Motor Protection

The document provides settings for the protection relays for motor data MEG Col. Reboiler Recirculation Pump-A/B. It includes settings for motor starting protection, thermal overload protection, motor restart inhibit protection, load jam protection, short circuit protection, earth fault protection, and negative sequence protection. The settings are based on parameters of the pump such as full load current, starting current, locked rotor withstand time, overload characteristics, and CT ratios to configure the protection relays for optimal motor protection.

Uploaded by

Abhijit Kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
401 views7 pages

Motor Protection

The document provides settings for the protection relays for motor data MEG Col. Reboiler Recirculation Pump-A/B. It includes settings for motor starting protection, thermal overload protection, motor restart inhibit protection, load jam protection, short circuit protection, earth fault protection, and negative sequence protection. The settings are based on parameters of the pump such as full load current, starting current, locked rotor withstand time, overload characteristics, and CT ratios to configure the protection relays for optimal motor protection.

Uploaded by

Abhijit Kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 7

2. Motor Data : MEG Col.

Reboiler Recirculation Pump-A/B


(42-PM-624A/B)
Relay type / Manufacturer : 7SJ612/ SIEMENS
Relay function : MPR (48, 49, 66, 51M, 50, 50N, 46)
Phase fault current : 41.4 kA
Earth Fault Current : 39.9 kA
Capacity : 110kW
Voltage : 0.415 kV
Full load current : 183A
Starting Current : 1006.5 A
Starting time at 75% V (sec) :2
Starting time at 100% V (sec) :1
Locked motor withstand time
(cold/hot) sec. at 75% V (sec) : 40.8/20.4
Locked motor withstand time
(cold/hot) sec. at 100% V (sec) : 24/12
CT ratio : 300/5A

MPR (48, 49, 66, 51M, 50, 50N, 46) setting

A. Motor Starting Protection (48)

Istart @ 85%
i) Startup Current :
CT ratio
(Min Voltage available at start is 85%)
1006.5 0.85 5
: 300

Recommended setting (4102) : 14.3 A

ii) Startup Time

This setting should lie above the starting time at normal startup current. The starting
time at 100% voltage is 1 sec.
Recommended setting (4103) : 2.5 sec

iii)Locked Rotor Time

Locked rotor time should be less than or equal to Thermal withstand (hot) at 100% V.

Recommended setting (4104) : 11 sec

iv) Startup T warm

This setting should lie above max starting time and below thermal withstand time at
100% V.

Recommended setting (4105) : 2.5 sec

v) Temp. Cold Motor

It is derived from the number of cold (n cold) and warm (n warm) motor startups.
(n cold) - (n warm)
limit : 100%
n cold
2 -1
: 100%
2
: 50%
The setting should be set below the limit value, considering safety margin.

Recommended setting (4106) : 25%

B. Thermal Overload Protection (49)

The overload protection prevents thermal overloading of the motor’s stator winding.
Ifl
i) Overload parameter, K-Factor :
Ict
183
: 300
: 0.61

Recommended setting (4202) : 0.61

ii) Time Constant

From motor thermal withstand characteristic curves (please refer TCC curve), a setting of
6.5 min time constant achieves the relay characteristics lie below the
motor hot characteristic.

Recommended setting (4203) : 6.5 min

iii)Thermal Alarm Stage (49 Alarm)

Thermal warning stage offers an additional warning stage before the tripping temperature
is reached. This is why it should be set to below the 100% tripping threshold, for example
90%.

With max permissible current of 1.1, over loading temperature rise limit value is, 1/k2
: 1/ (1.1 X 1.1)
: 83%

of the tripping temperature. A setting value of 90% therefore lies above the operationally
expected over temperature of 83%, but below the tripping temperature of 100%.

Recommended setting (4204) : 90%

iv) Current Alarm Stage (I Alarm)

A current alarm stage can be set in addition to thermal alarm stage. This can be set
equal to the continuously permissible secondary rated current.
183 5
: 300
: 3.05

Recommended setting (4205) : 3.05 A

v) K - Factor

The machines cool down behavior at standstill can be taken into account with the K
– Factor.
The default setting is 1.

Recommended setting (4207A) :1

vi) T Emergency

Recommended setting (4208A) : 100 sec

vii) 49 Temperature rise I

Recommended setting (4209) : 100°C


C. Motor Restart Inhibit (66)

The motor restart inhibit prevents restarting of the motor when this restart may cause the
permissible thermal limits of the rotor to be exceeded.

i) Starting Current / Motor Current (I start /I Mot. nom )I


start / I Mot. nom

1006.5
: 183
: 5.5

Recommended setting (4302) : 5.5

ii) Maximum Permissible Starting time ( T start max)

Recommended setting (4303) : 2.5 sec

iii) Rotor Temperature equalization time (T equal)

It defines the minimum dead time between individual starts. The default setting is 1
min.

Recommended setting (4304) : 1 min

iv) Rated Motor Current (I motor Nominal)

This can be set equal to the continuously permissible secondary rated current.
183 5
: 300
: 3.05

Recommended setting (4305) : 3.05 A

v) Max. Warm Starts

Max. No. of warm starts 2

Recommended setting (4306) 2

vi) #Cold-#Warm

This can be set equal to difference between allowed no. of cold and hot starts.

Recommended setting (4307) 1


vii) K at Stop

Extension factor for the time constant during cool down

K at Stop
Cooling Time Constant
: Heating Time
Constant

Recommended setting (4308) 5

viii) K at Running

This setting is shorter than K at stop because rotor operation involves intrinsic cooling.

Recommended setting (4309) 2

ix) Min restart inhibit time, T Min inhibit:

Recommended setting (4310) : 6 min

D. Load Jam Protection (51M)

i) Load Jam Current (I>)


: 2 Ifl
2 183 5
: 300
: 6.1 A

Recommended setting (4402) : 6.1 A

ii) Trip Delay

The default setting is 1 sec.

Recommended setting (4403) : 1 sec

iii)Alarm current (I Alarm)


: 90% of 2Ifl
: 0.9 6.1
: 5.5 A

Recommended setting (4404) : 5.5 A

iv) Alarm Delay


The default setting is 1 sec.

Recommended setting (4405) : 1 sec

v) Start Block Time (T Start BLK)

This value shall be equal to address code 4103.

Recommended setting (4406) : 2.5 sec

E. Short Circuit Protection (50)

Pickup Current

Disabled, since symmetrical fault will be cleared by fuse.

Recommended setting (1204) : Disabled

ii) Delay

Recommended setting (1205) : Disabled

F. Earth fault Protection (50N)

i) Pickup Current
: 10 % x ICT. Sec
: 0.1 5

Recommended setting (1304) : 0.5 A

ii) Delay

Recommended setting (1305) : 2 sec

G. Negative Sequence Protection (46)

This function is set in two stages. The first stage 46-1 is set for alarm, while 46-2 is set
for trip. Alarm is initialized when the negative sequence current exceeds 20% of full
load current for specified time delay.

i) 46-1 Pickup
: 20 % x IFLC
0.2 183 5
:
300
: 0.6 A
Recommended setting (4002) : 0.6 A

ii) Delay

Recommended setting (4003) : 1.5 sec

Tripping element 46-2 is set to pickup at 40% of the rated current with comparatively
shorter time delay of 0.5 sec.

iii) 46-2 Pickup


: 40 % x IFLC
0.4 183 5
:
300
: 1.2 A

Recommended setting (4004) : 1.2 A

iv) Delay

Recommended setting (4005) : 0.5 sec