Liebert APM Configuration Guide

This document provides configuration guidelines for two versions of the Liebert APM three-phase UPS - one with an internal modular battery option, and one with an internal modular output distribution option. It discusses the key technical specifications and components of the Liebert APM, including its modular power modules, communication card options, and external options like parallel cables and battery cabinets. The document also includes a battery runtime guide for the version with the modular internal battery option.

Uploaded by

truong_hoangvan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
832 views13 pages

Liebert APM Configuration Guide

This document provides configuration guidelines for two versions of the Liebert APM three-phase UPS - one with an internal modular battery option, and one with an internal modular output distribution option. It discusses the key technical specifications and components of the Liebert APM, including its modular power modules, communication card options, and external options like parallel cables and battery cabinets. The document also includes a battery runtime guide for the version with the modular internal battery option.

Uploaded by

truong_hoangvan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 13

Liebert APM Three-Phase UPS

Configuration Guide
For Asia Pacific
Ver 1.1
(Aug,2011)

NOTICE
THE INFORMATION CONTAINED IN THIS CONFIGURATION GUIDE IS
PROPRIETARY AND CONFIDENTIAL TO EMERSON NETWORK POWER CO.,
LTD. AND IS PROVIDED TO ENP ASIA PACIFIC MUS FOR SOLE PURPOSE OF
MAKING SURE TO CORRECTLY CONFIGURE LIEBERT APM PRODUCTS

Liebert APM Configuration Guide Ver 1.1 (Aug’11) Page 1 of 13


Liebert APM 400V — 50/60 Hz
30-150 kVA THREE-PHASE UPS

Contents
I. Liebert APM (for both versions) ................................................................................................ 3
1. Technical Notes: ................................................................................................................. 3
2. UPS Components ............................................................................................................... 4
II. Liebert APM Version with Modular Battery Option .............................................................. 5
1. Technical Notes: ................................................................................................................. 5
2. Liebert APM with Modular Battery Option UPS Composition.............................................. 6
3. UPS Components ............................................................................................................... 7
4. Standard Battery Runtime Guide for Liebert APM with Modular Battery Option ................. 8
III. Liebert APM Version with Inbuilt Output Distribution & Branch Circuit Monitoring Option .. 9
1. Technical Notes: ................................................................................................................. 9
2. Liebert APM with inbuilt modular PDU Internal Options.................................................... 10
3. Liebert APM with Output Distribution Option UPS Composition ....................................... 10
4. UPS Components ............................................................................................................. 12
IV. Common Options for both Liebert APM Versions ............................................................. 13
I. Liebert APM (for both versions)
PLEASE NOTE THAT THERE ARE TWO (2) VERSIONS OF LIEBERT APM:
a) LIEBERT APM WITH INTERNAL MODULAR BATTERY OPTION
b) LIEBERT APM WITH INTERNAL MODULAR OUTPUT DISTRIBUTION OPTION

HOW TO CORRECTLY CONFIGURE BOTH LIEBERT APM VARIANCE IS DISCUSSED IN


THE SUCCEEDING DECTIONS.

1. Technical Notes:
a) Liebert APM is a true on line, double conversion, full IGBT UPS system in
accordance with IEC62040-3 (VFI SS II).
b) Liebert APM can deliver power from 30kVA/kW to 150kVA/kW in a single APM
cabinet. With its modularity & scalability, it can have an N+1 system internally
within a single or parallel Liebert APM cabinet without inbuilt distribution option.
c) Liebert APM offers online double conversion mode efficiency of up to 96% for 50%
to 100% load conditions.
d) UPS system can offer dual bus functionality by use of cables only.
e) Liebert APM Power Modules are hot-swappable and can be added or removed at
site for up-gradation or maintenance.
f) Liebert APM is factory set to 380V, 50Hz input/output configuration. However,
400V/415V, 50Hz/60Hz can be easily be site configured by using the UPS software
program.
g) Each of Liebert APM power modules in a single cabinet shares common batteries.
h) Each Liebert APM UPS system is fitted with a 150kVA rated static switch assembly
module.
i) The UPS system accepts 30-40 blocks of 12V battery or 180-240 cells.
j) Please contact CTS for any query on products and it’s configuration not found in
this document.
k) Please refer to the user manual for more details on Liebert APM.

The standard Liebert APM Uninterruptible Power Supply is designed for front and back access
and is supplied with power connection provisions for the following:

AC Input to Rectifier: 3-phase, 3-wire plus earth


AC Input to Bypass: 3-phase, 4-wire plus earth
AC Module Output: 3-phase, 3- or 4-wire plus earth
DC Module Input: Positive, negative and center point

Liebert APM Configuration Guide Ver 1.1 (Aug’11) Page 3 of 13


Liebert APM 400V — 50/60 Hz
30-150 kVA THREE-PHASE UPS

2. UPS Components
Standard Supply
1. Liebert APM Cabinet
a. Standard 600mm x 1100mm x 2000mm server rack-look cabinet..
b. Bypass Module: Liebert APM is fitted with one static bypass module.
Bypass module has three (3) communication card slots which can offer
two (2) simultaneous monitoring option.
c. Switch Unit Module: Liebert APM is fitted with one switch unit module.
• For Liebert APM with output PDU & SPM option this module has
the input, output and maintenance bypass switch.
• For Liebert APM with modular battery option, this module has
only manual maintenance bypass switch.
d. LCD Panel: Liebert is equipped with a large 320 x 240 dot matrix graphic
LCD screen located at the front door of the UPS cabinet for user
interface.
2. Power Modules
Liebert APM uses modular scalable power modules in 30kVA / kW rating. Each
power modules are hot-swappable and can be added or removed at site provided
the remaining active power modules can support full capacity of the required load.
Minimum one Power module needs to be ordered with Liebert APM Cabinet.

Internal Options
1. Communication Options
Three (3) communication options are available to choose from depending on your
monitoring requirement. SNMP, Modbus & Relay cards are available. Please
choose the correct communication card from the table below.

External Options
1. Parallel Control Cable. (for APM with modular battery option ONLY!)
This is a cable option that is used for two (2) UPS up to four (4) connected in
parallel configuration.
2. Dual Bus Synchronization.
This is a cable option that is used for two (2) UPS in dual bus configuration. To
keep two independent units / systems synchronized.
3. Battery temperature Sensor.
Installed inside the battery cabinet to allow the DC charging voltage to be adjusted
automatically by the UPS controller in relation to the battery ambient temperature
to protect battery life.
4. External matching Battery Cabinet (non-modular battery cabinet)
Liebert APM standard battery cabinet in a standard 800mm x 1100mm x 2000mm
rack. It contains a battery disconnect circuit breaker. Depending on the battery to
be used, it can house 40 blocks of 90AH FM series Vision batteries inside. For
other battery rating, please contact CTS.
5. External Modular Battery Cabinet
Liebert APM standard battery cabinet in a standard 600mm x 1100mm x 2000mm
rack. It can hold up to 10 battery modules for extended back-up time requirement.
Multiple external modular battery cabinet can be paralleled to achieve desired
back-up time.
Liebert APM 400V — 50/60 Hz
30-150 kVA THREE-PHASE UPS

II. Liebert APM Version with Modular Battery Option


Please note that these are not applicable with the version with internal output distribution
option.

1. Technical Notes:
a) Liebert APM is a full modular UPS with hot-swappable power modules and internal
modular batteries in a single standard server rack (600mm x 1100mm) for up to
5min for a 90kVA UPS. A detailed battery runtime chart is shown in the following
section.
b) Liebert APM can be configured for a maximum of 150kVA requirement (150kVA,
120kVA+30kVA, 90kVA+60kVA, 60kVA+90kVA, 30kVA+120kVA). For increased
capacity or redundancy higher than 150kVA, Liebert APM can be paralleled up to a
maximum of up to four (4) Liebert APM modular UPS cabinet.
c) Please note that when paralleling two or more Liebert APM cabinets for capacity
enhancement (ex. 2 x 120kVA wherein the UPS will support a total load of 240kVA),
you need to add in bypass inductance chokes and if the total load is more than
150kVA. However, bypass inductance choke option for Liebert APM is currently
only available via SFA. Please contact CTS for this option.
d) Care should be taken when selecting the UPS rack cabinet as you have to select
the correct UPS rack cabinet configuration from the start to have the provision in
the future to upgrade Liebert APM either for redundancy or capacity.
e) Power modules can be site fitted anytime within the same UPS modular cabinet,
either for redundancy or up-gradation, without turning the whole UPS system into
bypass mode provided that the modular UPS rack cabinet is correctly sized from
the beginning to cater the additional power module/s.
f) Liebert APM has the option to choose from modular battery solution or
conventional battery option as required. Battery cabinets are available for each
requirement.
g) An external modular battery cabinet can house a maximum 10 battery modules for
extended battery back up requirement. Each battery modules contains 30 x 12V x
8AH battery blocks. Please refer to battery back-up time table below for the correct
modular battery configuration.
h) A conventional / standard matching battery cabinet (800mm x 1100mm) can also be
used that can house up to 40 blocks of 90AH battery (from Vision). For other
battery rating, please consult CTS for the correct configuration.
i) Please contact CTS for any query on products and it’s configuration not found in
this document.

Please refer to the user manual for more details on Liebert APM with modular battery
option.

Liebert APM Configuration Guide Ver 1.1 (Aug’11) Page 5 of 13


Liebert APM 400V — 50/60 Hz
30-150 kVA THREE-PHASE UPS

2. Liebert APM with Modular Battery Option UPS Composition

150kVA UPS rack cabinet with front and back view

Modular battery cabinet with front and back view


Liebert APM 400V — 50/60 Hz
30-150 kVA THREE-PHASE UPS

Battery module, part number 02352132

3. UPS Components

Modular Rack Cabinet and Power Module

Part Numbers Description Remarks


APM Rack cabinet cabled for 1 power module and 9
battery modules ONLY. This cabinet includes 1 x
30kW power module and 1 x 150kW STS. This
Liebert APM 030kVA UPS cabinet can accommodate up to 1 power module
NXrE0301005
Rack Cabinet ONLY and can be configured up to a maximum of
30kW UPS ONLY. Up-gradation of beyond 30kW is
not allowed.
APM Rack cabinet cabled for 2 power module and 8
battery modules ONLY. This cabinet includes 1 x
30kW power module and 1 x 150kW STS. This
cabinet can accommodate up to 2 power modules
Liebert APM 060kVA UPS
NXrE0302005 ONLY and can be configured as a 60kW or
Rack Cabinet
30kW+30kW UPS ONLY. Up-gradation of beyond
60kW is not allowed. For 60kVA or 30kVA+30kVA
requirement, you need to order one additional power
module.
APM Rack cabinet cabled for 3 power module and 7
battery modules ONLY. This cabinet includes 1 x
30kW power module and 1 x 150kW STS. This
cabinet can accommodate up to 3 power modules
Liebert APM 090kVA UPS
NXrE0303005 ONLY and can be configured as a 90kW or
Rack Cabinet 60kW+30kW or 30kW+60kW UPS ONLY. Up-
gradation of beyond 90kW is not allowed. For 90kVA
or 60kVA+30kVA requirement, you need to order two
additional power modules.
APM Rack cabinet cabled for 4 power module and 6
battery modules. This cabinet includes 1 x 30kW
power module and 1 x 150kW STS. This cabinet can
accommodate up to 4 power modules ONLY and can
Liebert APM 120kVA UPS be configured as a 120kW or 90kW+30kW or
NXrE0304005
Rack Cabinet 60kW+60kW or 30kW+90kW UPS ONLY. Up-
gradation of beyond 120kW is not allowed. For
120kVA, 90kVA+30kVA or 60kVA+60kVA
requirement, you need to order three additional
power modules.

Liebert APM Configuration Guide Ver 1.1 (Aug’11) Page 7 of 13


Liebert APM 400V — 50/60 Hz
30-150 kVA THREE-PHASE UPS
APM Rack cabinet cabled for 5 power module and 5
battery modules. This cabinet includes 1 x 30kW
power module and 1 x 150kW STS. This cabinet can
accommodate up to 4 power modules ONLY and can
Liebert APM 150kVA UPS be configured as a 150kW or 120kW+30kW or
NXrE0305005
Rack Cabinet 90kW+60kW or 60kW+90kW or 30kW+120kW UPS
ONLY. Up-gradation of beyond 150kW is not
allowed. For 150kVA, 120kVA+30kVA,
90kVA+60kVA or 30kVA+30kVA requirement, you
need to order four additional power modules.
Liebert APM 30kVA Power Each power module is
2351752 30kVA / kW rating.
Module

Modular Battery System Option

Part Number Description Remarks


Liebert APM modular battery 1. Holds up to 10 battery modules for extended
02352267
rack cabinet back-up time requirement
1. Contains 3 battery box with battery disconnect
within the battery module. 2. Choose the number
02352132 Liebert APM battery module of battery modules according to the required
back-up time.

Communication Option

Part Numbers Description Remarks

IS-WEBL OC Web Card (to be fitted at Site) Site interface card.

IS-485L ModBus / Jbus Card (to be fitted at Site) Uses Modbus protocol

IS-RELAY Relay Card (to be fitted at Site) Dry contacts cards

4. Standard Battery Runtime Guide for Liebert APM with Modular Battery
Option

Back-up Time Requirement in Minutes


5 10 15 20 30 60
UPS Modular Modular Modular Modular Modular Modular
kW Battery Battery Battery Battery Battery Battery
Battery Battery Battery Battery Battery Battery
Module Module Module Module Module Module
Cabinet Cabinet Cabinet Cabinet Cabinet Cabinet

30 n/a 3 n/a 4 n/a 5 n/a 7 n/a 9 1 14


60 n/a 5 n/a 8 1 10 1 13 1 17 2 28
90 n/a 7 1 11 1 15 2 19 2 25 - -
120 1 9 1 15 2 20 2 25 - - - -
150 1 11 2 19 2 25 - - - - - -

N/A – Not Applicable. Battery modules are house within the same cabinet as the power modules.
Liebert APM 400V — 50/60 Hz
30-150 kVA THREE-PHASE UPS
III. Liebert APM Version with Inbuilt Output Distribution & Branch
Circuit Monitoring Option
(Please offer this only when you need integrated output distribution option)

1. Technical Notes:
a) Liebert APM with output distribution and branch circuit monitoring is an Adaptive
Power Manager that consists of UPS power modules, UPS output power
distribution modules and a branch distribution circuit monitoring system, all in a
single cabinet.
b) Liebert APM is a modular & scalable UPS system with up to 5 hot-swappable
power modules rated at 30kVA/kW each with a maximum configuration of
120kVA/kW (120kVA/kW +30kVA/kW).
c) Standard Cabinet of Liebert APM is fitted with internal maintenance bypass, Input,
output switches. Battery protection is not inbuilt. Please ensure that battery
protection e.g battery breaker or switch-fuse unit is arranged/provided at site that
helps in maintaining battery bank.
d) Please choose the correct output distribution option and branch circuit monitoring
option from the table below.
e) A conventional / standard matching battery cabinet (800mm x 1100mm) can house
up to 40 blocks of 90AH battery (from Vision). For other battery rating, please
consult CTS for the correct configuration. (Please contact CTS for the use modular
battery option with Liebert APM with PDU & SPM option)
f) Please contact CTS for any query on products and it’s configuration not found in
this document.

Please refer to the user manual for more details on Liebert APM with modular battery
option.

Liebert APM Configuration Guide Ver 1.1 (Aug’11) Page 9 of 13


Liebert APM 400V — 50/60 Hz
30-150 kVA THREE-PHASE UPS

2. Liebert APM with inbuilt modular PDU Internal Options

a) Power Distribution Module


(a) Liebert APM can offer following two types of internal Power distribution
options, with or without Branch Circuit Monitoring Capabilities.
Maximum of three (3) output power distribution modules can be fitted in
one Liebert APM cabinet. Each module has 18 single MCBs with rating
from 10A-63A. Standard MCB rating is 25A if not otherwise stated when
ordering.
(i) Non-intelligent Distribution units (02352162 & 02352163) – This is
PDU assembly with basic distribution functionality only and does
not have provision for branch circuit monitoring.
(ii) Intelligent Distribution units (02352141 & 02352142) – This is PDU
assembly that comes with a provision for branch circuit monitoring.
In case Branch circuit Monitoring function is needed, even in future,
this type of PDU needs to be selected.
b) SPM / Branch Circuit Monitoring System
Optional SPM / BCMS can be used with Intelligent Power distribution Modules to
monitor load characteristics for each single phase branch and respective
measurements can be displayed in Liebert APM LCD panel. Only one (1) SPM
module is needed to monitor all three (3) output distribution modules.

3. Liebert APM with Output Distribution Option UPS Composition


Liebert APM 400V — 50/60 Hz
30-150 kVA THREE-PHASE UPS

Liebert APM Configuration Guide Ver 1.1 (Aug’11) Page 11 of 13


Liebert APM 400V — 50/60 Hz
30-150 kVA THREE-PHASE UPS

4. UPS Components

Liebert APM with PDU & SPM


Part
UPS Rating Description Remarks
Number
30kVA / 30kW 02351752 Liebert APM 30kVA Each power module is
Power Module 30kVA / kW rating.
Maximum of 01200534 Liebert APM 150kVA 1. Liebert APM rack cabinet is rated
120kVA Rack Cabinet 120kVA as maximum.
requirement 2. Can house up to 5 Liebert APM power
modules.
3. Please choose options for PDU and
SPM function accordingly. Please refer to
the table below
Output Power Distribution Unit with SPM Function
02352143 SPM Function Subassembly for Use this option with either 02352141 or
APM150 UPS 02352142 only.
02352141 Micro-breaker Distribution Subassembly 1. This includes provisions for PDU and
for APM150 UPS - intelligent SPM functionality.
2. This option shall be used with
02352143.
3. Not to be used together with
02353962.
02352142 Hot-plug Distribution Subassembly 1. This includes provisions for PDU and
for APM150 UPS - intelligent SPM functionality.
2. This option shall be used with
02352143.
3. Not to be used together with
02353963.
Output Power Distribution Unit without SPM Function
02353995 Basic Distribution Unit Subassembly for Use this option with either 02353962 or
APM150 UPS 02353963 only.

02353962 Micro-breaker Distribution Subassembly 1. This includes provisions for PDU


for APM150 UPS – non-Intelligent functionality only.
2. This option shall be used with
02353995.
3. Not to be used together with
02352141.
02353963 Hot-plug Distribution Subassembly 1. This includes provisions for PDU
for APM150 UPS – non-Intelligent functionality only.
2. This option shall be used with
02353995.
3. Not to be used together with
02352142.

Communication Options
Part Numbers Description Remarks

02351817 SIC Card Site interface card.

02354066 Modbus Card for NXr, APM and Adapt Uses Modbus protocol
16/20K
02354309 UPS RELAY CARD for APM Dry contacts cards

05112042 Site Monitor (Subscriber <=5) Network monitoring of ≤5 equipments.

05112043 Site Monitor (Subscriber <=20) Network monitoring of <20 equipments.

05112044 Site Monitor (Subscriber >20) Network monitoring of >20 equipments.

Page 12 of 13
Liebert APM 400V — 50/60 Hz
30-150 kVA THREE-PHASE UPS
IV. Common Options for both Liebert APM Versions

Part Numbers Description Remarks

Parallel and LBS Cables


04118683 Parallel / LBS Control Kit 5m Use for dual bus or parallel configuration
when UPS distance is 5m or less.
04118684 Parallel / LBS Control Kit 10m Use for dual bus or parallel configuration
when UPS distance is 10m or less.
04118685 Parallel / LBS Control Kit 15m Use for dual bus or parallel configuration
when UPS distance is 15m or less.
02350174 Battery Temperature sensor 1. Use to enable battery temperature
charging compensation function of UPS.
2. Shipped independently & assembled
on site.
24050100 Liebert APM External Battery Cabinet 1. For use with conventional (non-
modular) batteries.
2. Can accommodate 32 blocks as
standard of 100AH Vision FM series
battery (for above 32 blocks of batteries,
please contact CTS for SFA details)
3. Include inter cell cables and inter tier
cables.
4. Includes 400A circuit breaker, hence
it cannot be used for 150/160kVA (30-40
blocks) and 120kVA below 40 blocks
(other breaker ratings are available via
SFA).
Factory Witness Testings
Factory Witness Test ( USD/day/unit ) for
30-150 kVA

Battery Runtime Guide using modular battery


UPS kVA / runtime Number of Battery Module
in min 1 2 3 4 5 6 7 8 9 10
30 n/a 4 7 11 15 19 24 28 33 38
60 n/a n/a n/a 4 6 7 9 11 13 15
90 n/a n/a n/a n/a n/a 4 5 6 7 9
120 n/a n/a n/a n/a n/a n/a n/a 4 5 6
150 n/a n/a n/a n/a n/a n/a n/a n/a n/a 4

UPS kVA / runtime Number of Battery Module


in min 11 12 13 14 15 16 17 18 19 20
30 44 49 55 61 67 73 79 85 92 99
60 17 19 21 24 26 28 31 33 36 38
90 10 11 12 14 15 16 18 19 21 22
120 7 7 8 9 10 11 12 13 14 15
150 5 6 6 7 7 8 9 10 10 11

UPS kVA / runtime Number of Battery Module


in min 21 22 23 24 25 26 27 28 29 30
30 105 112 119 126 133 141 148 156 163 170
60 41 44 46 49 52 55 58 61 64 67
90 24 25 27 28 30 32 33 34 35 36
120 16 17 18 19 20 21 22 23 24 25
150 12 13 13 14 15 16 16 17 18 19
NOTE: Please consult CTS for the required external modular battery cabinets needed.