Electric Thrust Actuator ARI-PREMIO

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

ARI-PREMIO

Electric thrust actuator


Electric thrust actuator ARI-PREMIO

ARI-PREMIO
Electric thrust actuator 2,2 - 5 kN

Page 2

ARI-PREMIO
Electric thrust actuator 12 - 15 kN

Page 4

Features:
• 2 torque switches
• 1 travel switch
• Handwheel
• Operative ambient temperature -20qC to +70qC
• Enclosure IP 65
• Additional devices available;
e.g. potentiometer
• Travel indicator

Edition 01/07 - Data subject to alteration Data sheet 0000001


Electric thrust actuator ARI-PREMIO 2,2 - 5 kN

Pos. Description Pos. Description


50.1 Gearbox 50.38 Guide spindle
50.2 Cable gland 2 x M16x1,5 50.40 Synchronous motor, complete
50.4 Sealing plug 1 x M16x1,5 50.40.3 Capacitor
50.6 Hood 50.42 Board support
50.7 Hood seal 50.43 Standard board
50.8 Counter-sunk screw DIN EN ISO 10642 - M5 x 20 50.43.1 Travel switch (valve - open) S3
50.9 Sealing washer DIN EN ISO 7089 - 5,3 50.43.2 Torque switch
50.10 Column 50.45 Shift lever
50.12 Handwheel 50.47 Circuit diagram sticker, standard
50.14 Yoke 50.48 Connector, 3-pole (standard)
50.19 T-head bolt DIN 261 - M12 x 40 50.50 Trip slide
50.23 Lift dial 50.51 Setting spindle for switch S3
50.27 Coupling 50.52 Setting spindle for switch S4
50.30 Driving spindle 50.53 Setting spindle for switch S5
50.31 Spindle safety feature 50.54 Trip cam
50.32 Torsion safety feature 50.56 Spring for trip slide
50.34 Bellow 50.58 Protective conductor terminal
50.36 Bushing 50.87 Threaded bush
50.37 Grub screw DIN 913 - M3 x 5

2 Edition 01/05 - Data subject to alteration


Standard Acessories

Tele- Thermo- Current Voltage


Input resistance thermometer transmitter element 0(4)...20mA 0(2)...10V

Edition 10/06 - Data subject to alteration


Binary input Binary output Logic 12V
alternativ to
binary inputs
bin1 and bin2

power
supply

230V/3A Binary output (Out1)

230V/3A Binary outpu t (Out2)

Output to the actuator


Voltage and power
supply voltage are equal

Wire connections of the different valve types


3-way valve 3-way valve
Straightway valve with mixing plug with diverting plug HZ Heating resistor
DE Torque switch
closed A-AB open AB-B open Travel switch for limiting the travel distance
WE (S3)
in opening direction
open B-AB open AB-A open
RI 21 Electronic position indicator
Option NA: ES 11 Electronic position controller
same design but no RC circuit NA Low-voltage connection board, zero potential
and switches with gold contacts PA Standard-voltage connection board, zero potential
(Switching capacity 0.1A, 4-30V)
POT Potentiometer
WE Travel switch, zero potential
TTR Electronic temperature-controller dTRON316
Wiring diagram 2,2 - 5 kN

3
Electric thrust actuator ARI-PREMIO 12 - 15 kN

Pos. Description Pos. Description


50.1 Gearbox 50.38 Guide spindle
50.2 Cable gland 2 x M16 x 1,5 / 1 x M20 x 1,5 50.40 Synchronous motor, complete
50.6 Hood 50.40.3 Capacitor
50.7 Hood seal 50.42 Board support
50.8 Counter-sunk screw DIN EN ISO 10642 - M5 x 20 50.43 Standard board
50.9 Sealing washer DIN EN ISO 7089 - 5,3 50.43.1 Travel switch (valve - open) S3
50.10 Column 50.43.2 Torque switch
50.12 Handwheel (engageable) 50.45 Shift lever
50.24 Yoke 50.47 Circuit diagram sticker, standard
50.25 Hexagon nut DIN EN ISO 4032 - M12 50.51 Setting spindle for switch S3
50.26 2-ear clamp 50.52 Setting spindle for switch S4
50.27 Coupling 50.53 Setting spindle for switch S5
50.30 Driving spindle 50.54 Trip cam
50.31 Spindle safety feature 50.56 Spring for trip slide
50.32 Torsion safety feature 50.58 Protective conductor terminal
50.34 Bellow 50.87 Threaded bush
50.36 Set collar 50.101 Connector, 8-pole
50.37 Grub screw DIN 913 - M3x5

4 Edition 01/05 - Data subject to alteration


Standard Accessories

Tele- Thermo- Current Voltage


Input resistance thermometer transmitter element 0(4)...20mA 0(2)...10V

Binary input Binary output Logic 12V


alternativ to
binary inputs
bin1 and bin2

Edition 10/06 - Data subject to alteration


power
supply

230V/3A Binary output (Out1)

230V/3A Binary outpu t (Out2)

Option NA
same design as Standard but no RC
circuit and switches with gold contacts
(Switching capacity 0.1A, 4-30V) Output to the actuator
Wire connections of the different valve types Voltage and power
3-way valve 3-way valve supply voltage are equal
Standard Straightway valve with mixing plug with diverting plug

closed A-AB open AB-B open

open B-AB open AB-A open

HZ Heating resistor
DE Torque switch
Travel switch for limiting the travel distance
WE (S3)
in opening direction
RI 21 Electronic position indicator
ES 11 Electronic position controller
For external reversing contactor connect at L1, L2, L3.
L1, L2, L3 - actuator spindle drives in NA Low-voltage connection board, zero potential
L3, L2, L1 - actuator spindle drives out
POT Potentiometer
In all external reversing circuits the torque
switches S1 and S2/S3 have to be used to WE Travel switch, zero potential
switch off the actuator motor. TTR Electronic temperature-controller dTRON316
reversing
contactor WS Reversing contactor
(extern) Please check the operating direction
PR Phase control relay
of the actuator !
TS Temperature switch (motor)

5
Wiring diagram 12 - 15 kN
6
Accessories WS + PR

Wire connections of the different valve types


3-way valve 3-way valve
Straightway valve with mixing plug with diverting plug

closed A-AB open AB-B open

open B-AB open AB-A open

3-step input signal Connect 3 phases L1, L2, L3 only here

Accessories WS

HZ Heating resistor
DE Torque switch
Travel switch for limiting the travel distance
WE (S3)
in opening direction
RI 21 Electronic position indicator
ES 11 Electronic position controller
NA Low-voltage connection board, zero potential
POT Potentiometer
WE Travel switch, zero potential
3-step input signal Connect 3 phases L1, L2, L3 only here TTR Electronic temperature-controller dTRON316
WS Reversing contactor
Please check the operating direction of the actuator! PR Phase control relay
TS Temperature switch (motor)

Edition 10/06 - Data subject to alteration


Wiring diagram (accessories) 12 - 15 kN
Additional options

Additional travel switch Potentiometer


50.42 Board support 50.42 Board support
50.50 Trip slide 50.50 Trip slide
50.52 Setting spindle for switch S4 50.67 Potentiometer
50.53 Setting spindle for switch S5 50.68 Connecting cable
50.61.2 Travel switch S4 50.69 Self-tapping screw
50.61.3 Travel switch S5 50.70 Pinch spring
50.62 Connector, 6-pole 50.71 Slide block
50.73 Pinion
50.74 Connector, 3-pole

Electronic position controller ES 11


Operating voltage UB 24V-50/60Hz 115V-50/60Hz 230V-50/60Hz
Operating current without load IB 150 mA 40 mA 20 mA
Input control signal YU 0 (2) .... 10V DC - (RI = 30 kOhm)
Input control signal YI 0 (4) .... 20 mA DC - (RI = 125 Ohm)
Resistance RP 0 .... 1000 Ohm
Three-step switching current IS 4A max.

Electronic position indicator RI 21


Operating voltage UB 24V-50/60Hz 115V-50/60Hz 230V-50/60Hz
Operating current without load IB 150 mA 40 mA 20 mA
Output control signal YU 0 (2) .... 10V DC - (load resistance > 1000 Ohm)

Output control signal YI 0 (4) .... 20 mA DC - (load resistance max. 800


Ohm)
Resistance RP 0 .... 1000 Ohm

Edition 04/02 - Data subject to alteration 7


Technical data

Type ARI-PREMIO
Thrust force kN 2,2 5,0 12,0 15,0
Travel distance max. mm 50 80
Duty classification acc. to EN 60034-1/A11 S3 80% 1200 c/h S3 50% 1200 c/h
Control speed mm/sec. 0,25 0,38 0,38 1,0 0,79 0,38
Motor voltage 230V - 50Hz / 60Hz * 230V - 50Hz
Power consumption VA 10,3 11,7 25,3 52,9 109 96
2 pcs., fixed wiring, 2 pcs., fixed wiring,
Torque switch
switching capacity 10A, 250Va switching capacity 16A, 250Va
1 pc., fixed wiring, 1 pc., fixed wiring,
Travel switch
switching capacity 10A, 250Va switching capacity 16A, 250Va
Enclosure EN 60529 IP 65
Max. permissible ambient temperature -20 qC ... +70 qC
Handwheel Yes (always running) Yes (engageable)
Mounting position Horizontally to vertical above valve body (any position 90q from vertical).
Gear lubricant Klüber / Isoflex Topas NB152 Molyduval Valenzia H2
Weight kg 5,4 5,4 6,0 6,5 10,5
* Control speed and power consumption are 20% higher at frequency of 60 Hz.

Accessories
Type ARI-PREMIO
Thrust force kN 2,2 5,0 12,0 15,0
Additional travel switches 2 additional travel switches, zero potential, switching capacity 10A, 250Va
Additional travel switches 2 additional travel switches, zero potential, with gold contacts, for low switching capacities and at
for Low-voltage / electronic system aggressive atmosphere, switching capacity max. 0,1A, 4-30V
Maximum 2 possible.
Potentiometer
Different resistance-values: 100 Ohm, 200 Ohm, 500 Ohm, 1000 Ohm 1,5 watt
max. 2 only Ohmage 5000 or optional: 100, 200, 500, 1000 Ohm; 1,5 Watt;
TÜV-approved potentiometer
Not compatible for use with the heating resistor or RI21! No retrofitting possible!
0 (2) ... 10V; 0 (4) ... 20 mA - Only one potentiometer possible.
Electronic position indicator RI 21
Using the temperature controller, installation is only possible in the control cabinet.
Electronic position indicator RI 32 2 ... 10V; 4 ... 20 mA - Only one potentiometer possible.
0 (2) ... 10V; 0 (4) ... 20 mA - Only one potentiometer possible.
Electronic position controller ES 11
Not compatible for use with the temperature controller.
Heating resistor (automatic switching circuit) 230 VAC, 115VAC, 24VAC, 15 Watt
24V - 50Hz
24V - 50Hz / 24V - 60Hz*
24V - 60Hz*
24V - 50/60Hz * 115V - 50Hz / 115V - 60Hz*
Additional voltage / frequencies 115V - 50Hz
115V - 50/60Hz * 230V - 60Hz*
115V - 60Hz*
3~400V - 50Hz / 3~400V - 60Hz*
230V - 60Hz*
2 torque switches and 1 travel switch, zero potential, switching
Standard-voltage connection board PA Possible at standard design
capacity 10A, 250Va
2 torque switches and 1 travel switch, zero potential,
Low-voltage connection board
for free wiring, with gold contacts,
(electronic system) NA
for low switching capacities and at aggressive atmosphere, switching capacity max. 0,1A, 4-30V
Temperature controller (3-state stepper controller) in microprocessor technology.
Control range: -200˚C to 850qC (resistance thermometer)
Voltage: 24V, 115V or 230V 50/60Hz
Integrated temperature-controller dTRON 316
Compatible with resistance thermometers and thermocouples (provided by customer), standardized
active current or voltage signals.
Not compatible for use with the ES 11!
Actuator with 400V-50Hz and
440V-60Hz
Integrated reversing contactor --
Only 1 electronic module
possible!
Only in addition with
Phase control relay --
integrated reversing contactor!
DC-Module To control ARI-PREMIO 230V-50Hz with 24VDC.
--
3-step converter Not compatible for use with the temperature controller!
* Control speed and power consumption are 20% higher at frequency of 60 Hz.

Edition 01/07 - Data subject to alteration 8


Additional options
Integrated temperature controller dTRON 316
Features
• programmable analogue input
• 2 auto-tune methods
• Program function with 8 program sections or slope-function
• 2 Timer functions
• 4 limit-comparators
• Interlock for keyboard and level
• 4 programmable setpoints, two parameter sets
• 4 digit resolution (max. 2 decimal places)
• Controller characteristic P, PD, PI or PID
• Actual value input by usual temperature sensors (see in table)
• 2 relay outputs 230V/3A (shutter)
• 1 three-step output for actuator motor (by solid state relay 4A)
• 2 combinable binary inputs / binary outputs
Block structure Function in the ARI-PREMIO-Thrust actuator

Analogue input 2 relay (shutter)

Binary input or Logical output

Temperature-
Binary input or Logical output sensor

3-point-step output
for actuator motor

Input thermocouples Input resistance thermometer


Designation Measuring range Designation Type of connection Measuring range
Fe-CuNi „L“ -200 ...+900qC Pt 100 (standard) 2-wire / 3-wire / 4-wire -200...+850qC
Fe-CuNi „J“ DIN EN 60584 -200 ...+1200qC Pt 500 2-wire / 3-wire / 4-wire -200...+850qC
Cu-CuNi „U“ -200 ...+600qC Pt 1000 2-wire / 3-wire / 4-wire -200...+850qC
Cu-CuNi „T“ DIN EN 60584 -200 ...+400qC KTY11-6 2-wire -50...+150qC
NiCr-Ni „K“ DIN EN 60584 -200 ...+1372qC Sensor output resistance:
NiCr-CuNi „E“ DIN EN 60584 -200 ...+1000qC max. 30 Ohm each circuit at 3- and 4-wire connection
NiCrSi-NiSi „N“ DIN EN 60584 -100 ...+1300qC Measurement current: ca. 250 PA
Pt10Rh-Pt „S“ DIN EN 60584 0 ........+1768qC Circuit acjustment:
- at 3- and 4-wire connection not necessary.
Pt13Rh-Pt „R“ DIN EN 60584 0 ........+1768qC
- at 2-wire connection a circuit adjustment can be done with software by
Pt30Rh-Pt6Rh „B“ DIN EN 60584 0 ........+1820qC correcting the acual value.
W5Re-W26Re „C“ 0 ........+2320qC
W3Re-W25Re „D“ 0 ........+2495qC
W3Re-W26Re 0 ........+2400qC

Input standardized active current or voltage signals


Designation Measuring range
Voltage 0 (2) ... 10V, input resistance RE > 100 kOhm
Current 0 (4) ... 20mA, voltage drop d 1,5 V

Edition 10/06 - Data subject to alteration 9


10
Clearance required for
removal of hood

Clearance required for


removal of hood
Clearance required for
removal of hood

GERMAN QUALITY VALVES


Technology for the Future.
X L h
236 602 max. 30 mm
256 622 max. 50 mm

ARI-Armaturen Albert Richter GmbH & Co. KG, D-33756 Schloß Holte-Stukenbrock,
271 637 max. 65 mm
286 652 max. 80 mm

ARI-PREMIO 2,2 - 5 kN ARI-PREMIO 2,2 - 5 kN ARI-PREMIO 12 - 15 kN


Nominal travel max. 30 mm Nominal travel > 30 mm - 50 mm Nominal travel max. 80 mm

Tel. +49 52 07 / 994-0, Telefax +49 52 07 / 994-158 or 159 Internet: http://www.ari-armaturen.com E-mail: [email protected]
Edition 01/05 - Data subject to alteration
Dimensions

You might also like