Mitsubishi A Series AJ71UC24 Communication Module Delta A. HMI Factory Settings

This document provides factory settings and communication information for the Mitsubishi A Series AJ71UC24 Communication Module used with a DELTA controller. It outlines the default baud rate, station number, and control/state areas. It also defines the read/write address formats and ranges for registers and contacts in the controller, including inputs, outputs, relays, and timer/counter values. Finally, it shows the RS-422 pinout connections between the module and controller cable.

Uploaded by

ryo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
101 views2 pages

Mitsubishi A Series AJ71UC24 Communication Module Delta A. HMI Factory Settings

This document provides factory settings and communication information for the Mitsubishi A Series AJ71UC24 Communication Module used with a DELTA controller. It outlines the default baud rate, station number, and control/state areas. It also defines the read/write address formats and ranges for registers and contacts in the controller, including inputs, outputs, relays, and timer/counter values. Finally, it shows the RS-422 pinout connections between the module and controller cable.

Uploaded by

ryo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Appendix B Communication|ScrEdit Software User Manual

Mitsubishi A Series AJ71UC24 Communication Module DELTA

A. HMI factory settings

Baud rate: 9600, 8, ODD, 1.

Controller Station number: 0.

Control area/state area: D0 / D10.

NOTE

1) This driver use CheckSum.

2) Please set “PLC Mode” switch to position 5.

3) If some OUTPUT Replay (Y) and Special Data Relay (SM) are set to 1, PLC will stop communication
and the communication will not recover automatically. At this time, it is needed to reset PLC.

B. Definition of controller Read/Write address

Registers

Read/Write Range
Register Type Format Data length
Word No. Bit No.
Input Xn n: 0 ~ 7FF N/A Word (multiple of 16)
Output Yn n: 0 ~ 7FF N/A Word (multiple of 16)
Link Relay Bn n: 0 ~ FFF N/A Word (multiple of 16)
Internal Relay Mn n: 0 ~ 8191 N/A Word (multiple of 16)
Special Internal Relay SMn n: 9000 ~ 9255 N/A Word (9000 + multiple of 16)
Latch Relay Ln n: 0 ~ 2047 N/A Word (multiple of 16)
Annunciator Fn n: 0 ~ 2047 N/A Word (multiple of 16)
Timer Value TNn n: 0 ~ 999 N/A Word
Counter Value CNn n: 0 ~ 999 N/A Word
Data Register Dn n: 0 ~ 8191 N/A Word
Special Data Register SDn n: 9000 ~ 9255 N/A Word
File Register Rn n: 0 ~ 8191 N/A Word
Link Register Wn n: 0 ~ FFF N/A Word

Revision 05/30/2006, EH00 B-61


Appendix B Communication|ScrEdit Software User Manual

Contacts

Read/Write Range
Contact type Format
Word No. Bit No.
Input Xn N/A n: 0 ~ 7FF
Output Yn N/A n: 0 ~ 7FF
Link Relay Bn N/A n: 0 ~ FFF
Internal Relay Mn N/A n: 0 ~ 8191
Special Internal Relay SMn N/A n: 9000 ~ 9255
Latch Relay Ln N/A n: 0 ~ 2047
Annunciator Fn N/A n: 0 ~ 2047
Timer Contact TSn N/A n: 0 ~ 999
Timer Coil TCn N/A n: 0 ~ 999
Counter Contact CSn N/A n: 0 ~ 999
Counter Coil CCn N/A n: 0 ~ 999

C. Connections (Connector Pinouts)

RS-422

DOP Controller
9 pin D-SUB male (RS-422) Cable Connector (RS-422)

RXD+ (2) SDA


RXD- (1) SDB
TXD+ (3) RDA
TXD- (4) RDB

B-62 Revision 05/30/2006, EH00