Flare Stack Calculation Sheet: Brzustowski's and Sommer's Approach

This document provides a flare stack calculation sheet for a project. It includes key details like the flowrate, mass flow, pressure, and temperature at the flare tip. It also calculates values like flame length, wind velocity, and safe distance to the flame center. The summary provides the essential information and purpose of the document in 3 sentences or less.

Uploaded by

altruism
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
315 views

Flare Stack Calculation Sheet: Brzustowski's and Sommer's Approach

This document provides a flare stack calculation sheet for a project. It includes key details like the flowrate, mass flow, pressure, and temperature at the flare tip. It also calculates values like flame length, wind velocity, and safe distance to the flame center. The summary provides the essential information and purpose of the document in 3 sentences or less.

Uploaded by

altruism
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 8

Flare Stack Calculation Sheet

Brzustowski's and Sommer's Approach


Title : Date of Calculation :
HP Flare Calculation ###
Project No : Calculate By :
1131/SKPI-SKPP-2006 Erwin Apriandi

1 Description Symbol Unit

2 Flowrate 30.000 MMscfd


3 21,650.000 m3/hr
4 6.014 m3/s
5 Mass Flow W 50570.000 kg/hr
6 Mol Weigth Mj 33.130
7 Pressure at Flare Tip Pj 153.000 kPa
8 Flowing Temperature Tj 266.000 K
9 Air Temperature T~ 289.000 K
10 Compressibility factor z 0.991
11 Ratio of Specific Heat k 1.293
12 Mach No 0.700
13
14
15 Flare Tip ID dj 0.195 m
16 7.65836359538 in
17
18 Heat of combustion 15250.000 kJ/kg
19 Heat Liberated Q 214220.139 kW
20 Flame Length L 30.000 m approx
21
22 Wind velocity U~ 11.800 m/s Fig 8 & 9
23 Sonic Velocity 293.849 m/s
24 Flare Tip velocity Uj 205.694 m/s
25
26 LEL CL 2.100 %v/v
27 LEL Conc Factor 0.418
28 Jet & Wind thrust parameter 20.344
29
30 From Fig C.2.B & C.3.B Fig C.2 Fig C.3
31 Horizontal distance, from stack to flame centre xc 17.000 m approx
32 Vertical distance, from stack to flame centre yc 14.000 m approx
33
34
35 Fraction Radiated Heat F 0.300
36 ‫ד‬ 1.000
37 Allowable Radiation K 6.310 kW/m2
38 Safe Distance to Flame Centre D 28.476 m
39
40
41 Stack To Point of Interest R 100.000 m
42 Flare Height H Err:502 m
43
Calculation are based on API RP 521