in the mechanical data sheet of the equipment.

f. Seismic Loads

Seismic forces shall be based on site specific seismic spectra given in Doc. No.
6979-00-16-54-001(section 3.9) and the provisions of IS: 1893.

g. Impact & Vibratory Loads

Structures subjected to impact or vibratory loads shall be designed as per the


provisions of IS:875 & IS:2974. Requirements for overhead cranes and monorails
shall be as per IS:800.

1 For definition of unknown partitions refer clause 3.1.2 of IS: 875 (Part 2).
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 10 of 40
Padur.

h. Bundle Pull

Bundle Pull for different types of Exchanger shall be taken as under:


Fixed type - Nil
Kettle type - 0.30 x Bundle weight
All other types - 0.86 x Bundle weight or 30N/mm of diameter
whichever is greater

Total Bundle Pull shall be considered on fixed pedestal alone.

i. Soil and Hydrostatic Pressure

Pressure on basement walls - In the design of basement walls or similar


(approximately vertical) structures below grade, provision shall be made for
resisting lateral pressure of the adjacent soil. If a portion or whole of the adjacent
soil is below free water surface, pressure computations shall be based on the
diminished weight of the soil (due to buoyancy) plus full hydrostatic pressure. Due
allowance shall also be made for possible surcharges from fixed or moving loads.

Uplift on Floors - In the design of basement floors and similar (approximately


horizontal) constructions below grade, the upward pressure of water shall be taken
as full hydrostatic pressure applied over the entire plan area. The hydrostatic head
shall be measured from the underside of construction. The downward load due to
over burdens shall be calculated only for the volume over projected plan area (i.e.,
the volume of overburden beyond projected plan area shall not be considered).
Factors of safety against uplift shall be 1.2.

j. Other Loads
Apart from the specified live loads, any other equipment load or possible
overloading during construction/hydro-test/ maintenance/erection shall also be
considered in the design. Under hydro test condition the wind force shall be taken
as 25% of normal loading.
Design of all structures shall also consider any other relevant and consequential
load/stress imparted to the structure.

All liquid retaining/storage structures shall be designed assuming liquid upto the full
height of wall irrespective of provision of any over flow arrangement. Pressure relief
valves or similar pressure relieving devices shall not be made in underground water
retaining/storage RCC structures.

All buildings/structures shall be designed to resist the worst combination of the


above loads.

3.2 SOIL INFORMATION FOR FOUNDATION DESIGN

For soil information reference shall be made to the Geo-technical data (Doc. No. 6979-
00-67-41-GD-01). Type of cement, grade of concrete, minimum cement content and
maximum water cement ratio (for concrete), minimum cover to reinforcing steel to be
used in foundations and substructures and any other remedial actions required for
foundations due to aggressiveness of sub soil/water shall be as per the Geo-technical
data.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 11 of 40
Padur.

3.3 ANTI-TERMITE TREATMENT

No anti-termite treatment shall be provided inside the unit areas.


Offsite and utility buildings shall be provided with anti-termite treatment as per IS: 8944
and IS: 6313.

3.4 FOUNDATIONS

3.4.1 NGL (Natural ground level) and FGL (Finished ground level) shall be marked on all
drawings showing foundation/sub-structure details and related design documents.

3.4.2 Machine/static equipment foundations shall be separated from adjoining parts of


buildings, other foundations and floor/pavement slabs. Joints at floor/pavement slabs
shall be suitably sealed.

3.4.3 Foundations and structures for machines subject to vibrations shall be so proportioned
that the amplitude and frequency of the foundation/structure are within the permissible
limits as per relevant BIS codes (or as required by the machine vendor).

3.4.4 Machine foundations shall be designed and detailed as per IS: 2974. All appendages to
such foundations shall be reinforced suitably to ensure integral action.

3.4.5 Safe bearing pressure (allowable net safe bearing capacity) shall be based on the
following minimum criteria under Dead Load + Live Load (or with Operating) condition:

- Foundations in unit areas, utility areas


and foundations for Plant buildings. 25mm settlement.
- Non Plant buildings. 40mm settlement.
- Raft Foundations 40mm settlement

For transient loadings viz. with wind/seismic loads, settlement shall not be the criteria
and safe bearing capacity based on shear criteria shall be considered.

3.4.6 Structures supported on RCC strip footings shall be provided with suitable tie beams
connecting all footings at foundation level. Minimum width of footing shall be 1000 mm.

3.4.7 Foundations of structures in filled up soil shall be connected with suitable tie beams at
foundation level.

3.4.8 Raft foundations shall be designed as per IS: 2950.

3.4.9 Masonry walls shall be supported on continuous plain cement concrete mats/plinth
beams. Top of plinth beams shall be located minimum 300mm below the finished grade
level. Fouling of plinth beams with cable trenches, drains, pipe ducts, service lines etc.
shall not be acceptable.

3.4.10 Factors of safety for the design of foundations shall be as per Enclosure-I of this
document.

3.4.11 For the design of foundations for vertical vessels and process columns under hydro test
condition minimum 25% wind load shall be considered acting on the equipment.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 12 of 40
Padur.

3.4.12 Minimum depth of foundation for all structures shall be as per Geo-technical data.
Depth of ground water level shall be as per the Geo-technical data and hydrostatic
pressure shall be adequately accounted for in the design.

3.5 FLOORING DETAILS FOR BUILDINGS

TABLE-1 FLOORING DETAIL

SNo DESCRIPTION FLOORING TYPE

I II III

1(a) Sub Earthfill base compacted


Grade to 95% dry density.
1(b) Compacted layer of 200 THICK 200 THICK 150 THICK
boulder soling over
thoroughly compacted
Earth fill (in mm)
2(a) Strl Lean concrete 1:5:10 over 50 THICK 50THICK 50THICK
Grade sand layer (in mm)
Slab
Strl non suspended slab in 150 THICK 150 THICK 100 THICK
M20 Grade concrete
(Reinforced with 8mm dia
bars @200 c/c both ways)
over lean concrete.
2(b) R/F placed R/F placed in No reinforcement
centrally two layers at required.
top & bottom
3 Finish Floor finish As/Architectural As/Architectural As/ArchitecturalDetail
Detail Detail

Type I: Plant Buildings such as Sub-Stations, Control Rooms, Pump Houses,


Utility Compressor Houses, Parking Areas, Stores, Porches.
Type II: Ware Houses, Workshops, Cement Godowns, Fire Stations, Process
Compressor Houses.
Type III: Non Plant Buildings (viz. Administration, Laboratory, Canteen, Time
Office, Gate House, Training Centre, Guest House, Residential
buildings).

3.6 SPECIAL CONSIDERATIONS FOR CONCRETE STRUCTURES


3.6.1 General
a) All buildings, structures, foundations, machine/equipment foundations, liquid
retaining/storage structures, pipe/cable trenches, pits etc. shall be designed based
on referenced BIS Codes in general and other relevant BIS Codes as applicable. It
shall be ensured that the skin temperature of concrete at no time exceeds 800 C.
b) All Concrete structures exposed to atmosphere (including fireproofed surfaces) shall
be painted as per painting specifications.
c) High strength deformed steel bars of grade Fe 500 conforming to IS: 1786 shall be
used for all structures. 18 guage SWG wire shall be used for binding reinforcement
bars.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 13 of 40
Padur.

d) The minimum grade of reinforced cement concrete to be used for different


structures and foundations shall be M30. From Durability considerations the
minimum cement content and maximum water-cement ratio shall be as per the table
below. However, the maximum cement content shall not exceed 450 kg/m3.

TABLE-2 MINIMUM CEMENT CONTENT AND MAXIMUM WATERCEMENT RATIO


FOR DURABILITY
Exposure Plain concrete Reinforced concrete Remarks
condition
severe Grade of Minimum Maximum Grade of Minimum Maximum
Concrete cement free water- Concrete cement free water-
content cement content cement
(kg/m3) ratio (kg/m3) ratio
M20 250 0.5 M30 320 0.45

Note : The following cements shall be used for construction:

i) Grade 53 / 43 ordinary Portland Cement conforming to IS 12269 & IS 8112 /

Portland Pozzolana cement (fly ash based)I conforming to S:1489 (Part-1)

ii) Sulphate Resistance Cement conforming to IS 12330 shall be used for structures in
process areas only.

e) All structures shall be of frame-type construction. Detailing shall be as per


provisions of IS: 13920.

f) Unless otherwise specified elsewhere in this document only Limit state method as
per IS: 456 shall be followed in the design.

g) All machine/equipment foundations, cable/pipe trenches shall be of RCC


construction only. Cable/pipe trenches shall be suitably sloped and adequate
provision shall be made for draining out of accumulated water.

h) Cable and pipe trenches shall be provided with precast (300mm wide) covers,
adequately designed for the anticipated traffic movement (Cranes/Hydra etc.).
Trenches of different category of loading shall be clearly identified for design. The
covers shall, however, be designed for a minimum uniformly distributed load of
2.0T/m /concentrated load of 5MT at worst location. The walls of cable trenches
shall be designed to resist a minimum surcharge load of 1.0 T/m².Seating surface of
the slab shall be at least 100mm wide with structural ISA 50 x 50 x 6 edge
protection embedded throughout the length of trench.

i) Foundations placed at varied depths shall be designed considering bearing capacity


at that particular level with due consideration of an uplift/subsoil water table.

j) If the specified design depth of ground water table so warrants all underground pits,
tunnels, basements, cable trenches etc. shall be provided with leak-proof treatment.

k) Intermixing of different grades of concrete in the same structure/structural element


(excepting columns, walls, etc. with element extending in sub and super structure
both) shall not be accepted.
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 14 of 40
Padur.

l) Intermixing of different grades of steel (main reinforcement) in the same structure


shall not be accepted.

m) RCC pits, tanks etc. for storage of corrosive liquids shall be provided with
suitable anticorrosive treatment.

n) All liquid retaining/storage RCC structures shall be leak-proof and designed as


uncracked section as per IS: 3370 and shall be designed assuming liquid up to the
full height of the wall irrespective of provision of any over flow arrangement. Parts of
such structures not coming in contact with liquid may be designed in conformance
to IS: 456 except ribs of beams of suspended floor slabs & counter forts of walls
(located on the side remote from the liquid) and the roof which shall be designed as
uncracked section. No increase in permissible stresses in concrete and
reinforcement shall be allowed under wind or seismic conditions for such structures.

o) PVC water bars (230mm wide, 5mm thick) shall be provided at each construction
joint of all liquid retaining structures. Water bars shall be embedded in the concrete
as per manufacturers’ recommendations. All pipes embedded in concrete elements
shall be provided with welded puddle flange with 8mm thick plate and diameter as
“pipe dia + 200mm”. Pipes shall be placed in position prior to concreting. The
sequence of construction shall be clearly shown on the drawing.

p) The walls and slabs of liquid retaining/storage structures shall be provided with
reinforcement on both faces.

q) Provision of pressure relief valves or similar pressure relieving devices shall not be
permitted in underground liquid retaining/storage RCC structures.

r) Primary framing members and/or any other member which remains constantly in
contact with water or enclosed water vapor shall be designed as uncracked section.

s) RCC storage/process tanks located above floor or roof shall not rest directly on
slab/beam but shall have independent supporting structures which in turn shall rest
on (primary or secondary) beams and/or columns.

t) Liquid storage structures shall be tested for its water-tightness/leak-proofness as


detailed hereunder:

i) The structure shall be tested strictly in accordance with IS: 3370 for water-
tightness. The total drop in water surface level shall not exceed 6mm in 24
hours in case of covered reservoirs and 12mm in 24 hours in case of open
reservoirs.

ii) If the test proves structure to be defective the same shall be repaired. The
repaired structure shall again be tested as stated above. If the structure is still
found unsatisfactory it shall be dismantled and rebuilt.

iii) Testing after construction and remedial treatments shall conform to provisions of
IS: 6494.

u) Backfilling around underground liquid storage structures shall be allowed only after
successful hydro-testing and when so certified by the Owner/Owner’s
representative’s at site.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 15 of 40
Padur.

3.6.2 Minimum Cover to Main Reinforcement

Clear cover shall be considered over links / stirrups, unless otherwise specified the
minimum clear cover provided to super structures for R.C.C. works for slab and beam
shall be 30 mm. For column and pedestals the minimum cover from longitudinal
reinforcement shall be 40 mm. The clear cover for foundations and substructure shall
be greater of as recommend in IS: 456 (latest) or required as per the geotechnical
recommendations. Clear cover for liquid retaining structures shall be minimum 30 mm
or as required as per the geotechnical recommendations.

3.6.3 Minimum Thickness of Structural Concrete Elements

The following minimum thickness shall be followed:

- Footings (All types I With without beams) 300mm


(Note: Tapered footings shall not have thickness less than
150mm at the edges. Minimum average thickness shall
not be less than 300mm)

- Slab thickness in Raft foundations


with beam & slab construction 150mm

- Pile Cap 500mm

- Basement
- A) Wall 150mm
-
- B ) Base Slab With Beams 200mm
-
- C ) Base slab without Beams 300mm

- Floor/Roof Slab, Walkway, Canopy Slab 150mm

- Cable/Pipe Trench/Launder Walls & Base Slab 125mm

- Parapet 100mm

- Louvres / Fin. 100mm

- Pre-cast Trench Cover/Floor Slab

- Louvre ( in contact with liquid ) 125mm

- Liquid Retaning / Leak Proof Structure

A) Walls 150mm
B) Base slab with beams 200mm
C) Base slab without beams 300mm

- Underground Pit
- A) walls 150mm
- B) Base Slab with beams 200mm
- C) Base slab without beams 300mm

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 16 of 40
Padur.

3.6.4 Minimum Cover to Foundation Bolts

Minimum distance from the centerline of foundation/anchor bolt to edge of pedestal


shall be the maximum of the following:

i) Clear distance from the edge of the base plate/base frame to the outer edge
of the pedestal shall be minimum 50mm.

ii) Clear distance from the face of pocket to the outer edge of the pedestal shall be
100mm.

iii) Clear distance from the edge of the sleeve or anchor plate to the edge of
pedestal shall be 100mm.

3.6.5 Minimum Height of Pedestals

The minimum projection of outdoor/indoor pedestals supporting equipment/structures


shall be 300mm and 150mm respectively above the high point of pavement/finished
grade level/finished floor level, whichever is higher. The maximum projection of
pedestals for staircase/ladder shall be 200mm.

3.6.6 Concrete Mix

a) Reinforced Cement Concrete (RCC)

Unless otherwise noted, reinforced concrete conforming to IS: 456 (Grade as


specified in clause 3.6.1) shall be used using 20mm and down size graded crushed
stone aggregate.

b) Lean Concrete

Mud mat of minimum 75mm thickness of lean concrete mix 1:5:10 (by weight, using
40mm and down size grade crushed stone aggregate) shall be provided under all
RCC foundations except under base slabs of liquid retaining structures for which the
mix shall be 1:3:6 (by weight) and minimum thickness of mud mat shall be 100mm.
Mud mat shall extend 75mm on all sides beyond the edges of base slabs in case of
liquid retaining/storage structures and 50mm in case of other foundations. The
exposed surface of mud mat layer in case of liquid retaining/storage structure shall
be finished smooth. Lean concrete of grade1:5:10 (by weight) shall be used as filler
material wherever loose sub grade exists by removing the loose soil/fill.

c) Plain Cement Concrete (PCC)

Plain cement concrete mud mat of grade M20 (by weight) of minimum 150mm
thickness (using 40mm and down size graded crushed stone aggregate) shall be
provided under all masonry wall foundations.

Plain cement concrete of grade M 20 (by weight) of minimum 40mm thickness


(using 10mm & down size graded aggregates) shall be provided as damp proof
course at plinth level of all masonry walls.

Making-up of levels for placing the foundation at a shallower depth from the
NGL/FGL (from that as specified in the Geo-technical recommendations) by
means of filling of lean concrete is not acceptable.
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 17 of 40
Padur.

3.6.7 Grouting & Minimum Grout Thickness

The minimum thickness of grout shall be 25 mm. All anchor bolt sleeves/pockets and
spaces under column bases, shoe plates etc. shall be grouted with free flow, non-shrink
(premix type) grout with 28-day minimum cube crushing strength of 40N/mm2. Ordinary
cement sand (1:2) grout shall only be used under the base plates of crossover, short
pipe supports (not exceeding 1.5 m height) and small operating platforms (not
exceeding 2.0m in height) not supporting any equipment. Neat cement shall not be
used for grouting under any condition.

3.6.8 Movement Joints

Expansion and/or separation joints in non-suspended ground floor slab shall be filled
with sand for the full depth of slab except the top 12mm which shall be filled up with
approved two part liquid polysulphide sealing compound conforming to IS: 12118.
Joints in basement slabs shall be made leak proof by providing PVC water stops.

Joints in the super-structure shall be provided by means of gap between two


consecutive structural members. The gap shall be based on the design requirements
and shall be treated to a minimum as under:

a) When the vibrating equipment is separately supported on a structure, a clear air


gap shall be provided between the vibrating equipment supporting structure and
the surrounding floor with provision of suitable moulding/kerb to stop any
leakage/overflow of any floor wash to the next lower floor.

b) In normal floors, expansion and/or separation joints shall be covered both on top
and bottom with 3mm thick Aluminium sheet fixed on both sides of the joint with
brass screws. Provision of movement on one side shall be kept with proper
slotted holes. Similar cover plates shall be provided for all exterior columns on
both interior and exterior faces. The edges of these plates shall be properly
chamfered. Bitumen impregnated fibre board (as per IS:1838) shall be used
between the gap of the two members on either side of the joint for the full depth
in such movement joints. The top 12mm depth shall be filled up with two part
liquid polysulphide sealing compound (as per IS:12118).

c) For all liquid retaining structures expansion joints shall be filled up with non-
absorbent compressible sheet/bitumen impregnated fibre board (as per IS:1838)
except the top 12mm depth on the water faces which shall be filled with two part
liquid polysulphide sealant (as per IS:12118). In case of contraction and/or
construction joints, such polysulphide sealant shall be used for 12mm depth on
the water faces after forming suitable grooves in concrete. PVC water bars
230x5mm thick shall be invariably used at suitable location in all types of joints
in liquid retaining structures.

3.7 SPECIAL CONSIDERATIONS FOR STEEL STRUCTURES

3.7.1 General

Structural steel work shall include the following structures in general, but not limited to:

- Steel buildings/open structures


- Guide structures (for stacks, towers/columns)
- Platforms & walkways
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 18 of 40
Padur.

- Ladders, staircases & hand railing


- Pipe racks/pipe supports/cable racks
- monorail

Design, fabrication and erection of the above works shall be carried out in accordance
with the referenced BIS Codes in general and other relevant BIS codes as applicable to
the specific structure.
Basic consideration of structural frame work shall primarily be stability, ease of
fabrication/erection and overall economy satisfying relevant Indian Standard Codes of
Practice. Simple and fully rigid design as per IS:800 shall be used. Where fully rigid
joints are adopted they shall generally be confined to the major axis of the column
member.
Structural elements continuously exposed to temperatures above 2000 C shall be
designed for reduced stress as per Table 4 of IS:6533 (Part 2). The expected
temperature of steel components shall not be allowed to exceed 4000 C.

Where required by OISD-STD-164 norms structural steel members shall be fire-proofed


by concrete/shotcreting. Concreting shall be for structural members and shotcreting for
equipment skirts.

Steel staircases shall have channels provided as stringers with minimum clear width of
750mm and slope of 41 degree. The vertical height between successive landings shall
not be less than 2.6 m nor exceed 4.0 meters. Treads shall be minimum 230mm wide
made of grating (with suitable nosing) spaced equally so as to restrict the rise to
maximum 200mm.

Hand rails, 1000mm high, shall be provided to all walkways, platforms, staircases. Toe
plate (100mmx5mm) shall be provided for all handrailing (except for staircases).
Spacing of uprights shall be 1500mm (maximum). Two types of handrailing shall be
provided.

a) For walkways, platforms (except platform around circular vessels), staircases:


Top rail, mid-rail and upright shall be 32mm dia (NB) MS tubes.
b) For platforms around circular vessels: Top rail shall be 32mm dia (NB) MS tubes
but mid-rail and upright shall be of structural steel.

Welded connections shall be adopted as far as practicable except for cases where
bolted connections are required viz. (Galvanized) electrical switchyard structures and
transmission towers. Structural connections shall have minimum two bolts of 16mm dia.
unless otherwise limited by the size of members.

Minimum two nuts shall be used for all anchor bolts.

Steel Grade

Structural steel shall be of yield stress of 250 MPa conforming to grade A of IS:2062.
Tubular steel shall conform to Yst 240 of IS:1161.

3.7.2 Permissible Stresses

- Permissible stresses in structural members shall be as specified in:


IS: 800 Hot rolled sections (excluding switchyard structures).

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 19 of 40
Padur.

IS: 801 Cold formed light gauge sections


IS: 802 Switchyard structures
IS: 806 Tubular structures

- Permissible stresses in bolts shall be as specified in:

IS: 800 Hot rolled sections


IS: 801 Cold formed light gauge sections.
IS: 802 Switchyard structures.

- Permissible stresses in welds shall be as specified in:

IS: 801 Cold formed light gauge sections.


IS: 816 Hot rolled sections

3.7.3 Limiting Deflection

a) The limiting permissible vertical deflection for structural steel members shall be as
specified below:

- Gantry girder for electric overhead crane


(Capacity upto 50T) : L/750

- Gantry girder for electric over head crane


(Capacity over 50T) : L/1000

- Gantry girder for manually operated crane : L/500

- Girder/beam for supporting dynamic equipment/hoist : L/450

- Grating/Chequered plate : L/200 or 6mm


whichever is
minimum.
- Purlins supporting any type of roofing
material under (dead load+live load)
or (dead load+wind load) conditions : L/200

- Other structures/structural components : As specified in


BIS Codes
Where 'L' represents the span.

b) The limiting permissible horizontal deflection for multi storeyed steel


structure/building shall be Height/325.
c) The limiting permissible horizontal deflection for structures supporting two-phase
fluid flow piping shall be limited to 25mm or H/325 (H is the height of support above
the pedestal top), whichever is lower.

3.7.4 Design Criteria

i) Basic consideration of structural frame work shall primarily be stability satisfying


relevant Indian Standard Codes of Practice and specifications given herein.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 20 of 40
Padur.

Simple and fully rigid design as per IS:800 shall be used. Where fully rigid joints
are adopted they shall be confined to the major axis of the column member.

ii) Where required by OISD-STD-164 norms structural steel members shall be


fireproofed. All such structural steel members shall be provided with one coat of
primer compatible with fire proofing material.

iv) All steel staircases shall have channels (minimum size MC150) provided as
stringers with minimum clear width of 750mm and slope of 41 degrees. The
vertical height between successive landings shall not exceed 4.0 metres. Treads
shall be minimum 230mm wide made of grating (with suitable nosing) spaced
equally so as to restrict the rise to maximum 200mm.

v) Ladders shall be provided with safety cages when the top of the ladder is more
than 4.5m above the landing level. Safety cages shall start 2.5 metres above the
lower landing level. Ladders shall be of 450mm clear width with 20mm diameter
MS rungs spaced at 300mm (maximum). Ladders shall preferably be placed
vertical. In no case shall the angle with the vertical exceed five degrees (bottom
of the ladder to be farther from the top to provide a positive slope).

vi) Hand rails, 1000mm high, shall be provided to all walkways, platforms,
staircases. Toe plate (100mmx5mm) shall be provided for all hand railing
(except for staircases). Spacing of uprights shall be 1500mm (maximum). Two
types of hand railing shall be provided.

a) For walkways, platforms (except platform supported on vessels), and


staircases:

Top rail, mid rail and upright shall be 32 (M) NB galvanized MS tubes.

b) For platforms supported on vessels:

Top rail shall be 32 (M) NB galvanized MS tubes but mid rail (flat 50x6)
and upright (angle 50x50x6) shall be of structural steel.

vii) Electro-forged hot dipped galvanized welded MS Gratings shall be minimum


25mm deep. The maximum size of voids in the grating shall be limited to 30mm
x 55mm.The minimum thickness of galvanizing shall be 120 microns.

Gratings shall be hot dip galvanized in accordance with IS:2629 and tested as
2
per IS:2633 and IS:6745. Quantity of zinc coating shall be minimum 900 g/m of
surface area (0.12mm uniform thickness).

It shall be mandatory that a prototype of the grating fulfilling the following is


demonstrated satisfactorily to the Owner/owner’s site representative prior to
placement of bulk order(s):
a) above defined requirements.

b) for gratings manufactured using electro-forging process, the unfused


joints are not in excess of 5% of the total joints. If unfused joints found are
in excess of 5%, the prototype shall stand rejected and a fresh prototype
shall be prepared with revised welding parameters clearing the
requirement of unfused joints limited to 5% of the total joints.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 21 of 40
Padur.

c) the projection of secondary member above the main member is not more
than 1.5mm.

d) the unfused 5% joints of b) above are welded by SMAW/GMAW process.

e) the joints are able to sustain a minimum pull out load of 1.2 times the
allowable shear capacity of the secondary member.

f) gratings made by electro-forge process shall be subjected to a third party


inspection as per Owner/owner’s representative approval.

viii) Unless otherwise permitted in writing by Owner/owner’s representative only


welded connections shall be adopted. All permanent and erection connections
shall have at least two 20mm diameter and 16mm diameter bolts respectively.
ix) All connections shall be designed for full moment carrying capacity of the
connecting members together with 60% full shear carrying capacity for sections
with depth 200mm and above and 50% full shear carrying capacity for sections
with depth less than 200mm or for the actual design forces, whichever is more.

x) All fabricated structures (except electrical switchyard structures and


transmission towers) shall be given one shop coat of primer compatible with the
final paint system. The paint system shall conform to the painting specification.

xi) Minimum two nuts shall be used for all anchor bolts.

xii) Gusset plates of different thicknesses shall not be used in the same truss or
girders. Gusset plates for all bracing shall be of same thickness as that used for
truss/girders unless a higher thickness is required by design.

xiii) If so required by piping support detail, minimum 20mm diameter plain round MS
rod shall be welded on the top flange for full length on all transverse beams and
at locations where pipes are supported on longitudinal beams of pipe racks, pipe
supporting structural members.

3.7.5 Minimum Thickness

3.7.5.1 The minimum thickness of various structural components (Hot rolled sections)
shall be as given:

General Construction

Trusses, purlins, side girts & bracings 6mm

Columns, beams 7mm

Gussets in trusses & girders

i) Upto and including 12m span 8mm

ii) Above 12m span 10mm

Stiffeners 8mm

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 22 of 40
Padur.

Base plates 10mm

Chequered plate 6mm (on plain)

Grating 3mm

Insert plates 12mm

The minimum thickness of structural components (except gratings & chequered


plates), which are directly exposed to weather and inaccessible for repainting,
shall be 8mm.

Note: The minimum thickness for rolled beams and channels shall be the mean flange
thickness regardless of the web thickness.

3.7.5.2 The minimum thickness of tubes shall be as specified in IS:806.

3.7.5.3 Structural members exposed to marked corrosive action shall be increased in thickness
or otherwise suitably protected against corrosion.

3.8 SPECIAL CONSIDERATIONS FOR MASONRY WORKS

3.8.1 General

All masonry works shall be designed in accordance with the latest revision of
referenced BIS Codes in general and other relevant IS codes as applicable to the
specific structure. All external brick masonry walls shall be minimum 230mm thickness.
Compound wall shall be of Random Rubble Masonry.

3.8.2 Cement Mortar

All brick masonry work shall be constructed in cement sand mortar 1:5 for load bearing
walls and 1:6 cement sand mortar for non-load bearing walls except half brick partition
walls which shall be constructed in 1:4 cement sand mortar with two numbers of 6mm
diameter MS bars provided at every fourth course properly anchored with cross walls or
pillars. Compound wall in random rubble masonry shall be constructed in Cement sand
mortar 1:6.

3.8.3 Fire Walls

All masonry fire walls shall be of minimum 345 thickness.

4.0 DESIGN REQUIREMENTS FOR SPECIFIC APPLICATIONS

4.1 PIPE RACK

For designing the pipe rack superstructure and foundation the following loads shall be
considered.

Vertical Loading

At each tier a uniformly distributed load (udl) shall be placed. The magnitude of this udl
per unit length of the span shall be calculated as per the gross actual loading from
pipes at that tier level, including the actual weight of empty pipe, the weight of content
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 23 of 40
Padur.

and insulation, if any, divided by the actual extent of the span covered by these pipes. A
3
minimum density as 2600N/m shall be considered for insulation. The material content
shall be taken as one-third volume of pipe filled with water for gas/steam carrying pipes.
2
The minimum loading for any tier shall not be less than 1.25kN/m . If the calculated
2
loading is higher than 1.25kN/m , this shall be rounded off to the next higher multiple of
2
0.25 (ie 1.50, 1.75, 2.0kN/m ). This udl shall be assumed to be spread over the entire
span.

Vertical loads of flare pipes shall be taken as one-third full of water for Process Unit
piping and one-sixth full for Off site piping.

Friction Force (Longitudinal & Transverse)

Where the pipes are of similar diameter and service conditions, the friction force at each
tier on every portal both in longitudinal and transverse directions shall be 10% of the
design vertical loading of the pipes for four or more pipes supported on a tier, and 30%
of the design vertical loading of the pipes for single to three pipes supported on a tier.
Longitudinal friction force shall be considered as uniformly distributed over the entire
span of the beam at each tier and transverse friction force shall be considered as a
concentrated load at each tier level. Friction force on T-supports and trestles shall be
taken as 30% of the vertical loading in longitudinal direction and 10% of vertical loading
in transverse direction, both acting simultaneously, and/or vice versa.

For two-phase fluid flow/transfer lines the frictional force shall be minimum 50% of the
weight of pipe including contents and insulation, acting simultaneously in transverse
and longitudinal directions.

Anchor and Guide Force (Thermal load)

a) Longitudinal → As per piping inputs


b) Transverse → As per piping inputs

Wind Force

Transverse wind loading shall be calculated depending on the width of the Pipe Rack
as follows:

a) Basic wind pressure shall be considered as per IS: 875.

b) To calculate wind load in transverse direction of piperack, a projected height of


1.25m/1.5m/2.0m shall be considered on all tiers irrespective of height between two
tiers of rack widths of 4m/6m/8m and 10m respectively. For piperacks of widths
greater than 10m, the above projected height shall be taken as 0.8[diameter of
largest pipe including insulation (m)] + tan 10°[width of rack (m)]. However, this shall
not exceed the height between consecutive tiers.

c) For flare header or any other line supported on extended leg of piperack, the wind
force shall be considered separately.

Loading on Longitudinal Beams

Unless otherwise required from pipe support loadings, the longitudinal beams
connecting portal columns shall be sufficiently strong to sustain a minimum of 25% of
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 24 of 40
Padur.

the load on transverse beams. This total load shall be placed as two equal concentrated
loads acting at 1/3 rd span. This load shall be in addition to the piping loads transferred
from the intermediate beams. Other longitudinal axial forces coming on it from the
design of the supporting system shall also be simultaneously taken into account in the
design of the longitudinal beam. Friction & Anchor Forces as per piping requirements
shall also be considered in the design. If beams support monorails, all such loads shall
also be considered to be acting simultaneously along with other loads mentioned
above.

Cable Tray and Walkway Loads

The estimated actual load from electrical, instrumentation trays shall be considered at
the specified locations, together with walkways, if provided.

Earthquake Force

Seismic forces shall be based on site specific seismic spectra given in Doc. No. 6979-
00-16-54-001 (section 3.9) and the provisions of IS: 1893.

4.2 RCC / STEEL CHIMNEYS

RCC / Steel chimneys shall be designed as per the requirements of IS:4998, IS:6533
and Standard specification no. 6-68-0053.

4.3 MACHINE FOUNDATIONS

Machine foundations shall satisfy the following requirements:

a) The minimum grade of concrete to be used shall be as per clause 3.2 & 3.6.

b) Minimum reinforcement as per requirements of IS:2974 shall be provided unless


required otherwise by design.

c) All units of the foundation system, except foundation raft shall be provided with
symmetric reinforcement on opposite faces, even if not required by design
considerations.

d) The soil stress below foundations under dead loads shall not exceed 80% of the
allowable soil bearing capacity, or safe load on pile, for static loading.

e) The combined center of gravity of the machine and foundation system shall, as
far as possible, pass through the center of area of the foundation raft or centroid
of the pile group. Where unavoidable, eccentricity shall be less than 5% for
block foundations and 3% for frame foundations.

f) Foundations shall be so designed that natural frequency of the foundation


system shall not resonate with the following:

i) Operating speed of the motor.


ii) Operating speed of the machine.
iii) 2 x Operating speed of the machine.
iv) Critical speed of the machine (for centrifugal machines).

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 25 of 40
Padur.

Natural frequency of the foundation shall preferably be + 20% away from the
above-mentioned frequencies. However, amplitudes of vibration of the
foundation block shall always be checked to be within permissible limits.

g) Amplitudes of vibration shall be less than values specified by the machine


manufacturer. If not specified, provision of IS:2974 shall be followed.
h) The foundation and its superstructure shall be separated from adjacent
foundations and platforms. Clear air gaps shall be provided in the superstructure
to avoid transmission of vibration to adjacent structures. Special note shall be
given on the drawing in this respect, and suitable details shown as required.

i) Foundations resting partly on rock and partly on soil shall preferably be avoided.
However, if unavoidable, the soil area shall be replaced by lean concrete (1:4:8).
However, Owner/owner’s representative concurrence shall be obtained for such
cases.

j) Foundations shall not rest on previously backfilled or sensitive soils.

k) For frame foundations, base raft shall be cast in a single concreting operation. A
properly designed construction joint shall be provided between the base slab
and columns. The entire superstructure of columns and upper deck shall be cast
in a continuous concreting operation.

l) If height of the frame columns above raft level exceeds 8.0m, an additional
construction joint at the junction of columns/top-deck may be provided.

m) Block foundations shall be cast in a single concreting operation.

4.4 TANK FOUNDATIONS

Storage tanks up to 10.0 metres diameter, shall be supported on ring wall type of
foundations.

4.5 SUPPORTING ARRANGEMENTS FOR TRANSFER LINE

Structures supporting transfer lines and other two phase flow lines:

A list of piping with two-phase fluid flow, if any, shall be developed by the Contractor.
Pipe routing and structures supporting such lines shall be drawn. Only piping with
diameter more than 6" shall be considered critical and governed by this clause. Smaller
diameter piping shall be governed by relevant clauses for pipe rack.

4.5.1 Design loads

Horizontal force not less than 50% of the pipe weight (empty and contents) shall be
considered, acting simultaneously in two orthogonal directions (along the pipe and
across it) at that support.

4.5.2 Piping supported on Pipe racks

4.5.2.1 Pipe racks supporting two phase flow lines above 6" diameter shall have all portals and
longitudinal beams encased in structural grade concrete. Encasing shall be in all
shapes (excluding profile shapes) with a minimum 50mm cover over the largest
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 26 of 40
Padur.

dimension of the steel section. Minimum reinforcing steel as shrinkage/temperature


reinforcement shall be provided as welded wire fabric conforming to IS:1566 with mesh
size of 50mm x 50mm and wire thickness 3mm.

4.5.2.2 Between all successive portals supporting such lines, plan bracings shall be provided.
These shall be provided at least at their supporting elevation (bottom level in case of a
line with spring hangers). Longitudinal bays connecting portals shall be braced
vertically from supporting level downwards, at least in one bay.

4.5.2.3 If the level difference between two phase fluid piping support and normal pipe supporting
tier of pipe rack is 3 metres or more, additional vertical bracing shall be provided above
the pipe rack level in all such transverse frames.

4.5.3 Isolated trestles

Vertical bracing shall be provided on all faces and horizontal bracing at least at pipe
support level. All members including bracing shall be encased in concrete for the entire
height of the trestles and the fundamental frequency of the structure shall be isolated
from the most critical range which is 4 to7 Hz. The weight of pipe shall not be
considered for dynamic analysis. Encasing details shall be same as mentioned in
clause 4.6.2.1.

4.5.4 Supports from technological structures

Structural members supporting transfer lines from technological structures shall be


adequately braced. Floors shall have plan bracing to effectively transfer horizontal
forces to vertical frames of the structure.

Supports on/from cantilevers shall be avoided. However, if unavoidable, adequate plan


bracing shall be provided.

4.5.5 Permissible stresses

No increase in permissible stresses shall be allowed except in load combination with


wind and seismic, as permitted by IS codes.

4.5.6 Permissible deflections

The deflection at the top of the structure, with all the horizontal forces acting together,
shall be limited to 25mm or height/325, whichever is less.

5.0 MATERIAL REQUIREMENTS

5.1 General

5.1.1 The minimum requirements of various materials to be used in Civil and Structural works
are as below:

5.2 Water

5.2.1 Water used in construction for all civil & structural works shall be clean and free from
injurious amounts of oil, acids, alkalies, organic matters or other harmful substances
which may be deleterious to concrete, masonry or steel. The pH value of water sample

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 27 of 40
Padur.

shall be not less than 6. Potable water will be considered satisfactory. All requirements
of IS:456, have to be met.

5.2.2 Tests on water samples shall be carried out in accordance with IS:3025 and these shall
fulfill all the guidelines and requirements given in IS:456.
5.2.3 Water for curing shall be of the same quality as used for concreting and masonry works.

5.3 Aggregate (For Concrete)

5.3.1 General

Coarse and fine aggregates for Civil and Structural Works shall conform in all respects
to IS:383 (Specification for coarse and fine aggregates from natural sources for
concrete). Aggregates shall be obtained from an approved source known to produce
the same satisfactorily. Aggregates shall consist of naturally occurring (crushed or
uncrushed) stones, gravel and sand or a combination thereof. These shall be
chemically inert, hard, strong, dense durable, clean and free from veins, adherent
coatings, injurious amounts of alkalies, vegetable matter and other deleterious
substances such as iron pyrites, coal, lignite, mica, shale, sea shells etc.

Aggregates which may chemically react with alkalies of cement or might cause
corrosion of the reinforcement shall not be used.

The maximum quantities of deleterious materials in the aggregates as determined in


accordance with IS:2386 - Part II (Methods of Test for aggregates for concrete), shall
not exceed the limits defined in IS:383.

5.3.2 Coarse Aggregates

Coarse aggregates are the aggregates, which are retained on 4.75mm IS Sieve. It shall
have a specific gravity not less than 2.6 (saturated surface dry basis).

These may be obtained from crushed or uncrushed gravel or stone and may be
supplied as single sized or graded. The grading of the aggregates shall be as per
IS:383 or as required by the mix design, to obtain densest possible concrete.

5.3.3 Fine Aggregates

Fine aggregates are the aggregates which pass through 4.75mm IS sieve but not more
than ten percent (10%) pass through 150 micron IS sieve. These shall comply with the
requirements of grading zones I, II and III of IS:383. Fine aggregates conforming to
grade zone IV shall not be used for reinforced concrete works.
Fine aggregates shall consist of material resulting from natural disintegration of rock
and which has been deposited by streams or glacial agencies, or crushed stone sand or
gravel sand. Sand from sea shores, creeks or river banks affected by tides, shall not be
used for filling or concrete works.

5.3.4 Sampling and Testing


The Contractor shall carry out all tests including mix designs of concrete, at the start of
work as well as during any stage of construction as per the requirement. Tests shall be
carried out in accordance with IS:516-Methods of test for strength of concrete and
IS:2386-Methods of test for aggregates for concrete. The method of sampling shall be
in accordance with the requirements given in IS:2430.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 28 of 40
Padur.

5.3.5 Storage of Aggregates

Storage of all types of aggregates at the site of work shall be as specified in IS: 4082.
Aggregates shall in no case be stored near excavated earth or directly over ground
surface.
Fine aggregates delivered at the site in wet condition or becoming wet due to rain or
any other means, shall not be used for at least 24 hours. For the use of such
aggregates the contractor shall adjust the water content in accordance with IS:2386 to
achieve the desired mix.

5.4 Sand (For Masonry & Filling)

5.4.1 Sand for Masonry Mortars

The sand shall consist of natural sand, crushed stone sand or crushed gravel sand or a
combination of any of these. The sand shall be hard, durable, clean and free from
adherent coatings and organic matter and shall not contain the amount of clay, silt and
fine dust more than specified in IS:2116

The sand shall not contain any harmful impurities such as iron pyrites, alkalis, salts,
coal or other organic impurities, mica, shale or similar laminated materials, soft
fragments, sea shells in such form or in such quantities as to affect adversely the

hardening, strength or durability of the mortar.

The maximum quantities of clay, fine silt, fine dust and organic impurities in the sand,
when tested in accordance with IS:2386, shall not be more than 5% by mass in natural
sand, or crushed gravel sand or crushed stone sand. For organic impurities, when
determined in accordance with IS:2386, colour of the liquid shall be lighter than that
indicated by the standard solution specified in IS:2386.

5.4.2 Grading of Sand

The particle size grading of sand for use in mortars shall be within the limits as specified
below:
Grading Of Sand For Use In Masonry Mortars

IS Sieve Designation IS:460 Percentage Passing Reference To Method


(Part I) By Mass
4.75 mm 100
2.36 mm 90 to 100
1.18 mm 70 to 100
IS:2386 (Part-I)
600microns 40 to 100
300 microns 5 to 70
150 microns 5 to 15

In case of sand whose grading falls outside the specified limits due to excess or
deficiency of coarse or fine particles, this shall be processed to comply with the
standard by screening through a suitably sized sieve and/or blending with required
quantities of suitable sizes of natural sand particles or crushed stone screening which
are by themselves unsuitable. The various sizes of particles of which the sand is
composed shall be uniformly distributed throughout the mass.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 29 of 40
Padur.

5.4.3 Sampling and Testing

The method of sampling shall be in accordance with IS:2430. The amount of material
required for each test shall be as specified in relevant parts of IS:2386. All tests shall be
carried out in accordance with the relevant parts of IS:2386.

If further confirmation as to the satisfactory nature of the material is required,


compressive test on cement mortar cubes (1:6) may be made in accordance with
IS:2250 using the supplied material in place of standard sand and the strength value so
obtained shall be compared with that of another mortar made with a sand of acceptable
and comparable quality.

5.4.4 Sand for Filling

Sand for filling shall meet the requirements of IS:383 and shall be natural sand, hard,
strong, free from any organic and deleterious materials. Sand obtained from sea
shores, creeks or river banks affected by tides, shall not be used for filling. Fine
aggregates suitable for concreting works shall be suitable for filling also. No sand below
grading zone-III as per IS:383 shall be allowed for filling.

5.5 Cement
2
Unless otherwise specifically called for, cement for RCC and PCC/lean concrete works
shall be one of the following:

53 grade ordinary Portland cement IS:12269

43 grade ordinary Portland cement IS:8112

Portland slag cement IS:455

Portland Pozzolana cement (fly ash based) IS:1489 (Part-1)

Portland Pozzolana cement (calcined clay based) IS:1489 (Part-2)

Sulphate resisting Portland cement IS:12330

High alumina cement IS:6452

For masonry applications the use of Masonry cement (conforming to IS:3466) can be
made.

5.6 Steel

5.6.1 General

All steel bars, sections, plates, and other miscellaneous steel materials, etc. shall be
free from loose mill scales, rust as well as oil, mud, paint or other coatings. The
materials, construction specifications such as dimensions, shape, weight, tolerances,
testing etc, for all materials covered under this section, shall conform to respective BIS
codes.

2 The type of cement selected shall be appropriate for the intended use.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 30 of 40
Padur.

5.6.2 Structural Steel

Structural steel sections shall conform to following BIS codes:

Steel tubes for structural purposes IS:1161

Mild Steel Tubes, tubular and other wrought steel fittings IS:1239

Steel for general structural purposes (Grade A). IS:2062

Hollow steel sections for structural use. IS:4923

5.6.3 Miscellaneous Steel Materials

Miscellaneous steel materials shall conform to the following BIS codes:

Expanded Metal Steel Sheets for General purposes. IS:412

Specification for mild steel and medium tensile


steel bars and hard drawn steel wire for concrete
reinforcement (Grade I)
(For mild steel bars of anchor bolts, rungs, metal inserts,
grating etc.) IS:432

Hexagonal head bolts, screws & nuts of product Grade C. IS:1363

Cold formed light gauge structural steel sections. IS:811

Technical supply conditions for threaded steel fasteners. IS:1367

Plain washers IS:2016

Steel wire ropes for general engineering purposes IS:2266

Thimbles for wire ropes. IS:2315

Bulldog grips. IS:2361


Mild Steel Tubes, tubular and other wrought steel
fillings. (For Hand rail tubular sections) IS:1239

Drop forged sockets for wire ropes for general


engineering purposes. IS:2485

Steel chequered plates. IS:3502


Hexagonal bolts and nuts (M42 to M150). IS:3138

5.6.4 Anchor Bolts

Material for Anchor Bolts such as MS bars, washers, nuts, pipe sleeves and plates etc.
shall be as per relevant BIS codes mentioned above under Clauses 5.6.3.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 31 of 40
Padur.

5.7 Brick

5.7.1 General

Bricks for masonry works shall conform to IS:1077 - Specification for common burnt
clay building bricks and shall be variety of class 5.0 (with minimum compressive
2
strength of 5.0 N/mm ). Physical requirements, quality, dimensions, tolerances etc. of
common burnt clay building bricks shall conform to the requirements of IS:1077.

Bricks shall be hand-moulded or machine-moulded and shall be made from suitable


soils. The bricks shall have smooth rectangular faces with sharp corners and shall be
well burnt, sound, hard, tough and uniform in colour. These shall be free from cracks,
chips, flaws, stone or humps of any kind.

Testing of the bricks shall be done as per IS:5454 and IS:3495. Water absorption shall
not be more than 20% by its dry weight when soaked in cold water for 24 hours.

Locally available bricks of non modular size (230x115x75mm) in place of bricks of


modular size (190x90x90mm) can be used in case the bricks satisfy the other
requirements of IS:1077 (corresponding class as defined above).

5.8 Stone

5.8.1 General

All Stones used for masonry works shall conform to the requirements of following BIS
codes.

Method of identification of natural building stones IS:1123

Recommendations for dimensions and workmanship


of natural building stones for masonry work IS:1127

Recommendations for dressing of natural building stones IS:1129

5.8.2 Quality of Stones

Stones shall be hard, dense, strong, sound, durable, clean and uniform in colour. They
shall also be free from veins, adherent coatings, injurious amounts of alkalies,
vegetable matters and other deleterious substances such as iron pyrites, coal, lignite,
mica, sea shells etc. As far as possible stones from one single quarry shall be used for
anyone work. The strength of stones should be adequate to carry the imposed load
and shall meet all the requirements of IS:1905, taking into account the appropriate
crushing strength of stone and type of the mortar used. The percentage of water
absorption, when tested in accordance with IS:1124, shall not exceed 5 percent.

The length of the stone shall not exceed 3 times the height. Width of stone on base
shall not be less than 150mm and in no case exceed 3/4 th thickness of the wall.
Height of the stone shall not be more than 300mm.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 32 of 40
Padur.

5.9 Admixtures

5.9.1 General Requirements for Admixtures

All concrete admixtures shall comply with the following Indian standards:
Specification for integral cement water proofing compounds. IS:2645

Specification for other admixtures for concrete. IS:9103

In case of non-availability of any IS code for testing and acceptability criteria,


relevant American, British or German Code shall be applicable.

No admixture shall impair the durability of the concrete nor combine with the ingredients
to form harmful compounds nor increase the risk of corrosion of reinforcement. Use of
admixtures shall not reduce the dry density of concrete. Once the proportion of
admixtures have been established, strict check shall be maintained not to alter the
proportions of ingredients and water-cement ratio of the Design Mix during execution.

The chloride contents in admixtures shall not exceed 2% by mass of the admixture or
0.03% by mass of the cement.

Admixtures which do not meet the requirements stipulated in this document shall not be
used.

5.9.2 Water Proofing Compounds


The permeability of the specimen with the admixture shall be less than half of the
permeability with a similar specimen without the use of these compounds. These
compounds shall be used in such proportion as recommended by manufacturer but in
no case it shall exceed 3% by weight of cement.
The initial setting time of the cement with the use of these compounds shall not be less
than 30 minutes and final setting time shall not be more than 10 hours. Tests shall be
carried out in accordance with IS:4031.
2
Compressive strength of the specimen at 3 days shall not be less than 160kg/cm nor
80% of the 3 days compressive strength of mortar cubes prepared with same cement
and sand only, whichever is higher. Similarly compressive strength at 7 days shall not
2
be less than 220 kg/cm nor less than 80% of the 7 days compressive strength
prepared with the same cement and sand only, whichever is higher. The test to
determine the compressive strength shall conform to IS:4031.

5.10 Water Bars (Water Stops)


5.10.1 PVC water bars shall be used in reinforced concrete construction of liquid retaining
structures or any other structure to safeguard them from hydrostatic pressure and water
leakage and any relative movement between two parts of the structure due to thermal
loading shrinkage or differential movement of foundations. These shall be preformed
and shall provide a permanent water tight seal along the entire joint in the poured
concrete structures. These shall also be flexible enough to withstand
deflection/displacements at joints arising due to variation of temperatures or settlement
of foundations.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 33 of 40
Padur.

5.10.2 Performance requirements of PVC water bars shall meet the requirements of
IS:12200.These shall be of an approved make and of ribbed/serrated/plane type with a
bulb at the centre. The thickness and width of water bars shall in no case be less than
5mm and 150mm respectively. However, for concrete sections greater than 300mm
thick, the width of water bars shall not be less than 230mm.

5.11 Bitumen/bituminous Materials

Bitumen to be used for various types of work shall meet all the requirements of relevant
BIS codes as given below:

Specification of Paving Bitumen. IS:73

Specification for bitumen mastic for flooring (Grade IV) IS:1195


Specification for Bitumen felts for water proofing and damp proofing. IS:1322

Specification for Bituminous compounds for water proofing


and caulking purposes. IS:1834

Specification for preformed fillers for expansion joint


in concrete pavements and structures. IS:1838

Specification for bitumen mastic for use in water proofing of roofs IS:3037

Specification for bitumen primer for use in water proofing


and damp proofing. IS:3384

Specification for Bitumen Mastic for Tanking and Damp proofing. IS:5871

Specification for Glass fibre base coal tar pitch & bitumen felts IS:7193

Code of practice for damp proofing using bitumen mastic IS:7198

Specification for bitumen Mastic, Anti Static and


electrically conducting grade. IS:8374

Tests and acceptable criteria shall be as per relevant BIS codes.

5.12 PVC Pipes

PVC Pipes shall conform to the requirements of IS:4985.

5.13 Wood/timber

5.13.1 Wood recommended for platforms of cold vessels or below cold vessels/ exchangers
shall be hard and shall be of group A, grade I, and shall have safe permissible stress of
7N/mm2 in compression, perpendicular to grains on outside location as per IS:883.
General characteristics like durability, treatability etc. shall conform to IS:883 and
IS:3629.

5.13.2 Timber required to be used for form work shall be fairly dry before use. It should
maintain its shape during the use and even when it comes into contact with moisture
from the concrete. Storage of Wood/Timber shall be as per the requirements of
IS:4082.
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 34 of 40
Padur.

For proper identification and selection of suitable timber for form work, following codes
shall be referred.

Classification of commercial timbers and their zonal distribution IS:399

Specification for ballies for general purposes IS:3337

Specification for Ply wood for concrete shuttering work IS:4990

5.14 Anti-termite Compounds

5.14.1 Chloropyrifos emulsifiable concentrates (1%) conforming to IS:8944 shall be used for
treatment of soil for protection of buildings against attack by subterranean termites.
5.15 Polysulphide Sealants

5.15.1 All Polysulphide Sealants shall conform to IS:12118. Test conditions and requirements
shall be as given in the above referred BIS code.

6.0 CONSTRUCTION REQUIREMENTS

6.1 Construction

6.1.1 All concrete works shall be carried out as per the provisions of IS:456, IS:3370, IS:2974
and other relevant BIS Codes. Concrete mix proportioning and design mix; sampling
and strength test of concrete, production and control of concrete, tolerances and
placing of reinforcement and for cover; transporting, placing, compacting and curing etc,
inspection and testing of structure (including requirement of non-destructive testing)
shall be as specified in IS:456.

6.1.2 Continuous concreting shall be done for structures supporting dynamic equipment as
per the provisions of IS:2974.

6.1.3 The damp proof course shall be laid in two layers of equal thickness and each layer
given two coats of hot bitumen on top (grade A90/S90 conforming to IS:73) at the rate
of 1.7 kg/m2. Dry sharp sand shall be sprinkled evenly over the top layer of bitumen
before hardening.

6.1.4 Form work and stripping of form work shall be as per the provisions of IS:456.

6.1.5 Assembly of reinforcement in RCC structures shall conform to IS:456.

6.1.6 Fabrication of all structural steel works shall be carried out as per the provisions of
IS:800/801/802/806 and other relevant BIS codes. Fabrication shall include cleaning,
straightening, cutting, bending, holding, bolting, welding, machining, painting, marking,
assembling, erecting, inspecting and testing etc. Welding procedure and welder
qualification shall be as per IS:800 and/or referenced BIS codes only.

6.1.7 Erection of all structural steel works including supply of plant & equipment, storing and
handling, setting out, field connections, field welding and security during erection shall
conform to IS:800/801/802/806.

6.1.8 All masonry works shall be carried out as per the provisions of IS:1597/2212/4326 and
other relevant BIS codes.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 35 of 40
Padur.

6.1.9 The limits of dimensional tolerances for all works shall be as given below:

For Plain and Reinforced Cement Concrete Structures:

(a) Deviation from specified dimensions - 6mm to +12mm


of cross section of columns and beams.

(b) Deviation from dimensions of footings


(see Note below)

(i) Dimensions in plan -12mm to +50mm

(ii) Eccentricity 0.02 times the width of the footing in


the direction of deviation but not more
than 50 mm.

(iii) Thickness +0.05 times the specified thickness.

Note: Tolerances apply to cast-in-situ concrete dimensions only, not to positioning of vertical
reinforcing steel or dowels.

(c) Deviation in length (major dimension of single unit)

up to 3m ± 6mm
3m to 4.5m ± 9mm
4.5m to 6m ±12mm
additional deviation for every subsequent 6m ± 6mm

(d) Deviation in straightness or bow (deviation from specified line) for a single or
continuous member), e.g, beam, column or slab edge.

Up to 3m 6mm
3m to 6m 9mm
6m to 12m 12mm
additional for every subsequent 6m 6mm

(e) Deviation in squareness shall be measured taking the longer of two adjacent
sides as the base line.

The shorter side shall not vary in its distance from a perpendicular so that the
difference between the greatest and shortest dimensions exceeds 6mm. For this
purpose, any error due to lack of straightness shall be ignored. Squareness
shall be checked with respect to the straight lines that are most nearly parallel
with the features being checked. When the nominal angle is other than 90
degrees, the included angle between check lines shall be varied accordingly.

(f) Deviation in twists shall be within a limit such that any corner shall not be more
than the limit given below from the plane containing other three corners:

Up to 600mm wide and up to 6m in length : 6mm

over 600mm wide and for any length : 12mm


Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 36 of 40
Padur.

(g) Maximum deviation in flatness from a 1.5m straight edge placed in any position
on a nominally plain surface shall not exceed 6mm.

For Steel Structures:

(a) Columns and tower-type structures

- Deviation of column axes at foundation top level with respect to true axes.

i) In longitudinal direction ±5mm

ii) In lateral direction ±5mm

- Deviation in the level of bearing surface of columns at foundation top

with respect to true level. ±5mm

- Out of plumb (verticality) of column axis from true vertical axis measured at top:

i) Up to and including 30m height ±H/1000 or ±25mm


whichever is less.

ii) Over 30m height ±H/1200 or ±35mm


whichever is less.

- Deviation in straightness in longitudinal & transverse planes of column at any


point along the height . ±H/1000 or ±10mm
whichever is less

- Difference in the erected positions of adjacent pairs of columns along length or


across width of building prior to connecting trusses/beams with respect to true
distance. ±5mm

- Deviation in any bearing or seating level with respect to true level


±5mm

- Deviation in difference in bearing levels of a member on adjacent pair of


columns both across & along the building ±5mm

Note 1) Tolerance specified for out-of-plumbness should be read in conjunction with


‘Deviation in straightness....’ & ‘Difference in the erected positions.....’.

Note 2) 'H' is the column height in mm.

Note 3) Tolerance limits as given under clause (a) above for steel structures are
applicable to concrete columns/pedestals also.

(b) Trusses

- Shift at the centre of span of top chord member with respect to the vertical plane
passing through the centre of bottom chord. ±1/250 of height of
truss in mm at center
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 37 of 40
Padur.

of span or ±15mm
whichever is less

- Lateral shift of top chord of truss at the centre of span from the vertical plane
passing through the centre of supports of the truss ±1/1500 of span of
truss in mm or ±10
mm whichever is less

- Lateral shift in location of truss from its true position. ±10mm

- Lateral shift in location of purlin from true position. ±5mm

- Deviation in difference of bearing levels of truss from the true level


±1/1200 of span of truss in
mm or 20mm whichever is
less.

(c) Gantry girders and Rails

- Shift in the centre line of crane rail with respect to centre line of web of gantry
girder ± [ web thickness of girder(mm) +2mm]
2
- Shift of alignment of crane rail (in plan) with respect to true axis of crane rail
at any point ± 5 mm

- Deviation in crane track gauge with respect to true gauge.

i) For track gauge upto and ± 5 mm


including 15 m

ii) For track gauge more than 15m ± [5+0.25(S-15)] subject to


maximum ±10mm, where S in
metres is true gauge.

- Deviation in the crane rail level at ±10 mm


any point from true level

- Difference in level between crane track rails (across the bay) at

i) Supports of gantry girders 15 mm

ii) Mid span of gantry girders 20 mm

- Relative shift of crane rail surfaces 2 mm


(at a joining) in plan and elevation

6.1.10 Construction of all other items of works shall conform to relevant Indian
Standards and sound engineering practices.

6.1.11 The Contractor shall be responsible for the complete safety pertaining to all construction
works.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 38 of 40
Padur.

7.0 SPECIFIC REQUIREMENTS

7.1 GENERAL

7.1.1 Apart from the conditions mentioned in the Design requirements given in the document,
the following shall be strictly adhered to.

7.1.2 Cable/pipe trenches & precast slab covers shall be designed to withstand the load of
hydra-crane. Seating surface of the slab shall be at least 100mm wide with structural
ISA50x50x6 edge protection embedded through out the length of the trench.

7.1.3 Only steel shuttering shall be used for civil construction.

7.1.4 Contractor shall make necessary arrangement for placing the anchor bolts in position
before concreting. Whenever there are more than four foundation bolts, these shall be
fixed by using template. In case bolts are not available at site at the time of casting of
foundation, proper pockets shall be left as per direction of the Engineer-in-charge.

7.1.5 Contractor to ensure isolation of structures/equipments with difference of temperature


for free expansion while providing interconnecting platform and for connection to the
stair structure.

7.1.6 Contractor shall ensure lateral stability by providing box/built up sections for columns
wherever it is not feasible to provide vertical bracing in either direction.

7.1.7 Sub-station building shall be provided with anti termite treatment.

7.1.8 All designs, detailing & construction shall strictly conform to enclosed standards,
specifications & drawings. However drawings marked “Issued for Information only” are
for only guidance to the contractor.

7.1.9 Contractor shall furnish the BULK MTO for cement and High Strength Deformed TMT
bars (diameter wise) and Structural Steel (section wise) within 45 days from the date of
receipt of LOI/TOI. It shall also be updated at 50% & 90% stages of engineering
progress and shall be submitted to owner/owner’s representative for information.

7.1.10 Sequence of construction is to be shown on the AFC drawings by indicating


construction joints wherever required.

7.1.11 The minimum diameter of reinforcement bar for slabs, beam stirrups and column ties
shall be 8 mm and for footing slabs and vertical walls it shall be 10 mm. The maximum
spacing of these bars shall be restricted to 300 mm c/c.

7.1.12 No equipment shall be directly supported on suspended floor slab. Suitable


arrangement of beams shall be provided underneath to support the equipments.

7.1.13 The foundation design shall be based on approved Geotechnical investigation


recommendations attached in the bid package.

7.1.14 Contractor shall depute his concerned Civil-Structural design engineer to owner/owner’s
representative review office as and when required for review of his documents. During
such reviews involving computer aided analysis/design/drafting of structures, the
Contractor shall make his own arrangement of Personal Computer (PC) in the form of
Lap-top in the premises of owner/owner’s representative review office. This is required
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 39 of 40
Padur.

to expeditiously resolve all the comments including those involving the use of PC by
Contractor in his submission. The Contractor shall ensure that these PC's are fully
operational along with necessary software already loaded including the
input/output/drawing files of the structures being reviewed. The Contractor shall revise
and re-submit the analysis/design and drawings as required during review.

7.2 PAINTING OF STRUCTURAL STEEL WORKS

7.2.1 Painting on structural steel shall be as per the specification enclosed elsewhere in the
bid document.

7.3 REVIEW OF DESIGN AND APPROVED FOR CONSTRUCTION (AFC) DRAWINGS

7.3.1 Complete structural design and AFC drawings of review category shall be got reviewed
by owner/owner’s representative in detail before taking up any construction activity at
the work site.

Submission of typical review category documents shall be taken up prior to


corresponding information category documents. Owner/owner’s representative
comments on typical review category documents shall be duly taken care in information
category documents as well before issuing them for construction.

For all information / records category design and drawings, requisite number of copies
(as mentioned elsewhere) shall be sent simultaneously to owner/owner’s representative
for information and to site for construction.

The contractor shall furnish the quantities of different grades of concrete, reinforcement
and structural steel in the respective AFC drawings. Bar Bending schedule for all
RCC drawings shall be submitted by the contractor along with the AFC drawings.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


JOB SPECIFICATION SECTION: C-3.10
(STRUCTURAL)
6979-02-16-56-JS01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 40 of 40
Padur.

ENCLOSURE I

FACTORS OF SAFETY FOR FOUNDATION DESIGN

Minimum Factor Of Minimum Factor Of


Safety Against Safety Against % Weight Of
Type Of Overturning Sliding Overburden Over
Structure With Wind Without With Without Projected Plan
Or Wind Or Wind Or Wind Or Area Of Footing
Seismic Seismic Seismic Seismic
All Buildings/
Structures/Eqpts. 1.5 2.0 1.5 1.5 100
in Units
Pipe Rack
1.5 2.0 1.5 1.5 50$
(Offsite)
Flood Light Mast 1.5 - 1.5 - 50$
Retaining Wall 1.5 2.0 1.5 1.75 100
Tall
1.5 2.0 1.5 1.5 100
vessels/columns

# With blast pressure


$ In case area is paved, overburden shall be based on NGL (for area under filling) or
600mm below HPP whichever is lower. In case of unpaved area, it shall be w.r.t.
FGL.

Minimum Factor of safety against UPLIFT shall be 1.2 for all structures.
(Note: In case of sumps, lining weight shall not be included).

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 3 of 36
Strategic Storage Project, at Padur

1.1 BUILDING REQUIREMENT

The Buildings/ Sheds shall be constructed on the basis of requirements furnished in


Architectural Design Basis elaborated in document no. 6979-02-16-49-DB51.

1.2 SPECIFICATION OF ARCHITECTURAL FINISHES

1.2.1 GENERAL
(a) For any aspect of item not covered in the document, the contractor shall follow
instructions of the engineer-in-charge and execute the work as per relevant IS
codes/ recommendations of approved manufacturer/ good engineering practice
without any cost or time implication to Owner/ PMC. Contractor shall refer only
to the relevant part of the specifications given below.
(b) All materials shall be of first quality conforming to the specifications & IS or
equivalent with IS marks and shall be obtained from the approved Manufacturer.
The Contractor shall get the materials approved by the Engineer - In - Charge
before ordering & procurement. The Contractor shall furnish necessary certificates
etc. as asked by the Engineer - In - Charge. Further to that he shall get the
materials tested from approved test house if asked by the Engineers - In - Charge
& submit the test certificate at his own cost for which no extra payment shall be
made to him. The Engineer - In - Charge shall have the right to reject all or any of
the materials intended to be used and the Contractor at his own cost shall
immediately remove such materials from the site without any claim for
compensation etc. due to such rejection.
(c) Workmanship shall be to the satisfaction of the Engineer- In- Charge. The
contractor shall follow the specifications, relevant Codes & Manufacturer's
guidelines for achieving desired level of workmanship as per specification & good
engineering practice. The Contractor as directed by the Engineer-In-Charge shall
rectify any executed work, not conforming to the specification or not to the
satisfaction of the Engineer- In- Charge. No extra payment shall be made to the
Contractor for such rectification. The contractor shall use only first quality
approved material for all items.
(d) All specifications of various finishing items include construction supervision;
supply of all materials, labours, tools tackles, scaffoldings etc. and are applicable
for all heights, locations etc.
(e) For specifications of construction water, sand, cement, bricks/ stone, aggregates
etc. reference shall be made to the Civil/ Structural specifications attached in the
bid document.

1.2.2 FLOOR FINISHING


Reference shall be made to the following Indian Standards for any further information etc.
not covered in the specification. In case of any conflict/ contradiction, provision of
specification shall override.
IS: 4971 : Recommendations for selection of Industrial floor finishes.
IS: 1237 : Specification for Cement concrete flooring tiles.
IS: 777 : Specification for glazed earthenware wall tiles.
IS: 2571 : Code of practice for laying in situ cement concrete flooring.

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 4 of 36
Strategic Storage Project, at Padur

IS: 5491 : Code of practice for laying in situ granolithic concrete floor
topping.
IS: 4631 : Code of practice for laying of epoxy resin floor toppings.
IS: 4441 : Code of practice for use of silicate type Chemical resistant mortars.
IS: 4443 : Code of practice for use of resin type chemical resistant mortar.
IS: 1196 : Code of practice for laying Bitumen Mastic Flooring.
IS: 13753 : Specification for dust pressed Ceramic tiles with water
absorption of E >10%, Group (BIII)

(A) Cement Concrete Flooring


Cement concrete flooring shall consist of a sub base (laid on the compacted earth
or sand fill in case of ground floor only) a base course laid on the sub-base and
then finishing layer of floor finishing. The bed for flooring shall be prepared either
level or sloped as per drawings and as instructed by Engineer-in-charge.
The sub-base shall be laid on the prepared bed and shall be of specified thickness
and as per structural drawings and specifications. Sub base shall be laid in slope
ranging from 1:48 to 1:60 (1:30 for water closet area).
Cement concrete flooring shall be laid in average 25mm thickness over sub base
and shall generally conform to IS: 2571. The flooring shall be laid in panels and
shall consist of:
(a) 25 mm thick base course of M-15 grade cement concrete (with 6mm and
down size stone aggregate) laid on the sub-base in panels (each panel not
exceeding 2 Sq. Mtr. in area) in desired shape and pattern. The panels
shall be bound by 3x20mm PVC strips panel dividers; fixed in position with
their top at proper level maintaining the required levels, slopes, linearity
etc. as required. Base course shall be laid in alternate panels. Before
laying the base course, neat cement slurry @ 2Kg. of cement per Sq. Mtr.
of area shall be applied (brushed) over the prepared sub base surface.
Cement concrete shall be placed in position and beaten with trowel,
including tamping and finishing smooth. Finishing of the surface shall
follow immediately after completion of laying of base. The bed for flooring
shall be prepared either level or sloped as per drawings and as instructed
by Engineer-in-charge.
(b) Finishing of the surface shall follow immediately after the completion of
base course. The base course shall be free of excessive moisture before
starting the floor finishing. Use of dry cement, cement sand mixture
sprinkled on the surface to stiffen the concrete or absorb excessive
moisture shall not be permitted. Neat cement @ 2Kg. per Sq. Mtr. mixed
with water to form a thick slurry applied over the base course (when the
concrete is green), spread over the surface, pressed twice by means of
iron floats; once when the slurry is applied and second time when the
cement starts setting. The junction of floor with wall plaster, cladding,
skirting shall be rounded off uniformly upto a radius of 25mm unless
otherwise mentioned.
Each finished portion of floor, on completion shall be kept wet with ponding for a
minimum period of 10 days.

(B) Heavy Duty Flooring

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 5 of 36
Strategic Storage Project, at Padur

Heavy duty Flooring shall consist of a sub-base, a base course and a finishing
layer of floor finish.
The sub-base shall be laid on the prepared bed and shall be of specified thickness
and as per structural drawings and specifications. Sub base shall be laid in slope
ranging from 1:48 to 1:60.
Heavy duty Cement concrete flooring shall be laid in overall 50mm thickness over
sub-base and shall generally conform to IS: 5491 in workmanship. The flooring
shall be laid in panels and shall consist of:-
a) Base Course (Under layer) 35mm thick of cement concrete (1 cement: 1.5
coarse sand: 3.5 stone aggregates of 10mm to 6mm size by volume) laid
over sub base in panels (each panel not exceeding 2 Sq. M. in area) in
desired shape and pattern. The panels shall be bound by 3x40mm PVC/
Stainless Steel/ 4x40mm glass strips’ panel dividers; fixed in position with
their top at proper level maintaining the required levels, slopes, linearity
etc. as required. Base course shall be laid in alternate panels. Before
laying the base course, neat cement slurry @ 2Kg. of cement per Sq. Mtr.
of area shall be applied (brushed) over the prepared sub base surface.
The borders of the panels shall have mitred joints at the corners of the
room and intermediate joints shall be in straight line with panel joints.
Cement concrete shall be placed in position and beaten with trowel and
finished smooth. Beating shall cease as soon as surface is found covered
with cream of mortar. Necessary slope shall be provided. The cement
concrete mix shall be used within 30 minutes of its preparation.
b) Wearing Top layer/ finishing layer shall be of cement, hardener and stone
aggregate mix of 15mm thickness laid over the base course. Unless
otherwise mentioned, one part of approved quality hardener and four parts
of cement by weight shall be mixed dry. This dry mixture shall be mixed
with stone grit of 6mm and down size in the ratio of 1 hardener and cement
mixture: 2 stone grit by volume. Just enough water shall then be added to
the mix. The mixture so obtained shall then be laid on the base course
within 2 to 4 hours of latter's laying. It shall be firmly pressed into bottom
concrete so as to have a good bond with it. After the starting of initial
setting, the surface shall be finished smooth and true with steel
floats without any float mark. The junction of floor with wall plaster,
cladding, skirting shall be rounded off uniformly upto a radius of 25mm
unless otherwise mentioned.
Each finished portion of floor, on completion, shall be kept wet with ponding for a
minimum period of 10 days.

(C) Cement Concrete Granolithic Flooring


Cement concrete granolithic flooring shall consist of a sub-base, a base course
and a finishing layer of floor finish.
The sub-base shall be laid on the prepared bed and shall be of specified thickness
and as per structural drawings and specifications. Sub base shall be laid in slope
ranging from 1:48 to 1:60.
Cement concrete granolithic flooring shall be laid in overall 40mm thickness over
sub base and shall generally conform to IS: 5491 in workmanship. The flooring
shall be laid in panels and shall consist of:-

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 6 of 36
Strategic Storage Project, at Padur

(a) 25mm base Course (Under layer) of M-15 grade Concrete (shall generally
conform to Civil structural specifications) laid over sub base in panels
(each panel not exceeding 2 Sq.M. in area) in desired shape and pattern.
The panels shall be bound by 3x30 PVC strips panel dividers; fixed in
position with their top at proper level maintaining the required levels,
slopes, linearity etc. as required. Base course shall be laid in alternate
panels. Before laying the base course, neat cement slurry @ 2Kg. of
cement per Sq. Mtr. of area shall be applied (brushed) over the prepared
sub base surface. The borders of the panels shall have mitred joints at the
corners of the room and intermediate joints shall be in straight line with
panel joints. Cement concrete shall be placed in position and beaten with
trowel and finished smooth. Beating shall cease as soon as surface is
found covered with cream of mortar. Necessary slope shall be provided.
(b) 15mm thick Wearing top layer of cement mortar 1:3 (1cement: 3 course
sand by volume) which shall be laid within 15 minutes of laying the first
layer. The cement and aggregates for the top layer shall be mixed dry.
After mixing, sufficient quantity of washed sand and water shall be added
to make the mix plastic but not flowing. The top and bottom layer shall
firmly grip together. The base course shall be free of excessive moisture
before starting the floor finishing. Use of dry cement, cement sand mixture
sprinkled on the surface to stiffen the concrete or absorb excessive
moisture shall not be permitted.
(c) While the concrete is still green, cement @ 2 kg per Sq.M of floor area
shall be mixed with water to form thick slurry and spread over the surface.
It shall be pressed twice by means of iron floats, once when the slurry is
applied and second time when the cement starts setting. The junction of
floor with wall plaster, cladding, skirting shall be rounded off uniformly upto
a radius of 25mm unless otherwise mentioned.
Each finished portion of floor, on completion shall be kept wet with ponding for a
minimum period of 10 days.

(D) Cement Plaster Skirting


Cement mortar shall be of specified mix and thickness in accordance with civil
structural specification. Cement plaster skirting shall be laid with cement mortar (1
cement: 3 coarse sand by volume) shall be of 6mm/ 12mm/ 18mm thickness.
The surface on which the skirting is to be applied shall be prepared and skirting of
specified thickness shall be laid. The joints shall be raked out to a depth of at least
15mm in masonry walls. In case of concrete walls, the surface shall be roughened
by hacking. Skirting with specified mortar and to specified thickness shall be laid
immediately after the surface is prepared. It shall be laid along with the border or
adjacent panels of floor.
Finishing of skirting shall be done simultaneously with the borders of the adjacent
panels of floor. The cement to be applied in the form of slurry for smooth finishing
shall be @ 2kg of cement per litre of water applied over an area of 1 square
meter.

(E) Kota Stone Finish


Kota Stone Flooring shall be laid in minimum 40mm overall thickness over sub
base (as per structural drawings/ specifications). The Kota Stone slabs shall be of

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 7 of 36
Strategic Storage Project, at Padur

selected quality and shade, hard, sound, dense, and homogenous in texture, free
from cracks, decay, weathering and flakes. These shall be machine cut to the
requisite size and thickness and chisel dressed. For flooring and skirting/ dado/
riser the thickness of the stone slabs shall be 25mm and 18mm respectively.
Skirting shall normally be 125mm high unless specified otherwise.
The slabs shall have smooth top (exposed) face before being laid. Before starting
the work, the contractor shall get the samples of slabs approved by Engineer-in-
charge. Each slab shall be machine cut to the required size and shape and fine
chisel dressed at all edges to full depth and machine rubbed to a smooth surface
finish. All angles and edges of the slabs shall be true square and free from
chippings giving a plane and smooth surface.
Preparation of base shall include making it rough, cleaning thoroughly and
applying neat cement slurry @ 2 kg of cement per Sq.M. of area to receive the
mortar. Cement mortar shall be 15mm thick in 1:6 (1 cement: 6 Coarse sand by
volume) for flooring and 12mm thick in 1:3 (1 cement: 6 Coarse sand by volume)
for skirting. The mortar shall be laid for fixing one slab at a time. The slab shall be
washed clean before laying. It shall be laid over cement mortar bedding on top,
pressed and tapped gently to bring it in level. It shall be then lifted and laid aside.
Top surface of the mortar then shall be corrected by adding fresh mortar at
hollows and depressions. The mortar then shall be allowed to harden and cement
slurry of honey like consistency @ 4.4.kg of cement per Sq. M shall be spread
over the mortar. The edges of the slabs shall be buttered with white cement (with
necessary pigment) grout to match the shade of the slabs. The slabs shall then be
gently placed in position and tapped with wooden mallets till it is properly bedded
in level. The joints shall be as fine as possible. Surplus cement on the surface of
the slab shall be removed. The slabs in flooring shall continue for not less than 10
mm under the plaster/skirting. The finished surface shall be true to levels and
slopes as instructed by the Engineer-in-Charge. The slabs shall be laid in patterns
as per drawings and size shall not be less than 400 x 275mm, which shall be
uniform. Cut size may be used along periphery as required. Curing, as required
shall be done.
Grinding shall be commenced when the joints are properly set. Unevenness at the
meeting edges of slabs shall be removed by fine chiselling. Grinding shall be done
by machines except for skirting and small areas. First grinding shall be done with
Carborundum stones of 48 to 60 grade grit fitted in the machine. Water shall be
properly used during grinding. When the floor has been uniformly rubbed, it shall
be cleaned with water baring all pin holes. It shall then be covered with a thin coat
of cement mixed with pigments to match with colour of the Kota stone. This grout
shall be kept moist for a week. Thereafter the second grinding shall be started with
Carborundum stone of 120 grit. Grinding and curing shall follow again. Final
grinding shall be with Carborundum of grade 220 to 350 grit using water in
abundance. The floor shall be washed clean with water, oxalic acid powder shall
then be dusted at 35 gms/sq. m. on the surface rubbed with machine fitted
hessian bobs or rubbed hard with woollen rags. The floor shall then be washed
clean and dried with a soft cloth or linen. If any stone slab is disturbed or
damaged, it shall be refitted or replaced and properly jointed and polished.

(F) Tile Work (Vitrified Porcelain/ Ceramic)


(a) Vitrified Porcelain Tiles

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 8 of 36
Strategic Storage Project, at Padur

Vitrified Porcelain Tiles shall be of specified size, thickness and approved


color/ design/ texture, of first quality and conform to EN 176. The Vitrified
Porcelain tiles shall be decorative type of approved shade, pattern, texture
and design and of approved manufacturer. The sizes of Vitrified Porcelain
tiles shall be as per approved manufacturer’s standards as approved by
owner.

(b) Ceramic tiles


Ceramic tiles shall be of specified size, thickness and approved color/
design/ texture of first quality and shall conform to IS 13753. Ceramic tiles
for flooring shall be matt finished and non-slip type. All tiles shall be
decorative type of approved shade, pattern, texture and design and of
approved manufacturer. The sizes of the ceramic tiles shall generally be
300x300x8mm for flooring and 100x200x6mm or 300x200x6mm for walls
(dado).
The base on which tiles are to be laid shall be cleaned of all dust, dirt and
properly wetted by applying neat cement slurry @ 2 kg. of cement per Square
meter of area.
The tiles shall be laid over a coating of specified adhesive (as per approved
manufacturer’s specification) laid on base floor/wall plaster. The joints of the tiles
shall be cleaned off and all dust and loose mortar removed. The joints then shall
be flush pointed with cement paste (white cement and pigment conforming to IS:
2114, Table-l) or any other joint fixing compound as recommended by Tile
Manufacturer matching the shade of tiles.
Tiles shall be laid as per desired pattern. Joints shall be uniform kept as thin as
possible and in straight lines. Cut tiles shall be permitted only in unavoidable
cases as directed by Engineer- In- Charge.
For flooring, laying shall be generally from centre & proceed outwards in two
directions at 900.
For vertical surfaces, the tiles shall be corrected to proper planes with joints truly
vertical in required pattern and butt jointed. The fixing shall be done from bottom
upward. The top of skirting and dado shall be truly horizontal.

(G) Acid Resistant Tiles


The tiles shall be vitrified tiles of approved size, thickness and color as per
approved manufacturer’s specification and shall be homogeneous. They shall
have the following properties:-
S. No. Property Values Norms
1 Water Absorptions ± 0.5% ASTM C 373
2 Scratch Resistance  6 ASTM C 373
3 Chemical Resistance Unaffected ASTM C 650
4 Abrasion Resistance 100 ASTM C 501
5 Breaking strength 400 kg/sq.cm ASTM C 648
6 Density 2.0 Gm/CC

Base and background surface over which the tiles are to be laid shall be prepared
as per IS: 4443.

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 9 of 36
Strategic Storage Project, at Padur

Tiles shall be fixed on the prepared surface over bitumen priming layer, bitumen
mastic layer and resin type chemical resistant mortar in accordance with
manufacturer’s recommendation. The bitumen shall conform to IS: 702 and laying
of bitumen mastic shall conform to 1S:1196.
Joints shall be allowed to set for 24 hours. The floor shall then be washed as per
manufacturer's specifications to totally remove all marks from tile surface.

(H) Granite Stone Flooring and cladding


The Granite Stone slabs shall be minimum 18-19mm thick pre-polished (mirror-
polish), hard, sound, dense, homogenous in texture, free from cracks, decay,
weathering and flakes of selected premium quality (grade- I) and approved color/
texture/ design. The sample of granite stone slabs shall be got approved from the
Engineer-in-Charge.

The slabs shall be machined cut to the requisite dimensions as per approved
drawing and as directed by Engineer-In-Charge.
Tolerance of +3% shall be allowed for the thickness. In respect of length and
breadth of slabs, a tolerance of +2% shall be allowed.
Laying in floor:
Granite Stone Flooring shall be laid in minimum 40mm overall thickness over sub
base (as per structural drawings/ specifications). Preparation of base shall include
making it rough, cleaning thoroughly and applying neat cement slurry @ 2 kg of
cement per Sq. Mtr. of area to receive the mortar. It shall be laid over 20mm thick
cement mortar in 1:6 (1 cement: 6 Coarse sand by volume) bedding, pressed,
tapped gently to bring it in level. It shall be then lifted and laid aside. Top surface of
the mortar then shall be corrected by adding fresh mortar at hollows and
depressions. The mortar then shall be allowed to harden and cement slurry of
honey like consistency @ 4.4.kg of cement per square meter shall be spread over
the mortar. The edges of the slabs shall be buttered with white cement with or
without pigment grout to match the shade of the slabs. The slabs shall then be
gently placed in position and tapped with wooden mallets till it is properly bedded in
level. The joints shall be as fine as possible. Surplus cement on the surface of the
slab shall be removed. The slabs in flooring shall continue for not less than 10 mm
under the plaster/skirting. The finished surface shall be true to levels and slopes as
instructed by the Engineer-in-Charge.
The slabs shall be laid in patterns as per drawings and size. Cut size may be used
along periphery as required. The joints shall be uniform and in perfect line.
Laying in skirting/ dado/ risers:
The slabs shall be held in position by suitable temporary measure such as wooden/
bamboo supports, temporary hook etc. as approved by Engineer-In- Charge. The
outer face of the slabs shall be checked for plane and plumb and corrected. The
joints shall be as fine as possible and shall be filled with neat cement paste/ grout
with white cement and pigment to match the color of the slabs. The joints shall thus
be left to harden and then the rear gap between the slabs and backing surface shall
be packed with cement mortar of specified mix and thickness. Temporary supports
shall be removed after the mortar filling in the gap has acquired sufficient strength.
The top line of the skirting/ dado/ risers shall be truly horizontal and joints truly
vertical.

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 10 of 36
Strategic Storage Project, at Padur

Polishing and Finishing:


Unevenness at the meeting edges of slabs shall be removed by fine chiseling.
The day after the tiles are laid all joints shall be cleaned with a wire brush to a
depth of 5 mm and all dust and loose mortar removed and cleaned. Joints shall
then be grouted with grey or white cement mixed with or without pigment to match
the shade of the stones. If any stone is disturbed or damaged, it shall be refitted or
replaced and properly jointed and polished.

1.2.3 DOORS AND WINDOWS


Reference shall be made to the following Indian Standards for further information etc. not
covered in the specification. In case of any conflict/contradiction the provisions of the
specification shall override.
IS: 1948 : Specifications for Aluminium doors, windows and ventilators.
IS: 6248 : Specifications for metal rolling shutters and rolling grill.
IS: 1081 : Code of practice for fixing and glazing of metal (steel and
Aluminium) doors, windows and ventilators.
IS: 4351 : Specifications for steel door frames.
IS: 1361 : Specifications for steel windows for Industrial buildings.
IS: 1038 : Specifications for steel doors, windows and ventilators.
IS: 7452 : Specification for hot rolled steel sections for doors, windows
and ventilators.
IS: 2835 : Flat transparent sheet glass.
IS: 5437 : Wired and Figured glass.
IS: 3548 : Code of practice for glazing in buildings

IS: 3614 Part-1: Specification for fire check doors.


Part-1: Plate metal cover and rolling type
IS: 3614 Part-2: Specification for fire check doors.
Part-2: Resistance test & performance criteria

IS: 2202 Part-1: Specifications for wooden flush door shutters (solid core type)
Part 1: Plywood face panels.
IS: 2202 Part-2: Specification for wooden flush door shutters (solid core type)
Part 2 : Particle board and hardboard face panels
IS: 3087 : Specification for Wooden particle boards (medium density) for
general purposes.
IS: 3097 : Specification for veneered particle boards.
IS: 848 : Specification for synthetic resin adhesives for plywood (phenolic and
amino plastic)
IS: 205 : Specification for non ferrous metal butt hinges.
IS: 2338 : Code of practice for finishing of wood and wood based materials.
(Part I & II)
IS: 1341 : Specification for steel butt hinges.

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 11 of 36
Strategic Storage Project, at Padur

IS: 4021 : Specification for timber door, window and ventilator frames.
IS: 303 : Specification for plywood for general purposes.
IS: 204 Part-1: Specification for Tower bolts
Part-1: Ferrous metals
IS: 204 Part-2: Specification for Tower bolts
Part-2: Non- Ferrous metals
IS: 205 : Specification for non ferrous metal butt hinges
IS: 208 : Specification for Door handles

(A) Aluminium Glazed Doors/ Windows/ Ventilators


Aluminium glazed doors/window/ventilators shall be of specified sectional size,
dimension and profile as per drawing.
Aluminium glazed doors/ windows/ ventilators shall be made of extruded tubular
electrostatically powder coated (min. 30 microns) Aluminium sections conforming
to IS: 733 and IS: 1285 of approved manufacturer with 5.5 mm thick transparent
sheet glass conforming to IS: 2835 (wt.7.2 kg/Sq.M), fixed with rubber lining or
EPDM gasket and extruded anodised aluminium beading.
Extruded aluminium sections used for various applications shall have minimum
weights as under.
(a). Doors
1. For fixed frames
I) Sides & Top members : 1.975 Kg/RM
ii) Lock rail : 1.594 Kg/RM
iii) Bottom rail : 3.495 Kg/RM
2. For shutter frame : 1.202 Kg/RM
3. Glazing clips (beading) : 0.182 Kg/RM

(b). Window/Ventilator
1. For fixed frames : 0.639 Kg/RM
2. For shutter frame : 0.636 Kg/RM
3. Glazing clips (beading) : 0.165 Kg/RM
4. Coupling bars : 0.933 Kg/RM
5. Member for fixing the frame: 0.463 Kg/RM
The frames shall be square and flat, the corner of the frame being fabricated to
true right angles. Details of construction of frames, shutters etc. shall be as per
drawings. The frames shall be fixed to masonry by means of Aluminium lugs fixed
to the frame by counter sunk brass machine screws and grouted with M-15 grade
concrete in minimum 150 x 150 x 50 mm sized hole in the masonry. In case of
RCC, the frames shall be fixed with 12mm dia. dash fasteners. Any steel item
coming in contact with Aluminium shall be galvanised.
Aluminium glazed doors shall be provided with cup pivots (of aluminium alloy
conforming to IS designation NS-4 of IS 737 and IS designation of A-5-M of IS:

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 12 of 36
Strategic Storage Project, at Padur

617), riveted to outer and inner frames to permit to swing through an angle of 85
degree.
The handles for doors shall be of Aluminium and as per design. The door shutters
shall be provided with locking device, floor spring, door closer and any other hard
wares as specified.
Side hung window shutters shall be fixed to the frame with pivots, or aluminium
alloy friction hinges. For fixing the hinges, slots shall be cut in the fixed frames and
the hinges inserted inside may be riveted to the frame. The handles for side hung
shutters shall be of cast aluminium conforming to IS designation A-5-M of IS: 617
and shall be mounted on a handle plate riveted to the opening frames. The
handles shall have same finish as that of the window sections. The handles shall
have a two point nose which shall engage with an aluminium striking plate on the
fixed frame. The striking plate shall be finished in the same manner as for the
handle. In case of top hung shutters, aluminium alloy cast hinges and peg stays
shall be provided.
In case of composite Door/window/ventilator units, the units shall be coupled as
per drawing. Weather bar shall be provided wherever a coupling member is fitted
over an external opening shutter.
Glazing shall be fixed to the extruded sections by means of extruded aluminium
beading. Glass panes shall be provided with EPDM gasket/rubber lining before
fixing.
All Aluminium fittings/ fixtures shall be of same finish as that of frame & shutter.
The windows/ventilators/doors shall be checked to ensure smooth operation,
perfect level and plumb.
Wherever specified, decorative aluminium safety grills of approved design shall be
provided which shall be screwed to the main frame.

(B) Steel Doors


Steel doors shall consist of:
(a) Pressed steel door frame of overall 125x 65mm size conforming to IS :
4351 and made of 16 SWG pressed steel sheet bent to required shape
using bending machine to form solid/ true mitred edges/ corners, stiffened
with 50 x 5mm thick MS flat spacers welded to the frame facing the wall/
column @ 600mm c/c maximum vertical spacing. The frame shall be fixed
to the masonry by means of 300 x 25 x 6 mm thick MS hold fast welded to
the spacer and grouted with M-15 concrete in minimum 350 x 100 x 100
mm sized hole in the masonry. In case of concrete, the frames shall be
fixed by 96mm long, 12 mm dia metallic counter sunk type dash fasteners
through the frame & spacers. Provision for hinges, locking arrangement
and other hardware shall be provided in the frame by machine cutting of
required size cutouts in the frame and welding/ screwing to 3 mm thick MS
pad plates already welded over the cutout from behind. The hollow frame
shall be packed with PCC to fill the cavity without gap. The frame shall be
thoroughly cleaned of rust, mill scale, dirt, oil etc. by sand and shot blasting
and then finished with 2 or more coats of Epoxy paint of approved quality
and approved shade over a coat of approved quality primer as per
approved manufacturer’s specifications.

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 13 of 36
Strategic Storage Project, at Padur

(b) Pressed steel door shutter shall be made with 18 gauge steel sheets
formed by machine bending in the form of hollow box (overall 40mm thick)
welded at meeting of the sheets with pad plate of 3mm thick MS flat all
along the perimeter. The shutter shall be braced with channel shaped
35mm wide horizontal stiffeners by folding 16 gauge MS sheets @ 500mm
c/c fixed by flush riveting. 3mm thick MS pad plates shall be welded inside
at required locations for fixing of hardware. The cavity inside shall be
packed with rigid PU foam/ phenolic foam or glass wool insulation to fill
into the box cavity without gap.
For double shutters, an MS angle (25x 45x 3mm thick) shall be welded
to one of the shutter providing a minimum 25mm wide rebate for the
other shutter at the meeting point.
The shutters shall be fixed to the door frame by means of heavy duty
MS butt hinges of 150mm size conforming to IS: 1341 @ 500mm c/c
maximum.
In case of air tight door shutters, approved quality continuous
neoprene rubber beading shall be provided continuously along the door
frame rebate fixed with neoprene rubber adhesive of approved make.
In case of fully glazed door shutters (75mm wide stiles & top rail and
175mm wide lock & bottom rails), 5.5mm. thick toughened glass confirming
to IS: 5437 shall be fixed with glazing clips, putty and 10mmx10mm
channel shaped 16 gauge M.S. beading including providing 6mm thick
M.S. flat continuous along perimeter of glazing cut out welded to shutter.

Each door shutter shall have following accessories.


1. Spring loaded pressure die cast zinc alloy door stopper.
2. Heavy duty, MS aldrop 400mm long for double shutter & 300mm
long for single shutter.
3. 12mm dia, 300mm long pressure die cast zinc alloy handles on
both sides.
4. 12mm dia, 250mm long MS tower bolt at top and 12 mm dia
150mm long at bottom.
5. 3- way spring loaded locking & latching system.
6. Approved make heavy-duty overhead hydraulic door closer with
adjustable spanners, metal screws etc. conforming to IS: 3564
The entire shutter including all accessories, fittings & fixtures etc. shall be
thoroughly cleaned of rust, mill scale, dirt, oil etc. by sand and shot blasting
and then finished with 2 or more coats of approved quality synthetic
enamel paint of approved shade over a coat of approved quality red oxide
zinc chromate primer.

(C) Wooden Flush Doors


Flush doors shall consist of:-
(a) Aluminium door frames:

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 14 of 36
Strategic Storage Project, at Padur

Aluminium door frames shall be made of extruded tubular electrostatically


powder coated (min. 30 microns) Aluminium sections conforming to IS:
733 and IS: 1285 of approved manufacturer. The frames shall be square
and flat, the corner of the frame being fabricated to true right angles.
Details of construction of frames, shutters etc. shall be as per
drawings. The frames shall be fixed to masonry by means of Aluminium
lugs fixed to the frame by counter sunk brass machine screws and grouted
with M-15 grade concrete in minimum 150 x 150 x 50 mm sized hole in the
masonry. In case of RCC, the frames shall be fixed with 12mm dia. dash
fasteners. Any steel item coming in contact with Aluminium shall be
galvanised.
(b) Wooden door frames:-
Wooden door frame shall be made of second class Indian teakwood and
shall be in accordance with detailed drawings. The wooden members of
the frame shall be planed smooth and accurate to the full dimensions.
Rebates, rounding, moulding etc. shall be done before the members are
joined into frames. Joints in the frame work shall be perfect with square
edges and shall be pinned with hard wood/bamboo pins of 10 to 15 mm
dia. Wood work shall be painted/polished or otherwise treated as specified.
All exposed portions shall be coated with wood primer and concealed
surface by bituminous paints as specified. Before any surface treatment is
applied, the wood work shall be got approved by the Engineer-in-charge.
The frames shall be fixed to the masonry by 300mm x 25mm x 6mm MS
hold fasts embedded in M-15 grade concrete size of 350mm x 100mm x
100mm in the hole of masonry. In case of concrete, frames shall be fixed
by 96mm long, 12mm dia metallic dash fasteners.
(c) Block board flush shutter:-
Block board flush shutter shall conform to IS: 2202. Flush door shutters
shall be factory made and overall 35mm thick consisting of solid core block
board bonded with phenol formaldehyde synthetic resin conforming to IS:
848. The shutters shall be faced on both sides with approved quality 1mm
thick teakwood veneering conforming to IS: 303, BS: 476, part 7. 35 x
20mm second class Teakwood lipping shall be provided all around the
shutter by means of approved quality neoprene based adhesive and
nailing @ 300mm (maximum). Teakwood used for lipping etc. shall be
second class Indian teakwood (conforming to IS: 4021) of good quality,
well seasoned and free from defects such as cracks, dead knots, sapwood
etc. and shall be with no individual hard & sound knots more than 15
Sq.CM in area and the aggregate area of such knots not exceeding 2% of
area of the piece. The wood shall be fairly closed grains having not less
than 2 growth rings per Cm. Width in cross section. Teakwood lipping shall
be french polished (lacquer finish). The shutters shall be fixed to the frame
by means of 125mm long MS butt hinges conforming to IS: 1341 @
600mm c/c maximum.
Following hardware of approved quality and shade shall be provided in
each shutter:-
1. Heavy duty, overhead hydraulically operated door closer
conforming to IS: 3564.

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 15 of 36
Strategic Storage Project, at Padur

2. Anodised aluminium tower bolts as per IS: 204, 10mm dia 250mm
long (at top) and 150mm long (at bottom), one each for each
shutter on either side.
3. Brass body 6 lever mortice lock as per IS: 2209 including pair of
handles of pressure die cast zinc alloy (satin finished)
4. 3mm thick plastic kick/ push plate (150mm high at bottom for entire
width & 200mm x 100mm at handle location).
5. Zinc alloy pressure die cast chromium plated spring loaded door
stopper with heavy duty rubber shoes.
6. 150mm x 300mm Vision panel with of 4mm thick plain glass
conforming to IS: 2853 fixed with second class Teakwood beading
(not for toilet doors).

(D) Steel Windows and ventilators


Steel windows, ventilators shall in general confirm to IS: 1038 and IS: 7452.
Rolled steel sections for the fabrication of steel windows, ventilators shall conform
to IS: 7452.
Glass panels for glazing purpose shall be 4mm thick (wt. 7.2 kg/ Sq.M)
The profile and type of windows, ventilators (glazed, partly glazed/ louvered, side
hung/ top hung/ fixed shutter, composite) shall be as per approved drawings.
The frames shall be constructed of sections cut to size and mitred. Corners shall
be welded to form a fused welded joint. Process of welding shall be flash butt
welding. The welded joints shall be grinded to square and flat edges.
Where larger units are to be formed by coupling individual units, the mullions and
transoms shall be bedded in mastic to ensure weather tightness. Mastic shall be
applied liberally to the channels of the outside frame sections before assembly,
and the two units being coupled shall be drawn together tight with clamps, the
mastic being squeezed out and cut off neatly when the units shall be screwed
together tight.
The frame shall be completely cleaned and bedding putty shall be placed in the
rebate before glazing. Glass then shall be cushioned into the bedding and shall be
fronted with front putty in a manner so as to enable the painting to be done upto
the sight line. The back putty oozing out over the glazing rebate shall be cut off
square and smoothed down.
For panels exceeding 600 x 300 mm in size, glass shall be secured by special
glazing clips inserted in holes already provided in the steel sections, before
applying the front putty.
For glazing of very large areas, rust proof steel beading with mitred corners shall
be provided with screws @ 10 cm. from each corner and @ 20 cm. apart from
each other. Putty shall be provided to the face of the bead in contact with glass, in
addition to back putty.
In case of fixing with masonry, holes for fixing the lugs/hold fasts shall be cut at
required locations. In case of concrete or stone, the frames shall be fixed by
means of dash fasteners. In case of masonry, the lugs shall be grouted in the
holes with cement concrete, M-15 Grade when fixing to steel work, mastic shall be
applied to the sill of the opening and the unit shall be placed on it with the jambs

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 16 of 36
Strategic Storage Project, at Padur

and head buttered with mastic and the unit shall be fixed with special fixing dips or
with nuts and bolts.
All the steel surfaces shall be thoroughly cleaned free of rust, mill scale, dirt, oil
etc. by sand and shot blasting and then painted with 2 or more coats of Synthetic
enamel paint of approved quality and approved shade over a coat of approved
quality primer as per approved manufacturer’s specifications.

(E) Steel Rolling Shutter


M.S. rolling shutters shall conform to IS: 6248 and shall be constructed with
interlocking lath sections formed out of cold rolled 0.9mm thick, 80mm wide steel
strips for shutter width upto 3.5 M, or 1.25mm thick, 80mm wide steel strips for
shutter width beyond 3.5 M, joint less MS channel section of 3.15mm thickness
for guide, MS girders & bottom rail, shutter suspension stud with pulley & cage,
top rolling springs, locking arrangement etc. all complete as per manufacturers
approved drawings. The entire shutter including all accessories shall be painted
with 2 or more coats of approved quality & shade synthetic enamel paint over a
coat of approved quality red oxide zinc chromate primer. All the damaged
surfaces of wall, columns, plastering etc. shall be made good.
Wherever specified the Rolling shutters shall be grill type or partly grill & partly
solid type or fully solid type depending on ventilation requirement.

(F) Fire Check Door


Fire Check Door with frame shall have 2 hours fire rating and shall be procured
from an approved manufacturer. The door ensemble shall be certified by
CBRI/approved laboratory, and tested in accordance with IS: 3614 Part 2 & BS
476. The door shall have all necessary fixtures and fittings. It shall be fixed to
masonry/RCC by grouting the lugs with M-15 grade concrete. Perfect sealing in
frame rebate and between frame and shutters shall be ensured.

(G) Fire Check Glazed Window


Fire Rated glazed window with frame shall be of 2 hour fire rating/integrity. It shall
be procured from an approved manufacturer, certified by CBRI/approved
laboratory, tested in accordance with IS: 3614 Part 2 & BS 476, with all fixtures
and fittings. The window shall befixed to masonry/RCC by grouting the lugs with
M-15 grade concrete .Perfect sealing shall be ensured in the complete system.
1.2.4 PLASTERING
The plastering work shall include preparation of background surface which shall consist of
cleaning of all dust, loose mortar droppings, traces of algae, efflorescence or any other
foreign matter by water or by brushing, roughening up of smooth surfaces by wire
brushing or hacking, trimming of projections whenever necessary. The surface shall be
washed off and well wetted before applying the plaster.
Cement plaster shall be provided in following thickness:
a). 12mm thick in 1:6 cement mortar for all plumb of the internal masonry walls &
RCC Columns coming in line (flush) with this side of wall.
b). 15mm thick in 1:6 cement mortar for rough side of internal masonry walls RCC
Columns coming in line (flush) with this side of wall.

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 17 of 36
Strategic Storage Project, at Padur

c). 18mm thick cement plaster in 1:6 cement mortar for all external surfaces as
indicated.
d). 6mm thick in 1:4 cement mortar for all RCC ceiling, beam etc. However if the
undulation in ceiling is beyond 6mm thick plaster, extra thickness of plaster shall
be applied without any extra cost to give a smooth and fair surface to the
satisfaction of Engineer-In-Charge.
e). 20mm thick Sand face plaster consists of:
i) 13mm thick under layer in 1:4 cement mortar.
ii) 7mm thick top layer in 1:2 cement mortar.
For external plaster, the plastering shall be started from top floor and carried downwards.
Internal plastering shall start with ceiling. Plastering shall be applied evenly in specified
thickness. The entire surface shall be finished smooth by means of trowel or wooden
float.
All the masonry and RCC joints shall be provided with 20 gauge chicken wire mesh
stretched tight and fixed with G.I. “U” type nails before plastering.
The first layer shall be started from top floor and carried downwards. Before the first layer
hardens, surface of it shall be roughened up by edges of wooden tapers and close dents
shall be made on the surface. The subsequent layer shall be applied over the first layer
after the first layer has been allowed to set for 3-5 days depending on weather conditions.
The surface shall not be allowed to dry during this period.
20mm x 10mm grooves (horizontal and vertical) shall be provided in perfect straight line &
plumb in plastering as per drawings and instructions of Engineer- In - Charge.
Curing shall be started 24 hours after finishing the plaster. The plaster shall be kept wet
for a period of 7 days. During this period the plaster shall be suitably protected from all
damages at the contractor's expense by such means as approved by the Engineer-in-
charge. The date of execution of plastering shall be marked on the plastering to ensure
the proper duration of curing.
The plastering shall include provision of drip moulds, all scaffolding, damage rectification
etc. complete.

1.2.5 ROOF TREATMENT/ WATERPROOF COATING


Polymer Modified Bituminous Roof Water Proofing
The roof treatment/ waterproofing-cum-terracing shall consist of:-
(A) Material
Bituminous membrane for waterproofing shall be 4mm thick prefabricated polymer
(APP-atactic polypropylene) modified and shall be reinforced with nonwoven
Polyester and shall have following properties, Test methods of all these properties
shall be as per relevant ASTM codes.
1. Thickness : 4mm
2. Penetration at 25deg. C, 100g, 5 seconds : 25+_5mm
3. Softening point : 110 to 150 deg C
4. Low Temp. Flexibility : -2 deg C to -5 deg C
5. Tensile strength
Longitudinal : > 500N/ 5cm

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 18 of 36
Strategic Storage Project, at Padur

Transverse : > 500N/ 5cm


6. Elongation
Longitudinal : > 40%
Transverse : > 40%
7. Nail tearing resistance
Longitudinal : >= 130N
Transverse : >= 130N
8. Water absorption : 0.2% max.

(B) Workmanship
Base surface shall be thoroughly cleaned with a wire brush and all foreign matter
etc. shall be removed. Well defined cracks on the surface shall be cut to "V"
section, cleaned and filled up with a paste of one or two component Polyurethane
based crack filling compound and white cement in a ratio of 1:2
Potholes/depressions shall be filled up after removing weak cement concrete/
cement plaster etc. with PCC(1 cement :1.2 coarse sand :3.5 stone aggregate of
6mm & down size by volume,) laid over a coat of neat cement slurry @2.75 Kg of
cement per Sq.M of area, wherever required thus preparing smooth and properly
sloped surface. Slope and leveling of the existing surface shall be checked and if
necessary, adequate slope shall be provided by laying PCC laid over neat cement
slurry as above for effective roof drainage. Leak-prone areas shall also be
identified and rectified by raking out existing water proofing and filling up with PCC
as directed by Engineer-In-Charge. The surface thus shall be prepared smooth for
receiving the waterproof treatment over it.
One coat of bituminous solvent based primer of approved quality and conforming
to IS: 3384 shall be cold applied @ 0.2-0.4 ltr/Sq.M over the entire area to be
waterproofed including vertical surfaces. The primer shall be allowed to be dry for
minimum 24 hours.
APP polymer modified bituminous membrane shall be laid over the primer coat by
torch welding. The membrane shall be properly pressed during laying to remove
any entrapped air. The joints should be sealed properly with necessary side laps
of 100mm and end laps of 150mm.
The membrane shall be continued along the vertical surfaces upto a minimum
height of 300mm. Suitable fillet of 75mm radius shall be formed in cement
concrete (1 cement :2 coarse sand :4 stone aggregate of 6mm & down size by
volume) at the junction of horizontal/ vertical surfaces. The continued membrane
shall be terminated in minimum 20mm x 10mm chase to be provided in the vertical
surface and shall be sealed with approved polyurethane sealant.

(C) Protective layer


Unless otherwise mentioned, waterproofing treatment shall be protected by a layer
of plain cement concrete.
Plain cement concrete (1 cement: 2 coarse sand: 4 stone aggregate of 6mm &
down size by volume) of 35mm minimum thickness mixed with cement based
polymer modified waterproofing compound. The PCC layer shall be laid in panels
of max. 1.2Metre x 1.2Metre size and shall be reinforced with 24 SWG chicken
wire mesh (20mm x 20mm) as per IS 1556. Proper shuttering, tamping, curing etc
shall be done. The top surface shall be finished smooth in slope. Dummy square
joints @ 300mm x 300mm shall be marked on the top surface by pressing rope

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 19 of 36
Strategic Storage Project, at Padur

over finished surface. The joints between panels shall be raked out neatly (after
stipulated curing period) to a minimum 6mm X 6mm V groove and filled up with an
approved quality elastomeric compound sealant. Drain outlet shall be provided for
all spouts/rain eater pipes by suitable rounding, filling and sloping and by providing
minimum 450mm x 450mm khuras (rain water collecting pit, levelled down by
minimum 25mm from adjacent areas) in cement concrete (1 cement :2 coarse
sand :4 stone aggregate of 6mm & down size by volume) at all drainage
outlets..At the junction of the roof and parapet or any other vertical surfaces, a
fillet of 75mm radius shall be formed in cement concrete (1 cement :2 coarse sand
:4 stone aggregate of 6mm & down size by volume).

(D) GUARANTEE
A Guarantee of minimum 10 years shall be provided against the performance
of the finished waterproofing system.

1.2.6 WHITE/ COLOUR WASHING, PAINTING, POLISHING ETC.


Reference shall be made to the following Indian Standards for further information etc. not
covered in the specification. In case of conflict/ contradictions provisions of the
specification shall override.
IS: 6278 : Code of practice for white washing and colour washing.
IS: 2395 : Code of practice for painting concrete, masonry and plaster
surfaces.
IS: 712 : Specification for building limes.
IS: 55 : Specification for Ultramarine blue for paints.
IS: 63 : Specification for whiting for paint and putty.
IS: 5410 : Cement paint, colour as required.
IS: 384 : Brushes, paints and varnishes, flat.
IS: 486 : Brushes, sash, tool, for paints and varnishes.
IS: 110 : Ready mixed paint, brushing, grey filler enamels for use over
primers.
IS: 426 : Paste filler for colour coats.
IS: 106 : Ready mixed paint, brushing, priming for enamels, for use on
metals.
IS: 428 : Distemper (Oil Bound), colour as required.
IS: 5411 : Specification for plastic Emulsion paint for interior use.
IS: 345 : Wood filler, transparent liquid.
IS: 3585 : Ready mixed paint, aluminium brushing priming water resistant for
wood work.
IS: 2338Part-1: Code of practice for finishing of wood, and wood based
materials.
Part-1 : Operations & workmanship
IS: 2338Part-2: Code of practice for finishing of wood, and wood based
materials.
Part-2 : Schedule
IS: 2524Part-1: Code of practice for painting non ferrous metals in buildings.
Part-1 : Pretreatment
IS: 2524Part-2: Code of practice for painting non ferrous metals in buildings.

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 20 of 36
Strategic Storage Project, at Padur

Part-2 : Painting
IS: 1477Part-1: Code of practice for painting ferrous metals in buildings.
Part-1 : Pretreatment
IS: 1477Part-2: Code of practice for painting ferrous metals in buildings.
Part-1 : Painting
IS: 2395Part-1: Painting of concrete, masonry & plastered surface, code of
practice Part-1 : Operations and workmanship
IS: 2395Part-2: Painting of concrete, masonry & plastered surface, code of
practice Part-2 : Schedule

All materials required for the execution of painting work shall be obtained direct from
approved manufacturers and shall be brought to the site in makers drums, bags etc. with
seals unbroken.
In case of ready mixed paints, thinning if necessary, the brand of thinner shall be as per
recommendations of the manufacturer.
Paint shall be applied by brushing or spraying. The brushing operations are to be
adjusted to the spreading capacity advised by the manufacturer. During painting, every
time after the paint has been worked out of the brush bristles, the bristles shall be opened
up by striking the brush suitably.
Spray machine used may be of high pressure type or low pressure depending on the
nature and location of work. After work, the brushes shall be completely cleaned of paint
and shall be hung in a thinner if intended to be used afterwards. The spray guns shall be
cleaned thoroughly after every break in work. The paint containers, when not used shall
be kept close and free from air.
After the finishing of work, the adjacent surfaces not intended to be washed/ distempered/
painted/ polished shall be thoroughly cleaned of all paint patches and shall be finished in
accordance with surface finishing of such surfaces.

(A) White/ Colour Washing


White washing in general shall conform to IS: 6278. Scaffolding shall be erected
for white washing in such a way that no part of the scaffolding shall rest against
the surface to be white/ colour washed. The surface shall be thoroughly cleaned of
all dirt, dust, mortar dropping and other foreign matter before white wash is to be
applied. Surfaces already white/colour washed shall be broomed down to remove
all dust, dirt, loose scales of lime wash or other foreign matters.
All damaged portions of the surface plaster shall be removed to full depth of
plaster in rectangular patches and plastered again after raking the joints in
masonry properly. Such portions shall be wetted and allowed to dry before any
operation. All holes, cracks, patches etc. not exceeding 0.1 sq. m. in area shall be
made good with material similar to that of the surface. Surfaces affected by
efflorescence, moss, fungi, algae, lichen etc. shall be treated in accordance with
IS: 2395.
The fat lime conforming to IS: 712 shall be slaked at site and shall be mixed and
stirred with about 5 litres of water for 1 kg. of unslaked lime to make thin cream.
This shall be allowed to stand for a period of 24 hours and then shall be screened
through a clean coarse cloth. 4 kg of gum dissolved in hot water shall be added to
each cubic metre of lime cream. Ultramarine blue (for white wash) of approved

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 21 of 36
Strategic Storage Project, at Padur

quality conforming to IS: 55 @ 3 gram per kg. of lime shall be added to the
solution. The whole solution shall be stirred thoroughly before use.
For colour washing sufficient quantity of colour wash enough for the complete job
shall be prepared in one operation to avoid any difference in colour. Mineral
colours of approved shade and quality not affected by lime shall be added to the
white wash solution in proportions as directed by Engineer-in-charge. Solid lumps
etc. in the colour powder shall be ground to fine powder, sieved and mixed evenly
and thoroughly to the white wash solution.
White/ colour wash shall be applied with "MOONJ" brush to the in minimum 3
number of coats. The operation for each coat shall consist of stroke of the brush
from the top to down wards, another from the down to upwards over the first
stroke, similarly one stroke horizontally from right and another stroke from the left.
Each coat shall be allowed to dry before the next coat is applied. The white
washing on ceiling should be done prior to that on walls.
Surfaces of doors, windows, floors etc. shall be protected from being splashed
upon. Such surfaces shall be cleaned of white/ colour wash splashes.

(B) Oil Bound Distempering

Scaffolding shall be erected for distempering in such a way that no part of


the scaffolding shall rest against the surface to be distempered.
The oil bound distempering work shall consist of:-
(a) Preparation of surface:-
The surface shall be thoroughly brushed free from dust, dirt, grease,
mortar droppings, other foreign matter and shall be made smooth by sand
papering. In case of distempering over existing distempered surface, the
existing distempering shall be scrapped by steel scrappers leaving a clean
surface. All nails shall be removed. Pitting in plaster shall be made good
with plaster of paris mixed with distemper of colour to be used. The surface
then shall be rubbed down again with a fine grade sand paper and made
smooth. A coat of distemper shall be applied over the patches. The surface
shall be allowed to dry thoroughly. The surface affected by moss, fungus,
algae, efflorescence shall be treated in accordance with IS: 2395. Any
unevenness shall be made good by applying putty made of plaster of paris
mixed with water including filling up the undulation and then sand papering
the same after it is dry. Scaffolding wherever required shall be erected in
such a way that no part of the scaffolding shall rest against the surface to
be painted.
(b) The primer coat:-
The primer coat shall be alkali resistant primer or distemper primer and
shall be of the same manufacture as oil bound distemper. If the wall
surface plaster has not dried completely, alkali resistant primer otherwise
distemper primer shall be applied. The mixture of alkali resistant primer
shall be prepared as per approved manufacturer's instructions.
(c) Base preparation:-
After the Primer coat, the base preparation shall include applying two or
more coatings of oil based putty in paste form made from chalk powder

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 22 of 36
Strategic Storage Project, at Padur

mixed with linseed oil, white zinc, varnish etc. as per manufacturer’s
recommendations. After each coat of putty, sandpapering of the surfaces
shall be done.
(d) Application of Distemper:-
After the base preparation coats have dried, the surface shall be lightly
sand papered and dusted off avoiding rubbing off of the primer coat. The
distemper shall conform to IS: 428 and shall be diluted with water or any
other prescribed thinner recommended by the manufacturer. Minimum two
coats of distemper shall be applied with brushes in horizontal strokes
followed by immediate vertical strokes, which together shall constitute one
coat. The subsequent coats shall be applied after at least 24 hours
between consecutive coats to permit proper drying of the preceding coat.
The finished surface shall be even and uniform without patches, brush
marks drops etc. Application of a coat in each room shall be finished in one
operation. 14 cm double bristled distemper brushes shall be used. After
each days work brushes shall be thoroughly washed in hot water with soap
solution and hung down to dry.
Surfaces of doors, windows, floors etc. shall be protected from being splashed
upon. Such surfaces shall be cleaned of distemper splashes.

(C) Waterproof Cement Paint


The surface shall be thoroughly cleaned of all dirt, dust, mortar dropping and other
foreign matter before paint is to be applied. Surfaces already white/colour washed
shall be broomed down to remove all dust, dirt, loose scales of lime wash or other
foreign matters.
Scaffolding, Preparation of Surface shall be same as white wash. The surface so
prepared shall be thoroughly wetted with clean water before the paint is applied.
Waterproof cement paint of approved make shall be mixed with water and stirred
to obtain a thick paste, which shall then be diluted to brushable consistency. The
proportion of mixture shall be as per manufacturer's recommendation. The paint
shall be mixed in such quantity, which can be used up within an hour of mixing to
avoid setting and thickening of the paint.
The surface shall be treated with minimum two coats of waterproof cement paint.
No less than 24 hours shall be allowed between two coats and subsequent coats
shall be applied only after the preceding coat has become hard to resist marking
by subsequent brushing. The finished surface shall be even and uniform in shade
without patches, brush marks, paint drops etc. Cement paints shall be applied with
a brush with relatively short stiff hog or fibre bristles.
Curing shall be started after the paint has hardened. Curing shall be done by
sprinkling with water two or three times a day. This shall be done between coats
and for at least two days following the final coat.
Surfaces of doors, windows, floors etc. shall be protected from being splashed
upon. Such surfaces shall be cleaned of paint splashes.

(D) Plastic Emulsion Paint


The Plastic Emulsion paint work shall consist of
(a) Preparation of surface

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 23 of 36
Strategic Storage Project, at Padur

The surface shall be thoroughly brushed free from dust, dirt, grease,
mortar droppings, other foreign matter and shall be made smooth by sand
papering. In case of plastic emulsion paint work over existing distempered/
emulsioned surface, the existing distempering/ emulsion shall be scrapped
by steel scrappers leaving a clean surface. All nails shall be removed.
Pitting in plaster shall be made good with plaster of paris mixed with plastic
emulsion of colour to be used. The surface then shall be rubbed down
again with a fine grade sand paper and made smooth. A coat of plastic
emulsion shall be applied over the patches. The surface shall be allowed
to dry thoroughly. The surface affected by moss, fungus, algae,
efflorescence shall be treated in accordance with IS: 2395. Any
unevenness shall be made good by applying putty made of plaster of paris
mixed with water including filling up the undulation and then sand papering
the same after it is dry. Scaffolding wherever required shall be erected in
such a way that no part of the scaffolding shall rest against the surface to
be painted.
(b) The primer coat
The primer coat shall be alkali resistant primer or emulsion primer and
shall be of the same manufacture as plastic emulsion paint.
(c) Base preparation
After the Primer coat, the base preparation shall include applying two or
more coatings of oil based putty in paste form made from chalk powder
mixed with linseed oil, white zinc, varnish etc. as per manufacturer’s
recommendations. After each coat of putty, sandpapering of the surfaces
shall be done.
(d) Application of Plastic Emulsion Paint
After the base preparation coats have dried, the surface shall be lightly
sand papered and dusted off avoiding rubbing off of the primer coat. The
plastic emulsion paint shall conform to IS: 5411 (Part- I) and shall be
diluted prescribed thinner recommended by the manufacturer. The paint
mix shall be continuously stirred while applying for maintaining uniform
consistency. Number of coats shall be as specified. The painting shall be
laid evenly and smoothly by means of crossing and laying off. The crossing
and laying off consists of covering the area with paint, brushing the surface
hard at first, then brushing alternately in opposite direction 2 to 3 times and
then finally brushing lightly in a direction at right angles to the same. In this
process, no brush marks, no hair marks no clogging of paint puddles shall
be permitted. The full process of crossing and laying off will constitute one
coat. The paint shall be applied by means of brush or roller. Before starting
painting with plastic emulsion paint, the prepared surface shall be treated
with two coats of primer consisting of cement, primer, whiting and plastic
emulsion paint shall start only after the preceding coat has become
sufficiently hard to resist brush marking. Subsequent coats of plastic
emulsion paint shall also be started after the preceding coat is dried by
evaporation of water content. The surface on finishing shall present a flat,
velvety smooth finish, even and uniform shade without patches, marks,
paint drops etc. Application of a coat in each room shall be finished in one
operation.

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 24 of 36
Strategic Storage Project, at Padur

Brushes shall be quickly washed in water immediately after use and kept
immersed in water during break periods to prevent the paint from hardening on the
brush. Old brushes, if used shall be completely dried of turpentine/ oil paints by
washing in warm soap water. No oil base putties shall be used in filling cracks/
holes. Washing of painted surface shall not be done within 3-4 weeks of
application.
Surfaces of doors, windows, floors etc. shall be protected from being splashed
upon. Such surfaces shall be cleaned of splashes.

(E) Acrylic based Exterior Emulsion Paint


Exterior wall / surfaces shall be thoroughly cleaned of dust, loose paint and fungus
with the help of wire brush, water and sandpaper. Special attention shall be paid
to the top of parapets, cills and other horizontal surfaces where fungus is most
likely to grow. The surface affected by moss, fungus, algae, efflorescence shall be
treated in accordance with IS: 2395. All cracks shall be filled up with white cement
or cement –sand mixture.
Scaffolding , preparation of surface shall be same as for water proof cement
paint.
The paint shall be of ‘Apex’, ‘Ace’ of Asian paints or Snowcryl-XT of ‘Snowcem
India Ltd.or approved equivalent.

(F) Acrylic Copolymer Aggregate Finish


The textured coating shall consist of twin pack fine grade wall coating system; with
fine grade silica granules/ dry flakes made of special grade of china clay / granite
type flakes of ‘Heritage’ or equivalent in approved shade and texture; mixed in-situ
with 100% acrylic polymer bonding agent, inorganic pigments and other additives
to form a crack free, flexible, tough, waterproof coating.
The surface to be coated shall be cleaned and all dirt, dust, grease and loose
particles shall be removed. Any old textured surface shall be removed with
removing agent as per manufacturer's instructions.
The textured coating shall be applied over plastered surfaces. The granules/
flakes etc., bonding material, mixing, method of application surface preparation
etc. all shall be as per manufacturer’s recommendations and specifications.

(G) Plaster Of Paris Punning


Plaster of Paris punning shall be applied over roughened plastered surfaces.
Superior quality Plaster of Paris of approved make shall be mixed with water to
obtain paste like consistency and shall be applied on walls, ceiling etc. in sufficient
thickness to give an absolutely smooth, plumb and straight surfaces.

(H) Water Repellant Finish


It shall be a coating of silicon/ acrylic based Water Repellant finish (as per
approved manufacturer’s specifications) to be applied on walls. The surface shall
be cleaned of all dust, dirt etc. by rigorous brushing. All the cracks shall be filled
with white cement and pigment to match. The coating shall be applied evenly with
brush including curing, drying the coated surfaces for 24 hours etc. all complete as
per approved manufacturer’s specifications and recommendations.

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 25 of 36
Strategic Storage Project, at Padur

(I) Painting Of Wood Surfaces (Synthetic Enamel Paint)


Preparation of wood surface shall conform to IS: 2338 (Part-1) in general. All
woodwork shall be dry and free from any foreign matter. Nails shall be punched
well below the surface. The surface shall be smoothened off with abrasive paper
used across the grain prior to painting, with the grain prior to the staining. Any
knots, resinous or bluish sap wood, cutting out of which is not justified shall be
covered with red lead conforming to IS: 103.
Plywood and block board shall be treated in the same manner as for wood work.
Particle boards surface shall be filled with a thin brushable filler and finished as for
solid wood. Painting of wood surfaces shall consist of:
(a) Priming
Priming shall be in accordance with IS: 2338 (Part I and II). Dirt or any
other extraneous material on the surface shall be removed and the priming
shall be applied by brushing. Priming shall be done on all exposed and
unexposed surfaces. Unless specified otherwise all joinery work intended
to be painted shall receive at least 2 coats of primer. Type of primer shall
be in accordance with Table-1 and Table-2 of IS: 2338 (Part-II).
(b) Stopping and Filling
Stopping and filling shall be done after priming. Stopping shall be made to
the consistency of stiff paste and shall be used to fill holes and cracks.
Filler shall be used to level up slight irregularities of the surface. Filler shall
be applied with a putty knife and subsequently rubbed down to a level
surface with abrasive paper. The filler coat shall be allowed to fully flatten
and harden before subsequent coat is applied.
(c) Application of Undercoat
Under coat shall be applied after the surface has been primed, stopped
and filled, and rubbed down to a smooth surface. Under coat may be
brushed or sprayed. After drying the coat shall be carefully rubbed down
and wiped clean before the next coat is applied. The type of undercoat
shall be depending upon the finishing and in accordance with Table 1 and
Table-2 of IS: 2338 (Part II).
(d) Finishing
The finishing paint shall be two or more coats of synthetic enamel paint
and shall be applied either by the brush or by spraying to give a uniform,
smooth and glossy finish. Reference shall be made to the Table-1 and
Table-2 of IS: 2338 (Part-II).

(J) Polishing of Wooden surfaces (Application of Clear Finishes)


For the application of clear finishes, the following procedures shall generally be
adopted in accordance with IS: 2338 (Part-I).
a). Filling
b). Staining
c). Sealing
d). Finishing

(a) Filling

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 26 of 36
Strategic Storage Project, at Padur

Fillers shall be applied to prevent the excessive penetration of the finish to


the surface for obtaining a smooth finish. Fillers shall be conforming to IS:
345. Fillers shall be heavily applied to the wood surface by hand, using
hessian or jute rag across the grain. It shall be rubbed when still wet to get
better penetration. After 5-10 minutes it shall be wiped off by hand across
the grain followed by a light wipe with the grain. The filled surface shall be
dried preferably over night and smoothened with abrasive paper.
(b) Staining
i) Spirit Stains
Spirit stains are solutions of spirit soluble dyes in Industrial
methylated spirit.
ii) Oil Stains
Oil stains are solutions of oil soluble dyes in linseed oil, but,
usually consist of insoluble, semi-transparent pigments ground
in linseed oil and thinned with turpentine or other solvent.
iii) Preparation of Wood for Staining
Surface intended for staining shall be kept scrupulously clean and
free from greasy finger marks. It shall be prepared by careful
smoothing with fine abrasive paper used in the direction of the
grain. Small cracks/ nail holes shall be stopped with plastic wood/
fine plaster of paris. The stopping shall be rubbed down with fine
abrasive paper when hard and touched with a thinned knotting
before staining. In case of oil staining stopping shall be done after
staining using tinted putty or wood filler.
iv) Application of Stains
Stains shall be applied by brushing and wiping or by spraying. The
stain shall be so thinned that it can be applied fairly, liberally
without over staining and over lapping.
(c) Sealing
A suitable sealer shall be applied on the filled and sanded surface to
prevent absorption by the wood of the succeeding coats of finish and to
seal stain and filler and thus preclude their bleeding into the finish coat.
Sealer may be sprayed on taking care not to flood the surface and it shall
be allowed to dry hard. When fully dry the surface shall be sanded taking
care not to cut through at corners and edges. Dust shall be blown off and
surface wiped with a clean rag.

(d) Finishing
The stained surface shall be varnished, wax-polished or french polished as
required after it is dried.
i) Varnishing
Varnishing of wood and wood based material shall be in
accordance with IS: 2338 (Part-I).
Surfaces to be varnished shall be prepared to produce a smooth,
dry and matt surface and all dust and dirt shall be removed from
the surface. The Varnish shall be applied liberally with a brush and
spread evenly over a portion of the surface with short light strokes

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 27 of 36
Strategic Storage Project, at Padur

to avoid frothing. It shall be allowed to flow out while the next


section is being laid in. Excess Varnish shall be scraped out of the
brush and then the first section be crossed, re- crossed and laid off
lightly. The Varnish, once it has begun to set, shall not be
retouched. In case of any mistake, the Varnish shall be removed
and the work shall be started afresh.
Where two coats of varnish are applied, the first coat shall be a
hard drying under coating or flatting varnish which shall be allowed
to dry hard and then be flatted down before applying the finishing
coat. Sufficient time shall be allowed in between two coats.
When flat varnishing is used for finishing, a preparatory coat of
hard drying undercoating of flatting varnish shall first be applied
and shall be allowed to harden thoroughly. It shall then be lightly
rubbed down before the flat varnish is applied. On larger areas, the
flat varnish shall be applied rapidly, and the edges of each patch
applied shall not be allowed to set, but shall be followed up whilst in
free working conditions.

ii) French Polish


French polish shall conform to IS: 348. Suitable pigments shall
be added to get the required colour.
The surface to be French polished shall be rubbed down to
smoothness with sand paper and shall be well dusted. Pores in
the surface shall be filled up with fillers.
A pad of woolen cloth covered by a fine cloth shall be used to apply
the finish. The pad shall be moistened with polish and rubbed hard
on the surface in a series of overlapping circles applying the polish
sparingly but uniformly over the entire area to give an even surface.
A trace of linseed oil may be used on the face of the pad for the
purpose. The surface shall be allowed to dry and the remaining
coats applied in the same way. To finish off, the pad shall be
covered with a fresh piece of clean fine cloth, slightly damped with
methylated spirit and rubbed lightly and quickly with circular
motions. The finished surface shall have a uniform texture and high
gloss.

(K) Painting of Steel and Other Metal Surface


Reference shall be made to IS: 2524 and IS: 1447.
The surface, before painting, shall be cleaned of all rust, scale, dirt and other
foreign matter with wire brushes, steel wool, scrappers, sand paper etc. The
surface shall then be wiped finally with mineral turpentine, which shall then be
removed of grease etc. The surface then shall be allowed to dry.
In case of GI surface, surface so prepared shall be treated with Mordant solution
(5 litre for about 100 Sq.M.) by rubbing the solution generously with brush. After
about half an hour, the surface if required shall be retouched and washed down
thoroughly with clean cold water and allowed to dry.
Approved quality primer and paint in specified numbers of coats shall be applied
as per manufacturer's recommendations either by brushing or spraying. Each
subsequent coat shall be applied only after the preceding coat has dried.

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 28 of 36
Strategic Storage Project, at Padur

1.2.7 ROOFING
Reference shall be made to the following Indian Standards for information etc. not
covered in the specification. In case of any conflict/contradiction, provisions of
specification shall override.
IS: 277 : Galvanized steel sheet (plain & corrugated).
IS: 513 : Cold rolled low carbon steel sheets and strips.
IS: 730 : Hook bolts for corrugated sheet roofing.
IS: 1728 : Specification for sheet metal rain water pipes upto 100
mm nom. size gutters, fittings and accessories.
IS: 2527 : Code of practice for fixing rain water gutters and downpipes
for drainage
IS: 12866 : Specification for plastic translucent sheets made from
polyester resin (glass fiber reinforced)
IS: 1230 : Cast iron rainwater pipes & fittings.
The roof slope shall be as specified and in general not pitched flatter then 1:5. The
normal pitch if not specified shall be 1:2. Approved manufacturer shall supply materials.
The items supplied shall be free from cracks, chipped edges or corners or other
damages. Storage and safety precautions shall be taken to avoid damage to the
accessories.

(A) Precoated Zinc Aluminium Steel Sheet Roofing / Cladding


The base metal of the roofing shall be Cold Rolled Steel Sheet conforming to IS:
513. It shall be zinc aluminium coated by Hot-dip process as per AS: 1397/ IS:
277. The bottom unexposed surface shall then be coated with alkyd backer of
minimum 5 microns over a 5 micron coat of primer. Top exposed surface shall
have primer of minimum 5 microns followed by SMP/ Super Polyester top coat of
minimum 20 microns of specified colour.
The Precoated zinc aluminium steel sheets shall meet the following performance
standards:-
Pencil Hardness : Min. HB
T-Bending Test : 5T
Impact Resistance : Min. 10J
Salt Spray Test : 1000 hours (Exposed top side)
QUV – Wealterometer Test : 1000 hours
Humidity Test : 1000 hours
Temperature Resistance : 100 deg C for 24 hours
Fire Performance : Class-I
The profiles shall have a depth of not less than 28 mm at a pitch of 195 to 255mm
(with intermediate ribs). Overall total coated thickness shall be minimum 0.55mm
having base metal thickness of 0.50mm. Minimum weight (supply width) shall be
5.00 Kg/ Sq.M.
All roofing accessories like ridge, flashing, north light curves etc. shall be
fabricated out of the approved pre-coated sheet as per drawing. Metallic self
drilling self tapping fasteners for fixing shall be corrosion proof meeting
performance standard as per AS: 3566, Class-III having neoprene washers.
Sealants shall be neutral cure type and cold setting variety.

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 29 of 36
Strategic Storage Project, at Padur

(B) P.V.C. Rain Water Pipes


PVC rain water pipes shall be 110mm dia (O.D.) or 160mm dia (O.D.) as
specified/ indicated in drawings; of 6 Kg./ sq. cm. pressure rating. The pipes shall
be provided complete with necessary clamps, connections, bends, Tees, other
accessories (as per approved manufacturer’s specifications) and shall be jointed
with approved quality bonding solution. Embedded rain water pipes shall be
suitably embedded/ encased in masonry/ cement concrete (M-15) with nominal
reinforcement.

1.2.8 SANITARY FITTINGS AND FIXTURES


Reference shall be made to the following Indian Standards for any further information etc.
not covered in the specification. In case of any conflict/ contradiction provisions of
Specification shall override.

IS: 2556 : Specification for Vitreous Sanitary appliances (Vitreous-China,


Part 1-17).
IS: 774 : Specification for Flushing Cistern for Water Closets and Urinals.
IS: 781 : Specification for Cast copper alloy screw down bib taps and
stop valves for water services.
IS: 2064 : Code of Practice for Selection, Installation and Maintenance of
Sanitary appliances.
IS: 775 : Specification for cast iron brackets and supports for wash basins and
sinks
IS: 2064 : Code of Practice for Selection, Installation and Maintenance of
Sanitary appliances.
IS: 2548 Part-1: Specification for Plastic Seats and Covers for water closets
Part-1: Thermo set seats and covers
IS: 2548 Part-2: Specification for Plastic Seats and Covers for water closets
Part-1: Thermoplastic seats and covers
IS: 2326 : Specification for automatic flushing cistern for urinals (other
than plastic cisterns)
IS: 7231 : Specification for plastic flushing cisterns for water closets and
urinals
IS: 9758 : Specification for flush valves and fittings for water closets and
urinals
All plumbing fittings shall be as specified in Architectural Design Basis. All wall fittings
shall be fixed with nylon sleeve and CP brass screws and washers.

(A) Wash Down (European) Type Water Closet


Wash down water closet of approved make and colour shall be of pattern-1
conforming to IS: 2556 Part-II. Water Closet shall be of one piece construction,
double trap syphonic type. This shall be fixed with plastic seat and cover as per
IS: 2548 of approved make and colour, fixed with CP brass hinges and rubber
buffers and an integral 100 mm dia 'S' or 'P' trap with antisyphonage vent horn.
A low level earthenware cistern of approved make and colour conforming to IS:
774 of about 10 litres capacity, with 15mm dia PVC inlet pipe (with 15mm dia CP

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 30 of 36
Strategic Storage Project, at Padur

Brass stop cock) and brass union with wiped solder joint, internal overflow
arrangement, 40 mm dia CP brass flushing pipe. CI or MS supporting brackets
shall be fixed with the water closet. The closet shall be fixed firmly in the floor with
matching cement mortar. All exposed metallic surfaces shall be painted with two
coats of synthetic enamel paint of approved quality over a coat of red oxide zinc
chromate primer. The clearance between top of pan and bottom of cistern shall
not exceed 300 mm.
One number heavy grade approved quality CP Brass bib cock conforming to IS:
781 (with necessary connections); one number approved quality CP Brass Toilet
paper holder (fixed to wall with wooden cleats, CP Brass screws) shall be
provided with each WC.
The work shall include providing and fixing of all fittings, breaking floors and wall,
making good the same, making inlet and outlet connection to the cistern and the
closet, testing of joints, painting the exposed metallic surface with two coats of
synthetic enamel paint over a coat of primer etc. complete.

(B) Indian Type Water Closet


Squatting Pan shall be 550mm x 440mm Orissa Pan of approved make and
colour, conforming to IS: 2556 Part-III with integrated footrests. The closet shall be
fixed in the floor with 150 mm thick sand cushion and shall be connected with 100
mm dia CI `S' or `P' traps. The closet shall also be fitted with 10 litres valve less
syphonic type glazed earthenware flushing cistern of approved make and colour,
conforming to IS: 774, and complete with all accessories like 15 mm dia. PVC inlet
connection pipe 450mm long (with 15mm dia CP Brass stop cock and brass
union), PVC ball valves, C.P Brass handle, telescopic 32 mm dia GI telescopic
flushing pipe with union, 15 mm dia GI overflow pipe with mosquito proof net and
fixed with glazed earthenware cover.
The cistern shall be fixed on MS brackets at a minimum height of 2150 mm from
top of pan. All exposed metallic surface shall be painted with two coats of
synthetic enamel paint of approved quality over a coat of red oxide zinc chromate
primer (primer is not required for GI pipes).
One number heavy grade approved quality CP Brass bib cock conforming to IS:
781 (with necessary connections) shall be provided with each WC.
The work shall include providing and fixing water-closet and flushing cistern with
all accessories, breaking wall and floors and making good the same, all inlet and
outlet connections of cistern and water closet, finishing of solder joints, painting
and testing of all connections etc. complete.

(C) Urinals
(a) Urinals with flushing cisterns
Half stall type urinal shall be of approved make and colour, 610mm x
400mm x 380mm size and conforming to IS: 2556 Part VI. Urinals shall be
of single piece construction with integral flushing box rim. These shall be
mounted on walls. The flushing inlet pipe shall be of CP brass 15 mm
dia and waste pipe 32 mm dia GI, 750 mm long shall be embedded in
wall. Necessary unions and CP bottle trap shall be provided in the waste
line.

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 31 of 36
Strategic Storage Project, at Padur

Rawl plugs with CP brass screws shall be used for fixing the urinal. Fixing
shall ensure that no liquid is left over in the pan after flushing. Unless
otherwise indicated height above finished floors shall be 600 mm.
Urinals shall be connected to glazed earthenware automatic flushing
glazed earthenware cisterns either individually, or in groups. Where
individually connected to flushing cistern, the cistern capacity shall be 5
litres. For two urinals, one cistern of 10 litres capacity and for three urinals,
one cistern of 15 litres, capacity shall be provided.
Cistern inlet shall be 15 mm dia PVC pipe with brass union. Outlet pipe
from cistern shall be 25mm CP brass main, with 15 mm CP distributor pipe
of sufficient lengths to reach each bowl. Where individual cisterns are
provided the outlet shall be of 15 mm CP brass.
The work shall include urinals inlet and outlet pipes, flushing cistern,
breaking and making good the walls and flooring, making inlet and outlet
connections including all related G.I. piping work (embedded in wall),
painting exposed brackets and exposed metallic parts with two coats of
synthetic enamel paint of approved quality over a coat of red oxide zinc
chromate primer etc. all complete.
(b) Urinals with Sensors
Half stall type urinal of approved color & approved make (Parryware or
equivalent) of size 590mm x 375mm x 390mm, with in-built fully
automatic photo electric IR sensing system with fittings, standard size
CP brass flush (PARKO or approved equivalent heavy grade) pipe,
spreader with unions and clamps (all in CP brass) with waste fitting as
per IS: 2556, CP brass ‘P’ trap with stainless steel dome grating and
other couplings in CP brass including painting of fittings and brackets,
cutting and making good the walls and floors wherever required etc. all
complete; also including all necessary fittings/ accessories for photo
electric IR sensing with all necessary hard wares, switch and socket
and electrical fittings etc. all complete.
All the Urinals shall be separated by Granite/ Marble partitions (of minimum 19mm
thick slabs; each partition in one piece) of minimum size 1000mm x 600mm.
These partitions shall be inserted upto 100mm depth in the wall and fixed with
cement mortar 1:3 (1 cement: 3 coarse sand by volume) and suitable sized M.S.
Channel (embedded in wall with grouting) at bottom. The M.S. Channel at bottom
shall be finished with two coats of synthetic enamel paint of approved quality over
a coat of red oxide zinc chromate primer.

(D) Wash Basins


Wash Basins shall be flat back wash basin of approved size, colour, shape &
make with required number of tap holes and conforming to IS: 2556 Part-IV, with
anti splash rims on three sides. Wash basins shall be of one piece construction
including a combined overflow having an area of not less than 5 Sq. cm. shall be
provided in the front or back of the bowl and it shall be so designed as to facilitate
cleaning of the overflow. This shall be either fitted on CI or MS brackets or fitted
neatly in the cutout in the granite stone finished R.C.C. counter. Brackets shall
conform to IS: 775. Each wash basin shall be provided with 15mm dia pillar cock
of approved make, rubber plug with CP brass chain, 32mm CP Waste fitting of
standard pattern with 32mm dia G.I. pipe, CP Brass bottle trap, CP Brass 15mm

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 32 of 36
Strategic Storage Project, at Padur

dia stop cock etc. complete with all related accessories, fittings and fixtures. The
wall side shall be fixed well flushed with the plaster or wall and the joint if any,
shall be properly stopped with an elastomeric sealant. The top of rim of the wash
basin shall be fixed at 800 mm above finished floor level, unless otherwise
specified.
The work shall include provision and fixing of wash basin with all accessories,
providing stop cocks and pillar cocks, breaking and making good walls, fixing and
making inlet and outlet connections for stop cock, pillar cock and waste pipe,
providing cut out in granite slab counter top (and R.C.C. underneath), providing &
fixing MS brackets painted with two coats of synthetic enamel paint of approved
quality or aluminum paint over a coat of red oxide zinc chromate primer etc.
complete.
Following fixtures of approved quality shall be provided for each Wash Basin:-
1. Mirror : Full length beveled edged Mirror of 5.5mm thick
float glass with 6mm thick water proof plywood
or A.C sheet backing for counter Wash Basins.
OR
550mm x 400mm beveled edged Mirror of 5.5mm
thick plain glass with 6mm thick AC sheet backing
for all other Wash Basins.
2. Glass Shelf : 600mm x 120mm x 4mm thick Glass shelf with
CP brass bracket & guard rails fixed on wall.
3. Towel Rail : Chromium plated brass towel rail of 20 mm dia,
600mm length & 1.25mm thickness.
4. Liquid soap container: Chromium plated Liquid soap container.
All the fixtures shall be fixed to the wall at identified locations with wooden cleats
and CP Brass screws including cutting walls, making good the same etc.
complete.

(E) Glazed Chinaware Sink


This shall be white glazed vitreous china Lab sink/kitchen sink of 610mm x
450mm x 250mm size conforming to IS : 2556, Part-V. It shall be fixed with
approved quality M.S./C.I. brackets conforming to IS : 775. One 15mm dia CP
brass bibcock, 15mm dia PVC connection, C.P. brass chain with 40mm dia GI
pipe connected to floor trap with unions shall be provided. All exposed metallic
surfaces shall be painted with 2 coats of approved shade and quality synthetic
enamel paint (ICI or approved equivalent) over a priming coat of approved quality
red oxide zinc chromate. All necessary cutting of floor, walls, counter etc. shall be
made and then finished etc. all complete.

(F) Stainless Steel Sink


The stainless steel Kitchen/ Laboratory sink shall be of approx. size 610mm x
450mm 200mm and made of min. 1mm thick stainless steel sheet of `Salem Steel'
or equivalent. It shall be supported on M.S. brackets conforming to IS: 775. One
15mm dia C.P brass long body bib cock (if fixed to wall) or swivel type pillar cock
(if fixed to counter) shall be provided. 15mm dia PVC/ G.I. connections to floor
trap with unions shall be provided. All exposed metallic surfaces shall be painted
with min. 2 coats of synthetic enamel paint of approved make and shade over a

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 33 of 36
Strategic Storage Project, at Padur

coat of red oxide zinc chromate primer. All necessary cutting of floor, walls,
counter etc. shall be made and then finished etc. all complete.

1.2.9 FALSE CEILING, FALCE FLOORING, UNDERDECK INSULATION ETC.


(A) Aluminium Lineal False Ceiling
Aluminium lineal false ceiling shall consist of:-
(a) Panel Carriers:-
These shall be roll formed out of coated steel/ 0.95mm thick aluminium
alloy; 32mm wide and 39mm deep with cut-outs to hold panels in a module
of 90mm/ 100mm; all complete as per manufacturer’s standard details and
specifications. When two or more carriers are to be joined, they shall be
joined together by means of carrier splices which will clip on to holes in the
sides of the carriers and hold them firmly in place while maintaining the
required module. The carriers shall be suspended from roof by 4mm dia.
galvanized steel wire rod hangers, with height adjustment springs of
stainless steel. Hangers shall be fixed to roof by “J” hooks and nylon
inserts. Edge profiles shall be “L” shaped roll- formed out of 0.6mm
aluminium alloy with coating.
(b) Panels:-
Panels shall be 84mm wide, 16mm deep; roll formed out of 0.5mm
aluminium alloy 5050 or 3005. The aluminium panels shall be chromatised
and stove enamelled (coil coated) on both sides in approved shade.
Panels shall be factory cut in lengths upto 5 metres to suit site dimensions.
As per air- conditioning requirements, for return air, (wherever required)
perforated panels shall be used, which shall have 2mm dia holes at 5mm
centre to centre staggered in uniform pattern and symmetrically located in
the middle of the panel face.
The ceiling shall be erected in continuous manner as per approved manufacturer’s
recommendations, specifications etc. The false ceiling shall have perfect levels,
linearity etc. as required. Necessary cut outs for Electrical, AC and other fixtures
shall be provided as per drawing and in co- ordination with relevant construction
activities.

(B) Aluminium Planks/ Tiles False Ceiling


This false ceiling system shall consist of:-
(a) Panel carriers:-
These shall be rows of 0.5mm thick galvanized steel clip in profiles of size
40mm x 20mm. These shall be suspended from roof structure by means of
G.I. suspension angles, ceiling brackets and hold on clamps @ maximum
1200mm c/c all complete as per approved manufacturer’s specifications.
(b) Aluminium Tiles:-
Aluminium Ceiling Tiles shall be 600mm x 600mm manufactured out of
0.7mm thick aluminium alloy AA3105, chromatised and stove enamelled
(coil coated) with square edges produced on advanced equipments.
Exposed side of the tile shall have 20 micron (minimum) coil coated
polyester finish and 5 micron back coat of Alkyd primer. The short sides of
each plank shall be raised and pipped and stopped to ensure positive

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 34 of 36
Strategic Storage Project, at Padur

engagement into the spring clip- in profiles, and shall allow for demounting
of individual planks.

(C) Cavity (False) Flooring (Steel plate with cementitious infill)


The False flooring system shall consist of 600mm high truly leveled and aligned
cavity/ false flooring system having load bearing capacity of distributed load of
minimum 1350 kg/ sq. m, consisting of:
(i) Sub-structure/ pedestal assembly of zinc electro plated steel (designed for speedy
assembly/ removal for relocation/ maintenance) comprising of 75mm x 75mm x
3.5mm embossed head mechanically riveted to a 100mm long 19mm dia rolled
formed stud and 2 check nuts for level adjustment (for a maximum of 25mm) and
arresting vertical movement, pedestal head also consisting of an anti-vibrational
PVC cap (for panel and stringer location), pedestal base assembly consisting of
22.2mm dia (OD) pipe of 1.6mm thickness mechanically locked on a press for
perpendicularity and welded to base plate 100mm x 100mm x 2mm thick (with
stiffening folds) fixed/ anchored to main concrete floor @ 610mm c/c both ways by
means of adhesive or fastener as recommended by manufacturer

(ii) Stringers of size 21mm x 32mm x 0.8mm x 570mm length made of hot dip
galvanized steel cold rolled construction with ribs embossed on 3 sides (designed
for strength, lateral stability, rolling loads and to support panels on all four sides for
alignment), stringers having counter sunk holes at both ends to accommodate
bolting of M6 machine screws to the pedestal head assembly.

(iii) Access floor panel of size 600mm x 600mm made of all steel welded construction
(cleaned, degreased and phosphate with 11 tank process and coated with 40-60
micron epoxy coated and heated to achieve adhesion to the panel surface and
corrosion resistance) with an enclosed bottom pan consisting of multiple
hemispherical and reverse cones and top plain sheet fuse welded at 129 locations
to form a panel of an overall depth 37mm; the inner empty core of the panel
injected with light weight fire retardant, non-combustible cementitious compound
(at high pressure to fill all crevices of the panel); each panel finished on top with
2mm thick fire retardant floor grade high pressure laminate in approved design/
shade/ texture on a semi-automated lamination line; the edges of the laminated
panels provided with conductive PVC edge trim 5mm wide on all sides
(mechanically locked and sealed in place).

Necessary cut-outs shall be made in the panels for cable routing, control panel
fixation etc. as per drawing.

Necessary ramps, slopes, steps etc. shall be also provided for as per drawing.
Around a control panel/ rack, the residual space left out shall be filled up with cut
panels of uniform size as required to fully close the gap between the adjacent full
panel and the control panel base channel. In this case the part floor panel shall
extend upto the full width of the base channel and the cut size shall be determined
accordingly.

The cavity between false flooring and base floor shall be properly cleaned and
made dust free. The floor shall be finally coated with polyurethane based coating.

(D) Underdeck Insulation (Phenolic Foam)

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 35 of 36
Strategic Storage Project, at Padur

Underdeck insulation shall be of phenolic foam rigid slab of 25mm thickness and
approx. 1000mm x 500mm size as specified and shall conform to IS: 13204. It
shall have density of 32 kg / M3 and K Value 0.016 KCal/hr M C as per BS 4370,
Part 2. The insulation shall be classified as `Non Combustible' as per BS 476, part
5 and `Class I' for surface spread of flame as per BS 476, part 7. It shall be
prelaminated on both sides with kraft paper.
The entire soffit of slab and beams shall be thoroughly cleaned. Bituminous primer
or zinc chromate primer shall be applied evenly @ 0.5 kg/m2 over the entire
surface. Hot bitumen or CPRX adhesive shall then be applied on the insulation
panel @ 1.5 kg/Sq.M. The panels shall be pressed in position and further secured
by dash fasteners.
The underdeck insulation shall be fixed only after all fixtures like hooks, clamps,
cleats etc. for light fixtures, ducts etc. have been fixed in the ceiling.

1.2.10 MISCELLANEOUS ITEMS


(A) Plinth Protection (Without Drain)
The plinth protection (all round the buildings- without drain) shall consist of
a layer (150mm thick) of compacted sand and over that 100mm thick M-15
grade concrete top layer laid to slope. The top concrete layer shall be
trowel finished, cured etc. complete. The work also includes carrying out
the necessary excavation, disposal of surplus earthwork etc.
(B) G.I. Spout
50mm dia GI pipe spouts shall be fixed to slope for drainage of canopy,
sunshade etc., including puncturing the masonry/ RCC and grouting with
M-15 grade concrete, finishing etc. all complete.

(C) M.S. Pipe Handrail


The M.S. Pipe handrail shall consist of 25mm M.S. square balusters (one
on each step; similar spacing for horizontal portions) with 40mm x 40mm x
6mm M.S flat shoe welded at bottom of baluster; embedded into floor/
steps and grouted with M-15 grade concrete in a cut out of 100mm x
100mm x 150mm size block. 32mm dia N.B. (Medium) M.S. pipe handrail
shall be welded to balusters at top. The entire railing and balusters shall be
painted with two or more coats of synthetic enamel paint over a coat of
approved quality red oxide zinc chromate primer. All embedded metallic
portions shall be provided.

(D) Transformer Gates/ Fencing


Transformer gates/ fencing shall be made of 50mm x 50mm x 6mm M.S.
Angle frame, 50mm x 50mm x 6mm M.S. Tee stiffeners, 50mm x 50mm x
8mm welded mesh fixed to the frame by 20mm x 3mm M.S. flat beading.
The gate/ fencing shall be fixed to the masonry/ R.C.C. by M.S. hinge
arrangement (consisting of 65mm x 65mm x 6mm M.S. angle, bolt,
washers etc.) with M..S. holdfast grouted with M-15 concrete block. The
gate shall have M.S. pivot arrangement (ensuring smooth operation of the
gate), one heavy duty 450mm long M.S. aldrop, heavy duty M.S. tower
bolts etc. complete. The entire gate/ fencing with fittings/ fixtures/
accessories shall be finished with two or more coats of synthetic enamel
paint of approved make and shade over a coat of approved red oxide zinc

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SECTION: C-3.6
JOB SPECIFICATIONS
(Architecture) 6979-02-16-49-SP51 Rev.A
Process and Utility Facilities at Top Side
and Inside Cavern, for Crude Oil Page 36 of 36
Strategic Storage Project, at Padur

chromate primer. All embedded metallic parts shall be provided with


primer.

(E) Sealing of Expansion Joints


All expansion joints (25mm wide) of the building shall be sealed with
premium grade Silicon sealant (SILPRUF of GE Silicons or equivalent)
consisting of the following:-
(a) The surfaces over which it is to be applied shall be totally dried
and cleaned of all dirt, oils, mortar droppings, all loose material
etc. by vigorous wire brushing and wherever necessary by grinding
and blast cleaning (sand or water).
(b) A backup material or joint filler tapes (as per approved
manufacturer’s specifications) shall be fixed in the expansion
joint.
(c) A coat of primer as per approved manufacturers specifications
(specially developed for use with Silicon sealant material) shall
then be applied over the surface.
(d) Silicon sealant shall be applied by means of cartridge- type caul
gun, either hand or air pressure activated. The sealant shall be
applied in a continuous operation, horizontally in one direction and
vertically from bottom to top of joint opening. The sealant shall be
applied in excess so that a positive pressure adequate to properly
fill and seal the joint is created. The sealant shall be struck with
light pressure to spread the material against the back up material
and the joint surfaces properly. The sealant shall be tooled to
slightly conclave surface. As the work progresses, the excessive
sealant shall be removed. The masking tape shall be removed
immediately after tooling. The sealant shall be cured as per
approved manufacturer’s recommendations.
Entire work shall be carried out as per as per approved manufacturers
specifications and recommendations.

(F) Anti Termite Coating


All woodwork (frames, panels etc. including hidden/ embedded portions of
wooden members shall be provided with anti- termite coatings of approved
quality aldrine-chlornated phenol compound conforming to IS: 401. Three
or more coats as required @ 3 Sq. Mtr. per coat per Kg. covering capacity
shall be applied before applying the finishing (painting, polishing,
lamination etc. as specified) coats.

Format No. EIL-1641-1924 Rev.1 Copyrights EIL – All rights reserved


SITE SPECIFIC SEISMIC SPECTRA SECTION: C-3.9
(ETDD)
6979-00-16-54-0001 Rev. 0
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 2 of 3
Strategic Storage Project, at Padur

1.0 SITE SPECIFIC SEISMIC SPECTRA


Spectral Acceleration Coefficients (Sa/g) for Design Basis Earthquake (DBE)
[as per clause no.8.3.1 of IS 1893 (Part 4) :2005]
(numerical values tabulated below)

Spectral Acceleration Coefficients (Sa/g) for Design Basis Earthquake (DBE)

Time Percentage of critical damping


Period
( sec) 0.5 1.0 2.0 2.5 3.0 3.5 4.0 5.0 7.0

0.00 0.098 0.098 0.098 0.098 0.098 0.098 0.098 0.098 0.098
0.05 0.408 0.356 0.253 0.245 0.237 0.229 0.221 0.206 0.188
0.10 0.647 0.531 0.299 0.286 0.274 0.261 0.249 0.224 0.205
0.13 0.660 0.545 0.316 0.301 0.287 0.273 0.258 0.230 0.209
0.20 0.666 0.552 0.323 0.307 0.292 0.276 0.261 0.230 0.211
0.27 0.662 0.548 0.322 0.306 0.291 0.276 0.260 0.230 0.211
0.30 0.653 0.542 0.320 0.305 0.290 0.275 0.260 0.230 0.211
0.40 0.582 0.489 0.303 0.288 0.273 0.258 0.243 0.212 0.196
0.50 0.505 0.430 0.280 0.264 0.249 0.233 0.217 0.186 0.172
0.60 0.426 0.370 0.258 0.243 0.228 0.212 0.197 0.166 0.155
0.80 0.309 0.274 0.204 0.194 0.184 0.174 0.164 0.144 0.132
1.00 0.235 0.212 0.166 0.159 0.152 0.145 0.138 0.124 0.113
1.20 0.189 0.172 0.138 0.132 0.127 0.121 0.116 0.104 0.095
1.40 0.154 0.143 0.121 0.116 0.111 0.106 0.101 0.092 0.083
1.60 0.133 0.123 0.103 0.100 0.096 0.092 0.088 0.080 0.071
1.80 0.113 0.106 0.092 0.088 0.084 0.080 0.077 0.069 0.062
2.00 0.102 0.096 0.085 0.082 0.078 0.075 0.071 0.064 0.057
2.40 0.084 0.079 0.069 0.067 0.065 0.063 0.060 0.056 0.051
2.80 0.072 0.069 0.063 0.061 0.058 0.056 0.053 0.048 0.045
3.00 0.066 0.063 0.057 0.055 0.054 0.052 0.050 0.046 0.043
3.20 0.062 0.059 0.053 0.052 0.051 0.049 0.047 0.043 0.040
3.40 0.058 0.056 0.050 0.049 0.048 0.046 0.044 0.041 0.038
3.60 0.055 0.053 0.048 0.046 0.045 0.043 0.042 0.038 0.036
3.80 0.052 0.050 0.045 0.043 0.043 0.041 0.039 0.036 0.034
4.00 0.050 0.047 0.043 0.041 0.041 0.039 0.038 0.035 0.032

The spectral acceleration values for periods greater than 4.0 seconds may
be considered same as that for 4.0 seconds.
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
SITE SPECIFIC SEISMIC SPECTRA SECTION: C-3.9
(ETDD)
6979-00-16-54-0001 Rev. 0
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 3 of 3
Strategic Storage Project, at Padur

NOTE :

1. For methodology of calculation of seismic forces and other seismic design criteria, refer
latest revisions of the following codes:
IS 1893 (Part 1) : General provisions and buildings
IS 1893 (Part 4) : Industrial structures including stack-like structures

2. For underground structures and foundations of depth 30m or below, the design horizontal
seismic coefficient Ah shall be taken as half the value calculated using clause no.8.3.1 of IS
1893 (Part 4) : 2005. For structures and foundations placed between the ground level and
30m depth, the design horizontal seismic coefficient Ah shall be linearly interpolated
between Ah and 0.5Ah.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


WIND LOAD DATA FOR PIPING SECTION: C-3.9
(ETDD)
6979-02-16-54-0002 Rev. 0
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 2 of 3
Strategic Storage Project, at Padur

1.0 SCOPE

The scope of this document is to specify the wind pressure to be considered for
calculation of wind load on piping systems. The scope does not specify any method
for wind load analysis of piping.

The effect of wind on a piping system is to produce a set of vibratory/dynamic loads


acting along different directions depending on the configuration of the piping.
However, the design wind load for a piping system is often calculated on the basis of
a statically applied maximum pressure(s) that can be expected over the design life of
the unit.

2.0 GENERAL NOTES

The wind load analysis shall be done for the following piping systems.

(i) Flare Header.


(ii) Any other line of size 20” (O.D.) & above (including insulation, if any) running
above 10 meter height from HPP level.

However, all piping systems should have a sufficient number of horizontal


restraints/guides to resist the design wind load to be calculated as per the formula
indicated in section 3 of this document and to reduce excessive horizontal deflection
of pipe due to wind load.

A manual check may be performed to estimate the approximate wind effect on pipe
where the wind analysis is not required. However, In this case also, the horizontal
restraints should be adequate to resist the wind effect.

3.0 DESIGN WIND LOAD

The design wind load on a pipe shall be calculated from the following relation:

Fwz = Cf pz Do

Where Fwz = Wind load at height z per unit length of pipe


Cf = Shape factor (to be considered as 0.7)
Do = External diameter of pipe including the insulation
pz = Design wind pressure on pipe at height z which can be obtained from
the following table.

Height (in 'm') of


≤ 10 15 20 30 50 100
pipe above ground
Design wind
1026 1131 1174 1287 1404 1577
pressure (in 'N/m2')

Note: wind pressure for any intermediate height may be linearly interpolated.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


WIND LOAD DATA FOR PIPING SECTION: C-3.9
(ETDD)
6979-02-16-54-0002 Rev. 0
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 3 of 3
Strategic Storage Project, at Padur

4.0 LOAD COMBINATIONS

All supports should be adequate for the following load combinations due to wind load
alone in addition to other load conditions considered for the design of piping:

(i) Sustained load + Wind Load


(ii) Sustained load + Thermal load + Wind Load

However, the stress in the piping should be checked only for the first load case (i.e.,
Sustained load + Wind Load) and the maximum stress in the pipe should be limited to
1.33 times the allowable stress at the maximum operating temperature.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS/ PHILOSOPHY SECTION: C-2.9
(STRUCTURAL)
6979-02-16-56-DB01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 1 of 2
Padur.

DESIGN BASIS/ PHILOSOPHY


(STRUCTURAL)

Process and Utility Facilities at Top Side and Inside Cavern, for Crude Oil
Strategic Storage Project.

PROJECT : STRATEGIC STORAGE OF CRUDE OIL, Padur

OWNER : INDIAN STRATEGIC PETROLEUM RESERVES LTD.

PMC : ENGINEERS INDIA LTD.

JOB NO. : 6979

1 13.04.2010 REISSUED FOR BIDS AR CS BVK

0 15.02.2010 ISSUED FOR BIDS AR CS BVK


Rev. Prepared Checked Approved
Date Purpose
No by by by
Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved
DESIGN BASIS/ PHILOSOPHY SECTION: C-2.9
(STRUCTURAL)
6979-02-16-56-DB01 Rev.1
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil
Strategic Storage Project, at Page 2 of 2
Padur.

DESIGN BASIS/ PHILOSOPHY

Design Basis for designing of structures shall be as per the following attachments:

Sl. No. Document No. Title

1. 6979-02-16-56-JS01 Structural Job Specifications

2. 6979-02-16-56-SP01 Structural Scope of Work


Job Specification for Shop & Field Painting
3. 6979-002-06-42-PT-01
Geotechnical data
4. 6979-00-67-41-GD-01

5. 6979-00-67-41-SP-01 Geotechnical specification for Mounded Bullets


List of standard specifications (All standard specifications
6. 6979-02-16-56-SS01
attached)
List of engineering standards (All engineering standards
7. 6979-02-16-56-ES01
attached)

Note: Latest revision of above documents shall be referred.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


2 INFRASTRUCTURE AND PROCESS SECTION: C 2.9
FACILITIES AT TOP SIDE
STRATEGIC STORAGE OF CRUDE OIL 6979-00-67-41-GD-01 Rev. 0
PROJECT, PADUR Page 2 of 5

GEOTECHNICAL DATA FOR ABOVE GROUND UNIT


OF STRATEGIC STORAGE OF CRUDE OIL AT PADUR

1.0 GENERAL:

Indian Strategic Petroleum Reserve Limited (Owner) proposed to


construct underground unlined rock cavern storage for imported crude
oil at padur (India) for 2.5 MMT. This package comprises of above
ground unit like process area and plant. Subsoil data and foundation
recommendations include herein are based on site investigation carried
out at site which is enclosed in bid document. Bidder may carry out
confirmatory soil investigations if required, to check and confirm the soil
conditions and/or to develop additional soil data if so required for
foundation design purposes. However, the recommended bearing
capacity included herein shall not be exceeded in any case. Not
withstanding the information given herein, no extra claim on time and/or
money shall be entertained by client or his representative in case of
change in any data due to local variations. It is bidder’s responsibility to
become fully acquainted with the site before submission of bid.

2.0 SCOPE OF WORK:

2.1 A design basis for foundation and slopes shall be prepared by the
bidder clearly stating type of foundations and nature of slopes for all the
structures / facilities coming in the area as mentioned above or part of it
giving all back-up calculations and the same shall be submitted to
Client / PMC for review.

2.2 It is incumbent upon the bidder to seek all technical clarifications


concerning the job prior to the bid submission. No such clarifications
shall be entertained after the award of job. Notwithstanding this, the
decision of Engineer-in-Charge, in case of any disputes shall be final.
However, it must be clearly understood by the contractor that any extra
claim and / or time extension shall not be granted under any
circumstances.

3.0 SUBSOIL PROFILE:

As per the geophysical survey and core logging of the boreholes in this
area, it is observed that top soil is reddish brown clayey silty sand with
kankars of around 0.0 to 2.0 m thick, followed by a deposit of highly
weathered decomposed laterite formation.

The third layer consists of weathered rock, grayish-black in colour


having weak to medium strength. The fourth interpreted layer
comprises of massive Granites /Granites Gneiss having P wave
velocities are in the range of 3300-6000m/s and S wave velocities
velocity are in the order of 1500 m/sec to 3100 m/sec. The layer

EIL-1647-1883.5 Rev. 1 Copyrights EIL – All rights reserved


3 INFRASTRUCTURE AND PROCESS SECTION: C 2.9
FACILITIES AT TOP SIDE
STRATEGIC STORAGE OF CRUDE OIL 6979-00-67-41-GD-01 Rev. 0
PROJECT, PADUR Page 3 of 5

represents fresh solid rock, strong to very strong of greenish grey


colour.

Refer to Geotechnical factual report attached as Section G of


this bidding document for bore logs and geophysical records.

a) GROUND WATER TABLE:

The ground water table (GWT) in the nearby area is as observed in


bore logs. However, during peak rainy season, GWT fluctuates & may
rise substantially. Hence, for design of foundation and slopes GWT
shall be taken at Finished Ground Level.

b) FINISHED GROUND LEVEL:

For finished ground level and depth of fill / cut refer general civil
document given elsewhere.

c) FOUNDATION RECOMMENDATIONS:

1) Major Structures / Equipments Foundations:

Bearing capacities as given in the table –1 below is recommended for


the design of foundation of the structures. Bearing capacities have
been worked out based on available field and laboratory test results.
Settlement with the above pressure is expected to be with in 25 mm for
foundation size 1.0 m and above.

TABLE- 1

Type Width of Depth of Net safe bearing


Foundation Type foundation below Capacity
In ( M) EGL/FGL which In shear (T/M2)
ever is lower (iv)
(i) (M)
(iii)
B L/B<1.5
Laterite 1 to 3 Do 1.5 10

Weathered 1 to 3 Do 1.5 15
rock

• NGL (Natural Ground Level) & FGL ( Finished Ground Level)

NOTE:

i) Minimum width of foundation shall be 1.0m.

ii) The recommended bearing capacity may be increased by 25% under


wind / seismic conditions.

EIL-1647-1883.5 Rev. 1 Copyrights EIL – All rights reserved


4 INFRASTRUCTURE AND PROCESS SECTION: C 2.9
FACILITIES AT TOP SIDE
STRATEGIC STORAGE OF CRUDE OIL 6979-00-67-41-GD-01 Rev. 0
PROJECT, PADUR Page 4 of 5

iii) Foundation pit bottom shall be covered with mud mat immediately after
completion of excavation.

iv) Any filled up soil/soft patch if encountered at foundation level that shall
be completely removed and replaced with PCC/well-compacted sand
fill.

v) Due to functional requirements, if depth of foundation is required to be


increased, bearing capacity may be considered same as given above.

vi) Allowable bearing capacities indicated above shall not be exceeded in


any case.

2) Minor / Lightly Loaded Structures


Foundation for these structures may be placed at a depth of 1.0 m from
FGL for foundation width up to 2.0 m and for pressure not exceeding
5.0 t/m2. Back filling after casting of foundations shall be done as per
the compaction criteria given below. Minimum width of foundation shall
be 1.0m. Bottom of the excavated pit shall be compacted before
placing of foundation.

Fill up soil shall be removed up to 1.0 m deep and 1.0 m in all around
from the edge of the footing and replaced with well-compacted sand fill
to achieve relative density 95% as per IS 2720 Part VIII.

4.0 DEEP EXCAVATIONS

In case of deep excavations, because of the high water table


conditions, special measures like side supports and appropriate
dewatering system may have to be resorted to. It shall be contractor’s
responsibility to mobilize necessary equipments and carryout deep
excavations wherever required with out any extra cost and time
implication to the owner.

5.0 ROAD AND PAVEMENT:

For laying Road and pavement crust, formation shall be prepared as


per IRC-37. In the area of cut, the road and pavement shall be laid as
per EIL’s specification enclosed elsewhere, considering a CBR value of
6% over the compacted sub-grade. In filled up area soil up to a depth of
450mm below the road crust/pavement shall be re-excavated and the
bottom of formation pit shall be compacted to 95% maximum laboratory
dry density as per IS 2720 part-VIII. The excavated pit shall be
backfilled with coarse grained soil having PI <6 of 450mm thick, laid in
layers in 150mm maximum thickness and compacted to 95% maximum
laboratory dry density as per IS 2720 Part-VIII or 85% relative density
as the case may be before laying the road crust and pavement
considering a CBR value of 6%. Proper cambering and top sealing of
the road and pavement shall be provided to restrict the ingress of
rainwater in sub-grade.
EIL-1647-1883.5 Rev. 1 Copyrights EIL – All rights reserved
5 INFRASTRUCTURE AND PROCESS SECTION: C 2.9
FACILITIES AT TOP SIDE
STRATEGIC STORAGE OF CRUDE OIL 6979-00-67-41-GD-01 Rev. 0
PROJECT, PADUR Page 5 of 5

6.0 AGGRESSIVENESS OF SOIL AND GROUND WATER TO


FOUNDATION CONCRETE:

Chemical analysis of soil samples reveals that sulphate & chloride


contents in soil are within permissible. Hence ordinary Portland cement
/ Portland slag cement / Portland Pozzolana cement may be used for
all sub structure concreting work with minimum cement content of 320
kg/m3 with maximum water-cement ratio 0.45. Concrete grade for all
sub-structure RCC shall be M-30 & cover as per Engineering Design
Basis i.e. 50 mm.

7.0 DYNAMIC PARAMETERS OF SUB-SURFACE:

The footings of the structures with dynamic loads shall be founded at


least 1.5 m below NGL/FGL whichever is lower in weathered rock layer.
The Dynamic parameters of sub-surface having footing area 10 m2
may be considered as follows:

Coefficient of Elastic Uniform Compression (Cu) = 4.5 kg/cm3.

Coefficient of Elastic Non-Uniform Compression(Cφ ) = 8.65 kg/cm3

Coefficient of Elastic Uniform Shear (Cτ ) = 2.5 kg/cm3

Coefficient of Elastic Non- Uniform Shear (Cψ ) = 3.75 kg/cm3

8.0 SITE INVESTIGATIONS:

Refer to the enclosed bore logs, geophysical profile and other test data.

9.0 SLOPES

The slopes shall have a slope angle of 1:1.5 in soil and 1:1 in stiff
laterite/weathered rock. However, in sound rock the slope angle may
be steeper if required. Erosion protection measures like Jute Geotextile
of minimum 500 gsm and stone pitching (Ref. EIL spec. no. 6-65-0050)
can be adopted wherever required.

10 REFERENCES

Following is code designs shall be followed for analysis, design,


construction and Testing
• IS: 2720 for testing of Soil Properties.
• IS: 1786 Specification for High strength deformed steel bars and wires
for concrete reinforcement.
• IS 5249 Dynamic Soil Properties

EIL-1647-1883.5 Rev. 1 Copyrights EIL – All rights reserved


DESIGN BASIS/PHILOSOPHY SECTION: C-2.5
(GENERAL CIVIL)
6979-002-16-47-DP01 Rev.1
PROCESS AND UTILITY FACILITIES
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 2 of 21
PROJECT AT PADUR

LIST OF CONTENTS

PART A – GENERAL CIVIL WORKS............................................................................................... 3

1.0 REFERENCE PUBLICATIONS ....................................................................................... 3


2.0 DESIGN PHILOSOPHY / CRITERIA – GENERAL ......................................................... 3
2.1 OVERALL PLOT PLAN................................................................................................ 3
2.2 SITE GRADING ........................................................................................................... 3
2.3 ROADS ........................................................................................................................ 4
2.4 CONCRETE PAVEMENTS.......................................................................................... 4
2.5 SITE FINISH ................................................................................................................ 5
2.6 STORM WATER DRAINAGE ...................................................................................... 5
2.7 WATER SYSTEM ........................................................................................................ 8
2.8 SEWERS ................................................................................................................... 10
2.9 FENCING/COMPOUND WALL.................................................................................. 13
2.10 PROCESS CONTROL ROOM SAFETY.................................................................... 13
3.0 SITE DATA INFORMATION .......................................................................................... 13

PART B – FIRE PROTECTION WORKS........................................................................................ 16

1.0 CODES & STANDARDS ...................................................................................................... 16

2.0 FIRE PROTECTION SYSTEM ............................................................................................. 16

2.1 GENERAL ......................................................................................................................... 16


2.2 DESIGN PHILOSOPHY .................................................................................................... 16

3.0 DETAILED DESIGN BASIS ................................................................................................. 18

3.1 FIRE WATER NETWORK ................................................................................................. 18


3.2 WATER SPRAY SYSTEM ................................................................................................ 20
3.3 CLEAN AGENT FIRE EXTINGUISHING SYSTEM ........................................................... 21
3.4 FIRST AID FIRE FIGHTING EQUIPMENTS ..................................................................... 21
3.5 FIRE FIGHTING APPLIANCES......................................................................................... 21

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS/PHILOSOPHY SECTION: C-2.5
(GENERAL CIVIL)
6979-002-16-47-DP01 Rev.1
PROCESS AND UTILITY FACILITIES
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 3 of 21
PROJECT AT PADUR

PART A – GENERAL CIVIL WORKS

1.0 REFERENCE PUBLICATIONS


1. OISD Standard -118 (layout for Oil and Gas Installation).
2. OISD Standard-163 (Process Control Room Safety)
3. Petroleum Rules, 2002
4. The Static and Mobile Pressure Vessels (unfired) rules-1981
5. Director General of Civil Aviation Rules.
6. IS-456-2000 code of Practice for Plain & Reinforced Concrete
7. IS codes for various civil works (latest edition) as on NIT of tender
8. IRC codes for roads.
9. Home Ministry Circular on Perimeter Wall.
10. Manual for Water Supply and Treatment (by Ministry of Urban Development)
11. Manual on Sewerage and Sewage Treatment (by Ministry of Urban Development).
12. Specifications for Roads (Published by IRC on behalf of the Government of India,
Ministry of Road Transport & Highway).

2.0 DESIGN PHILOSOPHY / CRITERIA – GENERAL

2.1 OVERALL PLOT PLAN


2.1.1 The Overall Plot Plan shall be developed based on good Engineering practice and meeting
the requirements of various statutory bodies and local authorities.
2.1.2 Additionally the Overall Plot Plan shall also meet as applicable the requirement of OISD-
118 & 163, PESO Rules & SMPV Rules.
2.1.3 The Overall Plot Plan shall be submitted to the owner/PMC for review.
2.1.4 All statutory approvals shall be taken by EPC Contractor.

2.2 SITE GRADING


2.2.1 All the tree roots and vegetation shall be grubbed up and removed from site.
2.2.2 The grading of the area shall be done by cutting and filling with the following:
a. Cutting area : Thoroughly rolled and compacted.
b. Filling area : Compacted in layers not exceeding 30 cm in loose thickness
to achieve min. 95% of max. laboratory dry density as per
IS:2720 Part-VII.
2.2.3 Site grading philosophy shall be based on following:
Elevation of the site varies from +8.0m to +45m above mean sea level.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS/PHILOSOPHY SECTION: C-2.5
(GENERAL CIVIL)
6979-002-16-47-DP01 Rev.1
PROCESS AND UTILITY FACILITIES
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 4 of 21
PROJECT AT PADUR

2.2.4 Slope in Graded Areas:


As per Geotech specification/Recommendations

2.3 ROADS
2.3.1 Road Width
Location Road way Carriage way
Road around Cavern shaft top 9.0 m 7.0 m
Plant approach road 7.5 m 5.5 m
Roads around utility 6.0 m 4.0 m
Footpath (along
boundary wall) ------ 1.2 m

2.3.2 Camber 1:35


2.3.3. Radius of curve 12M for 7.5M, 9.0M & 12.5M wide road
8M for 6.0M wide roads.
2.3.4 CBR to be used for design As per soil data
2.3.5 Design standard IRC 37-2001 (using 2msa & design CBR)
2.3.6 Road finish Bituminous carpet with seal coat (50mm thick
Bituminous Macadam with 25 mm thick pre-mix
carpet) over 2 layers of base course 200 mm thick)
2.3.7 Finished road top level above FGL:
When pipe way bridges for
pipe ways are provided - 1.7 m (based on 24" max. 1.7 m (based on 24" max.
Pipe size, for higher dia. pipe road top level shall be
accordingly finalised)
- Road level shall be accordingly provided to restrict the
hump at PWB to ~ 0.5m
When overhead bridges are
provided for pipe ways - 1.05 m around hazardous units
- 0.40 m to 0.60 m for other areas

2.4 CONCRETE PAVEMENTS


2.4.1 Pavement slope 1 in 100
2.4.2. Type
a. Non vehicular movement areas
1. Cavern Shaft top area Type-II (150 mm thick) RCC - M25
2. Offsite pump stations Type-III (100 mm thick) RCC - M25
3. Utilities Type-II (150 mm thick) RCC - M25
b. Footpath PCC M20 (100thick)

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS/PHILOSOPHY SECTION: C-2.5
(GENERAL CIVIL)
6979-002-16-47-DP01 Rev.1
PROCESS AND UTILITY FACILITIES
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 5 of 21
PROJECT AT PADUR

NOTE:
i. Sub-Grade below RCC pavement shall be compacted to 95% of Max. lab dry Density
as per IS:2720 Part-VII and the slope of sub-grade shall be same as top of the
pavement slope.
ii. Provide minimum number of expansion joints as per standard.

2.5 SITE FINISH

AREA CONCRE ASPH BRIC GRAVEL OTHER


TE ALT K OR STONE COMPACTE
CHIPS D EARTH
SURFACE
CAVERN SHAFT TOP √
AREA (Refer
cl.2.4)
ROADS & √
APPROACHES
FOOTPATH* √
(PCC
M20)
Between Cavern Shaft √
top area & Roads
(Except approaches to
fire hydrant)
PARKING √
PIPE WAYS √

OPEN STORAGE / √
MAIN AREAS

* Refer Clause 2.4.2 b

2.6 STORM WATER DRAINAGE


2.6.1 The storm water quantities shall be calculated based on Design Rainfall Intensity of
115mm/hr (maximum recorded in one hr).

2.6.2 Run off co-efficient


a. Paved area - Concrete - 1.0
- Bituminous - 0.9
b. Compacted area such as /offsite areas/expansion area - 0.7
c. Unusable open area/ Green Belt area - 0.4

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS/PHILOSOPHY SECTION: C-2.5
(GENERAL CIVIL)
6979-002-16-47-DP01 Rev.1
PROCESS AND UTILITY FACILITIES
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 6 of 21
PROJECT AT PADUR

2.6.3 Sizing of drains

Design formula

SW drains shall be designed by using Manning’s Formula:

V=1/Nx R2/3 x S1/2 & Q=AV

Where V=Velocity in M/sec


N=Rugosity Coefficient = 0.025 for Rock Pitched drains
S=Slope
A=Area in M2
P=Wetted Perimeter in M
R=Hydraulic mean radius (A/P)
Q=Discharge in M3/sec

Limiting velocity in the drains:

Minimum velocity in ditch - 0.6m/sec


Maximum velocity in ditch - 2.4m/sec

Minimum Slope Preferred:

Generally for drains following minimum slope are kept:


Trapezoidal ditches - 1:1000
Rectangular drains - 1:500

Flow Calculations:

Storm water Flow shall be calculated based on the following formula:

The flow from catchment area Q=CIA

Where C = Run-off Coefficient


I = Design Rainfall Intensity
A = Catchment area

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS/PHILOSOPHY SECTION: C-2.5
(GENERAL CIVIL)
6979-002-16-47-DP01 Rev.1
PROCESS AND UTILITY FACILITIES
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 7 of 21
PROJECT AT PADUR

Check against hydraulic jump

For Drains:

The drains shall be checked against Hydraulic jump.


When Froude No. is less than one then the flow is Tranquil Flow.
Hydraulic jump occurs when Froud No (Fr) ≥ 1

Froude No. Fr= Q/A√(gd) (for rectangular drains)


Q/A√(gA/T) (for trapezoidal section)

Where
Fr = Froude No
Q = Actual Flow in cum/sec
A = Area in sq.m
g = Acceleration due to gravity in m/sec2
T = Top Width for Trapezoidal section in m
d = depth in m

For Box Culvert:

Velocity inside box culvert


V2 = SQRT (V12 + 2g H)
Where, H = (p1/w – p2/w)

Afflux/ Hydraulic Jump in U/S of Box Culvert


h1 = (V12/17.85 + .0152) * (A2/a2 – 1)

Afflux in D/S of Box Culvert


h2 = (- d/2 + ( 2 V22 d2/g + d2/4)½ )– (actual depth of flow in drain in D/S)

Where,
p1 = Pressure intensity in U/S of the drain
p2 = Pressure intensity in Box Culvert
w = Specific weight of water
V1 = velocity of flow in U/S drain in M/sec
V2 = velocity of flow in Box Culvert M/sec
h1 = Height of afflux/ Hydraulic jump above water level of the U/S drain.
h2 = Height of afflux/ Hydraulic jump above water level of the D/S drain.
A = Area of flow section in U/S drain (in M2)
a = Area of box culvert in M2
d = Depth of flow in Box Culvert in M
H = Differential Pressure Head in M
g = acceleration due to gravity

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS/PHILOSOPHY SECTION: C-2.5
(GENERAL CIVIL)
6979-002-16-47-DP01 Rev.1
PROCESS AND UTILITY FACILITIES
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 8 of 21
PROJECT AT PADUR

2.6.4 Ditches
a. Type Ditches shall be rectangular and/or trapezoidal type.
b. Construction
- Rectangular Ditches Random Rubble masonry with cement plaster in
offsites, RCC in cavern shaft top and other RCC
paved areas.
- Trapezoidal Ditches PCC (M20) lining for both horizontal and sloped
portion

2.6.5 Culverts and Road Crossings


a Pipe Culverts- Under Roads : RCC pipes (Class NP-3 as per IS:458)

b Storm Water Box culverts : RCC Precast/ Cast-in-situ Construction (RCC M30)

c Electric & Instrumentation Road : PVC pipe class-1 (IS 4985) embedded in PCC grade
Cable crossings

2.6.6 Storm Water Disposal Point


Storm water shall be routed to existing storm water drain outside plant battery limit.

2.7 WATER SYSTEM


2.7.1 Raw Water
2.7.1.1 Source
Road Tankers.

2.7.1.2 Storage
a. Type of reservoir RCC reservoir with top cover for Raw Water.
b. Capacity 4160 CUM in two compartments (2.5m U/G & 1.0 m A/G)
c. Source Road tankers

2.7.2 Drinking Water System


- Rate of water supply 30 gals/head/day (135 lpcd).
- System G.I. pipes and fittings for dia 6” and below. All U/G GI pipes shall be
coated with anticorrosive black paint.
- Storage - Underground tank of R.C.C. construction (2.5m U/G & 1.0 m A/G)
- Capacity - 6 hours, based on average daily demand
- Drinking water pumped to HDPE/PVC Syntex Tank or equivalent on
buildings

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS/PHILOSOPHY SECTION: C-2.5
(GENERAL CIVIL)
6979-002-16-47-DP01 Rev.1
PROCESS AND UTILITY FACILITIES
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 9 of 21
PROJECT AT PADUR

2.7.3 Drinking water Distribution

The drinking water distribution system shall consist of underground piping network laid
along the roadside or other convenient locations. The pipe shall be laid with a clear cover
of minimum 600 mm in open areas except at road crossings and paved area, where it shall
be considered as 1200 mm. The distribution network shall be laid in straight run with
bypass loop. An isolation valve with RCC valve pit shall be provided on drinking water line
before entering the building. Also isolation valves has been provided at following locations:
• At junctions of the network.
• If straight run exceeds 250 M.
• At battery limit of the building / unit.
Min. pressure at tappings (except safety shower & eye wash unit) shall be considered as
0.5Kg/cm2 (g) at hydraulically remotest point and adequate quantity of water supply of all
required places are ensured. Minimum pressure at safety shower & eye wash unit
considered as 2.1 Kg/cm2 (g). The minimum line sizes for tapping for any fixture has been
considered 15mm. The minimum line sizes for tapping for Safety Shower & Eye wash shall
be considered as 1 ½ inch

All underground C.S./M.S. pipes shall be provided with corrosion resistance protection as
per SMMS Specification.

2.7.4 Estimation of Design Drinking Water Demand

Drinking water demand depends on the following factors:


• No. of persons (users)
• Average daily consumption
• Any exceptional peak discharge

The average daily consumption considered as 135 lit per capita for plant area.

The following shall be considered:


• Total nos of person considered in offsite areas as 25
• Total nos of safety shower & eye wash considered as 2 nos in Shaft area.
• Total nos of safety shower & eye wash considered as 1 nos in ETP area.

Average daily consumption = No. of persons (n) x per capita daily consumption
of water (cum) = n x 135 lit/person/day
1000

25% extra to be considered for leakage and losses for drinking water system.

Net daily consumption for drinking water Qn (cum)= 1.25 x n x 135 lit/person/day
1000

Min. two nos. safety shower shall be considered as working during peak water demand.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS/PHILOSOPHY SECTION: C-2.5
(GENERAL CIVIL)
6979-002-16-47-DP01 Rev.1
PROCESS AND UTILITY FACILITIES
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 10 of 21
PROJECT AT PADUR

So, water requirement for safety shower=13.6 m3/hr.

Drinking water headers shall be designed to a capacity of 3 times the net daily flow

Hence, Design flow (Qd) = 3 x net daily discharge + Water requirement of 2 nos.
combined eye wash & safety shower

2.7.5 Material of Construction


Pipes (upto 150 mm NB) : GI as per IS:1239, Heavy Duty
Valves : C.I gate valves as per IS:780.
: Gun metal valves confirming to IS:778
Jointing : G.I screwed, M.S welded.

2.8 SEWERS
2.8.1 General
2.8.1.1 Storm water drains shall not be combined with oily waste sewer (OWS)/Sanitary Waste
Sewer (SWS) /combined sewer system.
2.8.1.2 OWS from the equipments and area around equipments, pumps etc. shall collect in oily
waste sewer through funnel points. OWS is routed to EFFLUENT TREATMENT PLANT
(ETP) through underground gravity sewers upto ETP.
2.8.1.3 First 15 min. of rain water/firewater flow from CRWS from SRV Skid and Pig receiving
areas & fuel forwarding area shall be routed to RCC sump & and pumped to ETP.
2.8.1.4 Required treatment as per process design data shall be provided in ETP.
2.8.1.5 All underground C.S. pipes shall be provided with corrosion resistance protection as per
SMMS specification.
2.8.1.6 Corrosion resistant protection given to underground CS pipe shall extend up to min.
500mm. above grade.
2.8.1.7 Transformer oil shall be drained to a RCC pit. The oil shall be pumped out of RCC pit time
to time using portable pump.

2.8.2 Types of Sewers and Disposal Method


2.8.2.1 Oily sewer ETP
2.8.2.2 Flare Blow Down As per Process P&ID
2.8.2.3 Sanitary Sewer To Septic tank & Soak Pit/upflow filter

2.8.3 Design of Process waste sewer


The OWS sewer shall be designed based on the quantities of process waste specified by
process department/ Licensor.
CRWS sewers shall be designed for rain water of firewater flow whichever is more. Two
way valve pit arrangement shall be provided for contaminated area to divert flow to storm
water drain in case no contamination is observed.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS/PHILOSOPHY SECTION: C-2.5
(GENERAL CIVIL)
6979-002-16-47-DP01 Rev.1
PROCESS AND UTILITY FACILITIES
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 11 of 21
PROJECT AT PADUR

Hydraulic formula:

Manning’s formula shall be used for designing sewers

V = (1/n) * R2/3 * S1/2


Where, V = velocity of flow (in m/s)
S = Slope
n = 0.013 for pipe

Velocity

The slopes shall be provided in such a way so as to have the following velocities with
sewers running full for CRWS and running two third full for OWS.
- Min. velocity 0.6 m/sec
- Max. velocity 2.4 m/sec

Requirement of manholes & spacing


i) Manholes shall be provided in the following position:
- At spacing as given hereunder:
Manholes shall be spaced as per IS: 1742 and IS:4111 (Part-I) and generally as given
below:
• For sewers up to 12” dia : at 30M maximum spacing
• For Sewers more than 12” dia and up to 20” dia : at 45M maximum spacing
- At change of grade or size of mains.
- At junction of sewers.
- Dead end of mains.

ii) Sealed manholes should be provided in the following positions.


- At change of direction of the line.
- At entry of branch line to manhole or mainline.

Sealed manhole with bend pipes, seal type shall be used for CS pipes upto dia 12". For
pipes greater than dia 12" CS pipes double compartment type manholes shall be used

iii) Vent Pipe: Vent pipes shall be provided at suitable intervals on the manholes on the
main header of OWS. The pipes shall be taken 2M above last layer of pipes on pipe rack in
unit areas and 3M above ground level in offsites areas.

2.8.4 Design of Sanitary Sewer


The sanitary sewer shall be designed for 3 times the average flow flowing half full incase of
lateral sewer and flowing 2/3 full in case of Main Sewers.

Sanitary sewage system shall collect waste from toilet facilities provided in various plant
and non plant buildings. Acid, caustic, hydrocarbon, rain water or other chemical waste
shall not be discharged into system.

Following factors shall be considered in estimating the rate of flow:

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS/PHILOSOPHY SECTION: C-2.5
(GENERAL CIVIL)
6979-002-16-47-DP01 Rev.1
PROCESS AND UTILITY FACILITIES
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 12 of 21
PROJECT AT PADUR

The average number of persons served.


Average daily consumption of water per head
Any exceptional peak discharge due to simultaneous use of fittings in buildings

Generally 90% of the water supply may be expected to reach sewers. The sewer shall be
designed for minimum 120 l/capita/day

A minimum velocity of 0.75 m/s at design flow is considered. A maximum velocity of 2.4
m/s at design peak flow shall considered

Hydraulic formula:

Manning equation has been used.


V = (1/n) * R2/3 * S1/2

Where
v= velocity of flow in m/s
R= hydraulic mean depth in m
S= hydraulic gradient
n= Mannings coefficient depends on roughness of pipe

The sanitary waste is collected from all building shall be discharged to Septic tank & soak
pit/upflow filter.

2.8.5 Cover for Sewer Line


2.8.5.1 Minimum cover over sewer line shall be 600 mm.
2.8.5.2 Under road, sewer shall be protected by concrete encasement and minimum cushion shall
be 1200 mm.

2.8.6 Material of Construction for Manholes


2.8.6.1 Oily water sewer & contaminated rain water sewer
RCC (M30) Manhole.

2.8.6.2 Sanitary Sewer - RCC (M30) Manholes.

2.8.6.3 Manhole Seal


For trapping of gas or prevention of spread of fire through oily sewer from one area to
another, a liquid seal of minimum 150 mm shall be provided in manhole along with suitable
vents. Location of sealed manholes shall be decided accordingly. All vent pipes of sealed
manholes shall be provided with flame arrestor.

2.8.7 Material of Construction for Sewers


2.8.7.1 Oily Sewer

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS/PHILOSOPHY SECTION: C-2.5
(GENERAL CIVIL)
6979-002-16-47-DP01 Rev.1
PROCESS AND UTILITY FACILITIES
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 13 of 21
PROJECT AT PADUR

a. Within Cavern Shaft top area : Carbon Steel (as per A96A)
b. Offsite gravity sewer : RCC pipes class Pl (as per IS : 458) Socket
and spigot, rubbering joints (Suitable
concrete supports at all socket/ spigot joints
of underground piping shall be provided.)
c. Offsite Pumping Sewer : Carbon Steel (as per A96A)
2.8.7.2 Sanitary Sewer
a. Toilet block up to inspection chamber CI pipes (as per IS: 3486/1729)
b. Gravity main & lateral RCC class Pl (as per IS: 458)
Socket and spigot, rubbering joints (Suitable
concrete supports at all socket/ spigot joints
of underground piping shall be provided.)
2.8.7.5 Manhole for acid/ alkali sewer shall be provided with Acid/ Alkali proof lining.

2.9 FENCING/COMPOUND WALL


Protection of Main/Process area - Chain Link Fencing
Protection of land acquisition limit - Rubble Masonry Compound wall

2.10 PROCESS CONTROL ROOM SAFETY


Control room shall be sized and designed meeting requirements of OISD-163 (Process
Control Room Safety).

3.0 SITE DATA INFORMATION

1.0 REFERENCE DOCUMENTS


1.1 METEOROLOGICAL DATA
1.2 SURVEY DRAWINGS
2.0 SITE LOCATION
2.1 STATE WHERE LOCATED Karnataka
2.2 NEAREST IMPORTANT TOWN Udupi (12 Km)
AND DISTANCE
2.3 NEAREST RAILWAY STATION AND Udupi (12 Km)
DISTANCE
2.4 PROPOSED RAILWAY APPROACH -
2.5 NEAREST PORT AND DISTANCE Mangalore
2.6 NEAREST AIR PORT AND Bajpe (Mangalore) 45 km
DISTANCE

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS/PHILOSOPHY SECTION: C-2.5
(GENERAL CIVIL)
6979-002-16-47-DP01 Rev.1
PROCESS AND UTILITY FACILITIES
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 14 of 21
PROJECT AT PADUR

2.7 NEAREST HIGHWAY MILE STONE National Highway NH-17 (5km


AND DISTANCE approx.)
2.8 APPROACH ROAD
- EXISTING
- PLANNED APPROACH TO SITE
3.0 GEOGRAPHICAL DATA
3.1 GEOGRAPHICAL BEARING OF As per attached Survey drgs.
SITE
3.2 HEIGHT ABOVE MEAN SEA LEVEL +8 M to +45M
3.3 BENCH MARK LEVEL AND -
LOCATION
3.4 SITE CHARACTERISTICS Undulated with rock mounds
(TERRAIN TYPE)
3.5 GRADE / VARIATION – LOW POINT
/ HIGH POINT
3.6 OVERHEAD POWER LINES IF ANY Yes, existing
3.7 UNDER GROUND LINES -
OBSTRUCTIONS, IF ANY
3.8 HISTORICAL MONUMENT, IF ANY NA
3.9 SPECIAL FEATURES, IF ANY -
4.0 METEOROLOGICAL DATA
4.1 CLIMATE OF AREA -
4.2 AIR TEMPERATURE MAX. / MIN.
TEMP.
DESIGN DRY BULB / WET BULB 27°C / 24°C
TEMPERATURE
AMBIENT TEMPERATURE MAX. / Min: 16°C,/ Max: 38°C and Average:
MIN. 27°C
4.3 RAINFALL
ANNUAL MAX. / MIN. / AVERAGE 4703mm/2270mm/3467mm
MAX. RECORDED IN 1 HOUR 115mm/hr
MAX. RECORDED IN 24 HOUR 360.9mm/day
DESIGN INTENSITY FOR 115mm/hr
SURFACE WATER RUN OFF
4.4 RAINY SEASON (MONSOON) June to September

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS/PHILOSOPHY SECTION: C-2.5
(GENERAL CIVIL)
6979-002-16-47-DP01 Rev.1
PROCESS AND UTILITY FACILITIES
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 15 of 21
PROJECT AT PADUR

4.5 HFL RECORDED BASED ON 20


YEARS DATA
4.6 RELATIVE HUMIDITY %
MAXIMUM
MINIMUM
4.7 BAROMETRIC PRESSURE
MAXIMUM 762 mmHg
MINIMUM 749 mmHg
AVERAGE
4.8 WIND VELOCITY AND DIRECTION
WIND MAXIMUM /
VELOCITY MINIMUM
AVERAGE 61.2 KM / HR
WIND DIRECTION AND %
PREVAILING WIND DIRECTION Morning E to W, Evening NW to SE
Earthquake design -
5.0 WATER SUPPLY
5.1 SOURCE OF WATER By road tankers
5.2 QUALITY OF WATER -
6.0 POWER SUPPLY
6.1 MAIN POWER SOURCE AND -
DISTANCE

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS/PHILOSOPHY SECTION: C-2.5
(GENERAL CIVIL)
6979-002-16-47-DP01 Rev.1
PROCESS AND UTILITY FACILITIES
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 16 of 21
PROJECT AT PADUR

PART B – FIRE PROTECTION WORKS

1.0 CODES & STANDARDS


a. Fire Protection Manual (Internal appliances, fire engines, trailer pumps, and hydrant
systems) (By Tariff Advisory Committee)
b. Rules of TAC for
a. Sprinkler System
b. Water Spray System
c. BIS Codes For Fire Fighting Equipments.
d. OISD Standard 117 (Fire Protection Facilities For Petroleum Depots, Terminals,
Pipeline Installations and Lube Oil Installations)
e. OISD Standard-163 (Process Control Room Safety) 2001 edition
f. OISD Standard 173 (Fire Prevention and Protection System for Electrical Installations)
g. NFPA - 2001 Clean Agent Extinguishing System.

2.0 FIRE PROTECTION SYSTEM


2.1 GENERAL
This specification described below gives design and functional requirements for fire
protection system for Strategic Storage of Crude Oil Project, Padur. The Fire Protection
system shall be conceived to operate both in prevention and fighting mode, depending on
the relevant actions have been selected either manual or automatic. The fire fighting
system shall be based on the following fighting agents.
- Water
- Foam
- Clean Agent System
- Portable Fire extinguishers

2.2 DESIGN PHILOSOPHY


Cavern Shaft top area, utilities shall be provided with hydrants and monitors located as per,
OISD/TAC standards, design requirements, safe engineering practices.
Fire protection facilities will be based on following:
- Monitoring and Alarm by alerting, locating fire and operating advise
- Action by water/ clean agent/ Portable Fire Extinguishers
Network
- Hydrant system shall be capable to fight ONE major fire.
- Firewater storage & pumping system shall be provided.
Shaft Top
- Shall be provided with fixed spray/sprinkler system and Water cum foam monitors
with foam in container of HDPE material of capacity 500L for each monitor.
- Heat exchangers shall be provided with water spray / sprinkler system.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS/PHILOSOPHY SECTION: C-2.5
(GENERAL CIVIL)
6979-002-16-47-DP01 Rev.1
PROCESS AND UTILITY FACILITIES
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 17 of 21
PROJECT AT PADUR

Utilities & Offsite


- The facilities like metering station ,bullets, pumps & transformer shall be protected
with fixed water spray / sprinkler system
- Diesel tank shall be provided with water spray and fixed & semi fixed foam system

Buildings
- Console room, UPS room, rack room, battery room etc of main Central control room
shall be protected by clean agent system as per NFPA-2001. Clean Agents to be
considered are IG-541, IG-100, IG-55 and IG-01 as per NFPA 2001.

Design criteria for various facilities:-


I Cavern Shaft Top Area (application rate)

A Application rate
- Shaft Top 10.2 lpm/sqm
- Heat Exchangers 10.2 lpm/sqm
- Cooling of Process piping within 10.2 lpm/sqm
paved area
B First Aid Eqpt. As per OISD

II. Offsite facilities

A. Pressurized Storage (Mounded Bullet)


Automatic fire water spray protection with deluge vales and pneumatic detection
system shall be provided on pipe domes, nozzles, RCC tunnels, pump house etc.
as per OISD

B. Transformers
Automatic (deluge) high velocity water spray system shall be provided for
transformer having oil capacity equal to or greater than [email protected] ltr./min/sq.
meter. Actuation of deluge valve (wet system) shall be with the help of Quartzoid
bulb (QB)..

C. Tankages
Water spray system & fixed and Semi Fixed foam system shall be provided for
tankages.

C. Buildings & Other Miscellaneous Structures


- Landing valves for multi storied buildings at first floor and above and at sub-
stations with cellars as per TAC rules.
- Hose reels near landing valves.
- First Aid Equipments as per TAC / OISD rules as applicable.
- Clean agent for control room as per NFPA 2001
- Detection and actuation as per Electrical and Instrumentation specifications.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS/PHILOSOPHY SECTION: C-2.5
(GENERAL CIVIL)
6979-002-16-47-DP01 Rev.1
PROCESS AND UTILITY FACILITIES
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 18 of 21
PROJECT AT PADUR

3.0 DETAILED DESIGN BASIS

3.1 FIRE WATER NETWORK


- Location of Hydrants & Monitors:
o Hydrants shall be provided @ 45m c/c around utilities
o Hydrant & water cum foam monitors shall be provided 30m c/c around
tankages
o Hydrants & Monitors shall be placed near the facility for proper coverage as
per TAC guidelines
- The minimum header size for hydrant and monitor branches shall be as under
• Hydrant connection - 4"
• Water Monitor connection - 6"
• Minimum Size of Network - 8”
- Above ground fire water piping shall be painted with Fire Red Paint to shade No.
536 of IS:5 as per painting specification.
- Radiography requirements as per TAC. At least 10% of all welded joints shall be
radio graphed and shall be found in order. At least 50% of welded joints selected for
radiography shall be field joints.

¾ Restriction Orifice
- Suitable restriction orifice shall be provided in fixed high/medium velocity water
spray systems to maintain the pressure requirements as per TAC/ OISD.

¾ Isolation valves
- Isolation valves shall be provided at crossings (Junctions) to ensure easy
maintenance and uninterrupted water supply in case of break down.
- Isolation valve shall also be provided below monitor and at all hydrants.
- Isolation valve shall be provided at all tapping points on firewater headers.
- Landing valves on buildings shall have individual isolation valve at each tapping.
- Only carbon steel Gate valves shall be used. No cast iron valves shall be used.

¾ Hydrants, Monitors, Hose Reels & Hose boxes

Hydrant shall be BIS approved with following detail


Outlet : 63mm double headed
Pipe size : 4" CS
Capacity : 36 cum/hr
Type : Oblique angle type as per TAC requirement
Monitor shall be BIS approved with following detail
Nozzle bore size : 38mm (Water– cum - foam diffuser type)
Pipe size : 6" CS
Capacity : 144 cum/hr
Water cum Foam Monitors shall be BIS approved with following detail
Pipe size : 8" CS

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS/PHILOSOPHY SECTION: C-2.5
(GENERAL CIVIL)
6979-002-16-47-DP01 Rev.1
PROCESS AND UTILITY FACILITIES
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 19 of 21
PROJECT AT PADUR

Capacity : 2580lpm
Hose reel shall be 40m long of 20mm bore size.

Hose boxes shall be provided at every alternate hydrant points and every landing
valves.
Hoses shall be as per BIS kept in each hose cabinet.

¾ Landing Valve
- Double headed
- To be provided on landings of first floor and above.

¾ Material of Construction
Following materials shall be used for fire protection system;
Pipe, fittings, valves - Carbon steel as per piping material specification
Specification - GI pipes for water spray (Downstream of isolation
valve)
Hydrant, Monitors, landing
valves - Bureau of Indian Standards
Hose reels, hose Box and Accessories: BIS marked

¾ Water Supply and Storage


a. Supply From road tankers
b. Storage capacity Based on 4-hour storage of installed
capacity of pumps.
c. Material of construction CS Firewater Tank
d. Make up water From Raw water sump
e. Emergency connection From Raw water sump

¾ Fire Water Main Pumps


a. Capacity System Capacity - 820cum/hr.(TAC approved)
Head 8.8 kg/cm2g min.
b. Type Horizontal
c. Standby pumps Capacity - 410 cum/hr & Head-8.8 kg/cm2g
d. Drive Electrical (main pump) / diesel engine (stand by)
as per OISD.
e. Power supply to To meet the requirement of the OISD.
Electrical driven pumps
f. Diesel Driven Pumps To meet the requirement of OISD
Diesel - day tanks capacity – Minimum 12 Hour
running storage
g. Mode of Operation
Starting of pumps Automatic through pressure switches and
manual

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS/PHILOSOPHY SECTION: C-2.5
(GENERAL CIVIL)
6979-002-16-47-DP01 Rev.1
PROCESS AND UTILITY FACILITIES
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 20 of 21
PROJECT AT PADUR

Stopping of pumps Manual


h. Fire water Jockey
Pumps
-Capacity 2 nos. (Capacity - 50 m3/hr)
-Head To keep the system pressurized at 8.8kg/cm2
continuously
-Type Horizontal
-Drive Electric
To run on emergency power as well.
Mode of operation Automatic through pressure switches with
provision to start and stop manually.

¾ Fire Water Pump House


Firewater pump house shall be RCC frame construction having R.C.C. roof with brick
walls as per TAC norms. It shall have provision for separate battery room. A HOT crane
shall be provided for maintenance and erection. A local fire control panel in operator’s
room shall be provided for all controls of firewater pumps.

3.2 WATER SPRAY SYSTEM

Rate of Water Application & Mode of Operation of Water Spray System


Facilities Mode of Operation Rate of application
Mounded Bullet Automatic 10.2 lpm/sqm
Metering station Manual 10.2 lpm/sqm
Shaft top Manual 10.2 lpm/sqm
Heat exchangers Manual 10.2 lpm/sqm
On pumps(Booster) Manual 20.4 lpm/sqm
Transformers Auto (Deluge system) 12.5 lpm/sqm
Diesel Storage Tank Manual 3.0 lpm/sqm

NOTE:
1. For transformers automatic deluge operation shall be with QB detectors.

¾ Material of Construction
Pipes, fittings CS for mains and MS-GI(HVY) screwed piping for spray
system and as per PMS
Valves and flanges CS as per PMS
Spray nozzles Cu Alloy/SS
Deluge valves CS
Detector piping GI

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS/PHILOSOPHY SECTION: C-2.5
(GENERAL CIVIL)
6979-002-16-47-DP01 Rev.1
PROCESS AND UTILITY FACILITIES
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 21 of 21
PROJECT AT PADUR

3.3 CLEAN AGENT FIRE EXTINGUISHING SYSTEM


Clean agent fire extinguisher system shall be provided in control room as per NFPA 2001.
The system shall be automatic with detection and actuation, meeting the requirement of
NFPA 2001.

3.4 FIRST AID FIRE FIGHTING EQUIPMENTS


This shall be provided as per OISD norms.

3.5 FIRE FIGHTING APPLIANCES


- Hoses & Hose boxes with accessories shall be provided as per OISD requirements.
- Safety equipments like fire shoes, fire blankets, breathing apparatus.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


DESIGN BASIS SECTION: C-2.6
(Architecture) 6979-02-16-49-DB51 Rev.0
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 4 of 18
Strategic Storage Project, at Padur

1.0 ARCHITECTURAL DESIGN REQUIREMENT


Architectural design shall be in accordance with the following clauses.

1.1 REFERENCED PUBLICATIONS


Provisions of following references shall be taken care in architectural design:
1. National Building Code of India.
2. State Govt. Factory Acts.
3. Local Municipality or any other Authority’s Bye-laws as applicable.
4. TAC (Tariff Advisory Committee) Recommendations.
5. BPE (Bureau of Public Enterprises) Guidelines.
6. Process Control Room Safety - OISD-STANDARD-163.
7. Any other rules/regulations/recommendations as applicable for a particular
project.

1.2 DESIGN REQUIREMENT

1.2.1 SPATIAL REQUIREMENTS


Spatial requirements inside a building shall be decided based on activities to be performed
in the building and consequent occupancy pattern equipment layout etc. Spaces can be
generally classified as follows, which shall be provided in all the buildings/sheds.

1. Functional Spaces
Functional areas of any building/shed are constituted by the main activity areas for
which the building is to exist. Various spaces/rooms shall be judiciously sized and
shall be integrated logically to generate the total building plan taking into account
the following parameters.
A. Activities, group of activities and consequent work-flow pattern.
B. Site conditions i.e. dimensions, contours etc.
C. Climatic conditions vis-a-vis orientation.
D. Safety regulations.
E. Lighting and ventilation.
F. Acoustics.
G. Services.
H. Security.
I. Economy.
J. Aesthetics.
K. Any specific requirement pertaining to particular buildings.
L. All other established Architectural design parameters.

The objective of spatial arrangement shall be to satisfy functional requirements and


physical comfort and safety regulations as well as aesthetics which has significant
role in creating a favorable working and living condition.

2. Circulation Spaces

Template No. 5-0000-0001-T2 Rev. 1 Copyrights EIL – All rights reserved


DESIGN BASIS SECTION: C-2.6
(Architecture) 6979-02-16-49-DB51 Rev.0
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 5 of 18
Strategic Storage Project, at Padur

Following spaces are classified as circulation spaces. These spaces shall be


provided for integrating various types of spaces and as means of access/exit.
A. Corridors & passages.
B. Staircases.
C. Entrance lobby/Foyer including Reception & waiting.
D. Gangway/walkways.
E. Equipment loading/unloading platforms.
F. Emergency Exits.

3. Amenity Spaces
Following spaces are classified as amenity spaces.
A. Toilet (Gents & Ladies).
B. Drinking Water Facility.
C. Locker & Change room.
D. Rest room/Lunch room.
E. Wash rooms & space for drying clothes.
F. Canteen/Pantry room.
G. First-aid room.
Toilets & Drinking Water enclosure shall be mandatory requirement for buildings
with human occupancy.

4. Utility Spaces
Utility spaces are the spaces requirement of which are generated due to provision
of services like Air-conditioning, pressurisation, fire fighting, electrical, telephone
etc. Following are the examples. These spaces shall be provided as per specified
building services.
A. Air-conditioning plant room.
B. Air handling rooms.
C. Electrical distribution panels rooms.
D. Fire Fighting Equipment room.
E. Telephone Exchange Equipments room
F. UPS room
G. Battery room

However following are the limiting sizes/ dimensions for various purposes, which are to be
adhered to:
A. Minimum size of any habitable room : 9 Sq.M. with minimum dimension
not less than 2.5m.
B. Minimum ht. of any habitable room : 3m which may be reduced to
2.75m for air-conditioned areas.
C. Maximum ht. of habitable rooms : 3.6m
D. Scale of accommodation for : @14cu.m. per occupant.
Industrial work spaces. Minimum clear height of such
workspaces shall be 3.6m.

Template No. 5-0000-0001-T2 Rev. 1 Copyrights EIL – All rights reserved


DESIGN BASIS SECTION: C-2.6
(Architecture) 6979-02-16-49-DB51 Rev.0
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 6 of 18
Strategic Storage Project, at Padur

1.2.2 DAY LIGHTING AND NATURAL VENTILATION


1. Day lighting
Established level of illumination shall be maintained for all parts of the buildings
by means of windows, sky lights etc. Following references shall be adhered to in
this regard.
A. National Building Code of India
B. State Factory Act
2. Natural Ventilation
Established level of ventilation in terms of air charges per hour shall be maintained
for all spaces.
Following references shall be adhered to for the purpose.
A. National Building Code of India.
B. State Factory Act
Natural ventilation shall also be supplemented by mechanical or electrical means of
ventilation in all human occupied areas.

1.2.3 ACOUSTICS AND SOUND INSULATION


Specified acceptable noise level and reverberation time shall be maintained inside a
building/shed.
Following references shall be referred to for the purpose:
A. National Building Code of India
B. State Factory Act
Required noise level in any space shall be maintained by means of:
A. Segregating noise sources by buffer zones
B. Dampening of noise levels by damping devices
C. Providing Acoustic treatment with acoustic material (on walls, ceilings, floors, as
required).

1.2.4 SAFETY REQUIREMENTS


Safety from fire and like emergencies shall be taken into account in building/shed design.
Every building/shed meant for human occupancy shall be provided with exits sufficient to
permit safe escape of occupants in case of emergency.
The exits shall be in terms of doorway, corridors, and passageways to internal/ external
staircase or to areas having access to the outside.
Following references shall be adhered to in this regard:
A. National Building Code of India.
B. State Factory Act.
C. Stipulations of Collector NOC/ CCOE/ Advisor Safety.
For Control Room safety requirements, provisions of OISD-STD-163 shall be followed.

Template No. 5-0000-0001-T2 Rev. 1 Copyrights EIL – All rights reserved


DESIGN BASIS SECTION: C-2.6
(Architecture) 6979-02-16-49-DB51 Rev.0
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 7 of 18
Strategic Storage Project, at Padur

1.2.5 SITE PLANNING


Site planning of buildings shall take into account aspects like inter-relationship of the
building with the whole system, movement pattern, traffic and road net-work, safety
regulations, service network, fire safety, climatic and environmental aspects, site
conditions like site dimension, contour, drainage, noise level, view, future expansion, visual
aspects etc.
Main and service/maintenance entrances of buildings shall be provided with vehicular
access. All exit points also shall be provided with footpath/vehicular access. Parking
space in accordance with traffic load shall be provided for all buildings. Road network and
open space around the buildings shall be designed considering movement and functioning
of Fire tenders.
Climatic factors like wind direction, solar geometry shall be taken into account in orienting
the buildings depending on type of climate. Orientation of building shall also consider
noise and smell propagation, views, and visual effect from various directions.
Sufficient open space shall be provided for planned expansion of buildings. Sufficient
open space shall also be provided around the buildings for lighting and ventilation in
accordance with Factory Acts & National Building Code.
Site plan shall also take into account, landscaping aspects. The inherent characteristics of
site, such as contours, land form, vegetation, trees, plants, shape shall be fully utilized in
the design.

1.2.6 BUILDING SERVICES


Following services shall be provided for all buildings/sheds as essential services or as
specified.

1. Water supply, distribution and drainage, sanitary services.


This service is essential for all human occupied bldgs/ sheds. All buildings with
human occupancy shall have provision of toilet and drinking water as per following
references:
A. National Building Code of India
B. State Factory Act
Drinking water provisions shall be provided within an enclosure separated from the
toilets. Space for janitor shall be provided in the toilets. All service pipes showing
on the external wall hall be suitably concealed or shall be provided within a shaft.
2. Electrical Services
This service shall be provided as essential service for all buildings/sheds. Electrical
services for buildings shall consist of electrical supply and distributions, Electrical
lighting installations, telephone network, fans, exhaust fans, lighting protection
system etc. including all accessories, cabling etc.
3. Air conditioning and heating
Areas of Control room, spaces housing equipments/machinery/panels etc., which
require conditioned environment and certain specified areas like offices, specific
office accommodation shall be air-conditioned.

1.2.7 AESTHETICS

Template No. 5-0000-0001-T2 Rev. 1 Copyrights EIL – All rights reserved


DESIGN BASIS SECTION: C-2.6
(Architecture) 6979-02-16-49-DB51 Rev.0
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 8 of 18
Strategic Storage Project, at Padur

Apart from the fulfilment of functional & safety requirement, aesthetic requirement of the
building shall be taken care of in the design. As specific guidelines for achieving required
aesthetics are difficult to establish, preliminary drawings indicating Architectural treatment
shall be submitted for Owner’s approval. Elements like Canopies, overhangs & shading
devices, gutters, door; Window/ Ventilator composition, External wall location with respect
to columns, Colour Scheme, grooves in plaster etc. shall be considered as contributory
elements to aesthetics and their design etc. shall be subjected to the Owner’s approval.

1.2.8 STRUCTURAL AND CONSTRUCTION ELEMENTS


Type of structure & construction shall be as specified. However following table may be
followed as a guideline.

SL. NO BUILDING TYPE OF STRUCTURE


Control Room, Administration &
Amenities Building, Sub Station, Fire
• RCC frame & roof.
1. water pump house, Workshop/
Warehouse, Drinking water pump • Brick masonry infill walls.
House, Guard Rooms, Service water
pump House, Watch tower
• RCC columns.
Car/ Scooter Parking Shed, • Steel truss.
2. Compressor House, D.G. Shed,
• Precoated Steel sheet
Boiler House, other Sheds
(Galvalume/ Zincalume) roofing &
cladding.

1.2.9 BUILDING ELEMENTS

1. Finished Floor Level (FFL)


In general, FFL of the Buildings, sheds shall be determined with respect to top of
approach road or pavement. Following schedule shall be adhered to for FFL of
various buildings & sheds.
A. Transformer bays - Top of approach Road level + 150mm.
B. False floor areas - Top of approach Road level +600 depth
of cavity.
C. Loading, Unloading bays - Top of approach Road level + 1100mm
D. All other areas - Top of approach Road level + 300 to
600mm.
Notes:
A. In case of approaches with different top levels, the highest top level of approach
road/pavement shall be considered.
B. FFL shall be same throughout in a building/shed. Split-levels may be
considered in exceptional cases due to ground terrain etc. or if any functional
requirement, with the approval of the Owner.

Template No. 5-0000-0001-T2 Rev. 1 Copyrights EIL – All rights reserved


DESIGN BASIS SECTION: C-2.6
(Architecture) 6979-02-16-49-DB51 Rev.0
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 9 of 18
Strategic Storage Project, at Padur

C. FFL of external loading/ unloading bays/ platforms, toilet, shall be 6 - 12 mm


lower than that of the building/shed’s FFL to check ingress/spillage of water.
D. FFL of Warehouse may be kept lower than loading/ unloading bays/ platforms
where Forklifts etc. are used for internal movement of items. Adequate
arrangement for negotiating the level difference shall be provided in that case.

2. Steps/ Ramps
Steps/ramps shall be provided for access to the buildings/sheds for
pedestrian/vehicular, equipment entry. Minimum 1200 mm wide platform shall be
provided in between Entrance door and steps/ramps. Following dimensions of the
steps/ramps shall be adhered to.
A. Tread - 250 mm minimum
B. Riser - 175 mm maximum
C. Slope of Ramp - Not steeper than 1:6
D. Ratio of Tread & Riser
i) Control bldg., Administration- Riser + tread = 420-450 mm
& Amenities Bldg.
ii) Other bldgs. - 2 Riser + Tread = 600-650 mm

3. Walls
Following schedule shall be adhered to for wall material and thickness:
A. External, load bearing walls - Minimum 230 mm thk. Brick wall
B. Fire wall (Around Transformers)- Minimum 345 mm thk. Brick wall or as
per TAC requirement.
C. Internal partition wall - 230/115 mm thk. Brick wall/ Glazed
partition
Notes:
1. 115 mm thk. Partition walls shall be provided with RCC horizontal bands or
230 mm thk. Brick pillars for stability.
2. Wherever conduits or pipes are required to be concealed within partition
wall, the wall thickness shall be increased suitably.

4. Doors
Doors shall be provided for access, security and safety at all entry & exits of rooms,
functional areas & the buildings. Sizes of the doors shall be determined on the
basis of the following schedule:

A. Equipment, Panel area - Size of maximum equipment


including packing.
B. Other areas - Volume of movement through the
door.

Template No. 5-0000-0001-T2 Rev. 1 Copyrights EIL – All rights reserved


DESIGN BASIS SECTION: C-2.6
(Architecture) 6979-02-16-49-DB51 Rev.0
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 10 of 18
Strategic Storage Project, at Padur

C. Minimum Ent. door size - 1500 mm x 2100 mm (wall


opening size)
D. W.C., Bath Cubicle Door - 750 mm x 2100 mm (wall opening
size)
E. Minimum size of other doors - 1000 mm x 2100 mm (wall
opening size)
Notes:
1. Normally, entrance doors shall be provided covering full width of the
Entrance lobby. In that case the door shall be of composite type
consisting of openable shutters & fixed portions.
2. Mechanically operated Rolling shutters shall be provided wherever area
requirement of openable shutters exceed 2500 mm x 2500 mm.

5. Windows/ Ventilators
Windows/ ventilators shall be provided in all areas for natural lighting, ventilation
and visibility at working level.
For the purposes of ventilation, total openable area of the windows/ ventilators shall
be as per Factory Act subjected to a minimum of 15% of the floor area to be
ventilated. However, for Control Room, security block of Gate Houses and in office
areas etc. where visibility from inside is of prime importance, increased window
area shall be provided. Areas accommodating panels/ equipments shall be
normally provided with ventilators at high level for unobstructed distributed lighting.
Windows/ventilators/openings of Control Room shall be provided in accordance
with OISD-STD-163.
Notes:
A. Requirement of window/ ventilation area as stipulated above is for
maximum room/ area height of 4000 mm. For height more than 4000
mm additional window/ventilator shall be provided in the same manner at
every work area such as walkway/gangway etc. at all such working levels.
In such cases additional windows/ ventilators shall also be provided to ensure min.
illumination & ventilation at every level of the building/ shed.
B. Wherever due to limitation of external wall area or any other reasons,
stipulated area of window/ventilation cannot be provided, suitable
mechanical/electrical devices shall be provided.

6. Canopy/ Overhang
Canopy/ overhangs shall be provided at all entries & exits for rain & sun protection,
accentuation of the entry/exit and movement from or to parked vehicle as per
following schedule.
A. For Administration & Amenities Building and Control Room, canopy shall be
provided at all entrances. Canopy or overhangs shall also be provided for
sub stations and sheds where regular vehicular movement & loading/
unloading take place. Size of the canopy shall be decided based on vehicle
parking & covered access to the building/ shed, movement around the
vehicle and aesthetics of the building/ shed.

Template No. 5-0000-0001-T2 Rev. 1 Copyrights EIL – All rights reserved


DESIGN BASIS SECTION: C-2.6
(Architecture) 6979-02-16-49-DB51 Rev.0
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 11 of 18
Strategic Storage Project, at Padur

B. Overhangs shall be provided over all exits. Size of the overhang shall
be decided based on the aesthetics of the building/shed subject to
minimum of 900 mm.
Waterproofing & drainage provision shall be provided for the canopies &
overhangs.

7. Shading Devices
Shading devices shall be provided over all windows, openable ventilators for rain &
sun protection. These devices shall be in form of horizontal projections, vertical
projected fins or combination of both as per building facade treatment. Minimum
projection shall be 600 mm. The top surface of the shading devices shall be
finished with cement plaster mixed with waterproofing (laid to slope) compound and
shall be provided with GI spouts for drainage.

8. Parapet
Parapets shall be minimum 500 mm high for non-approachable roof and 900
mm high for approachable roof. Parapet shall be of RCC.

9. Roof Gutter
Roof Gutter with rain water pipes shall be provided for all the building/ sheds for
roof water drainage. Sizing of the gutter shall be based on area to be drained and
number of outlets. Gutters shall be of RCC or sheet metal depending on type of
structure. Gutters may be avoided in the cases of sloped roofs if sufficient roof over
hangings are provided to prevent roof water splashing on the building surfaces.

10. Rain Water Pipes, Spouts


Rain water pipes shall be provided for roof water drainage. Number of rain
water pipes shall be decided on the basis of roof Area, slope and rainfall intensity.
Rain water pipes shall be embedded in concrete or brick. RCC or GI spouts may be
used for drainage of chajja/ small canopies of ground floor only.

11. Entrance Lobby


Entrance lobby shall be provided as a common entrance for all Buildings/sheds
accommodating separate or similar functional spaces integrated together.
Individual entries to such functional spaces shall be from this lobby by means of
passages/corridors. Apart from common entry lobby, separate independent entries to
these functional spaces shall also be provided if functionally required. Size of the
entrance lobby shall be decided on the basis of volume of the movement subjected to the
minimum requirement of 9 Sq.M.

12. Passages/Corridors
Passages/corridors shall be provided to integrate various spaces. Width of the
passages/corridors shall be as per following schedule.
A. Singly loaded passage/corridor = Minimum 1200 mm.
B. Doubly loaded passage/corridor = Minimum 1800 mm

Template No. 5-0000-0001-T2 Rev. 1 Copyrights EIL – All rights reserved


DESIGN BASIS SECTION: C-2.6
(Architecture) 6979-02-16-49-DB51 Rev.0
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 12 of 18
Strategic Storage Project, at Padur

But whenever passages/ corridors are to be used for equipment/ machinery/


panels etc. the width shall be determined on the basis of equipment/
machinery/ panel sizes.

13. Service Entry


Separate service entry shall be provided for service areas such as Air- condition
plant, Electrical Rooms etc. A common service entry may be provided depending on
spatial arrangement.

14. Air Lock Lobby


Air lock lobby shall be provided for all entry & exits of air-conditioned space.
However, air lock lobby may be avoided in case of small air-conditioned habitable
spaces.

15. Emergency Exits


Emergency exits shall be provided for all the building/ sheds as per Factory Act &
OISD Norms. Emergency exits for individual function spaces such as console area,
cable cellar, switchgear hall shall also be provided. Emergency exits shall be
located in such a manner that escape route is direct, unobstructed & without
passing through any other function areas to safe area. Corridors/ staircases shall
be provided as escape route to the emergency exits.

16. Staircases
Staircases shall be provided for vertical circulation & emergency exits. Number of
staircases shall be based on building/ shed sizes and emergency exit
requirements. At least one staircase/ ladder shall be provided for access to the flat
roofs for maintenance.

17. Railings
1000mm high Railings shall be provided in stairs and in all unprotected openings in
slabs as a safety device. Railings in loading/ unloading bay of Substations
shall be of removable type to facilitate the purpose.

18. Toilet
Toilet shall be provided for all buildings/ sheds having human occupancy. Toilet
shall consist of Gents Toilet, Ladies Toilet (as per requirement), and separate
drinking water enclosure. Requirement of fittings & fixtures shall be as per National
Building Code of India & Factory Act.

19. Electrical Room


Electrical Room may be provided to accommodate electrical/telephone main
distribution box. However, depending on size, space requirement, the same may
be mounted in wall recess.

20. Partitions

Template No. 5-0000-0001-T2 Rev. 1 Copyrights EIL – All rights reserved


DESIGN BASIS SECTION: C-2.6
(Architecture) 6979-02-16-49-DB51 Rev.0
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 13 of 18
Strategic Storage Project, at Padur

Partitions shall be provided for flexible space arrangement in Office spaces if


specified. The partitions shall be of removable type. Partitions shall be provided
between console rooms & rack room in Control Room. Glazed panels shall be
provided for visibility in the partitions as per requirement.

21. False Ceiling & Underdeck Insulation


False ceilings shall be provided for following purposes wherever required.
A. To reduce room volume and hide ducting etc. for air-conditioned space.
B. To maintain acoustic level inside any space.
C. To reduce habitable room, corridor, lobby, toilet heights located in high
ceiling building/shed to min. 3000 mm.
Underdeck Insulation will be provided wherever air-conditioning is provided.

22. False/ Cavity flooring


False/ cavity flooring shall be provided to accommodate under floor cabling in
Instrumentation Console, Rack and U.P.S. Room etc.

23. Plinth Protection


All the buildings/ sheds shall be provided with 1000mm wide plinth protection
around the building /sheds.

Template No. 5-0000-0001-T2 Rev. 1 Copyrights EIL – All rights reserved


DESIGN BASIS SECTION: C-2.6
(Architecture) 6979-02-16-49-DB51 Rev.0
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 14 of 18
Strategic Storage Project, at Padur

PART II - ARCHITECTURAL FINISHES

CONTENTS
2.0 GENERAL
2.1 FLOOR FINISHES
2.2 WALL FINISHES
2.3 INTERNAL CEILING FINISHES
2.4 DOORS, WINDOWS & VENTILATORS
2.5 ROOFING TREATMENT
2.6 SANITARY FITTINGS/ FIXTURES
2.7 ROOFING/ CLADDING

Template No. 5-0000-0001-T2 Rev. 1 Copyrights EIL – All rights reserved


DESIGN BASIS SECTION: C-2.6
(Architecture) 6979-02-16-49-DB51 Rev.0
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 15 of 18
Strategic Storage Project, at Padur

2.0 GENERAL
All the building elements i.e. floor, wall, ceiling, roof, doors & windows etc. shall be
provided with Architectural finishes as shown in the clauses 2.1 to 2.7.
Note:
1. All the Architectural finishes shall be as per attached Specifications, Standards &
Approved list of vendors.
2. Color Scheme for all Architectural items shall be approved by the Owner in
consultation with EIL Architect.

2.1 FLOOR FINISHES

Sl. No. Building Room/Area Finish


Entrance foyer, Reception Area,
corridors, Toilets/ Drinking water areas Granite patterned flooring/ skirting.
1.
etc. of Control Room, Administration &
Amenities Building.
• Vitrified Tiles flooring/ skirting in
Laboratory, Office rooms of Control glazed or Matt finish.
2. Room, Administration & Amenities
Building. • Marbo-Granite Tiles (in select areas
as per requirement).
Entrance foyer, corridors etc. of other
3. Kota stone flooring/ skirting.
buildings.

4. Office rooms of other buildings. Vitrified Tiles flooring/ skirting.

Equipment rooms, A/C Plant Room/


5. AHU, Ware House, Workshop. Heavy-duty cement concrete floor finish.

Acid resistant tile finish on Granolithic


6. Battery Rooms.
flooring/ cement plaster dado.
Console Room, Rack Room, UPS False Flooring finished with high
7.
Room etc. pressure laminate (Antistatic).
Ceramic tile flooring & dado with Granite
8. Kitchen, Pantry, Dining Areas
stone counter-top.
Toilets/ Drinking water areas etc. of all
Non-slip ceramic tile flooring and dado
9. buildings except Control Room,
(Full ht.)
Administration & Amenities Building.
10. All other areas. Granolithic/ cement concrete floor finish.

Skirting shall be provided in all areas. Cement plaster skirting shall be provided in areas
having cement concrete granolithic/ heavy duty cement concrete flooring. For other areas,
skirting shall be of same material as that of flooring.
Panel dividers shall be provided in cement concrete granolithic/ heavy duty flooring.

2.2 WALL FINISHES (Plastering, Painting)

Template No. 5-0000-0001-T2 Rev. 1 Copyrights EIL – All rights reserved


DESIGN BASIS SECTION: C-2.6
(Architecture) 6979-02-16-49-DB51 Rev.0
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 16 of 18
Strategic Storage Project, at Padur

Sl. No. Surface Finish

ALL BUILDINGS: Internal finish

Entrance foyer, Reception Area, • Plastic emulsion paint over cement


1. corridors of Control Room, plaster & POP.
Administration & Amenities Building. • Granite stone cladding (in Slabs).
Office rooms of all buildings, Entrance Plastic emulsion paint over cement
2.
Lobbies of other buildings. plaster & POP.
Console Room, Rack Room, UPS Plastic emulsion paint over cement
3.
Room etc. plaster & POP.
Equipment rooms of Workshop & Waterproof Cement Paint over cement
4.
Warehouse. plaster.
Oil bound distemper over cement
5. All other areas.
plaster.
ALL BUILDINGS: External finish
• Granite flakes (“Heritage” or eq.)
over Plain cement plaster finished
with water repellant coating.
Control Room, Administration &
1. • Marble grit plaster as per
Amenities Building.
requirement.

Marble/ Granite stone finishing as
per requirement.
Workshop/ Warehouse, Guard Sand face cement plaster and acrylic
2.
Rooms, Sub Station Exterior emulsion paint (Snowcryl or eq.)
Waterproof Cement Paint over Plain
3. All Other Buildings
cement plaster/ sand face plaster

Grooves in plaster shall be provided at the junction of different materials and as per
external facade treatment.

2.3 INTERNAL CEILING FINISHES

Sl. No. Surface Finish


All Air-conditioned areas and other Aluminium panel false ceiling (Luxalon
1.
areas where false ceiling is required. or eq.), 600x600 size panels.
Waterproof Cement Paint/ Oil bound
2. Other areas not indicated above
distemper over cement plaster.

2.4 DOORS, WINDOWS & VENTILATORS

Sl. No. Building Room/ Area Finish

Template No. 5-0000-0001-T2 Rev. 1 Copyrights EIL – All rights reserved


DESIGN BASIS SECTION: C-2.6
(Architecture) 6979-02-16-49-DB51 Rev.0
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 17 of 18
Strategic Storage Project, at Padur

ALL BUILDINGS: Doors

• Glazed powder coated Aluminium


Doors for Entrance, Exit, Circulation doors with 5.5mm thk. Toughened
1. areas, Console Room, Rack Room, glass/ 6.3mm thk. Laminated glass.
UPS Room of Control Room. Fire• check Doors as per
requirement.
Doors for Entrance, Exit, Circulation Glazed powder coated Aluminium doors
2. areas, Laboratory of Administration with 5.5mm thk. Toughened glass/
& Amenities Building; Guard Rooms. 6.3mm thk. Laminated glass.
Office rooms, Dining areas, stores Teak veneered flush doors with wooden
3. etc. of all buildings. frames.
Laminated (matching with Teak veneer)
Kitchen, Pantry, Toilets of all
4. flush doors with powder coated
buildings.
Aluminium frames.
Equipment rooms, Workshop, Ware
5. Steel rolling shutters.
Houses.

6. All other areas. Pressed steel doors.

ALL BUILDINGS: Windows/ Ventilators

• Glazed powder coated Aluminium


Windows/ ventilators with 5.5mm thk.
Toughened glass/ 6.3mm thk.
1. Control Room. Laminated glass.

Fire check Windows/ ventilators as
per requirement.
Glazed powder coated Aluminium
Administration & Amenities Building, Windows/ ventilators with 5.5mm thk.
2.
Guard Rooms. Toughened glass/ 6.3mm thk. Laminated
glass.
Glazed anodised Aluminium Windows/
3. Substation ventilators with 5.5mm thk. Toughened
glass.
Glazed/ Louvered steel Windows/
All other Buildings & Sheds (as per
4. ventilators with enamel painted Steel
requirement).
Frame.

2.5 ROOFING TREATMENT (Waterproofing)

Sl. No. Surface Finish


Atactic polypropylene modified reinforced
1. Rcc. roofs of all buildings. bituminous waterproofing membrane
coating over cement screed laid to slope

Template No. 5-0000-0001-T2 Rev. 1 Copyrights EIL – All rights reserved


DESIGN BASIS SECTION: C-2.6
(Architecture) 6979-02-16-49-DB51 Rev.0
Process and Utility Facilities at Top
Side and Inside Cavern, for Crude Oil Page 18 of 18
Strategic Storage Project, at Padur

on Rcc slab.

2.6 SANITARY FITTINGS/ FIXTURES

Sl. No. Building Fitting/ Fixture


• Floor mounted coloured European
type W.C.
• Orissa pan coloured Indian type W.C.
• Oval/ Round coloured wash basin on
Control Room, Administration &
1. counter
Amenities Building.
• Sensor type coloured glazed
urinals.
• “Jaquar”/ “Crabtree” plumbing
fixtures.
• Floor mounted white European type
W.C.
• Orissa pan white Indian type W.C.
2. Other Buildings.
• White wash basin.
• White glazed urinals with cistern.
• CP brass plumbing fixtures.

2.7 ROOFING/ CLADDING

Sl. No. Shed Roofing/ Cladding


Precoated steel sheet (Galvalume/
1. All Sheds. Zincalume) with minimum 30 micron
thick coating on both faces/surfaces.

Template No. 5-0000-0001-T2 Rev. 1 Copyrights EIL – All rights reserved


SCOPE OF WORK & SUPPLY SECTION: C-1.7
(GENERAL CIVIL) 6979-002-16-47-SOW01,
PROCESS AND UTILITY FACILITIES
Rev.1
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 2 of 15
PROJECT AT PADUR

LIST OF CONTENTS
1. BRIEF SCOPE OF WORK......................................................................................................... 3

2. DETAIL SCOPE OF WORK ....................................................................................................... 4

2.1 SURVEY WORKS ............................................................................................................... 4


2.2 SITE GRADING .................................................................................................................. 4
2.3 FENCING REQUIREMENT................................................................................................. 5
2.4 STORM WATER DRAINAGE WORKS & CULVERTS ........................................................ 5
2.5 ROADS, APPROACH ROADS, FOOTPATH & WALKWAYS.............................................. 6
2.6 RCC PAVEMENT ................................................................................................................ 6
2.7 DYKE & FIRE WALL FOR TANKAGE AREA ...................................................................... 6
2.8 PIPE SLEEPERS ................................................................................................................ 7
2.9 ROAD CROSSINGS (ERC, SCRC, IRC, PWB & PIPE SLEEVES) ..................................... 7
2.10 RAW WATER SYSTEM ...................................................................................................... 7
2.11 DRINKING WATER SYSTEM ............................................................................................. 8
2.12 SAFETY SHOWER & EYEWASH (SS & EW) ..................................................................... 9
2.13 ACID/ ALKALI PROOF LINING ........................................................................................... 9
2.14 SANITARY SEWER SYSTEM............................................................................................. 9
2.15 INTERNAL PLUMBING & SANITARY WORKS IN BUILDINGS .......................................... 9
2.16 RAIN WATER HARVESTING FROM STORM WATER DRAINS & BUILDING DRAINAGE 9
2.17 OILY WATER & CONTAMINATED RAIN WATER SEWER SYSTEM............................... 10
2.18 STORAGE & DISTRIBUTION NETWORK FOR TREATED EFFLUENT........................... 10
2.19 MOUNDED BULLET ......................................................................................................... 11
2.20 FIRE PROTECTION SYSTEM .......................................................................................... 11
2.21 FIRE STATION ................................................................................................................. 13
2.22 STATUTORY APPROVALS .............................................................................................. 14
2.23 DRAWINGS & DOCUMENTS ........................................................................................... 14
2.24 MISCELLANEOUS............................................................................................................ 14

3. SCOPE OF SUPPLY ................................................................................................................ 15

3.1 OWNER’S SCOPE OF SUPPLY ....................................................................................... 15


3.2 CONTRACTOR’S SCOPE OF SUPPLY ........................................................................... 15

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


SCOPE OF WORK & SUPPLY SECTION: C-1.7
(GENERAL CIVIL) 6979-002-16-47-SOW01,
PROCESS AND UTILITY FACILITIES
Rev.1
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 3 of 15
PROJECT AT PADUR

1. BRIEF SCOPE OF WORK

The scope of work for General Civil works shall cover design, detail engineering, supply of all
materials, construction, fabrication, erection, painting, testing, commissioning of all systems &
obtaining approval from Statutory Authorities as per detailed scope of work, design basis,
Specifications, scope drawings attached & local & International codes, etc for Shaft area (Top
of caverns), Raw water system, Drinking water system, Compressed Air system, Boiler, fuel
forwarding area, fuel oil tanks (Diesel Tanks), Nitrogen system, Flare system, Service water
system, Fire protection system including fire water tanks, fire water pumps and pump house,
Fire Station, Sub-station, Switch yard, DG shed, Control room, Sanitary waste system,
Mounded LPG bullet including unloading of LPG, Buildings, parking shed, Effluent treatment
plant, Treated Effluent System.
The scope involves following in brief:

• Survey Works
• Site Grading & Micro grading of the area
• Slope protection
• Fencing & gates
• Drainage works
• Road works, Approach roads, Footpaths
• Storm water drainage, RCC box culverts, RCC pipe culverts
• RCC Pavement
• Dyke wall & Fire wall for fuel oil (diesel) tanks
• Instrument cable road crossings (IRC), Electrical cable road crossings (ERC)
• Pipe sleepers, Pipe way culverts for road crossings
• Raw water system
• Drinking water system
• Plumbing & building drainage
• Oily water system
• Contaminated Rain Water system
• Sanitary sewer system
• Fire protection system
• Safety shower & Eye wash
• Rain water harvesting from roof of buildings & Strom water Drains
• Treated Effluent Storage & Disposal
• Approval from statutory authorities

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


SCOPE OF WORK & SUPPLY SECTION: C-1.7
(GENERAL CIVIL) 6979-002-16-47-SOW01,
PROCESS AND UTILITY FACILITIES
Rev.1
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 4 of 15
PROJECT AT PADUR

2. DETAIL SCOPE OF WORK

The General civil works involved in the work shall include, but not be limited to, the following:

2.1 SURVEY WORKS


EPCC contractor shall carry out all survey works required for the job.
The Topography survey drawing for the complex (GP 08-09/ISPRL/PADUR/TOPO/PART1 &
GP 08-09/ISPRL/PADUR/TOPO/PART2 dated 11.04.09) is enclosed with this tender
package. The topographical survey was carried out before construction of U/G cavern works.
Contractor shall carry out survey work to ascertain existing levels/topography as per
Specification for Survey works (6979-002-16-47-SP-02) enclosed with the bid.
The Scope of Work shall include survey of the entire area shown in the Plot Plan inside the
boundary wall.

2.2 SITE GRADING


Contractor is required to visit the area physically and collect all the necessary data required for
completion of works in all respects within contract scope limit.
Grading shall be done as per EIL specifications/ standards. The existing ground levels as
shown in survey drawings which are enclosed with this tender are for reference purpose only.
The EPCC contractor shall carry out the survey works & ascertain levels as per actual site
conditions handed over to the contractor.
A conceptual site grading layout is enclosed with the bid. Contractor to develop site grading
layout during detail engineering and submit the same to owner/PMC for review.
Contractor shall grade the area as per approved site grading layout. The work shall include
cutting of trees of all sizes, clearing and stripping of all vegetation, grass and roots, rock
blasting/cutting, excavation in hard and soft rock, Filling/ Cutting required to bring the site up
to the finished grade levels. Any earth required for filling upto final FGL (Finished grade level)
shall be arranged by the contractor at his own cost from approved borrow areas (to be
arranged by the contractor) outside complex covering all lifts & leads.
Scope of work of contractor for Site grading shall be for the entire area within his scope of
work. Following area shall be graded:
- Upto grading limit as shown in the site grading layout and any additional area as per
layout developed by the contractor
- Along the approach road for Process Area, ETP, Flare & Pipeline facilities including
corridor required for drains
- Along approach road from portal towards emergency exit as indicated in the layout
drawing
- Site grading inside plant along the slopes as shown in the Site grading Layout.
- Cutting and filling required for construction of Footpaths anf drain along boundary wall.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


SCOPE OF WORK & SUPPLY SECTION: C-1.7
(GENERAL CIVIL) 6979-002-16-47-SOW01,
PROCESS AND UTILITY FACILITIES
Rev.1
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 5 of 15
PROJECT AT PADUR

In addition to the areas listed above any other area required for completion of work shall also
be graded.
Micro grading and site finish after completion of work to achieve final finish in the complex
shall be done by EPCC contractor. Unserviceable material shall be disposed off beyond
ISPRL’s compound wall by the contractor. Rock shall be disposed in the dump area as
indicated in site grading drawing. Disposal areas/ borrow areas for earth shall be arranged by
the contractor. All taxes, royalties shall be borne by the EPCC Contractor.

2.3 FENCING REQUIREMENT


Providing & constructing Chain link fencing with gates around Fuel Oil Tank Unloading area,
LPG Unloading area, LPG mounded vessel, building area, monitoring Boreholes,
transformers, nitrogen storage within the plant.
Chain link fencing shall be provided as per drawing No. 6979-002-16-47-3302. Contractor
shall provide chain link fencing as per requirement of Statutory Authorities. Any additional
requirement of statutory authorities shall be part of Scope of Work.
Gates shall be provided on Chain Link Fencing at locations shown in the Plot Plan as per
Standard/Specification of Structure/Architecture.

2.4 STORM WATER DRAINAGE WORKS & CULVERTS


Design and construction of storm water drainage system within the plant boundary and
outside along north of plant boundary & diversion of existing nallah towards south west of
plant as shown in the Layout drawing is in Scope of the Contractor. Conceptual Strom water
drain layout, drawing no. 6979-002-16-47-0012 is enclosed with the bid. Contractor shall
develop a detailed layout of storm water drainage system and submit for review to
Owner/PMC. Design calculations of storm water drainage shall be prepared by the contractor
and submitted to Owner/PMC for review.
Strom water drain inside the plant boundary wall shall be designed for catchment area inside
plant boundary wall. Drain along north of plant shall be provided along boundary wall outside
plant area designed for flow from catchment area as shown in the layout.
The type of drain shall be rectangular/trapezoidal as shown in the layout. The material of
construction shall be as per Design Basis. Minimum width of drains shall be 500mm. The
Slope of drain shall be provided as per Design Basis. In case the velocity is exceeding the
design basis limits, RCC steps shall be provided in drain to restrict the velocity.
Indicative locations of RCC box culvert & Pipe culvert are shown in the drawing. Contractor
shall finalize the requirement and size Box/Pipe culvert and submit for PMC/Owner for
review.
Hot Dip Galvanised (HDG) grating on drains shall be provided by the contractor inside paved
area (RCC/PCC/Paver Block).
The Strom water from the plant shall exit plant boundary at exit as shown in the layout.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


SCOPE OF WORK & SUPPLY SECTION: C-1.7
(GENERAL CIVIL) 6979-002-16-47-SOW01,
PROCESS AND UTILITY FACILITIES
Rev.1
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 6 of 15
PROJECT AT PADUR

Existing Nallah in SW of plant passing within the plant boundary limit shall be dismantled &
Trapezoidal drain of same capacity as shall be provided to route the storm water. Drain shall
be connected to existing nallah.
Contractor shall provide mesh of reinforced bars at entry & exit point of the drain in boundary
wall. Typical arrangement of Reinforcement bars mesh is shown in the layout drawing.

2.5 ROADS, APPROACH ROADS, FOOTPATH & WALKWAYS


All Roads as shown in drawing no. 6979-002-16-47-0011 are in scope of the contractor.
Approach roads/ walk ways/ footpaths/ steel bridges (as applicable)/ cross-over to all hydrants,
monitors, pump houses, and to all other operating and maintenance areas and utility valve
operating areas etc. all buildings, pump stations or any other place required as per detailed
engineering/ execution/ maintenance/ commissioning requirement etc. as per PMC/ Client
requirement within the plant shall be in Contractor’s scope.
Any additional approach roads to facilitate crane movement or any other vehicle movement
during construction shall be in contractor’s scope of work.
The road cross section as per drawing no. 6979-002-16-47-4304 attached with the bid is
indicative. Contractor to design cross section of roads for 2msa as per IRC. Roads shall be
designed based on the CBR values to be obtained by contractor.
1.2 m wide PCC access footpath with RCC steps shall be provided by the contractor all along
boundary wall inside the plant and as indicated in the Plot Plan. For details of PCC footpath
refer drawing No. 6979-002-16-47-3305. Slope for footpath shall not exceed 1:6. Wherever
slope is steeper than 1:6 RCC steps with minimum tread of 300mm & maximum riser of
200mm riser shall be provided.

2.6 RCC PAVEMENT


RCC pavement for all pump stations, process area, Flare areas, Nitrogen area, Boilers area,
fuel forwarding area, LPG unloading area, ETP (as per operation, maintenance & access, as
defined in Environmental input), piping manifold areas, below and around A/G piping drain
points, and any other place as required for operation and maintenance shall be provided by
EPCC.
Type II pavement as per standard 7-65-0404 shall be provided as for all the above areas
except vehicular movement areas where pavement shall be Type I as per std. no. 7-65-0404.

2.7 DYKE & FIRE WALL FOR TANKAGE AREA


Dyke enclosure shall be of stone masonry construction. The enclosure shall be designed as
per OISD/ PESO rules. All the tanks in common enclosure shall be separated by firewall
(stone masonry construction) as per PESO’s rules and OISD guidelines. Minimum 600 mm
wide walkway over all dyke walls shall be provided.
The location of tankage along with dyke shall be kept keeping safety distances from above
ground facilities as per OISD & PESO rules.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


SCOPE OF WORK & SUPPLY SECTION: C-1.7
(GENERAL CIVIL) 6979-002-16-47-SOW01,
PROCESS AND UTILITY FACILITIES
Rev.1
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 7 of 15
PROJECT AT PADUR

2.8 PIPE SLEEPERS


Construction of pre-cast and cast-in-situ Pipe Sleepers (sliding/ anchor), as required, for
above ground piping as per Piping requirements and for above ground Fire water header.
The sleeper height shall be 300mm to 500mm above finished ground level.

2.9 ROAD CROSSINGS (ERC, SCRC, IRC, PWB & PIPE SLEEVES)
All road crossings including Electrical Road crossings (ERC), Street Light Cable Road
Crossings, IRC (Instrumentation Road crossings), Pipe-way Bridges (culverts), Pipe sleeves
etc. shall be constructed by EPCC based on requirement of Electrical, Instrumentation and
Piping requirements.
Carbon steel sleeves (PMS-A3A) shall be provided for road crossings for firewater, process
piping as per attached standard 7-44-0404. In case sufficient cover is not available, the pipe
sleeve shall shall be encased as per std. 7-65-0213.

2.10 RAW WATER SYSTEM


Design, construction, installation, testing and commissioning of complete Raw water system
comprising of Raw water Reservoir and associated works, service water pumps complete
underground distribution piping from Raw water reservoir to FW tanks is in the scope of
EPCC contractor. The raw water shall be provided by road tankers
Raw water system mainly consists of the following:
- RCC Raw water Reservoir: Design and construction of covered RCC reservoir for
4050cum capacity in two compartments. Work including excavation for RCC reservoir
up to the required level and gradient, construction of water retaining RCC structure,
construction of RCC cover over reservoir including Manhole & Rungs, Pipe line entry to
reservoir, valve arrangement, etc. shall be carried out as per drawing no. 6979-002-16-
47-3103 (P&ID for raw water system) by EPCC Contractor. Contractor to develop GA
drawing for Raw water reservoir & pump station piping and submit to Owner/EIL for
review.
- Raw water & Firewater Make up Pumps and Sump: Supply and Installation of
Service water & Firewater makeup pumps including construction of pump station with
associated piping, instrumentation shall be provided by contractor in raw water pump
station. RCC Raw water sump and pump station shall be provided as per specification,
conceptual layout and P&ID attached with the tender document.
- Raw water piping up to reservoir & upto Firewater Tanks: Complete above ground
and underground piping including providing valves, instrumentation, flanges etc. from
Battery Limit of the plant to Raw Water reservoir & Drinking water sump inside the plant
limits shall be provided by EPCC. Supply & laying of firewater make-up piping from raw
water reservoir/ pump station to Fire Water tanks is in scope of EPCC. Scope shall also
include construction of RCC sleepers/supports for aboveground piping, necessary
excavation/backfilling for underground lines. All aboveground pipes shall be painted as
per specifications & underground piping shall be provided with coating & wrapping as
per specifications.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


SCOPE OF WORK & SUPPLY SECTION: C-1.7
(GENERAL CIVIL) 6979-002-16-47-SOW01,
PROCESS AND UTILITY FACILITIES
Rev.1
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 8 of 15
PROJECT AT PADUR

2.11 DRINKING WATER SYSTEM


Design, construction, installation, testing and commissioning of complete drinking water
system is in scope of EPCC contractor. Drinking water system shall consists of drinking water
Sump of 90cum capacity, drinking water pumps, Piping from raw water pipeline upto drinking
water sump, providing Vacuum type chlorinator for chlorination in the sump, drinking water
distribution piping from drinking water sump to drinking water tanks (HDPE Syntex or
equivalent tank) located on top of the buildings and safety shower & eye wash at various
locations.
The complete work shall be carried out as per drawing, P&ID and specifications attached with
the tender document. For Details refer P&ID no. 6979-002-16-47-3102 attached with the
tender.
The header sizes shown on this drawing is minimum requirement. Contractor shall check the
sizes as per hydraulic analysis and provide higher sizes as required. Suitable number of
isolation valves shall be provided.
Contractor to develop GA drawing for drinking water reservoir & pump Station piping and
submit to Owner/EIL for review. Conceptual GA for Drinking water sump and pump station is
attached with the bid for reference purpose.
(NOTE: The drinking water network shall cater to 25 persons and 2 numbers of safety
shower and eyewash acting simultaneously. Building wise break-up shall be decided during
detailed engineering in consultation with the Owner. The pipe size shall be designed for 3
times the average daily demand. 25% design margin shall be kept while designing drinking
water system to take care of leakage and wastage.)
The requirement given above is minimum. Contractor to design the Drinking water system
and submit P&ID, Layout & Design calculations to PMC/Owner for review.

DRINKING WATER DISTRIBUTION: Drinking water distribution piping from sump to


Administration building, Guard Rooms, substation building, control room buildings or any
other Buildings as shown in Plot plan, drinking water Posts, safety shower and eyewash in
shaft area, ETP Area or any other place as per process requirement is in scope of contractor.
Drinking water post shall be provided by the contractor. Drinking water overhead tank
(HDPE Sintex or equivalent shall be provided on top of every building to cater to the
requirement of toilets, floor cleaning, drinking water posts etc. The capacity of tank shall be
decided based on the average daily demand of 135 litres per capita per day (lpcd). The
minimum line size at tie-in point shall be 2”. Isolation valve in piping including valve pit at all
consumption points shall be provided.
Contractor shall develop Layout for Drinking water system drawing & submit to Owner/EIL for
review.
Drinking water shall be J2A class.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


SCOPE OF WORK & SUPPLY SECTION: C-1.7
(GENERAL CIVIL) 6979-002-16-47-SOW01,
PROCESS AND UTILITY FACILITIES
Rev.1
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 9 of 15
PROJECT AT PADUR

2.12 SAFETY SHOWER & EYEWASH (SS & EW)


Contractor shall provide minimum 1 number combined safety shower and eyewash at ETP,
shaft top area, areas where either caustic or other chemicals are handled or toxic chemicals
may be present. No. of SS & EW to be provided shall be as per process P&IDs and
equipment layout and hazardous area requirements. Water shall be fed from drinking water
line. Discharge from safety shower/eye wash unit shall be connected to neutralisation pit and
after neutralisation, it shall be connected to storm water drain.

2.13 ACID/ ALKALI PROOF LINING


Contractor shall provide Acid/Alkali proof floor lining within and around the Caustic treatment/
Handling/ Wash areas/ Amine handling areas over RCC pavement and on associated
equipment foundation and kerb wall on both the sides. The entire area shall be kerbed by
RCC kerb wall. Acidic/ caustic waste shall be collected and discharged into neutralization pit.
The neutralized waste from this pit shall be routed to roadside storm water drain.

2.14 SANITARY SEWER SYSTEM


Design, construction, installation, testing and commissioning of complete sanitary water
system is in scope of the contractor. Sanitary Sewer (SS) System from various buildings (i.e.
Administration building, sub- station, control room, Guard rooms etc) shall be collected via
gravity sewer piping and connected to Septic tank & subsequently to soak pit/upflow filter.
RCC manholes, Inspection chambers, Gully trap etc. shall be provided as per design
requirement shall be provided by the contractor. Contractor shall develop Layout for Sanitary
waste water system drawing & submit to Owner/EIL for review. Contractor shall submit the
Design Calculations for PMC/Owner Review.

2.15 INTERNAL PLUMBING & SANITARY WORKS IN BUILDINGS


Design, installation, testing and commissioning of water supply lines (concealed piping),
drains for soil and wastewater within buildings are in EPCC contractor’s scope of work. All the
sanitary fixtures and fittings shall be as per architectural drawings/ specifications and relevant
Indian standard codes. EPCC contractor to connect the sanitary sewer to septic tank and soak
pit/upflow filter by gravity flow.

2.16 RAIN WATER HARVESTING FROM STORM WATER DRAINS & BUILDING DRAINAGE
Design and providing rainwater harvesting system for all storm water drains as per layout of
Strom water drains and standards enclosed with the bid. Rain water harvesting pit for Strom
water drain shown in the layout is minimum & indicative only. Contractor to finalize the exact
number & location of same during detail engineering.
Rainwater falling on roofs of buildings shall be collected through a system of pipes and routed
to recharge bore well suitably located on ground. The same shall be provided as per standard
enclosed in the bid. One Rain water harvesting pit shall be provided for each building.
Contractor shall develop Layout drawing & detail of rain water harvesting system & submit to
Owner/EIL for review

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


SCOPE OF WORK & SUPPLY SECTION: C-1.7
(GENERAL CIVIL) 6979-002-16-47-SOW01,
PROCESS AND UTILITY FACILITIES
Rev.1
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 10 of 15
PROJECT AT PADUR

2.17 OILY WATER & CONTAMINATED RAIN WATER SEWER SYSTEM


Design, construction, installation, testing and commissioning of underground OWS & CRWS
system is in scope of EPCC Contractor. The discharge shall flow by gravity to OWS/CRWS pit
& shall be pumped to ETP.
OWS from all equipment, pumps etc. shall be collected through funnels points as specified in
Process P&ID enclosed in the Bid to be disposed to OWS sump through gravity. The discharge
is collected through underground carbon steel pipes (piping material class shall be as per
enclosed Process P&ID, Process Package and Piping Material specification developed by the
contractor).
Underground RCC gravity sewer shall be provided to collect CRWS flow from all units in
process area and discharged to OWS/CRWS pit through gravity.
In tank farm area an underground carbon steel waste collection piping system shall be
provided for collection of tank drains. The sewer shall be routed outside tank farm & joined to
offsite OWS sewer through a sealed manhole. RCC open drains for rainwater drainage shall be
provided for tankage Area. A sand trap & a two way valve pit shall be provided for diversion of
rain water to Strom water or Oily Waste Sewer (OWS) depending upon the contamination.
Manholes & catch pits shall be provided with puddle flanges in concrete walls for all inlet &
outlet pipes. All underground carbon steel piping shall be tape coated as per specification /
cathodic protection to restrict corrosion as per enclosed specification.
OWS shall be routed, in offsite through gravity to ETP in underground RCC sewers with
intermediate RCC manholes. CRWS shall be routed in offsite upto sump in underground
RCC sewers with intermediate RCC manholes & from sump it shall be pumped to ETP by CS
pipes.
Supply & installation of CRWS pumps included construction of sump & pump station, with
associated piping, instrumentation works etc. shall be provided by the contractor. For details
refer P&ID for CRWS Pumping system (6979-002-16-47-3104)
Transformer oil shall be drained to a RCC pit. The oil shall be pumped out of RCC pit time to
time using portable pump. One no. Portable Electric driven pump for pumping oil shall be
provided by EPCC.
Contractor shall develop P&ID, Layout drawing etc. & submit to Owner/EIL for review. Design
Calculation of the OWS system shall be submitted for Owner/PMC review.

2.18 STORAGE & DISTRIBUTION NETWORK FOR TREATED EFFLUENT


Design, construction, installation, testing and commissioning of complete Treated Effluent
water System comprising of Treated Effluent Storage & distribution system.
- Treated Effluent Pond: Design and construction of Open Earthen reservoir of
3,600cum holding capacity including excavation for reservoir up to the required level
and gradient, construction of earthen reservoir with HDPE film with plain cement
concrete lining on side slope and bottom of the reservoir & providing Plain cement
concrete lining outside slopes of reservoir including providing Contraction/Expansion
joints, sleepers below joints etc., Pipe line entry to reservoir, valve arrangement, etc.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


SCOPE OF WORK & SUPPLY SECTION: C-1.7
(GENERAL CIVIL) 6979-002-16-47-SOW01,
PROCESS AND UTILITY FACILITIES
Rev.1
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 11 of 15
PROJECT AT PADUR

shall be carried out as per drawing no. 6936-00-16-47-3602 by EPCC Contractor. The
drawing attached is indicative. Contractor to develop GA drawing and detailed layout for
Effluent water reservoir & pump station piping and submit to Owner/EIL for review.
- Sump and Pumps: Supply and Installation of Treated Effluent pumps. The same shall
be used for Firewater Makeup & Gardening. Construction of RCC Sump & pump station
with associated piping, instrumentation shall be provided by contractor in pump station.
RCC sump and pump station shall be provided as per specification, conceptual layout
and P&ID attached with the tender document. Contractor to develop P&ID for Treated
effluents storage, pumping and distribution system & furnish to owner/EIL for review.
- Piping: Complete above ground and underground piping including providing valves,
instrumentation, flanges etc. from ETP to Effluent Disposal Pond shall be provided by
EPCC. Supply & laying of firewater make-up piping from treated effluent pond / pump
station to Fire Water tanks is in scope of EPCC. Scope shall also include construction
of RCC sleepers/supports for aboveground piping, necessary excavation/backfilling for
underground lines. All aboveground pipes shall be painted as per specifications &
underground piping shall be provided with coating & wrapping as per specifications.
Complete distribution network using HDPE pipes (underground main header) all around
the periphery of the green belt for irrigation and gardening of green belt within the
Complex along with tapping with isolation valves and hose coupling is in scope of
EPCC contractor. Minimum size of HDPE Pipe shall be 4”. Minimum 1” dia tapping with
isolation valves, sprinkler, necessary supports etc. shall be provided @50m c/c.
Contractor shall develop P&ID, Layout drawing etc. & submit to Owner/EIL for review.
2.19 MOUNDED BULLET
LPG bullet (1 no) shall be provided as per Process P&ID and data sheets and Static
Equipment data sheets with mounded enclosures including construction of mounds. Approval
from PESO/ TAC shall be taken by the contractor. Contractor shall develop the detail layout
as per requirement of OISD standards. Storm water drains shall be provided around the
storage areas to ensure proper drainage. Automatic fire water spray protection with deluge
vales and pneumatic detection system shall be provided on pipe domes, nozzles, RCC
tunnels, pumps etc. as per OISD in addition to the peripheral hydrant system. Other works
like hard stand requirements for erection of mounded bullets/ vessels, balance site-grading
and micro-grading, approach road, RCC footpath, chain link fencing with appropriate no. of
gates, culverts, RCC pipe sleepers, RCC stairs with handrail etc. shall also be in the scope of
the contractor. Contractor shall develop P&ID, GA, Layout drawing etc. & submit to
Owner/EIL for review

2.20 FIRE PROTECTION SYSTEM


Design, providing, construction, installation and testing complete fire protection system as per
design basis enclosed with the bid, TAC requirement, OISD requirement, international codes
& practices. The scope of work mentioned below is minimum. Contractor to design complete
Fire protection system and submit for PMC/Owner for review. Firewater Pumping P&ID, piping
Layout, Pump house GA, hydraulic analysis, design calculations shall be submitted by the
contractor for PMC/Owner for review. Firewater system shall be designed and provided as per
OISD 117 for single major fire and TAC.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


SCOPE OF WORK & SUPPLY SECTION: C-1.7
(GENERAL CIVIL) 6979-002-16-47-SOW01,
PROCESS AND UTILITY FACILITIES
Rev.1
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 12 of 15
PROJECT AT PADUR

- Fire water Storage & Pumping:


Providing 2 nos CS above ground tanks for fire water storage of minimum capacity
1640cum each and associated works including sand pad foundation, Fire water RCC
Pump House, Fire water pumps (motor driven and Diesel driven including diesel day
tanks of 12 hours of running storage) with associated piping, electrical and
instrumentation works & piping network (both above ground and underground) as per
P&ID no. 6979-002-16-47-3101 and pump data sheets. All the requirements of TAC
and OISD shall be met with. The system under the scope of EPCC shall be got
approved from TAC accredited agency including preparation of all documents, all
liaison works, modification/ correction as per the comments of the agency without any
extra cost and time implication to the owner. The line size furnished in the P&IDs are
indicative and is minimum requirement and higher sizes required as per detailed design
and hydraulic analysis shall be provided by the contractor. Contractor shall prepare
P&ID, GA drawing & submit to Owner/EIL for review
- Firewater network shall be laid in closed loops with isolation valves. Pipes shall be laid
underground in RCC/ PCC paved areas and for road crossing and approach to the
building. Above ground fire water pipes shall be laid on independent sleepers. Above
ground piping shall be painted fire red paint conforming to shade no. 536 of IS: 5.
Underground piping shall be protected from corrosion by applying tape coating as per
specification enclosed with the package. In RCC paved areas fire water pipes shall be
laid in sand filled RCC trench with RCC precast cover. The fire water lines laid in these
RCC trenches shall also be provided with corrosion protection tape coating. Under
ground fire water headers at road crossings shall be laid in CS sleeves with bitumen
mastic at both the ends. All headers rising from underground to above ground shall be
provided with corrosion protection tape coating up to 500mm above grade. Contractor
shall develop Firewater layout and submit to Owner/EIL for review.
- Fire water pipes, valves, fittings etc. shall be of Carbon steel material.
- Design & providing Auto actuated, Total flooding, Centralized Clean agent fire
extinguishing system including Fire detection & alarm system for Control room as per
NFPA-2001 specification for Clean Agent System (6-66-0050). The areas for protection
of building with Clean agent shall consists of Console room, computer room, UPS room,
Rack room etc. The system shall be provided as per specifications & NFPA 2001
(2008). Clean Agents to be considered are IG-541, IG-100, IG-55 and IG-01 as per
NFPA 2001
- Auto actuated High velocity water spray system for transformer of oil capacity more
than 2000 litres
- Medium velocity Water Spray, Fixed & Semi fixed foam system shall be provided for
Diesel Tank
- Fixed water Spray shall be provided around each shaft area.
- Water cum Foam Monitors with HDPE storage container (1 for each monitor) suitable
for storing foam of capacity 500L shall be provided around shaft area, LPG unloading
Area and Diesel Storage Area

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


SCOPE OF WORK & SUPPLY SECTION: C-1.7
(GENERAL CIVIL) 6979-002-16-47-SOW01,
PROCESS AND UTILITY FACILITIES
Rev.1
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 13 of 15
PROJECT AT PADUR

- Approval of complete fire protection system from TAC accredited agency


- Hydrants and monitors to be provided on all Fire water headers along roadsides at all
locations as per OISD requirement. Contractor to finalize the exact location and nos. of
hydrants/ monitors etc. as per TAC/ OISD requirements and covering the entire area/
facilities. Hydrants & monitors shall be provided with operating platforms as per
standard & specifications.
- Hydrant system (each hydrant post with two numbers of type-A hydrant valve). Each
hydrant post shall be provided with 4” isolation valve. Hydrant shall be BIS approved.
- All monitors shall be non-aspirating type water cum foam with arrangement of jet and
spray (aqua fog/ foam). All monitors shall be BIS approved. Each monitor shall be
provided with 4” isolation valve on 6” branch pipe).
- Hose box type-II as per spec. no. 6-66-47 near the alternate fire hydrants.
- hose reel shall be provided as per TAC/ OISD requirements.
- Hose boxes and hose reels shall be placed on suitable foundations at appropriate
height.
- Landing valves on all landings for buildings and on all working platforms with hose
reels and hose boxes.
- Fire extinguishers/ First Aid Fire fighting equipments of various types and capacities
in all building, pump stations, pump houses etc. as per TAC norms/ OISD norms
requirements.
- Potable Fire extinguishers shall be provided at all various locations based on OISD
requirement
- All the equipments of fire water system shall either be ISI marked or FM/UL listed
- All Firewater CS Pipes shall be hydro tested at 22.5 kg/cm2g and minimum test
pressure downstream of Restriction Orifice for water spray system shall be taken as 8.4
kg/cm2g
- Provide suitable restriction orifice as per TAC requirement for hydrants and water
spray system.
- Provide suitable strainers, isolation valve, drain valve, vent at each tapping point for
spray cooling system.
- Flushing arrangements at various loops of Fire Water Network & spray system.
- Detailed drawings conforming to TAC/ OISD requirement shall have to be prepared by
the Contractor.
- Taking approval of the complete fire fighting system from TAC accredited agency
including preparation of all documents, write-up & drawings. Any change/ alterations
required to be made to meet the requirements of TAC accredited agency shall be done
by the EPCC contractor without any extra time and cost implication. EPCC Contractor
shall design the fire protection system to obtain maximum rebate on insurance
premium.
- Any other specific protection required or identified during detailed engineering

2.21 FIRE STATION


Fire Station building with the following facilities shall be constructed as per Architectural and
structural scope of work and specification attached with this package tender:

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


SCOPE OF WORK & SUPPLY SECTION: C-1.7
(GENERAL CIVIL) 6979-002-16-47-SOW01,
PROCESS AND UTILITY FACILITIES
Rev.1
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 14 of 15
PROJECT AT PADUR

The center for use of fire protection equipment shall be Fire Station under control of fire
Marshal of the complex. All fire safety controls shall be operable from fire station where a
control room shall be set up for operational controls. Fire detection, fire alarm communication
shall be controlled at fire station for necessary follow up action. Fire station shall have the
following facilities:
- Fire Fighting Agents
- Fire Fighting Equipments
- Mobile Fire Fighting Equipments i.e. Water cum Foam Tender
- Ambulance*
- Safety equipments like fire suits, fire blankets, breathing apparatus *
- Centralised Fire Alarm Panel
- Supervisory and Control Panel
- Emergency Communication
- Fire Control Panel for Operation of Fire Equipments.
Fire Station shall also include the followings:
- Sufficient store for respirator, non-respiratory equipment, firefighting equipment, foam and
dry chemical powder, hoses and spares.
- Overhead foam storage & loading facility shall be provided at fire station to store 25KL
foam.
- Fire station shall have separate exit and entry for fire vehicles from two different roads.
* Procurement of these items shall be done by Owner through separate MR.

2.22 STATUTORY APPROVALS


Approval of the facilities from Chief Controller of Explosives (PESO), Tariff Advisory Committee
(TAC) accredited agency, DGCA (Director General & Civil Aviation), Environmental Authorities,
Local Authorities shall be obtained by the package contractor. Contractor to comply with the
requirement of these authorities irrespective of, if it is mentioned or not in this package & shall
form part of contractor’s scope of work including preparation of required drawings/ documents.
Contractor shall comply with the requirement of local bodies including preparation of required
drawings/ documents. Any change/ modification required by these authorities shall be carried
out by package contractor and final approval shall be obtained from these authorities without
any time and cost implication.

2.23 DRAWINGS & DOCUMENTS


Plot Plan, P&IDs, PFDs, Detailed Area drawings and layout drawings shall be prepared for all
facilities, services & utilities under the scope of contractor. The drawings/documents shall be
submitted to EIL/Owner for review. For details of drawings to be submitted refer Section A-
5.2.5.

2.24 MISCELLANEOUS
- Temporary approaches, culverts, fencing etc. as required during construction activity of
EPCC shall be designed and provided by EPCC contractor.
- EPCC package contractor shall prepare and submit the list of all codes and standards
including local codes, standards and regulations that are related to design.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved


SCOPE OF WORK & SUPPLY SECTION: C-1.7
(GENERAL CIVIL) 6979-002-16-47-SOW01,
PROCESS AND UTILITY FACILITIES
Rev.1
AT TOP SIDE AND INSIDE CAVERN,
FOR CRUDE OIL STRATEGIC STORAGE Page 15 of 15
PROJECT AT PADUR

- Any temporary activities required during the execution shall be included/ carried out by
EPCC contractor.
- EPCC contractor shall be responsible for completion of works in all respects whether
specifically mentioned or not in the contract.

3. SCOPE OF SUPPLY
3.1 OWNER’S SCOPE OF SUPPLY
Nil
3.2 CONTRACTOR’S SCOPE OF SUPPLY
- All items, consumables/non consumables required to complete the job.
- All tools tackles, plant machinery etc to complete the job.
- Mandatory spares as listed in Section A-4.5.
- Erection and commissioning spares.
- Quotes for spares for 2 years of normal operation.

Format No. EIL-1641-1924 Rev.1 Copyright EIL – All rights reserved

You might also like