LON Multisensor ILA-22 (42320-105) : Date: 16.05.2007 Changes Possible Page 1 of 4
LON Multisensor ILA-22 (42320-105) : Date: 16.05.2007 Changes Possible Page 1 of 4
______________________________________________________________________
Description
______________________________________________________________________
Function
Installed on the ceiling of a room, the Multi-sensor registers the presence
of persons
within a certain detection area and simultaneously measures the intensity
of the natural light.
Furthermore a built-in infrared receiver is integrated.
The Multi-sensor is used to control lighting, blinding, heating, ventilation
and air-conditioning applications.
The integrated brightness sensor measures permanently the lux level in a range of 10 .. 1.000 lux
and propagates the values to the LON network.
It can be used for a constant light control by regulating of the room brightness.
By means of the IR Remote Control (part-no.: 42083-107) up to 10 network channels of the Multi-
sensor can be remotely controlled.
Mounting
The Multi-sensor is for flush-mounted installations in interior rooms.
In combination with the Surface Mounting Box for Multi-sensors (part-no.: 42020-106) it can also
be mounted to ceilings which have not been suspended.
There is only the LON link power required to supply the device.
The network is connected via a 2-pole pluggable bus terminal included in delivery which
allows up to 4 pairs of wires to be connected.
The terminal is suited for conductor cross-sections of 0.6 .. 0.8 mm².
For the right operation of the Multi-sensor an appropriate application program is needed, which
is provided by SVEA free of charge (part-no.: 92091-059).
It can be also directly downloaded from the SVEA website (www.svea-bcs.de).
______________________________________________________________________
Remarks
Installation and assembly of electrical devices may take place only by an electrical specialist.
When planning and installation of electrical system the relevant standards, guidelines and
regulations of the respective country are to be considered. Beyond that the device specifications
are to be kept. For project engineering, assembly and line-up detailed expertise of the LonWorks
technology is presupposed.
The function of the device is software dependent. Only application programs may be loaded,
which are approved by SVEA for this device.
The system integrator has to carry ensuring that the loaded application program and the
configured parameters in it correspond with the outside wiring of the device. This applies in
particular if for different use several application programs for a device are available.
______________________________________________________________________
Technical Data
Power supply
Power consumption (max.): <= 285 mW (1 LPU) at DC 42.8 V network voltage
Network interface
Transceiver type: LON Link Power Transceiver (LPT-11)
Sensor Head
Measuring square: 360º
Scope: Radius of max. 7 m at a mounting height of 2.50 m
Number of zones: 136 with 544 Switch segments
Brightness sensor: Direct from app. 10 .. 1,000 lux
Controls
Service pin: Propagates the Neuron ID
Indicators
Service LED (red): lit: network access error
flashes: module unconfigured
Connections
Bus: 2-pole plug-in and branch terminal (Type: WAGO 243)
Housing
Protection class: IP20 (EN 60 529/IEC 144)
Mounting: Screw mounting in a flush-mounted wall socket (60mm) or by a separate
mounting socket (part-no. 42020-106)
Dimensions: Diameter: app. 100 mm Height from ceiling: app. 50 mm
Site conditions
Operating temperature: -5 °C .. +45 °C(the motion detecting is reduced at temperatures > 30 °C)
Storage / transportation temperature: -25 °C .. +55 °C
Relative humidity: 5 .. 93 % without moisture condensation
EU Directive: Low voltage guideline 73/23/EWG and EMC guideline 89/336/EWG