0% found this document useful (0 votes)
62 views1 page

Design Calculation Sheet: A-Water Demand

The document is a design calculation sheet for domestic water calculations for a staff residential building project. It calculates the water demand and fixture units for various fixtures and the total required flow. It also calculates the pipe lengths, equivalent length, estimated pipe size, friction loss, static head, residual pressure and total head to determine the water pressure requirements.

Uploaded by

febous
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
62 views1 page

Design Calculation Sheet: A-Water Demand

The document is a design calculation sheet for domestic water calculations for a staff residential building project. It calculates the water demand and fixture units for various fixtures and the total required flow. It also calculates the pipe lengths, equivalent length, estimated pipe size, friction loss, static head, residual pressure and total head to determine the water pressure requirements.

Uploaded by

febous
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

Design calculation sheet

Project no.: S08060 Date: 19/10/2009 Sheet no.: 1 of 1 Computed by: A.A.
Subject: SAFA- DOMESTIC WATER CALCULATIONS Checked by: A.A.
Staff Residential building Approved by: A.E.

A-WATER DEMAND

FIXTURE TYPE QUANTITY FIXTURE UNIT TOTAL FU


LAV-1 36 1 36
WC (FT) 36 5 180
WC (FV) 0 10 0
SHOWER 36 3 108
HB 0 2.5 0
UR 0 5 0
JS 1 4 4
WT 0 2 0
DF 0 2 0
KS-1 36 4 144
FLOOR TOTAL FU 472

REQUIRED FLOW = 120 GPM


CONNECTION SIZE = 65mm

TOTAL REQUIRED FLOW = 120 GPM =7.57 L/S

B-PRESSURES
Friction
Estimated pipe length (m) = 62
Total Equiv. Length (m) = 77.5
Estimated Pipe Size (inch) = 2.5
Pressure drop, (psi / 100 ft) = 3.95
Total Friction Loss (psi) = 10
Total Friction Loss (m) = 6.8

STATIC HEAD IN METERS = 6.8 (GROUND )

RESIDUAL PPRESSURE IN METERS = 3.5

FRICTION LOSS IN METERS = 6.8

TOTAL HEAD IN METERS = 17.1 = 1.71322933 BARS