Mitsubishi Q Series Cpu Port Delta A. Hmi Factory Settings: Appendix B Communication - Scredit Software User Manual

The document provides information about communication settings and register definitions for connecting an HMI to a Mitsubishi Q Series CPU. It details the factory baud rate, station numbers, and control/state areas for the HMI. It also defines the read and write ranges for various register types including inputs, outputs, timers, counters, and relays. Finally, it shows the pinout connections for establishing an RS-232 communication link between the HMI, controller, and DOP adapter.

Uploaded by

ryo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
26 views3 pages

Mitsubishi Q Series Cpu Port Delta A. Hmi Factory Settings: Appendix B Communication - Scredit Software User Manual

The document provides information about communication settings and register definitions for connecting an HMI to a Mitsubishi Q Series CPU. It details the factory baud rate, station numbers, and control/state areas for the HMI. It also defines the read and write ranges for various register types including inputs, outputs, timers, counters, and relays. Finally, it shows the pinout connections for establishing an RS-232 communication link between the HMI, controller, and DOP adapter.

Uploaded by

ryo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Appendix B Communication|ScrEdit Software User Manual

Mitsubishi Q Series CPU Port DELTA

A. HMI factory settings

Baud rate: 19200, 8, ODD, 1.

Controller Station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC)
communication is allowed.)

Control area/state area: D-0 / D-10.

NOTE

1) Please notice that no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication
is allowed.

2) If communication baud rate is not correct, HMI will set PLC baud rate as HMI baud rate automatically.
Therefore, do not worry if the baud rate is set incorrectly.

3) This driver support Mitsubishi Q00 and Q00J series with password protection models.

B. Definition of controller Read/Write address

Registers

Read/Write Range
Register Type Format Data length
Word No. Bit No.
Input X-n n: 0 ~ 1FFF N/A Word (multiple of 16)
Output Y-n n: 0 ~ 1FFF N/A Word (multiple of 16)
Direct Input DX-n n: 0 ~ 1FFF N/A Word (multiple of 16)
Direct Output DY-n n: 0 ~ 15 N/A Word (multiple of 16)
Latch Relay L-n n: 0 ~ 8191 N/A Word (multiple of 16)
Annunciator F-n n: 0 ~ 2047 N/A Word (multiple of 16)
Edge Relay V-n n: 0 ~ 2047 N/A Word (multiple of 16)
Step Relay S-n n: 0 ~ 8191 N/A Word (multiple of 16)
Link Relay B-n n: 0 ~ 1FFF N/A Word (multiple of 16)
Special Link Relay SB-n n: 0 ~ 7FF N/A Word (multiple of 16)
Internal Relay M-n n: 0 ~ 8191 N/A Word (multiple of 16)
Special Internal Relay SM-n n: 0 ~ 2047 N/A Word (multiple of 16)
Timer Value TN-n n: 0 ~ 2047 N/A Word
Retentive Timer Value SN-n n: 0 ~ 2047 N/A Word
Counter Value CN-n n: 0 ~ 1023 N/A Word
Data Register D-n n: 0 ~ 12287 N/A Word
Special Data Register SD-n n: 0 ~ 2047 N/A Word
Index Register Z-n n: 0 ~ 15 N/A Word
File Register R-n n: 0 ~ 32767 N/A Word

B-66 Revision 05/30/2006, EH00


Appendix B Communication|ScrEdit Software User Manual

Read/Write Range
Register Type Format Data length
Word No. Bit No.
File Register ZR-n n: 0 ~ 32767 N/A Word
Link Register W-n n: 0 ~ 1FFF N/A Word
Special Link Register SW-n n: 0 ~ 7FF N/A Word

¾ Xn, Yn, DXn, Bn, SBn, Wn, SWn : n is in hexadecimal.

Contacts

Read/Write Range
Contact type Format
Word No. Bit No.
Input X-n N/A n: 0 ~ 1FFF
Output Y-n N/A n: 0 ~ 1FFF
Direct input DX-n N/A n: 0 ~ 1FFF
Direct output DY-n N/A n: 0 ~ 15
Latch Relay L-n N/A n: 0 ~ 8191
Annunciator F-n N/A n: 0 ~ 2047
Edge Relay V-n N/A n: 0 ~ 2047
Step Relay S-n N/A n: 0 ~ 8191
Link Relay B-n N/A n: 0 ~ 1FFF
Special Link Relay SB-n N/A n: 0 ~ 7FF
Internal Relay M-n N/A n: 0 ~ 8191
Special Internal Relay SM-n N/A n: 0 ~ 2047
Timer Contact TS-n N/A n: 0 ~ 2047
Timer Coil TC-n N/A n: 0 ~ 2047
Retentive timer Contact SS-n N/A n: 0 ~ 2047
Retentive timer Coil SC-n N/A n: 0 ~ 2047
Counter Contact CS-n N/A n: 0 ~ 1023
Counter Coil CC-n N/A n: 0 ~ 1023

¾ Xn, Yn, DXn, Bn, SBn : n is in hexadecimal.

Revision 05/30/2006, EH00 B-67


Appendix B Communication|ScrEdit Software User Manual

C. Connections (Connector Pinouts)

RS-232

DOP Controller Controller


9 pin D-SUB male 6 pin Mini DIN male 6 pin Mini DIN male
(RS-232) (RS-232) (RS-232)
RXD (2) (2) SD (TXD)
2 1
TXD (3) (1) RD (RXD) 3
6 5
GND (5) (3) GND
(5) DSR (DR) Top View

(6) DTR (ER)

B-68 Revision 05/30/2006, EH00