ASCO 7000 Product Catalog
ASCO 7000 Product Catalog
ASCO 7000 Product Catalog
ascopower.com
ASCO 7000 SERIES ORDERING INFORMATION
To order an ASCO 7000 SERIES Power Transfer Switch, complete the following catalog number:
J 07ATS A 3 0600 N 5X C
Notes:
1. 200 and 230 amp switch limited to 480 volts maximum, for D7ATS only.
2. Conventional switched neutral is provided on closed and delayed transition transfer products when specified.
3. Type 3R enclosures are not suitable for installations likely to experience windblown snow or rain conditions.
4. Type 304 stainless steel is standard. To provide an improved reduction in corrosion in salt or marine environments, specify optional type 316 stainless steel.
5. Double door enclosures are door over internal dead front panels/doors. All controls are mounted on internal panel/door. External door is pad-lockable for
secure applications.
A comprehensive ASCO Limited Guardian Warranty covers 7000 SERIES Power Transfer Switch(s) and warranties the product to be free of defects in material
and workmanship from date of shipment. The warranty provides:
• 2 years for labor and travel expenses (extendable in 1 year increments up to 5 years for a nominal fee).
• 5 years for parts (2 years for circuit breakers).
• 10 years for main contacts.
H Frame (Front Connected) 800 - 960A Three #1/0 AWG to 600 MCM #1/0 AWG to 600 MCM
H Frame (Rear Connected) 800 – 1200A Four #1/0 AWG to 750 MCM #1/0 AWG to 600 MCM
G Frame 1000 - 1200A1 Four #1/0 AWG to 750 MCM #1/0 AWG to 600 MCM
G Frame 1600 – 2000A 1
Six #1/0 AWG to 750 MCM #1/0 AWG to 600 MCM
G Frame 2600 – 3000A 1
Ten #1/0 AWG to 750 MCM #1/0 AWG to 600 MCM
G Frame 4000A1 Twelve #1/0 AWG to 750 MCM #1/0 AWG to 600 MCM
Notes:
1. All main terminals are rear connected
3
ASCO 7000 SERIES DESIGNED TO FIT ANYWHERE
Automatic Transfer Switching – Open Transition: 7ATS, 7NTS, 7MTS (Non-Bypass)
Dimensions and Shipping Weights*
Notes:
1. Consult ASCO for dimensions on enclosures other than UL type 1.
2. Open weights include transfer switch and controller. 1200-4000 amp enclosures require ventilation openings, refer to drawing for details.
3. Enclosures are free-standing with removable top, sides, and back.
4. Order accessory 40MY for 1600A and 40NY for 2000A Front Connected (F/C) design.
*All dimensions and weights shown are approximate and should not be used for construction purposes. Verified dimensions can be furnished upon request.
4
ASCO 7000 SERIES DESIGNED TO FIT ANYWHERE
Automatic Transfer Switching – Closed and Delayed Transition: 7ACTS, 7ADTS, 7NCTS, 7NDTS
Dimensions and Shipping Weights*
Notes:
1. Consult ASCO for dimensions on enclosures other than UL type 1.
2. Open weights include transfer switch and control panel. 1200-4000 amp enclosures require ventilation openings, refer to drawings for details.
3. Enclosures are free-standing with removable top, sides, and back.
4. Order accessory 40MY for 1600A and 40NY for 2000A front connected design.
*All dimensions and weights shown are approximate and should not be used for construction purposes. Verified dimensions can be furnished upon request
5
ASCO 7000 SERIES DESIGNED TO FIT ANYWHERE
Automatic Transfer Bypass-Isolation – Open Transition: 7ATB, 7NTB
Dimensions and Shipping Weights*
Notes:
1. Handles extend 6-1/4 inches (159mm).
2. Open weights include transfer switch, bypass-isolation switch and controller. 1600-4000 amp enclosures require ventilation openings, refer to drawings for details.
3. Specify optional accessory 40J Y for 800 Amp front, 40KY for 1000 Amp, and 40LY for 1200 Amp - front connected arrangement. All service and load cables limited
to top entry only.
4. Recommended clearance to enclosure: 3 feet (914mm) from rear, 4 feet (1219mm) from front (25 inches required for transfer switch draw out). Side or
rear access required.
*All dimensions and weights shown are approximate and should not be used for construction purposes. Verified dimensions can be furnished upon request.
6
ASCO 7000 SERIES DESIGNED TO FIT ANYWHERE
Automatic Transfer Bypass-Isolation: Closed and Delayed Transition: 7ACTB, 7ADTB, 7NCTB, 7NDTB
Dimensions and Shipping Weights*
Notes:
1. Handles extend 6-1/4 inches (159mm).
2. Open weights include transfer switch, bypass-isolation switch and controller. 1600-4000 amp enclosures require ventilation openings, refer to drawings for details.
3. Specify optional accessory 40J Y for 800 Amp front, 40KY for 1000 Amp, and 40LY for 1200 Amp - connected arrangement. All service and load cables limited to
top entry only.
4. Recommended clearance to enclosure: 3 feet (914mm) from rear, 4 feet (1219mm) from front (25 inches required for transfer switch draw out). Side or
rear access required.
*All dimensions and weights shown are approximate and should not be used for construction purposes. Verified dimensions can be furnished upon request.
7
ASCO 7000 SERIES 30 CYCLE ORDERING INFORMATION
To order an ASCO 7000 SERIES Power Transfer Switch, complete the following catalog number:
P 07ATS A 3 0600 N 5X C
Notes:
1. Conventional switched neutral is provided on closed and delayed transition transfer products when specified.
2. Type 3R enclosures are not suitable for installations likely to experience windblown snow or rain conditions.
3. Type 304 stainless steel is standard. To provide an improved reduction in corrosion in salt or marine environments, specify optional type 316 stainless steel.
4. Double door enclosures are door over internal dead front panels/doors. All controls are mounted on internal panel/door. External door is pad-lockable for
secure applications.
A comprehensive ASCO Limited Guardian Warranty covers 7000 SERIES Power Transfer Switch(s) and warranties the product to be free of defects in material
and workmanship from date of shipment. The warranty provides:
• 2 years for labor and travel expenses (extendable in 1 year increments up to 5 years for a nominal fee).
• 5 years for parts (2 years for circuit breakers).
• 10 years for main contacts.
8
ASCO 7000 SERIES DESIGNED TO FIT ANYWHERE
30 Cycle Automatic Transfer Switch (Non-Bypass) & Bypass - Isolation Switch
7ATS, 7NTS, 7ACTS, 7ADTS, 7NTCS, 7NDTS, 7ATB, 7NTB, 7ACTB, 7ADTB, 7NCTB, 7NTB
Dimensions and Shipping Weights*
Type 1 Enclosure1, 2
Frame Switch Ratings Amp Switch Configuration Width In Height In Depth In Weight
(mm) (mm) (mm) lb (kg)
600 - 800A ATS/NTS 470 (214)
34 (864) 72 (1829) 20 (508)
(Front Connected ATS) ACTS, ADTS, NCTS, NDTS 480 (219)
P
600 - 800A ATB/NTB 1420 (648)
38 (965) 91 (2311) 48 (1219)
(Front Connected BPS) ACTB, ADTB, NCTB, NDTB 1445 (659)
600 - 1600A ATS/NTS 1005 (458)
38 (965) 87 (2210) 23 (584)
(Front Connected ATS) ACTS, ADTS, NCTS, NDTS 1105 (504)
Q
600 - 1600A ATB/NTB 2385 (1086)
38 (965) 91 (2311) 60 (1524)
(Rear Connected BPS) ACTB, ADTB, NCTB, NDTB 2485 (1131)
800 - 2000A ATS/NTS 1645 (749)
38 (965) 91 (2311) 60 (1524)
(Rear Connected ATS) ACTS, ADTS, NCTS, NDTS 1745 (794)
S3
800 - 2000A ATB/NTB 23.5 2890 (1318)
38 (965) 87 (2210)
(Rear Connected BPS) ACTB, ADTB, NCTB, NDTB (597) 2990 (1364)
1600 - 2000A ATS/NTS 1350 (616)
38 (965) 91 (2311) 48 (1219)
(Front & Rear Connected ATS) ACTS, ADTS, NCTS, NDTS 1400 (638)
1600 - 2000A ATB/NTB 2385 (1088)
38 (965) 91 (2311) 60 (1524)
(Rear Connected BPS) ACTB, ADTB, NCTB, NDTB 2565 (1170)
2600 - 3000A ATS/NTS 2180 (994)
38 (965) 91 (2311) 60 (1524)
(Rear Connected ATS) ACTS, ADTS, NCTS, NDTS 2230 (1017)
G3
2600 - 3000A ATB/NTB 60 2930 (1329)
91 (2311) 72 (1829)
(Rear Connected BPS) ACTB, ADTB, NCTB, NDTB (1524) 3360 (1532)
4000A ATS/NTS 60 2290 (1044)
91 (2311) 72 (1829)
(Rear Connected ATS) ACTS, ADTS, NCTS, NDTS (1524) 2380 (1085)
4000A ATB/NTB 60 6325 (2884)
91 (2311) 96 (2438)
(Rear Connected BPS) ACTB, ADTB, NCTB, NDTB (1524) 6925 (3158)
26001, 3000A1 ATS/NTS 60 5200 (2373)
91 (2311) 72 (1829)
(Rear Connected ATS) ACTS, ADTS, NCTS, NDTS (1524) 5300 (2418)
U3
2600 , 3000A
4 4 ATB/NTB 60 6700 (3057)
91 (2311) 96 (2438)
(Rear Connected BPS) ACTB, ADTB, NCTB, NDTB (1524) 6725 (3069)
4000 A ATS/NTS 60 5400 (2464)
91 (2311) 72 (1829)
(Rear Connected ATS) ACTS, ADTS, NCTS, NDTS (1524) 5600 (2555)
U3
4000A 4 ATB/NTB 60 6900 (3149)
91 (2311) 96 (2438)
(Rear Connected BPS) ACTB, ADTB, NCTB, NDTB (1524) 6925 (3160)
Notes:
1. Consult ASCO for dimensions on enclosure other than UL Type 1.
2. For Bypass-Isolation Switches Only: handles extend 6-1/4 inches (159 mm).
3. Enclosures are free standing with removable top, sides and back.
4. Recommended clearance to enclosure: 3 feet (914 mm) from rear, 4 feet (1219 mm) from front (25 inches required for transfer switch draw out).
S Frame 1600 - 2000 Six #1/0 AWG to 750 MCM #1/0 AWG to 600 MCM
G Frame 1600 - 2000A Six #1/0 AWG to 750 MCM #1/0 AWG to 600 MCM
G Frame 2600 - 3000A Ten #1/0 AWG to 750 MCM #1/0 AWG to 600 MCM
9
U Frame 2600 - 40002 Twelve #1/0 AWG to 750 MCM #1/0 AWG to 600 MCM
ASCO 7000 SERIES SERVICE ENTRANCE POWER TRANSFER SWITCHES
ORDERING INFORMATION
To order an ASCO 7000 SERIES Power Transfer Switch, complete the following catalog number:
J 07AUS A 3 0600 N 5X C
Phase Voltage Group
Frame Transition Type Neutral Code Amperes Enclosure
Poles Code Code
D = 70A - 225A Automatic A = Solid 2 0070 A = 115 50 C = Type 1 Enclosure
AUS/NUS Only 07AUS Automatic, Neutral No Optional
Conventional 2 - position 3 0100 B = 120 Accessories M = Type 3R2
J = 150A - 600A, B1 = Switched Secure Double Door5
200A, 225A 7ACUS Automatic, Closed Neutral 0150 C = 208 5X Enclosure
ADUS/NDUS Transition Optional
and ACUS/NCUS C = Overlapping 0200 D = 220 Accessories N = Type 4 Secure
Only 7ADUS Automatic, Neutral Double Door5
Delayed Transition 0225 E = 230 5Z Enclosure
H = 600A, VATS
800A-1200A 07AUB Automatic, Open 0260 F = 240 P = Type 4X3
Transition Bypass 5D Secure Double Door5
G = 1000A, 0400 H = 380 VATS Enclosure
1600A-4000A 7ACUB Automatic, Closed Distribution
Transition Bypass 0600 J = 400 Q = Type 12 Enclosure
Double Door5
7ADUB Automatic, 0800 K = 415 Enclosure
Delayed Transition Bypass
1000 L = 440 R = Type 3RX3, 4
Non-Automatic Secure Double Door5
07NUS Non Automatic, 1200 M = 460 Enclosure
Conventional 2 - position
1600 N = 480 S = Type 3RX3, 4
7NCUS Non Automatic, Secure Double Door5
Closed Transition 2000 P = 550 Enclosure
(316 Stainless Steel)
7NDUS Non Automatic, 2500 Q = 575
Delayed Transition V = Type 4X Secure
3000 R = 600 Double Door5
07NUB Non Automatic, Enclosure
Open Transition Bypass 4000 (316 Stainless Steel)
Notes:
1. Conventional switched neutral is provided on closed and delayed transition transfer products when specified.
2. CAUTION: Type 3R enclosures are not suitable for installations likely to experience windblown snow or rain conditions.
3. Type 304 stainless steel is standard. To provide an improved reduction in corrosion in salt or marine environments, specify optional type 316 stainless steel.
4. Type 3RX limited to 1600 - 4000 amperes only.
5. Double door enclosures are door over internal dead front panels/doors. All controls are mounted on internal panel/door. External door is pad-lockable for
secure applications.
6. AUS represents a switch with a utility service entrance breaker. In addition to the AUS, ASCO offers AGS - Generator breaker, APS - Utility and Generator
breaker, and ARS - Utility and Generator breaker, dual service entrance.
A comprehensive ASCO Limited Guardian Warranty covers 7000 SERIES Power Transfer Switch(s) and warranties the product to be free of defects in material
and workmanship from date of shipment. The warranty provides:
• 2 years for labor and travel expenses (extendable in 1 year increments up to 5 years for a nominal fee).
• 5 years for parts (2 years for circuit breakers).
• 10 years for main contacts.
J 150, 250, 400 38 (965) 91 (2311) 28 (711) 880 (407) 41 (1041) 95 (2426) 33 (838) 1880 (544)
200, 225
J 7ADUS/7NDUS and 38 (965) 91 (2311) 28 (711) 880 (407) 41 (1041) 95 (2426) 33 (838) 1880 (544)
7ACUS/7NCUS only
J 6002 38 (965) 91 (2311) 28 (711) 980 (452) 41 (1041) 95 (2426) 33 (838) 1280 (590)
H 600, 8002 38 (965) 91 (2311) 28 (711) 1280 (590) 41 (1041) 95 (2426) 33 (838) 1480 (683)
H 10002 38 (965) 91 (2311) 48 (1219) 1280 (590) 41 (1041) 95 (2426) 62 (1575) 1480 (683)
H 12002 38 (965) 91 (2311) 48 (1219) 1480 (683) 41 (1041) 95 (2426) 62 (1575) 1940 (895)
G 1000, 16002, 20002 38 (965) 91 (2311) 48 (1219) 1800 (831) 41 (1041) 95 (2426) 62 (1575) 2200 (1015)
G 26002, 30002 38 (965) 91 (2311) 72 (1829) 2180 (1006) 41 (1041) 95 (2426) 85 (2159) 2854 (1317)
G 40002 60 (1524) 91 (2311) 72 (1829) 3485 (1606) 63 (1600) 100 (2540) 91 (2311) 4300 (1981)
Notes:
1. Type 3R enclosures are not suitable for installations likely to experience windblown snow or rain conditions.
2. Unit is designed for top and bottom cable entry for all services and load.
*All dimensions and weights shown are approximate and should not be used for construction purposes. Verified dimensions can be furnished upon request.
A comprehensive ASCO Limited Guardian Warranty covers 7000 SERIES Power Transfer Switch(s) and warranties the product to be free of defects in material
and workmanship from date of shipment. The warranty provides:
• 2 years for labor and travel expenses (extendable in 1 year increments up to 5 years for a nominal fee).
• 5 years for parts (2 years for circuit breakers).
• 10 years for main contacts.
11
ASCO 7000 SERIES SERVICE ENTRANCE POWER TRANSFER SWITCH
30 CYCLE ORDERING INFORMATION
To order an ASCO 7000 SERIES 30 Cycle Service Entrance Power Transfer Switch, complete the
following catalog number:
P 07AUS A 3 0600 N 5X C
Phase Voltage Group
Frame Transition Type Neutral Code Amperes Enclosure
Poles Code Code
P = 600A - 800A Automatic A = Solid 2 0600 A = 115 50 C = Type 1
AUS/CUS/DUS Only 07ATS Automatic , Neutral No Optional Enclosure
Conventional 2 - position 3 0800 B = 120 Accessories
P = 600A - 1200A B1 = M = Type 3R2
AUB/CUB/DUB 7ACTS Automatic, Closed Switched 1000 C = 208 5X Secure Double Door4
Only Transition Neutral Optional Enclosure
1200 D = 220 Accessories
Q = 600A - 1600A 7ADTS Automatic, N = Type 4 Secure
Delayed Transition 1600 E = 230 5Z Double Door4 Enclosure
VATS
S = 800A - 2000A 07ATB Automatic, Open 2000 F = 240 P = Type 4X3
Transition Bypass 5D Secure Double Door4
2600 H = 380 VATS with Enclosure
G = 1600A - 4000A 7ACTB Automatic, Closed Distribution
Transition Bypass 3000 J = 400 Breakers Q = Type 12
Double Door4
U = 2600A - 4000A 7ADTB Automatic, 4000 K = 415 Enclosure
Delayed Transition Bypass
L = 440 R = Type 3RX2, 3
Non-Automatic Secure Double Door4
07NTS Non Automatic, M = 460 Enclosure
Conventional 2 - position
N = 480 S = Type 3RX2
7NCTS Non Automatic, Secure Double Door4
Closed Transition P = 550 Enclosure (316
Stainless Steel)
7NDTS Non Automatic, Q = 575
Delayed Transition V = Type 4X Secure
R = 600 Double Door4
7NTB Non Automatic, Enclosure
Open Transition Bypass (316 Stainless Steel)
Notes:
1. Conventional switched neutral is provided on closed and delayed transition transfer products when specified.
2. Type 3R enclosures are not suitable for installations likely to experience windblown snow or rain conditions.
3. Type 304 stainless steel is standard. To provide an improved reduction in corrosion in salt or marine environments, specify optional type 316 stainless steel.
4. Double door enclosures are door over internal dead front panels/doors. All controls are mounted on internal panel/door. External door is pad-lockable for
secure applications.
A comprehensive ASCO Limited Guardian Warranty covers 7000 SERIES Power Transfer Switch(s) and warranties the product to be free of defects in material
and workmanship from date of shipment. The warranty provides:
• 2 years for labor and travel expenses (extendable in 1 year increments up to 5 years for a nominal fee).
• 5 years for parts (2 years for circuit breakers).
• 10 years for main contacts.
12
ASCO 7000 SERIES DESIGNED TO FIT ANYWHERE
30 Cycle Service Entrance Power Transfer Switch (Non-Bypass Configurations)
Dimensions and Shipping Weights*
Type 1 Enclosure1 Type 3R Enclosure1
Frame Switch Ratings Amp Width In Height In Depth In Weight Width In Height In Depth In Weight
(mm) (mm) (mm) lb (kg) (mm) (mm) (mm) lb (kg)
6001, 8001
41
P (Front Connected) 38 (965) 91 (2311) 48 (1219) 1800 (821) 95 (2426) 62 (1575) 2000 (912)
(1041)
7AUS/7NUS Only
6001, 8001,
41
Q 10001, 12001, 16001 38 (965) 91 (2311) 48 (1219) 2000 (912) 95 (2426) 62 (1575) 2200 (1004)
(1041)
(Front Connected)
8001, 10001,
41
S 12001, 16001, 20001 38 (965) 91 (2311) 72 (1829) 2800 (1278) 95 (2426) 86 (2184) 3010 (1374)
(1041)
(Rear Connected)
1600 - 2000A 41
G 38 (965) 91 (2311) 48 (1219) 1800 (831) 95 (2426) 86 (2184) 2200 (1015)
(Rear Connected) (1041)
2600 - 3000A 41
G 38 (965) 91 (2311) 72 (1829) 2180 (1006) 95 (2426) 62 (1575) 2854 (1317)
(Rear Connected) (1041)
4000A 63
G 60 (1524) 91 (2311) 72 (1829) 3485 (1606) 100 (2538) 91 (2311) 4300 (1981)
(Rear Connected) (1600)
26001, 30001 60
U 60 (1524) 91 (2311) 72 (1829) 4850 (2213) 100 (2538) 91 (2311) 5160 (2354)
(Rear Connected) (1523)
40001 60
U 60 (1524) 91 (2311) 72 (1829) 4850 (2213) 100 (2538) 91 (2311) 6800 (3103)
(Rear Connected) (1523)
Notes:
1. Type 3R enclosures are not suitable for installations likely to experience windblown snow or rain conditions.
*Dimensional data is approximate and subject to change. Verified dimensions available upon request.
All 30 cycle service entrance enclosures are freestanding and designed for top and bottom cable entry for all services and load.
13
ASCO 7000 SERIES DESIGNED TO FIT ANYWHERE*
Optional Front Connected Design Saves Valuable Space
Ground Bus
17.00
Load Lugs
Field Wiring
Terminal Normal Lugs
Bypass Block (TB)
Switch Emergency Lugs
Manual
Operation
Handle Bypass
Handle
38.76
Group 5
Controller
User Isolation
91.00
Interface Handle
Controls
and
*All dimensions and weights
Indication
shown are approximate
59.05 and should not be used for
Isolation REF construction purposes.
12.42 REF
Handle Transfer Switch Verified dimensions can be
furnished upon request.
Compartment
35.24
39.00
CG
38.00 34.00
Cable Access
Hinge Cover
Ground Bus
Emergency Lugs Load Lugs
Field Wiring
Terminal Normal Lugs
Block (TB)
Bypass
Switch Manual
Operation
Handle
6.22
Group 5 Isolation REF
91.00 Controller Handle
User
Interface
Controls and
Indication
59.05
REF
Isolation
Handle
Transfer Switch
Compartment
14
ASCO UL1008 Withstand and Closing Ratings 1,2,7
(RMS Symmetrical Amps)
300, 4000 & 7000 Series 4000 & 7000 Series 7000 Series
Notes: 1) All WCR values indicated are tested in accordance with the requirements of UL 1008, 7th Edition. See ASCO Pub. 1128 for more WCR information
2) Application requirements may permit higher WCR for certain switch sizes.
3) Short Time ratings are provided for applications involving circuit breakers that utilize trip delay settings for system selective coordination
4) Max fuse rating is 1200A on front connected H frame switches
5) Switches utilizing overlapping neutral (code "C") have 35kA, 0.050 Sec time based rating at 480V Max
6) Rating shown is for Bypass switches only, Transfer Switch rating is 100kA
7) See ASCO for Service Entrance Switch ratings
8) These frames are only available on the 7000 Series product
9) Short Time Rating applies to 600A Bypass switch only, the 600A Transfer Switch does not have a Short Time Rating
13-Jan-20
ASCO Power Technologies - Global Headquarters
160 Park Avenue www.ascopower.com
Florham Park, NJ 07932 [email protected]
Tel: 800 800 ASCO
© 2020 ASCO Power Technologies. All Rights Reserved. Life Is On Schneider Electric is a trademark and the property of Schneider Electric SE, its subsidiaries and affiliated companies.