Catalog Systemair IN CDRE D
Catalog Systemair IN CDRE D
Catalog Systemair IN CDRE D
Fans
Noise levels:
These plug fans are mounted on a motor supporting frame;
The technical data show the A-weighted sound pressure
the motor and impeller assembly is balanced dynamically in
levels LPA.
two levels according to VDI 2060. quality 0 2, 5.
Tolerance in accordance with technical conditions of supply
of fans DIN 24166, class 3, noise level ca. 0.5 x \pfa max.
Tolerance in accordance with technical conditions of supply
of fans DIN 24166, class 3. The Systemair selection criteria:
• Size
Panel insulation is provided by non flammable (AI) mineral • Air volume
fibre slab in accordance with DIN 4102. • Static Pressure
• Sound requirements
Thermal insulation K = 0.89 W/m²k in acc. With DIN 52210
Sound insulation Rw = appr. 25dB in acc. With DIN 52210.
Rectangular Cabinet Fan | 3
CDR
Safety Rules :
CDR Model ( Rectangular Cabinet Fan )
E /D 315
• Before you do any work on the fan you must disconnect
E = Single phase AC Impeller diameter
the electrical supply first.
D = Three phase AC
• The buyer is responsible that the local codes are being
followed.
• During all maintenance works, the electrical connections
must be checked.
Warranty rules :
• The buyer is responsible for the selection and operations
of the fan.
• The warranty is only for fans which are operating under
normal conditions. Warranty is only valid when thermal
protections (TK) are used.
• If the delivered goods shows failures, the customer can
claim the exchange of the product or parts of it up to the
amount of the buying price.
• Claims for secondary damages are not accepted.
• We reserve the rights to change the construction and
design without notice, for the purpose of technical
progress.
CDRE
3 81
400 76
Static Pressure Ps [Pa]
2 82
74
300
1
73
73
200
71 82
77
72
100
70
74
71 75 78 84
0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000
SOUND DATA
Performance certified is for installation type
Single figure on performance curves are overall inlet LwiA sound power levels, derived from measurements D-Ducted inlet. Ducted outlet. Speed (RPM)
taken in laboratory specifically under ducted conditions. Following is the inlet Lwi sound power levels (dB) in shown is nominal. Performance is based on
eight octave bands maximum airflow (0Pa) : actual speed of test. Performance ratings do
not include the effects of appurtenances
(accessories)
Model 63 125 250 500 1K 2K 4K 8K Overall The A-weighted sound ratings shown have
been calculated per AMCA international
CDRE 315 84 83 72 66 60 58 57 48 87 Standard 301. Values shown are for inlet Lwi
and LwiA sound power levels for installation
CDRE 355 86 88 74 69 63 60 63 55 90 type D ducted inlet, ducted outlet. Ratings
CDRE 400 90 88 79 75 67 64 63 71 92 include the effects of duct end correction.
Sound pressure level LpA at 3m are not
CDRE 450 88 93 84 79 74 73 74 70 95 licensed by AMCA international.
The sound power level rating shown are in decibel, referred to 10 -12 watts calculated per AMCA International
Standard 301.
Rectangular Cabinet Fan | 5
Dimensions
DC B
D
CB
A
IN METRIC
CDRE A B C(P.C.D.) D
2 86
800 88
1
82 84
600
88
82
400
86
83
1… CDRD 500 – 1435rpm 200
2… CDRD 560 – 1456rpm
3… CDRD 630 – 1471rpm
83 87 89
0
0 2000 4000 6000 8000 10000 12000 14000
Air Volume, Q [m3/h]
• Performance certified is for installation type D – Ducted inlet, Ducted outlet, Speed (RPM) shown is nominal.
Performance is based on actual speed of test. Performance ratings do not include the effects of appurtenances
(Accessories).
• The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. The sound power
level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. Values
shown are for inlet Lwi and Lwi(A) sound power levels for installation type D : ducted inlet, ducted outlet. Ratings include
the effects of duct end correction. Sound pressure level LpA at 3m are not licensed by AMCA International.
Rectangular Cabinet Fan | 7
Dimensions
SIDE VIEW FRONT INLET
Features A B
• The CDRD Cabinet In-line Duct D
Fan – a series of duct mounted
in-line centrifugal suitable for
supply or exhaust from
applications ranging from
residential & commercial to
AIR FLOW
industrial.
• Galvanised steel housing and D C (P.C.D.)
flanged connections.
• Backward curve centrifugal
impellers.
• Fan units are lightweight and can
be mounted at any angle.
IN METRIC
Motors
• Type – can supplied with direct- MODEL A B C D
driven standard TEFC motors.
• Electrical supply – three-phase to CDRD 500 650 710 680 650
suit a wide range of voltages and CDRD 560 750 785 755 725
frequencies.
CDRD 630 800 860 825 800
[email protected]
www.systemair.in