Flare Stack Calculation Sheet: Brzustowski's and Sommer's Approach
This document provides a flare stack calculation sheet for a project. It includes key details like the flowrate, mass flow, pressure, and temperature at the flare tip. It also calculates values like flame length, wind velocity, and safe distance to the flame center. The summary provides the essential information and purpose of the document in 3 sentences or less.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
315 views
Flare Stack Calculation Sheet: Brzustowski's and Sommer's Approach
This document provides a flare stack calculation sheet for a project. It includes key details like the flowrate, mass flow, pressure, and temperature at the flare tip. It also calculates values like flame length, wind velocity, and safe distance to the flame center. The summary provides the essential information and purpose of the document in 3 sentences or less.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 8
Flare Stack Calculation Sheet
Brzustowski's and Sommer's Approach
Title : Date of Calculation : HP Flare Calculation ### Project No : Calculate By : 1131/SKPI-SKPP-2006 Erwin Apriandi
1 Description Symbol Unit
2 Flowrate 30.000 MMscfd
3 21,650.000 m3/hr 4 6.014 m3/s 5 Mass Flow W 50570.000 kg/hr 6 Mol Weigth Mj 33.130 7 Pressure at Flare Tip Pj 153.000 kPa 8 Flowing Temperature Tj 266.000 K 9 Air Temperature T~ 289.000 K 10 Compressibility factor z 0.991 11 Ratio of Specific Heat k 1.293 12 Mach No 0.700 13 14 15 Flare Tip ID dj 0.195 m 16 7.65836359538 in 17 18 Heat of combustion 15250.000 kJ/kg 19 Heat Liberated Q 214220.139 kW 20 Flame Length L 30.000 m approx 21 22 Wind velocity U~ 11.800 m/s Fig 8 & 9 23 Sonic Velocity 293.849 m/s 24 Flare Tip velocity Uj 205.694 m/s 25 26 LEL CL 2.100 %v/v 27 LEL Conc Factor 0.418 28 Jet & Wind thrust parameter 20.344 29 30 From Fig C.2.B & C.3.B Fig C.2 Fig C.3 31 Horizontal distance, from stack to flame centre xc 17.000 m approx 32 Vertical distance, from stack to flame centre yc 14.000 m approx 33 34 35 Fraction Radiated Heat F 0.300 36 ד 1.000 37 Allowable Radiation K 6.310 kW/m2 38 Safe Distance to Flame Centre D 28.476 m 39 40 41 Stack To Point of Interest R 100.000 m 42 Flare Height H Err:502 m 43 Calculation are based on API RP 521