Maximum element usage is 93.43% for Steel Pole "Trial" in load case "WL+2.1TL"
Maximum insulator usage is 78.84% for Clamp "C1" in load case "WL+2.1TL"
Maximum pole deflection usage is 50.45% for "Trial" in load case "WL+TL"
*** Analysis Results for Load Case No. 1 "WL+2.1TL" - Number of iterations in SAPS 10
Joint X-Displ Y-Displ Z-Displ X-Rot Y-Rot Z-Rot X-Pos Y-Pos Z-Pos
Label (m) (m) (m) (deg) (deg) (deg) (m) (m) (m)
-----------------------------------------------------------------------------------
Trial:g 0 0 0 0.0000 0.0000 0.0000 0 0 0
Trial:t 4.884e-005 0.3411 -0.00732 -3.4222 0.0004 0.0000 4.884e-005 0.3411 11.09