Technical Data of The Fan: RZR 13-1250: To Motor: Siemens-IE3 1LE1003-1CC03-4AB4/IE3

Download as rtf, pdf, or txt
Download as rtf, pdf, or txt
You are on page 1of 3

Technical data of the fan: RZR 13-1250 fulfills the ErP requirements 2015

Description Value Dimension


Installation acc. DIN 24163 Part 1 B
Reference density (Rho1) 1.20 kg/m³
Medium temperature (t) 20 C
Air flow rate (V) 15000 ft³/min
Total pressure rise (dpt) 0.47 in wg
Dynamic pressure at discharge (pd2) 0.03 in wg
Static pressure rise (dpfa) 0.44 in wg
Fan speed (nv) 1) 216 min-1
Power on fan shaft (Pw) 1.03 kW
Absorbed power of the system (P1) with V-belt / flat belt drive 1.32 / 1.29 kW
Total efficiency (ETAt) 80 %
Static efficiency (ETAfa) 75 %
System efficiency (ETA faS ) (over all efficiency of fan (static), motor, and V-belt / flat belt drive) 59 / 60 %
Specific Fan Power (SFP-factor) with V-belt / flat belt drive 186 / 182 W/(m3/s)
Nozzle calibration factor (K10) 3000 m2s/h
Differential pressure on nozzle (dpD) 0.17 in wg
Velocity at discharge area (c) 3.5 m/s
Fan weight 1100 kg
1)
Speed deviations within ±4% may be possible with the final selection of the belt drive which may slightly modify technical

data

A-weighted sound power level discharge/intake LwA4/7 62/62 dB


2)
Unweighted octave sound power level Octave mid frequencies
63/125/250/500/1k/2k/4k/8k Hz
72/67/65/59/54/48/43/34 dB discharge LwOkt4
61/64/63/60/56/53/48/41 dB intake LwOkt7
2)
The octave sound power levels can be higher at octave bands at or close to blade passing frequency.

To motor: Siemens-IE3 1LE1003-1CC03-4AB4/IE3


Phases-Voltage-Frequency 3~400/690-50 V-Hz
Frame size-poles: 132-6
Rated power (PN) 3.00 kW
Rated speed (nN) 970 min-1
Rated current (IN) 6,6/3,8 A
Speed up time at direct start (tA) 8 s
operational limits
Max. fan speed (nvmax) 1100 min-1
Max. power on shaft (Pwmax) 146 kW
Temperature range for conveying medium (tmin ...tmax) -20...80 C
ErP-Data at best efficiency and density 1.20 kg/m^3
measurement- / efficiency category B / total
design status of VSD without VSD
overall efficiency with V-belt / flat belt drive (ETAopt) 66.8 / 68.6 %
achieved efficiency grade with V-belt / flat belt drive (Nist) 72.4 / 74.3
required efficiency grade in 2013 / 2015 (N) 61 / 64
Air flow rate (Vopt) 20753 ft³/min
pressure rise (dpopt) 0.81 in wg
Fan speed (nvopt) 286 min-1
motor power input with V-belt / flat belt drive (P1opt) 2.93 / 2.86 kW
specific ratio (ddpopt) 1.002

Fan curve to RZR 13-1250

30.07.2021 1/3 proSELECTA II Version 2.02.07.29 / 131106 - June 2021


30.07.2021 2/3 proSELECTA II Version 2.02.07.29 / 131106 - June 2021
Dimensions to RZR 13-1250

Motor fitted to: without


Rotation: RD
Handing: 90

30.07.2021 3/3 proSELECTA II Version 2.02.07.29 / 131106 - June 2021