Origin USA USA USA Europe: Standards ASTM D1816 Astm D 877 IEC 60156 Procedure A Procedure B

This document summarizes and compares several standards for dielectric breakdown voltage testing of insulating liquids: 1) ASTM D 877 and ASTM D1816 are US standards that have similar procedures and requirements for electrodes, temperature controls, test voltages and breakdown definitions. 2) IEC 60156 is a European standard that also specifies electrodes, temperatures and test voltages but provides more details on breakdown measurements and acceptable variations in results. 3) The standards have many similar aspects but also differences in electrodes, stirring methods, temperature ranges and requirements for silicone oils.

Uploaded by

Optus 583
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
692 views1 page

Origin USA USA USA Europe: Standards ASTM D1816 Astm D 877 IEC 60156 Procedure A Procedure B

This document summarizes and compares several standards for dielectric breakdown voltage testing of insulating liquids: 1) ASTM D 877 and ASTM D1816 are US standards that have similar procedures and requirements for electrodes, temperature controls, test voltages and breakdown definitions. 2) IEC 60156 is a European standard that also specifies electrodes, temperatures and test voltages but provides more details on breakdown measurements and acceptable variations in results. 3) The standards have many similar aspects but also differences in electrodes, stirring methods, temperature ranges and requirements for silicone oils.

Uploaded by

Optus 583
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

ASTM D 877

Standards ASTM D1816 IEC 60156


Procedure A Procedure B

Origin USA USA USA Europe

Shape
Electrodes

Gap size 2 mm or 1 mm* 2.54 mm 2.54 mm 2.5 mm


Impeller yes optional
Oil sample stirring Magnetic not stirred not stirred
no option optional
bead

20 - 30 ºC must 20 - 30 ºC must
At ambient - must record temperature record temperature 15 - 25 ºC
Laboratory test Liquid
record as collected and as collected and for referee tests
temperature when tested when tested

Ambient 20 - 30 ºC Must record Must record Within 5 ºC of oil sample

At ambient - must
Outside test Liquid Must record Must record 15 - 25 ºC
record
temperature
Ambient Referee tests 20 - 30 ºC Must record Must record Within 5 ºC of oil sample
Rise rate 0.5 kV/s 3 kV/s 3 kV/s 2 kV/s
Test voltage
Frequency 45 - 65 45 - 65 45 - 65 45 - 62
Definition <100 V <100 V <100 V 4 mA for 5 ms

Number in 1 - 5 different
5** 5* 6
sequence samples
Breakdowns
Time
between 1 to 1.5 min 1 min n/a 2 min
breakdown

Test voltage Normal (e.g.


Not specified Not specified Not specified <10 ms
switch off time mineral oil)
following break-
down Silicon oil Not specified Not specified Not specified <1 ms

Time between filling and start


3 - 5 min 2 - 3 min 2 - 3 min 2 min
of test

SABE EN 60156
BS EN 60156
VDE0370 part 5
CEI EN 60156
Equivalent standards (adopted AS1767.2.1
None None None IRAM 2341
into) PA SEV EN 60156
UNE EN 60156
NRS 079-1*
FN EN 6056
IS6729*

Can be used if
modified in accord-
Can be used provided discharge energy in OK if test instrument can comply with
Notes on testing silicon oil ance with D2225 if
sample <20 mj voltage switch off time requirements
procedure A cannot
be used

* If breakdown does
not occur at 2 mm,
reduce gap to 1 mm
** Tests must be
*Tests must be repeated if range of BD
repeated if range of Expected range of standard deviation/
voltages recorded are more than 92% of
Special conditions BD voltages recorded mean ratio as a function of the mean
mean. If range of 10 BD voltages is more
are more than 120% provided as a chart
than 151% investigate why
of mean with 1 mm
electrode gap and 92%
of mean with 2 mm
electrode gap

Used if any insoluble Used if any insoluble *With some stand/stir timing differences.
Test vessel requires
breakdown products breakdown products Test cell/vessel must be transparent.
cover or baffle to
Comments in oil completely do not settle Reconditioned/reclaimed oil to BS148
prevent air from
settle between between breakdown is tested to IEC60156 following update
contacting circulating oil
breakdown tests tests in 2009.