LG Master K120S/200S Delta A. Hmi Factory Settings: Appendix B Communication - Scredit Software User Manual

This document summarizes the communication settings and register definitions for connecting an HMI to an LG PLC controller. The HMI uses a baud rate of 38400, 8 data bits, no parity, 1 stop bit. The controller station number is 0, allowing only one-to-one communication between the HMI and PLC. The control and state areas are defined as DW0 and DW10. The document defines the register types and formats for reading from and writing to the PLC, including word, bit, and contact types located in memory areas like MW, LW, and CW. It also provides the pinout information for the RS-232 connection to the PLC.

Uploaded by

ryo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
48 views2 pages

LG Master K120S/200S Delta A. Hmi Factory Settings: Appendix B Communication - Scredit Software User Manual

This document summarizes the communication settings and register definitions for connecting an HMI to an LG PLC controller. The HMI uses a baud rate of 38400, 8 data bits, no parity, 1 stop bit. The controller station number is 0, allowing only one-to-one communication between the HMI and PLC. The control and state areas are defined as DW0 and DW10. The document defines the register types and formats for reading from and writing to the PLC, including word, bit, and contact types located in memory areas like MW, LW, and CW. It also provides the pinout information for the RS-232 connection to the PLC.

Uploaded by

ryo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Appendix B Communication|ScrEdit Software User Manual

LG Master K120S/200S DELTA

A. HMI factory settings

Baud rate: 38400, 8, None, 1. (RS-232)

Controller station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC)
communication is allowed.)

Control area/state area: DW0 / DW10.

B. Definition of controller Read/Write address

Registers

Register Type Format Word No. Bit No. Data Size

WORD_DEVICE_PW PWn n: 0 ~ 15 N/A Word


WORD_DEVICE_MW MWn n: 0 ~ 191 N/A Word
WORD_DEVICE_KW KWn n: 0 ~ 31 N/A Word
WORD_DEVICE_LW LWn n: 0 ~ 63 N/A Word
WORD_DEVICE_FW FWn n: 0 ~ 63 N/A Word
WORD_DEVICE_TW TWn n: 0 ~ 255 N/A Word
WORD_DEVICE_CW CWn n: 0 ~ 255 N/A Word
WORD_DEVICE_DW DWn n: 0 ~ 9999 N/A Word

Contacts

Contact type Format Word No. Bit No.


BIT_DEVICE_P Pnb n: 0 ~ 15 b: 0 ~ f
BIT_DEVICE_M Mnb n: 0 ~ 191 b: 0 ~ f
BIT_DEVICE_K Knb n: 0 ~ 31 b: 0 ~ f
BIT_DEVICE_L Lnb n: 0 ~ 63 b: 0 ~ f
BIT_DEVICE_F Fnb n: 0 ~ 63 b: 0 ~ f
BIT_DEVICE_T Tn N/A n: 0 ~ 255
BIT_DEVICE_C Cn N/A n: 0 ~ 255

B-46 Revision 05/30/2006, EH00


Appendix B Communication|ScrEdit Software User Manual

C. Connections (Connector Pinouts)

RS-232

DOP
Controller 9 pin D-SUB male Controller 9 pin D-SUB male
9 pin D-SUB male
(RS-232 for LG K120S/200S) (RS-232 for LG K120S/200S)
(RS-232)

RXD (2) (3) TXD

TXD (3) (2) RXD


GND (5) (5) GND
Top View

NOTE

1) If connecting to Pin 4 (RXD), Pin 7 (TXD) and Pin5 (SG), it indicates that CNet protocol is used (Please
refer to the section “LG Master-K CNET” on page B-50. 120S/200S protocol and CNet protocol cannot
be used simultaneously. The users only can select either 120S/200S protocol or CNet protocol.

Revision 05/30/2006, EH00 B-47