Feature
ZL-7830 series are humidity controller with 30A output relay. Compact with IP65 level front panel, convenient operation
and easy installation.
Model Function
Model Function
ZL-7830A Humidify / de-humidify
ZL-7830B Humidify / de-humidify; Alarm output
Specification
Power supply: 100 ~ 240Vac, 50/60Hz
Input signal: one humidity sensor (L = 1500mm)
Output load: R1, 30A/250Vac. R2/R3, 3A/250Vac. The parameters are based on resistive load.
Set range: humidity 0 ~ 100% RH. Resolution 0.1%
Absolute measurement accuracy: humidity 5%
Working environment: -20 ~ 45℃, 10 ~ 90% RH without dewing
Device dimension: 78 * 34.5 * 71 (mm, W * H * D)
Drilling template: 71 * 29 (mm, W * H)
Case materials: PC + ABS (fireproof)
Protection level: IP65 (front panel)
Set Parameters
Keep〖P〗depressed for 3 seconds:
If the code is not “0000”, the display shows “---0”.
Press〖▼〗to select the digit of the password. Press〖▲〗to set the value (0 ~ 9) of the digit.
Press〖S〗to confirm. If the password is correct, enter into the set status. Else exit.
If the code is “0000”, then the password is not necessary. Enter into the set status directly.
Parameter Table
Code Function Range Remark Default
U10 Humidify / de-humidify H/P H: humidify; P: de-humidify P
U11 Hysteresis 0.1 ~ 20% 5
U12 R1 delay protection 0 ~ 30 min 0
U13 Humidity calibration -9.9 ~ +9.9% 0
U14 Humidity up limit 0 ~ 100% 100
U15 Humidity low limit 0 ~ 100% 0
U16 Over limit alarm delay 0 ~ 600 sec 30
U99 Password 0000 ~ 9999 0000: no password is necessary 0000
Control Function
Humidity Control (R1)
Dehumidify control (U10 = P)
If room humidity ≥ set-point, and R1 has stopped for U12, R1 will be energized.
If room humidity ≤ set-point – U11, R1 will be de-energized.
Warning
When sensor fails, the controller displays blinking “E1”, keeps beeping, R1 is de-energized.
When room humidity ≥ U14 for U16 time, the controller displays “E2”, keeps beeping, alarm output acts, R1 keeps.
When room humidity ≤ U15 for U16 time, the controller displays “E3”, keeps beeping, alarm output acts, R1 keeps.
Alarm output:
Terminal Remark
R3 Open when alarm. Close when ok. Open when no power supply.
R2 Close when alarm. Open when ok. Close when no power supply.
COM Common terminal
Sensor Calibration
When the sensor has tolerance, it can be calibrated by U13.
Installation Attention
Insert the controller into drilling hole. Do not connect and de-connect lines when power
Slide the bracket to fix the device. supplied, including sensor.
Terminal Drawing This product has been strictly tested before shipping.
The company warranty is one year, the
responsibility is limited to the sale of the product
itself. Damage caused by improper usage is not
covered by the warranty.