Single Package: Engineering Product Data

Download as pdf or txt
Download as pdf or txt
You are on page 1of 53

Engineering Product Data

R-410A

Single Package
(50Hz/R410A)

5CUK0-01B
Replaces 5CUK0-01A
Introduction 5CUK0-01B

Introduction
Preface
Thank you very much for your special patronage of LG air conditioners.

LG’s "Roof Top or Single Package" is an ideal choice when we talk about high load applications.
As the name Roof Top signifies, this unit is generally installed on the top of the roof. Also the Single Package signifies that
both condenser and evaporator are enclosed in a single body(same as window type). The unit is used along with ducts and
has flexible air flow as per installation conditions. The air flow can be horizontal or vertically downward which offers wider
flexibility in the field applications.

Apart from common features, this unit offers some unique features like High & Low static driver kit, Oversize motor option,
Manual Hood for fresh air intake, Compact design etc.

This unit is ideal for Single story and Double story houses as they offer high static pressure.
With its easy installation and simple control system, this product is suitable for Factories, Shopping malls, Multiplex, Hotels
etc.

A lot of information regarding the design & installation of this system is provided in this edition. This new product series con-
tains data on the same pattern.
Please utilize all the information for conducting your business efficiently.
Make sure the specification, dimensions and other technical data are same as provided in enginering data book before you
start the project.

We look forward to your continuing support.

LG Electronics Inc.
Air Conditioning Division

2 Single Package 50Hz, R410A


5CUK0-01B

Publication history
Pub. No. Frequency Category Type Product name Refrigerant Models Notes Published in
AK-H1208C00
AK-H1808C00
5CUK0-01A 50Hz CAC Single Single Package R410A AK-H2408C00 New edition of EPDB July.2006
EK-H1808C00
EK-H2408C00

5CUK0-01B 50Hz CAC Single Single Package R410A AK-H1208C00 Model Update Dec.2006

50Hz, R410A Single Package 3


Table of contents

1. Model line up ...............................................................................................................5


2. Nomenclature ..............................................................................................................6
3. Features & Benefits .....................................................................................................7
4. List of functions..........................................................................................................11
5. Specifications ............................................................................................................12
6. Dimensions ................................................................................................................13
7. Roof Curbs ................................................................................................................17
8. Wiring diagrams.........................................................................................................19
9. Selection procedure...................................................................................................22
10. Performance data ....................................................................................................26
11. Electrical data ..........................................................................................................43
12. Piping diagrams .......................................................................................................44
13. Operation range.......................................................................................................47
14. Controller .................................................................................................................48
15. Installation guide at the seaside ..............................................................................50
16. Mechanical specifications ........................................................................................51
17. Appendix..................................................................................................................52

4 Single Package 50Hz, R410A


5CUK0-01B Model line up

1. Model line up
1.1 Heat Pump
Nominal Capacity Model Power Supply
Ton Refrigerant Model Name Ø, V, Hz
10 AK-H1208C00
AK-H1808C00
15
R410A EK-H1808C00 3Ø, 380-415V, 50Hz
AK-H2408C00
20
EK-H2408C00

50Hz, R410A Single Package 5


Nomenclature 5CUK0-01B

2. Nomenclature

EK-H1808C00

Development Sequence

SEER Grade
Type SEER 10 11 12 13 14 15
MICOM Control 0 1 2 3 4 5
3~5RT
Mechanical Cont. A B C D E F
6~6.5RT There is no SEER regulation for these units
so "0" is allotted to these units.

Type of Flow
C: Convertible

Electric Standard (Volts, Freq., Phase)


8 : 380-415V, 50Hz, 3ø

Heating Capacity

Ex) 120 : 120,000 Btu/h, 180 : 180,000 Btu/h


240 : 240,000 Btu/h

Model Type
H : Heat Pump

Type of Air Conditioner

EK: LG Single Package Air Conditioner, Turkey, R410A


AK: LG Single Package Air Conditioner, Changwon, R410A

6 Single Package 50Hz, R410A


5CUK0-01B Features & Benefits

3. Features & Benefits


■ Easy Installation, Maintenance & Sevice
• Compact & light weight design
• U-shape Air Flow.
• Safety Condenser Fin Guard
• Forklift Base rail
• Easy access Panel.

■ Reliablity
• Time delay relay is standard component
• Low pressure Switch is standard component
• LG Scroll compressor with internal high-pressure & over-
current protector
• Strainer is adopted
• Durable painting steel cabinet
• Factory charged refrigerant
• Direct-drive multi-speed PSC blower Motor.
• Direct-drive PSC condenser fan Motor

Easy Installation, Maintenance & Service


The unit can be installed outside to save valuable indoor space or where no ceiling space is available. Install
the unit on the ground or on the roof. This means that the installation is totally flexible depending on your
requirements.
Since the unit has not been split into two, maintenance is easy, especially because all access panels are on the
same side of the unit and all wiring inside has been colour coded.

Additional functions available with duct system


All units come standard in Reverse Cycle, however electric heating can be added (Electric Heating provided
by Specialist Dealers). You have complete control over the fresh air input, amount of air purification and
zone controls (extras provided by Specialist Dealers), all using the powerful LG control system.

Typical Installation
Roof Jack Installation
Slab on Ground Installation

50Hz, R410A Single Package 7


Features & Benefits 5CUK0-01B

Cooling, Heating & Fan Operation :


- LG air conditioners can provide cooling, heating & fan operation. In the cooling mode, it cools the air with an
operation range of 18~30°C. In the heating mode, it heats the air with an operation range of 16~30°C. In the
fan operation mode, only indoor fan at the selected speed will run, outdoor fan and compressor will be off.

Auto Restart Operation :


- Whenever there is electricity failure the system shuts off and resumption of the power, unit will start in the
same mode as prior to the power failure. Memorized condition are on / off condition, operating mode (cool-
ing/heating), set temperature and fan speed.

LCD Wired Remote Control :


- It can control all the functions of the unit. You can
check/set temperature, change operation mode,
set timer & also diagnose the error of the unit. It
also has the weekly program.

Two Thermistor Control(Return Air Control):(Accessory)


- There may be a significant difference between the return air temperature in the duct and the room tempera-
ture. Return air sensing tempeaturee is designed to control temperature more accurately by applying addition-
al thermistor which senses the return air temperature inside the duct specially.
After selecting the duct thermistor, which is connected to the main PCB, the room temperature measurement
by LCD wired remote control thermistor is neglected. It helps to control the room temperature more accurate-
ly.(Thermistor is a field-installed accessory)

1 2 ........ 16

Group Control :
- It enables to control max of 16 units with the help of
one wired remote controller. All the units will follow
same setting of temperature & other sub functions.
........

8 Single Package 50Hz, R410A


5CUK0-01B Features & Benefits

Child Lock Function :


- It prevents the children or others from tampering
with the control buttons. Unit can be controlled by
the wireless remote controller. This can be easily set
by pressing timer key & Min key simultaneously.
After child lock is set, by pressing any key CL will be
displayed on the LCD for 3 seconds and all the keys
are ineffective.

CHILD LOCK
-Display
Defrost / Deicing :
- In the heating mode, it prevents the ice formation on the outdoor unit. The heating cycle is reversed to the
cooling cycle to defrost the evaporator pipe of the outdoor unit. While defrost cycle, the compressor is on and
indoor fan, outdoor fan and 4-way valve are off.

Hot Start Function :


- During starting of the unit in the heating mode it prevents cold air blow from the unit.It starts the indoor fan
only after indoor unit pipe temperature reaches a preset value.

Time Delay Relay :


- It delays restarting of the compressor by three minutes thereby preventing damage to the compressor .

Self Diagnosis Function :


- This function provides diagnosis of the unit. An error code will be displayed on the LCD wired remote con-
troller & diagnosis can be done as per the code indication.The same is also printed on key cover of the LCD
wired remote controller.

Central Control :(Accessory) Main M M M M M M


- It enables to control 16 x 8 = 128 units with the help PCB 1 2 16 17 18 128
of 8 controllers. All units can be put on and off from T/B T/B T/B T/B T/B T/B
one Central Room.For Setting Temperature, Fan 1 2 16 17 18 128
Speed and other sub functions, access the LCD
wired remote controller of each unit.

Controller Controller Controller


#1 #2 #8
(T/B: Terminal Block)

50Hz, R410A Single Package 9


Features & Benefits 5CUK0-01B

Weekly Program :
- It provides on / off schedule of operation for a period of one
week.

Wireless Remote Control:(Accessory)


- It provides ease of control.

Electric Heater:(Accessory)
- Electric Heater can be used to provide heat in addition to cycle
heat. It also provides quick heating. It can also work as a stand
alone heater with only fan operation.

Fire Alarm Function:


- By purchasing a fire alarm locally, installation of the fire alarm is
possible.In case of any fire, alarm will sound and the unit will be
completely stopped.

[Salt spray test for 15 days]


Energy Saving Gold Fin:(Optional)
- Single Package Heat Exchanger fins are coated with anticorro-
After 15 days LG Gold Fin™
sive & hydrophilic layers. It prevents the corrosion of heat Corrosion free
exchanger. Fins remains as new even after long time and main-
tains efficiency of heat exchanger. Saves power & maintenance Gold fin
Cost.

Conventional
After 15 days
starting to
corrode

Soft Start Function: Uncoated aluminum

- All single package air conditioners has soft start function i.e.
Indoor fan, outdoor fan & compressor start in sequence to pre-
vent overcurrent during starting.

10 Single Package 50Hz, R410A


5CUK0-01B List of functions

4. List of functions
AK-H1808C00 AK-H2408C00
Category Function AK-H1208C00 EK-H1808C00 EK-H2408C00
Air supply outlet 1 1 1
Airflow direction control(left & right) - - -
Airflow direction control(up & down) - - -
Auto swing(left & right) - - -
Air flow Auto swing(up & down) - - -
Airflow steps(fan/cool/heat) - - -
Chaos swing - - -
Chaos wind(auto wind) - - -
Jet cool(Power wind) - - -
Swirl wind - - -
Deodorizing filter - - -
Air purifying Plasma air purifier - - -
Prefilter(washable / anti-fungus) O O O
Drain pump - - -
E.S.P. control - - -
Installation
Electric heater(operation) Accessory Accessory Accessory
High ceiling operation - - -
Hot start - - -
Self diagnosis O O O
Soft dry operation O O O
Defrost / Deicing O O O
Reliability High pressure switch O O O
Low pressure switch O O O
Phase protection O O O
Restart delay (3-minutes) O O O
Soft start - - -
Test function O O O
Auto changeover - - -
Auto cleaning - - -
Auto operation(artificial intelligence) - - -
Auto restart operation O O O
Child lock O O O
Convenience Forced operation - - -
Group control O O O
Sleep mode - - -
Timer(on/off) O O O
Timer(weekly) O O O
Two thermistor control Accessory Accessory Accessory
Standard wired remote controller O O O
Deluxe wired remote controller - - -
Individual Simple wired remote controller - - -
control Wired remote controller(for hotel use) - - -
Wireless remote controller(simple) Accessory(AUWRHS) Accessory(AUWRHS) Accessory(AUWRHS)
Wireless LCD remote control - - -
General central controller (Non LGAP) Accessory Accessory Accessory
CAC network Dry contact - - -
function Network Soluation(LGAP) - - -
PDI(power distribution indicator) - - -
Zone control - - -
Special CTIE Accessory Accessory Accessory
function kit Electro thermostat - - -
Low ambient operation - - -
Others - - - -
Note:
O : Applied, X : Not applied, – : No relation
* Option : Model name & price are different according to options, and assembled in factory with main unit.
* Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.

50Hz, R410A Single Package 11


Specifications 5CUK0-01B

5. Specifications
Nominal Capacity (Ton) 10 15 20
Models AK-H1208C00 AK-H1808C00 AK-H2408C00
EK-H1808C00 EK-H2408C00
Capacity Gross Cooling Capacity kW 34.6 50.1 69.1
Btu/h 118,000 171,000 235,900
Net Cooling Capacity kW 32.8 48.6 65.9
Btu/h 112,000 166,000 225,000
Net Heating Capacity kW 32.8 52.8 73.3
Btu/h 112,000 180,000 250,000
Electrical Data Power Supply Ø / V / Hz 3/380~415/50 3/380~415/50 3/380~415/50
M.C.A Cooling A 38.2 57.2 74.4
(with Standard Motor) Heating A 38.2 57.2 74.4
Power Input Cooling W 14,400 20,000 26,500
Heating W 11,600 17,000 27,800
Performance Air Circulation(Nominal) CFM 3,700 5,500 8,000
EER Btu/h.W 7.78 8.30 8.50
SEER Btu/h.W - - -
COP W/W 2.83 3.10 2.64
Sound Rating bell 9.20 9.20 9.20
Indoor Coil Type High efficiency High efficiency High efficiency
Tube Size(O.D) mm(inch) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Rows / Column / FPI 3R / 44C / 16FPI 3R / 44C / 16FPI 3R / 52C / 16FPI
Length mm(inch) 900(35 7/16) 1,000(39 6/16) 1,000(39 6/16)
Face Area m2(sq.ft) 1.01(10.8) 1.12(12.1) 1.32(14.2)
Indoor Fan Type * No. Used Centrifugal Blower Centrifugal Blower Centrifugal Blower
Diameter mm(inch) 380(14 31/32) 380(15) 460(18)
Width mm(inch) 280(11 1/32) 380(15) 460(18)
Drive Type / Motor Step Belt / 1 Belt / 1 Belt / 1
No. Motors 1 1 1
Motor Output(Standard / Oversized) Hp 3.0 / 5.0 4.0 / 5.0 5.0 / 7.5
Motor RPM(Standard / Oversized) 1,400 / 1,430 1,380~1,400 / 1,400~1,430 2,892~2,900 / 2,870~2,900
No. of Outdoor Units - - -
Compressor Type * Quantity SCROLL * 2(Non Tropical) SCROLL * 3(Non Tropical) SCROLL * 4(Non Tropical)
Model ARA073YAA AR073YAB AR073YAB
Maker LG LG LG
Capacity Btu/h 62,000 61,000 61,000
Motor Type Three Phase Three Phase Three Phase
Motor Input W 6,020 6,289 6,289
Oil Type FVC68D(PVE) FVC68D(PVE) FVC68D(PVE)
Oil Charge cc 1,800±10 2,325±10 2,325±10
Outdoor Coil Type High efficiency High efficiency Corrugate Corrugate Corrugate Corrugate
Tube Size(O.D) mm(inch) 9.52(3/8) 9.52(3/8) 7(9/32) 7(9/32) 7(9/32) 7(9/32)
Rows / Column / FPI 2R / 32C / 17FPI 2R / 32C / 17FPI 3R / 52C / 17FPI 2R / 42C / 17FPI 3R / 46C / 17FPI 3R / 46C / 17FPI
Length mm(inch) 1,100(43 5/16) 1,100(43 5/16) 1,300(51 3/16) 1,300(51 3/16) 2,000(78 12/16) 2,000(78 12/16)
Face Area m2(sq.ft) 0.89(9.58) 0.89(9.58) 1.42(15.3) 1.15(12.3) 1.93(20.8) 1.93(20.8)
Outdoor Fan Type * No. Used Propeller * 2 Propeller * 2 Propeller * 4
Diameter inch 23.6 23.6 22
Drive Type Direct Direct Direct
Air Circulation CFM 3,125 3,125 3,125
No. Motor / Motor Output(Hp) Hp 2EA / 0.5 2EA / 0.5 4EA / 0.4
Motor RPM 910 910 950
Service Valve Liquid mm(inch) - - -
Gas mm(inch) - - -
Connecting Tube Liquid mm(inch) - - -
Gas mm(inch) - - -
Length(Standard) mm(inch) - - -
Dehumidification Rate l/h 8.10 13.3 20.0
Drain Connection Size(inch) 1 1 1
Refrigerant Refrigerant Charge kg 4.1/Circuit 4.65 2.9 5.6/Circuit
lbs 9.04/Circuit 10.25 6.39 12.35/Circuit
Type R-410A R-410A R-410A R-410A
Refrigerant Control Capillary Tube Capillary Tube Capillary Tube Capillary Tube
Dimensions Indoor Unit (W * H * D) mm - - -
inch - - -
Outdoor Unit or S/Package mm 2170 * 1244 * 1460 2,230 * 1,244 * 1,540 2,898 * 1,250 * 2,200
(W * H * D) inch 85 7/16 * 49 * 57 8/16 87 13/16 * 49 * 60 10/16 114 2/16 * 49 3/16 * 86 10/16
Net Weight Indoor Unit kg(lbs) - - -
Outdoor Unit or S/Package kg(lbs) 450(992) 550(1,212) 900(1,984)
Fliter Size * No. Used 925*418 * 1EA 1045*980 * 1EA 510*625 * 2ea
Filter Rack Thickness inch 1, 2 1, 2 1, 2
Notes:
1. Capacities are based on the following conditions: 2. Nominal CFM : Fan operation mode with clean filter, dry coil.
Cooling: - Indoor Temperature 27.0°C(80.6°F) DB/19.0°C(66.2°F) WB 3. The specification may be subject to change without notic for purpose of improvement.
- Outdoor Temperature 35°C(95°F) DB/24°C(75.2°F) WB
Heating: - Indoor Temperature 20.0°C(68°F) DB/15.0°C(59°F) WB
- Outdoor Temperature 7.0°C(44.6°F) DB/6.0°C(42.8°F) WB
- Level Difference of Zero

12 Single Package 50Hz, R410A


5CUK0-01B Dimensions

6. Dimensions
Model No.: AK-H1208C00
UNIT Dimensions (Figure B)
Unit: inch(mm)

UNITS 10RT

H 48 5/16 (1227)
I 54 13/16 (1392)
CLEARANCE 34"
J 85 7/16 (2170) CLEARANCE 16"

K 45 1/16 (1144)
103
Drain Connection Hole 1"
L 7 2/16 (181)
1021
M 4 (100) Figure A

K
M
L
J
I
CLEARANCE 34"
CLEARANCE 46"

Figure B
HORIZONTAL FLOW APPLICATION (Figure C)
Unit: inch(mm)
CLEARANCE 34"
UNITS 10RT CLEARANCE 16"

A 18 8/16 (470)
B 11 15/16 (303)
C 15 8/16 (393)
D F
1 8/16 (38)
E
E 3 15/16 (100)
F 35 8/16 (902) C
H D
CLEARANCE 46" B
G 4 (102) CLEARANCE 34"
A
H 30 10/16 (778) G

A B C D Figure C
DOWN FLOW APPLICATION (Figure D)
Unit: inch(mm)
E

G
F

UNITS 10RT
H

SUPPLY
RETURN
A 15 6/16 (390)
B 12 8/16 (317)
C 18 10/16 (473)
D 6 4/16 (158)
E 2 11/16 (68)
F 35 7/16 (900)
G 2 11/16 (68)
TOP VIEW Figure D
H 30 11/16 (780)

50Hz, R410A Single Package 13


Dimensions 5CUK0-01B

Model No.: AK-H1808C00, EK-H1808C00


UNIT Dimensions (Figure A)
Unit: inch(mm) CLEARANCE 34"
CLEARANCE 16"

UNITS 15/17.5RT
A 49 (1244)
B 60 10/16 (1540)
C 87 13/16 (2230)
F
D 44 3/16 (1123) E
E 7 1/16 (180) A
F 3 15/16 (100)

C B CLEARANCE 34"
D

CLEARANCE 46"
Figure A

HORIZONTAL FLOW APPLICATION (Figure B)


Unit: inch(mm)

UNITS 15/17.5RT CLEARANCE 34"


CLEARANCE 16"
A 37 (950)
6/16

B 5 11/16 (145)
C 2 11/16 (68)
D 17 15/16 (455)
E 14 6/16 (365)
A
F 18 12/16 (476)
G 5 2/16 (130)
B
G 31 3/16 (800)

H C
D
CLEARANCE 46" E
CLEARANCE 34"
G F

Figure B
DOWN FLOW APPLICATION (Figure C)
Unit: inch(mm)
A B C D
UNITS 15/17.5RT
A 7 29/32 (455)
E

B 14 11/32 (364)
F

C 18 3/4 (476) SUPPLY


RETURN
D 6 31/32 (177)
E 3 27/32 (98)
F 37 13/32 (950)
G 3 27/32 (98)
H 31 1/2 (800)

TOP VIEW Figure C

14 Single Package 50Hz, R410A


5CUK0-01B Dimensions

Model No.: AK-H2408C00, EK-H2408C00


UNIT Dimensions (Figure A)
Unit: inch(mm) CLEARANCE 34"
CLEARANCE 16"
UNITS 20 RT

H 49 3/16 (1250)
I 86 10/16 (2200)
J 114 2/16 (2898) K

N H
K 7 1/16 (180)
M
L 49 1/16 (1246)
J
I
M 3 2/16 (80) L
CLEARANCE 34"
CLEARANCE 46"
N 3 2/16 (80)

Figure A
HORIZONTAL FLOW APPLICATION (Figure B)

Unit: inch(mm)
CLEARANCE 34"
UNITS 20 RT CLEARANCE 16"

A 34 12/16 (882)
B 17 (432)
C 23 11/16 (602)
F
D 3 6/16 (86)
E
E 6 10/16 (168)
F 39 7/16 (1002) C
B D
CLEARANCE 46"
G 5 6/16 (137) CLEARANCE 34"
H A
G
H 25 11/16 (652) Figure B

A B C D
DOWN FLOW APPLICATION (Figure C)
E

Unit: inch(mm)
F

UNITS 20 RT
H

SUPPLY
RETURN
A 23 5/8 (600)
B 15 5/8 (396)
C 34 12/16 (882)
D 6 10/16 (168)
E 6 9/16 (167)
F 39 6/16 (1000)
G 6 13/16 (173)
H 25 13/16 (655)
TOP VIEW Figure C

50Hz, R410A Single Package 15


Dimensions 5CUK0-01B

Weights
Maximum Unit and Corner Weights (lbs) and Center of Gravity Dimensions (In.)
Unit Maximum Weights (lbs) Corner Weights (lbs) Center of Gravity (mm)
Tons Model No. Shipping Net A B C D E F
10 AK-H1208C00 970 772 260 196 146 168 37 20
AK-H1808C00
15 1455 1213 411 310 228 264 40 28
EK-H1808C00
AK-H2408C00
20 2171 1808 639 438 320 411 43 31
EK-H2408C00
Note: 1.Corner weights are given for information only.
2. Weights are approximate.

A B

D C
CENTER OF GRAVITY

16 Single Package 50Hz, R410A


5CUK0-01B Roof Curbs

7. Roof Curbs
Model No.: AK-H1208C00

30
30

1304 1025
106
"A" 2080
603
83
30
30
100
Detail View "A"

30

30
2022
220
2122
30
549 1344

(Unit : mm)

Note: Roof Curb – Galvanized steel


Remove the Fork Guides for Roof Curb installation

Model No. : EK-H1808C00/AK-H1808C00

40 40

1452 40 1055

250 "A"
40 2142
40
457
40

Detail View "A"


150
100 202

2062
2162
80
108

632

40 (Unit : mm)

Note: Roof Curb – Galvanized steel


Remove the Fork Guides for Roof Curb installation

50Hz, R410A Single Package 17


Roof Curbs 5CUK0-01B

Model No.: EK-H2408C00/AK-H2408C00

1064
2020
1930 50
50 2716
230 208 2626
50

650 "A" 50

80

Detail View "A"

100 550

88
40

2626
2776
1930
2080

(Unit : mm)

Note: Roof Curb – Galvanized steel


Remove the Fork Guides for Roof Curb installation

18 Single Package 50Hz, R410A


5CUK0-01B Wiring diagrams

8. Wiring diagrams
Model No.: AK-H1208C00

Notes:
RY RELAY EH ELECTRIC HEATER COMP COMPRESSOR
BK BLACK OR ORANGE YL YELLOW
BR BROWN RD RED BL BLUE
WH WHITE FACTORY WIRING FIELD WIRING

50Hz, R410A Single Package 19


Wiring diagrams 5CUK0-01B

Model No.: AK-H1808C00, EK-H1808C00

Notes:
RY RELAY EH ELECTRIC HEATER COMP COMPRESSOR
BK BLACK OR ORANGE YL YELLOW
BR BROWN RD RED BL BLUE
WH WHITE FACTORY WIRING FIELD WIRING

20 Single Package 50Hz, R410A


5CUK0-01B Wiring diagrams

Model No.: AK-H2408C00, EK-H2408C00

Notes:
RY RELAY EH ELECTRIC HEATER COMP COMPRESSOR
BK BLACK OR ORANGE YL YELLOW
BR BROWN RD RED BL BLUE
WH WHITE FACTORY WIRING FIELD WIRING

50Hz, R410A Single Package 21


Selection procedure 5CUK0-01B

9. Selection procedure
Selection Procedure - Heat pump(English)

Cooling

Step 1. Based on building's cooling load calculation from ASHRAE or any approved
standard method.
a. Cooling Capacity ...................................................................200,000 Btu/h
b. Sensible Cooling Capacity.....................................................170,000 Btu/h
c. Heating Capacity ...................................................................200,000 Btu/h
d. Outdoor Entering-air Temperature ........................................95°F
e. Outdoor Air winter design Temperature(DB) .........................39.2°F
f. Indoor Air winter design Temperature(DB)............................68°F
g. Indoor Entering-air Temperature(DB/WB) .............................80°F/67°F
f. Indoor air-flow........................................................................8,000 CFM
g. Electrical Characteristics(V-Ph-Hz) .......................................380~415-3-50
h. External static pressure .........................................................0.70 in.Aq.

Step 2. Select unit based on required cooling capacity.


Based on total cooling capacity choose suitable model from Specifications table.

20RT unit can be selected.

Verify the unit performance at the given conditions in accordance with step #3.

Step 3. From Gross Cooing Capacity(MBH) 20 ton EK-H2408C00 (English) table, at 8,000 CFM and 95
DB ambient temperature, with 80°F DB. 67°F WB air entering temperature.
Total cooling capacity= 235,900 Btu/h, Sensible capacity = 186,400 Btu/h
To find the capacity at intermediate points between any two values mentioned in the
capacity table, interpolation should be used. Extrapolation is not recommended.

22 Single Package 50Hz, R410A


5CUK0-01B Selection procedure

Selection Procedure

Step 4. The capacity estimated at step #3 is the gross capacity of the selected unit. The generated heat
from indoor motor is a function of CFM & static pressure. The total unit static pressure is as follows:

External Static(Duct system) 0.70 in. Aq.


Standard Filter 0.1 in. Aq.
Total static pressure 0.8 in. Aq.

Evaporator fan motor performance table has deducted the pressure drop for filter already in the unit.
Therefore, the actual total static pressure is 0.7 in. Aq.
With 8,000CFM and 0.7 in Aq., Evaporator Fan Performance EK-H2408C00 (English) table shows
3.6 BHP for this unit.
FAN MOTOR HEAT;
3.1 x Fan BHP = MBH
3.1 x 3.6 = 11.20 MBH
Now subtract the fan motor heat from the gross cooling capacity of the unit;

Net cooling capacity 235.9 MBH - 11.2 MBH = 224.7 MBH


• MBH = kBtu/h
Net sensible cooling 186.4 MBH - 11.2 = 175.2 MBH

Step 5. If the selected unit performance will not meet the required load, either total or sensible cooling, the
next higher size unit should be selected.

Heating

Step 1. Calculate the building heating load using the ASHRAE calculation or from other standard accepted
method.
Step 2. From Heating Capacity EK-H2408C00 (English), The heating capacity is 238,000 Btu/h at 8,000
CFM with 39.2°F outdoor DB temperature and 68°F indoor DB temperature. The required heating
capacity is 200,000 Btu/h.
Since heating capacity 238,000 Btu/h is greater than required heating capacity 200,000 Btu/h. So
additional electric heat is not required.
Step 3. If the selected unit performance will not meet the required load. The additional electric heater should
be selected from Electric Heating Capacity table.

50Hz, R410A Single Package 23


Selection procedure 5CUK0-01B

Selection Procedure - Heat pump(SI)

Cooling

Step 1. Based on building's cooling load calculation from ASHRAE or any approved
standard method.
a. Cooling Capacity ...................................................................58.6 kW
b. Sensible Cooling Capacity.....................................................49.8 kW
c. Heating Capacity ...................................................................58.6 kW
d. Outdoor Entering-air Temperature ........................................35°C
e. Outdoor Air winter design Temperature(DB) .........................4°C
f. Indoor Air winter design Temperature(DB)............................20°C
g. Indoor Entering-air Temp.(D.B/W.B) .....................................26.7°C / 19.4°C
f. Indoor air-flow........................................................................3,776 l/s
g. Electrical Characteristics(V-Ph-Hz) .......................................380~415-3-50
h. External static pressure .........................................................17.78mm Aq.

Step 2. Select unit based on required cooling capacity.


Based on total cooling capacity, choose suitable model from Specifications table.

20RT unit can be selected.

Verify the unit performance at the given conditions in accordance with step #3.

Step 3. From Gross Cooing Capacity(kW) 20 ton EK-H2408C00 (SI) table, at 3,776 l/s and 35°C out-
door ambient temperature, with 26.7°C DB. 19.4°C WB air entering temperature.
Total cooling capacity= 69.1kW, Sensible capacity = 54.6kW
To find capacity at intermediate conditions not in the table.
Interpolation should be used when design conditions are between two numbers that are in the
capacity table. Extra-polation is not recommended.

24 Single Package 50Hz, R410A


5CUK0-01B Selection procedure

Selection Procedure

Step 4. The capacity estimated at step #3 is the gross capacity of the selected unit. The generated heat
from indoor motor is a function of l/s & static pressure. To determine the total unit static pressure.
External Static(Duct system) 17.78 mm Aq.
Standard Filter 2.54 mm Aq.
Total static pressure 20.32 mm Aq.

Evaporator fan motor performance table has deducted the pressure drop for filter already in the unit.
Therefore, the actual total static pressure is 17.78 mm Aq.
With 3,776 l/s and 17.78 mm Aq., Evaporator Fan Performance EK-H2408C00 (SI) table shows 2.68
BkW for this unit.
FAN MOTOR HEAT;
1.22 x Fan Bkw = kW
1.22 x 2.68 = 3.27kW
Now subtract the fan motor heat from the gross cooling capacity of the unit;
Net cooling capacity 69.1kW - 2.68 kW = 66.42 kW
Net sensible cooling 54.6kW - 2.68 kW = 51.92 kW

Step 5. If the selected unit performance will not meet the required load, either total or sensible cooling, the
next higher size unit should be selected.

Heating

Step 1. Calculate the building heating load using the ASHRAE calculation or from other standard accepted
method.
Step 2. From Heating Capacity EK-H2408C00 (SI) table, The heating capacity is 69.7 kW at 3,776 l/s with
4°C outdoor temperature and 20°C indoor temperature. The required heating capacity is 58.6kW.
Since heating capacity 69.7kW is greater than required heating capacity 58.6kW. So, additional elec-
tric heat is not required.
Step 3. If the selected unit performance will not meet the required load. The additional electric heater should
be selected from Electric Heating Capacity table.

50Hz, R410A Single Package 25


Performance data 5CUK0-01B

10. Performance data


Gross Cooling Capacity (kW) 10 ton AK-H1208C00 (SI)
Outdoor DB(°C) 29.4 35.0
Indoor WB(°C) 16.1 19.4 22.8 16.1 19.4 22.8
l/s DB(°C) TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI
23.9 31.1 24.7 12.80 34.4 18.6 13.21 36.9 8.3 13.45 29.0 23.7 14.01 32.0 17.8 14.45 34.4 7.9 14.72
26.7 32.4 28.3 12.84 35.0 23.4 13.25 37.0 15.3 13.49 30.2 27.1 14.05 32.6 22.5 14.49 34.5 14.6 14.76
1397
29.4 33.7 31.1 12.88 35.5 28.1 13.29 36.9 21.2 13.53 31.4 29.8 14.09 33.1 26.9 14.54 34.4 20.3 14.81
32.2 34.8 32.8 12.92 35.9 31.3 13.33 36.6 25.9 13.57 32.4 31.4 14.13 33.4 30.0 14.58 34.1 24.8 14.85
23.9 32.4 27.3 12.92 35.8 20.5 13.33 38.5 9.1 13.57 30.2 26.1 14.13 33.4 19.6 14.58 35.9 8.7 14.85
26.7 33.8 31.2 12.96 36.4 25.8 13.37 38.5 16.9 13.61 31.5 29.9 14.17 34.0 24.7 14.62 35.9 16.1 14.89
1571
29.4 35.1 34.2 13.00 37.0 30.9 13.41 38.4 23.4 13.65 32.7 32.7 14.22 34.5 29.6 14.67 35.8 22.4 14.94
32.2 36.2 36.2 13.03 37.4 34.5 13.45 38.2 28.6 13.69 33.8 33.8 14.26 34.8 33.0 14.71 35.6 27.4 14.98
23.9 33.4 29.7 13.06 36.9 22.3 13.47 39.6 9.9 13.72 31.1 28.4 14.28 34.4 21.4 14.73 37.0 9.5 15.01
26.7 34.8 34.0 13.10 37.5 28.1 13.51 39.7 18.3 13.76 32.4 32.4 14.33 35.0 26.9 14.78 37.0 17.6 15.05
1746
29.4 36.1 36.1 13.13 38.1 33.7 13.55 39.6 25.4 13.80 33.7 33.7 14.37 35.5 32.2 14.82 36.9 24.4 15.10
32.2 37.3 37.3 13.17 38.5 37.5 13.59 39.3 31.1 13.84 34.8 34.8 14.41 35.9 35.9 14.87 36.6 29.8 15.14
23.9 34.0 31.8 13.13 37.6 23.9 13.54 40.4 10.6 13.79 31.7 30.4 14.36 35.0 22.9 14.82 37.7 10.2 15.09
26.7 35.5 35.5 13.17 38.3 30.1 13.58 40.4 19.6 13.83 33.1 33.1 14.41 35.7 28.8 14.86 37.7 18.8 15.14
1921
29.4 36.8 36.8 13.21 38.8 36.0 13.62 40.3 27.2 13.88 34.3 34.3 14.45 36.2 34.5 14.90 37.6 26.1 15.18
32.2 38.0 38.0 13.25 39.2 39.2 13.66 40.1 33.3 13.92 35.4 35.4 14.49 36.6 36.6 14.95 37.3 31.9 15.23
23.9 34.3 33.6 13.20 37.9 25.3 13.62 40.8 11.3 13.87 32.0 32.0 14.44 35.3 24.2 14.90 38.0 10.8 15.17
26.7 35.8 35.8 13.24 38.6 31.9 13.66 40.8 20.8 13.91 33.4 33.4 14.49 36.0 30.5 14.94 38.0 19.9 15.22
2095
29.4 37.1 37.1 13.28 39.2 38.1 13.70 40.7 28.8 13.95 34.6 34.6 14.53 36.5 36.5 14.99 37.9 27.6 15.26
32.2 38.4 38.4 13.32 39.6 39.6 13.74 40.4 35.3 13.99 35.8 35.8 14.57 36.9 36.9 15.03 37.7 33.8 15.31

Outdoor DB(°C) 40.6 46.1 51.7


Indoor WB(°C) 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
l/s DB(°C) TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI
23.9 26.2 22.3 15.38 29.0 16.8 15.87 31.1 7.5 16.16 22.1 20.4 17.05 24.5 15.4 17.59 26.3 6.8 17.91 24.4 22.8 16.58 27.0 17.2 17.10 29.0 7.6 17.42
26.7 27.3 25.5 15.43 29.5 21.1 15.92 31.2 13.8 16.21 23.1 23.1 17.10 24.9 19.4 17.64 26.3 12.6 17.97 25.5 25.5 16.63 27.5 21.6 17.15 29.1 14.1 17.47
1397
29.4 28.4 28.0 15.47 29.9 25.3 15.96 31.1 19.1 16.26 24.0 24.0 17.15 25.3 23.2 17.69 26.2 17.5 18.02 26.5 26.5 16.68 27.9 25.9 17.20 29.0 19.6 17.52
32.2 29.3 29.3 15.52 30.2 28.2 16.01 30.9 23.4 16.31 24.7 24.7 17.20 25.5 25.5 17.75 26.1 21.4 18.08 27.3 27.3 16.73 28.2 28.2 17.25 28.8 23.9 17.57
23.9 27.3 24.6 15.52 30.2 18.5 16.01 32.5 8.2 16.30 23.1 22.5 17.20 25.5 16.9 17.74 27.4 7.5 18.07 25.5 25.2 16.72 28.1 18.9 17.25 30.3 8.4 17.57
26.7 28.5 28.1 15.57 30.7 23.3 16.06 32.5 15.2 16.35 24.1 24.1 17.25 25.9 21.4 17.80 27.4 13.9 18.13 26.6 26.6 16.77 28.6 23.9 17.30 30.3 15.6 17.62
1571
29.4 29.6 29.6 15.61 31.2 27.8 16.10 32.4 21.0 16.40 25.0 25.0 17.31 26.3 25.6 17.85 27.3 19.3 18.18 27.6 27.6 16.82 29.1 28.5 17.35 30.2 21.6 17.68
32.2 30.5 30.5 15.66 31.5 31.1 16.15 32.2 25.7 16.45 25.8 25.8 17.36 26.6 26.6 17.90 27.2 23.6 18.24 28.5 28.5 16.87 29.4 29.4 17.41 30.0 26.4 17.73
23.9 28.1 26.7 15.68 31.1 20.1 16.18 33.4 8.9 16.48 23.7 23.7 17.39 26.3 18.4 17.93 28.2 8.2 18.27 26.2 26.2 16.90 29.0 20.6 17.44 31.2 9.2 17.76
26.7 29.3 29.3 15.73 31.7 25.3 16.23 33.4 16.5 16.53 24.8 24.8 17.44 26.7 23.2 17.99 28.2 15.2 18.32 27.4 27.4 16.95 29.5 26.0 17.49 31.2 16.9 17.81
1746
29.4 30.5 30.5 15.78 32.1 30.3 16.28 33.3 22.9 16.58 25.7 25.7 17.49 27.1 27.1 18.04 28.2 21.0 18.38 28.4 28.4 17.00 29.9 29.9 17.54 31.1 23.5 17.87
32.2 31.5 31.5 15.83 32.5 32.5 16.33 33.1 28.0 16.63 26.6 26.6 17.54 27.4 27.4 18.10 28.0 25.7 18.43 29.3 29.3 17.06 30.3 30.3 17.59 30.9 28.7 17.92
23.9 28.7 28.6 15.77 31.7 21.5 16.27 34.1 9.6 16.57 24.2 24.2 17.48 26.8 19.7 18.03 28.8 8.8 18.37 26.7 26.7 17.00 29.5 22.0 17.53 31.8 9.8 17.86
26.7 29.9 29.9 15.82 32.3 27.1 16.32 34.1 17.7 16.62 25.2 25.2 17.53 27.2 24.9 18.09 28.8 16.2 18.42 27.9 27.9 17.05 30.1 27.8 17.59 31.8 18.1 17.91
1921
29.4 31.0 31.0 15.87 32.7 32.4 16.37 34.0 24.5 16.67 26.2 26.2 17.59 27.6 27.6 18.14 28.7 22.5 18.48 28.9 28.9 17.10 30.5 30.5 17.64 31.7 25.1 17.96
32.2 32.0 32.0 15.91 33.1 33.1 16.42 33.8 30.0 16.72 27.1 27.1 17.64 27.9 27.9 18.20 28.5 27.5 18.53 29.9 29.9 17.15 30.8 30.8 17.69 31.5 30.7 18.02
23.9 28.9 28.9 15.86 32.0 22.8 16.36 34.4 10.1 16.66 24.4 24.4 17.58 27.0 20.9 18.13 29.0 9.3 18.47 27.0 27.0 17.09 29.8 23.3 17.63 32.0 10.4 17.96
26.7 30.2 30.2 15.91 32.5 28.7 16.41 34.4 18.7 16.71 25.5 25.5 17.63 27.5 26.3 18.19 29.0 17.2 18.52 28.1 28.1 17.14 30.3 29.4 17.68 32.1 19.2 18.01
2095
29.4 31.3 31.3 15.95 33.0 33.0 16.46 34.3 26.0 16.76 26.4 26.4 17.68 27.9 27.9 18.24 29.0 23.8 18.58 29.2 29.2 17.19 30.8 30.8 17.73 32.0 26.6 18.06
32.2 32.3 32.3 16.00 33.4 33.4 16.51 34.1 31.8 16.81 27.3 27.3 17.74 28.2 28.2 18.30 28.8 28.8 18.64 30.2 30.2 17.24 31.1 31.1 17.79 31.8 31.8 18.12
Notes:
1. All capacities are gross, evaporator fan motor heat is not deducted. To obtain net cooling capacity, subtract evaporator fan motor heat.
2. DB = Dry Bulb Temperature (°C), WB = Wet Bulb Temperature (°C)
3. l/s = Liters per second
4. TGC = Total Gross Cooling Capacity(Unit : kW)
5. SHC = Sensible Heat Capacity(Unit : kW)
6. PI = Power Input(kW), Sum of Compressor & Outdoor Fan Power Input

26 Single Package 50Hz, R410A


5CUK0-01B Performance data

Gross Cooling Capacity (kW) 15 ton AK-H1808C00, EK-H1808C00 (SI)


Outdoor DB(°C) 29.4 35.0
Indoor WB(°C) 16.1 19.4 22.8 16.1 19.4 22.8
l/s DB(°C) TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI
23.9 43.0 36.2 15.94 47.5 27.4 16.45 51.1 12.1 16.75 41.4 36.9 17.59 45.8 27.9 18.14 49.3 12.3 18.48
26.7 44.8 41.6 15.99 48.3 34.3 16.49 51.1 22.5 16.80 43.2 42.4 17.64 46.6 35.0 18.19 49.3 22.9 18.53
2077
29.4 46.5 45.6 16.04 49.0 41.3 16.54 50.9 31.1 16.85 44.9 44.9 17.69 47.3 42.1 18.25 49.1 31.7 18.59
32.2 48.0 48.0 16.09 49.6 45.9 16.59 50.6 37.9 16.90 46.3 46.3 17.74 47.8 46.8 18.30 48.8 38.6 18.64
23.9 45.0 38.6 16.08 49.7 29.2 16.59 53.4 12.9 16.90 43.4 39.4 17.72 47.9 29.8 18.28 51.5 13.2 18.62
26.7 46.9 44.4 16.13 50.6 36.6 16.64 53.5 24.0 16.95 45.2 45.2 17.78 48.8 37.3 18.34 51.6 24.4 18.68
2336
29.4 48.7 48.6 16.18 51.3 44.1 16.69 53.3 33.2 17.00 47.0 47.0 17.83 49.5 45.0 18.39 51.4 33.8 18.73
32.2 50.3 50.3 16.23 51.9 49.0 16.74 53.0 40.4 17.05 48.5 48.5 17.88 50.0 49.9 18.45 51.1 41.2 18.79
23.9 46.1 41.5 16.22 51.0 31.4 16.73 54.9 13.9 17.04 44.5 42.3 17.93 49.2 32.0 18.49 52.9 14.1 18.84
26.7 48.1 47.6 16.27 51.9 39.3 16.78 54.9 25.8 17.09 46.4 46.4 17.98 50.1 40.1 18.55 52.9 26.3 18.89
2596
29.4 50.0 50.0 16.32 52.7 47.4 16.83 54.7 35.6 17.14 48.2 48.2 18.04 50.8 48.3 18.61 52.8 36.3 18.95
32.2 51.6 51.6 16.36 53.3 52.6 16.88 54.4 43.4 17.19 49.8 49.8 18.09 51.4 51.4 18.66 52.5 44.2 19.01
23.9 46.9 43.4 16.36 51.9 32.9 16.87 55.8 14.5 17.18 45.3 44.3 18.00 50.1 33.5 18.57 53.8 14.8 18.91
26.7 49.0 49.0 16.40 52.8 41.2 16.92 55.8 27.0 17.24 47.2 47.2 18.05 51.0 42.0 18.62 53.8 27.5 18.97
2856
29.4 50.8 50.8 16.45 53.6 49.6 16.97 55.7 37.3 17.29 49.0 49.0 18.11 51.7 50.5 18.68 53.7 38.0 19.03
32.2 52.5 52.5 16.50 54.2 54.2 17.02 55.3 45.4 17.34 50.6 50.6 18.16 52.3 52.3 18.73 53.4 46.3 19.08
23.9 47.5 44.8 16.49 52.6 33.9 17.01 56.5 15.0 17.33 45.9 45.6 18.14 50.7 34.6 18.71 54.5 15.3 19.06
26.7 49.6 49.6 16.54 53.5 42.5 17.07 56.5 27.8 17.38 47.8 47.8 18.19 51.6 43.3 18.77 54.5 28.4 19.11
3115
29.4 51.5 51.5 16.59 54.3 51.2 17.12 56.4 38.5 17.43 49.7 49.7 18.25 52.4 52.1 18.82 54.4 39.2 19.17
32.2 53.2 53.2 16.64 54.9 54.9 17.17 56.0 46.9 17.49 51.3 51.3 18.30 52.9 52.9 18.88 54.1 47.8 19.23

Outdoor DB(°C) 40.6 46.1 51.7


Indoor WB(°C) 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
l/s DB(°C) TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI
23.9 40.0 36.0 18.92 44.2 27.2 19.51 47.5 12.0 19.87 37.7 35.0 20.01 41.7 26.5 20.65 44.9 11.7 21.03 35.0 33.4 20.94 38.6 25.3 21.60 41.6 11.2 22.00
26.7 41.7 41.3 18.97 45.0 34.1 19.57 47.6 22.3 19.93 39.4 39.4 20.07 42.5 33.2 20.71 44.9 21.7 21.09 36.5 36.5 21.00 39.3 31.7 21.66 41.6 20.7 22.06
2077
29.4 43.3 43.3 19.03 45.7 41.1 19.63 47.4 30.9 19.99 40.9 40.9 20.13 43.1 40.0 20.77 44.8 30.1 21.16 37.8 37.8 21.06 39.9 38.1 21.73 41.5 28.7 22.13
32.2 44.7 44.7 19.09 46.1 45.6 19.69 47.1 37.6 20.05 42.2 42.2 20.20 43.6 43.6 20.83 44.5 36.6 21.22 39.1 39.1 21.13 40.3 40.3 21.79 41.2 34.9 22.20
23.9 41.9 38.4 19.05 46.3 29.0 19.65 49.7 12.8 20.02 39.5 37.3 20.15 43.7 28.3 20.79 46.9 12.5 21.17 36.6 35.6 21.08 40.4 27.0 21.74 43.5 11.9 22.14
26.7 43.7 43.7 19.11 47.1 36.4 19.71 49.8 23.8 20.08 41.2 41.2 20.21 44.5 35.4 20.85 47.0 23.2 21.24 38.2 38.2 21.14 41.2 33.8 21.81 43.5 22.1 22.21
2336
29.4 45.3 45.3 19.17 47.8 43.8 19.77 49.6 33.0 20.14 42.8 42.8 20.27 45.1 42.6 20.91 46.8 32.1 21.30 39.6 39.6 21.20 41.8 40.7 21.87 43.4 30.6 22.28
32.2 46.8 46.8 19.23 48.3 48.3 19.83 49.3 40.1 20.20 44.2 44.2 20.33 45.6 45.6 20.98 46.5 39.1 21.36 40.9 40.9 21.27 42.2 42.2 21.94 43.1 37.3 22.34
23.9 43.0 41.2 19.19 47.5 31.2 19.80 51.1 13.8 20.16 40.5 40.1 20.29 44.8 30.4 20.93 48.2 13.4 21.32 37.6 37.6 21.21 41.5 29.0 21.88 44.6 12.8 22.29
26.7 44.8 44.8 19.25 48.4 39.1 19.86 51.1 25.6 20.22 42.3 42.3 20.35 45.6 38.0 20.99 48.2 24.9 21.38 39.2 39.2 21.28 42.3 36.3 21.95 44.7 23.8 22.36
2596
29.4 46.5 46.5 19.31 49.1 47.0 19.92 50.9 35.4 20.29 43.9 43.9 20.41 46.3 45.8 21.06 48.1 34.4 21.45 40.7 40.7 21.34 42.9 42.9 22.01 44.5 32.9 22.42
32.2 48.0 48.0 19.36 49.6 49.6 19.98 50.6 43.1 20.35 45.3 45.3 20.47 46.8 46.8 21.12 47.8 41.9 21.51 42.0 42.0 21.40 43.3 43.3 22.08 44.3 40.0 22.49
23.9 43.7 43.1 19.33 48.3 32.7 19.94 51.9 14.4 20.31 41.2 41.2 20.43 45.6 31.8 21.07 49.0 14.0 21.46 38.2 38.2 21.35 42.2 30.3 22.02 45.4 13.4 22.43
26.7 45.6 45.6 19.39 49.2 40.9 20.00 52.0 26.8 20.37 43.0 43.0 20.49 46.4 39.8 21.14 49.0 26.1 21.53 39.9 39.9 21.42 43.0 38.0 22.09 45.4 24.9 22.50
2856
29.4 47.3 47.3 19.45 49.9 49.3 20.06 51.8 37.0 20.43 44.6 44.6 20.55 47.1 47.1 21.20 48.9 36.1 21.59 41.4 41.4 21.48 43.6 43.6 22.16 45.3 34.4 22.57
32.2 48.9 48.9 19.50 50.4 50.4 20.12 51.5 45.1 20.49 46.1 46.1 20.61 47.6 47.6 21.26 48.6 43.9 21.66 42.7 42.7 21.54 44.1 44.1 22.22 45.0 41.9 22.64
23.9 44.3 44.3 19.47 48.9 33.7 20.08 52.6 14.9 20.45 41.8 41.8 20.57 46.2 32.8 21.21 49.6 14.5 21.61 38.7 38.7 21.49 42.8 31.3 22.17 46.0 13.8 22.58
26.7 46.2 46.2 19.53 49.8 42.2 20.14 52.6 27.6 20.52 43.6 43.6 20.63 47.0 41.1 21.28 49.7 26.9 21.67 40.4 40.4 21.55 43.5 39.2 22.23 46.0 25.7 22.65
3115
29.4 47.9 47.9 19.58 50.5 50.5 20.20 52.5 38.2 20.58 45.2 45.2 20.69 47.7 47.7 21.34 49.5 37.2 21.74 41.9 41.9 21.62 44.2 44.2 22.30 45.9 35.5 22.71
32.2 49.5 49.5 19.64 51.1 51.1 20.26 52.2 46.5 20.64 46.7 46.7 20.75 48.2 48.2 21.41 49.2 45.3 21.80 43.3 43.3 21.68 44.6 44.6 22.37 45.6 43.2 22.78
Notes:
1. All capacities are gross, evaporator fan motor heat is not deducted. To obtain net cooling capacity, subtract evaporator fan motor heat.
2. DB = Dry Bulb Temperature (°C), WB = Wet Bulb Temperature (°C)
3. l/s = Liters per second
4. TGC = Total Gross Cooling Capacity(Unit : kW)
5. SHC = Sensible Heat Capacity(Unit : kW)
6. PI = Power Input(kW), Sum of Compressor & Outdoor Fan Power Input

50Hz, R410A Single Package 27


Performance data 5CUK0-01B

Gross Cooling Capacity (kW) 20 ton AK-H2408C00, EK-H2408C00 (SI)


Outdoor DB(°C) 29.4 35.0
Indoor WB(°C) 16.1 19.4 22.8 16.1 19.4 22.8
l/s DB(°C) TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI
23.9 59.3 49.3 18.66 65.5 37.3 19.25 70.4 16.5 19.60 57.2 50.3 20.58 63.2 38.1 21.23 67.9 16.8 21.62
26.7 61.8 56.6 18.71 66.7 46.8 19.30 70.5 30.6 19.66 59.6 57.7 20.64 64.3 47.7 21.29 68.0 31.2 21.69
3021
29.4 64.2 62.1 18.77 67.7 56.3 19.36 70.3 42.4 19.72 61.9 61.9 20.70 65.3 57.4 21.36 67.8 43.2 21.75
32.2 66.3 65.4 18.83 68.4 62.6 19.42 69.8 51.6 19.78 63.9 63.9 20.77 66.0 63.8 21.42 67.4 52.6 21.82
23.9 62.0 52.6 18.82 68.6 39.8 19.41 73.7 17.6 19.77 59.8 53.6 20.74 66.1 40.6 21.40 71.1 17.9 21.79
26.7 64.7 60.4 18.88 69.8 49.9 19.47 73.7 32.7 19.83 62.4 61.6 20.80 67.3 50.9 21.46 71.1 33.3 21.86
3398
29.4 67.1 66.2 18.93 70.8 60.1 19.53 73.5 45.2 19.89 64.8 64.8 20.87 68.3 61.2 21.53 70.9 46.1 21.92
32.2 69.3 69.3 18.99 71.6 66.8 19.59 73.1 55.0 19.95 66.9 66.9 20.93 69.0 68.0 21.59 70.5 56.1 21.99
23.9 63.7 56.5 18.98 70.4 42.8 19.58 75.7 18.9 19.94 61.4 57.6 20.98 67.9 43.6 21.64 73.0 19.2 22.05
26.7 66.4 64.9 19.04 71.6 53.6 19.64 75.7 35.1 20.00 64.1 64.1 21.05 69.1 54.6 21.71 73.0 35.8 22.11
3776
29.4 68.9 68.9 19.09 72.7 64.5 19.70 75.5 48.5 20.06 66.5 66.5 21.11 70.1 65.8 21.78 72.8 49.5 22.18
32.2 71.2 71.2 19.15 73.5 71.7 19.76 75.0 59.1 20.12 68.7 68.7 21.17 70.9 70.9 21.84 72.4 60.2 22.25
23.9 64.7 59.2 19.14 71.6 44.8 19.75 77.0 19.8 20.11 62.5 60.3 21.07 69.1 45.7 21.73 74.2 20.2 22.13
26.7 67.6 67.6 19.20 72.9 56.1 19.81 77.0 36.7 20.17 65.2 65.2 21.13 70.3 57.2 21.80 74.3 37.4 22.20
4154
29.4 70.1 70.1 19.26 73.9 67.6 19.86 76.8 50.8 20.23 67.6 67.6 21.19 71.3 68.8 21.86 74.1 51.8 22.27
32.2 72.4 72.4 19.31 74.7 74.7 19.92 76.3 61.9 20.29 69.9 69.9 21.26 72.1 72.1 21.93 73.6 63.1 22.33
23.9 65.6 61.0 19.30 72.5 46.2 19.91 78.0 20.4 20.28 63.3 62.2 21.23 69.9 47.1 21.90 75.2 20.8 22.30
26.7 68.4 68.4 19.36 73.8 57.9 19.97 78.0 37.9 20.34 66.0 66.0 21.29 71.2 59.0 21.96 75.2 38.6 22.37
4531
29.4 71.0 71.0 19.42 74.9 69.7 20.03 77.8 52.4 20.40 68.5 68.5 21.35 72.2 71.0 22.03 75.0 53.4 22.44
32.2 73.3 73.3 19.48 75.7 75.7 20.09 77.3 63.8 20.46 70.7 70.7 21.42 73.0 73.0 22.09 74.6 65.0 22.50

Outdoor DB(°C) 40.6 46.1 51.7


Indoor WB(°C) 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
l/s DB(°C) TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI
23.9 55.2 49.0 22.14 61.0 37.1 22.84 65.6 16.4 23.26 52.1 47.7 23.42 57.6 36.1 24.16 61.9 15.9 24.61 48.2 45.5 24.50 53.3 34.4 25.28 57.3 15.2 25.75
26.7 57.6 56.2 22.20 62.1 46.4 22.90 65.6 30.4 23.33 54.3 54.3 23.49 58.6 45.2 24.24 61.9 29.6 24.69 50.3 50.3 24.58 54.3 43.1 25.35 57.3 28.3 25.82
3021
29.4 59.7 59.7 22.27 63.0 55.9 22.97 65.4 42.1 23.40 56.4 56.4 23.56 59.4 54.4 24.31 61.7 40.9 24.76 52.2 52.2 24.65 55.1 52.0 25.43 57.2 39.1 25.90
32.2 61.7 61.7 22.34 63.7 62.1 23.04 65.0 51.2 23.47 58.2 58.2 23.64 60.1 60.1 24.38 61.4 49.9 24.83 53.9 53.9 24.73 55.6 55.6 25.51 56.8 47.6 25.98
23.9 57.7 52.3 22.30 63.8 39.6 23.00 68.6 17.5 23.43 54.5 50.9 23.59 60.2 38.5 24.33 64.8 17.0 24.78 50.5 48.5 24.67 55.8 36.8 25.44 60.0 16.2 25.92
26.7 60.2 60.0 22.37 65.0 49.6 23.07 68.7 32.5 23.50 56.8 56.8 23.66 61.3 48.2 24.40 64.8 31.6 24.86 52.7 52.7 24.74 56.8 46.0 25.52 60.0 30.1 25.99
3398
29.4 62.5 62.5 22.43 65.9 59.7 23.14 68.5 44.9 23.57 59.0 59.0 23.73 62.2 58.1 24.48 64.6 43.7 24.93 54.6 54.6 24.81 57.6 55.4 25.60 59.8 41.7 26.07
32.2 64.6 64.6 22.50 66.6 66.3 23.21 68.0 54.7 23.64 60.9 60.9 23.80 62.9 62.9 24.55 64.2 53.2 25.00 56.4 56.4 24.89 58.2 58.2 25.67 59.5 50.8 26.15
23.9 59.3 56.1 22.46 65.5 42.5 23.17 70.4 18.8 23.60 55.9 54.6 23.75 61.8 41.4 24.50 66.5 18.3 24.95 51.8 51.8 24.83 57.3 39.5 25.61 61.6 17.4 26.09
26.7 61.8 61.8 22.53 66.7 53.2 23.24 70.5 34.9 23.67 58.4 58.4 23.82 62.9 51.8 24.57 66.5 33.9 25.03 54.1 54.1 24.90 58.3 49.4 25.69 61.6 32.4 26.16
3776
29.4 64.2 64.2 22.60 67.7 64.1 23.31 70.3 48.2 23.74 60.6 60.6 23.89 63.9 62.4 24.64 66.3 46.9 25.10 56.1 56.1 24.98 59.1 59.1 25.76 61.4 44.8 26.24
32.2 66.3 66.3 22.66 68.4 68.4 23.38 69.9 58.7 23.81 62.5 62.5 23.96 64.5 64.5 24.72 65.9 57.1 25.18 57.9 57.9 25.05 59.8 59.8 25.84 61.1 54.5 26.32
23.9 60.3 58.7 22.62 66.6 44.5 23.34 71.7 19.6 23.77 56.9 56.9 23.91 62.9 43.3 24.66 67.6 19.1 25.12 52.7 52.7 24.99 58.3 41.3 25.78 62.6 18.2 26.25
26.7 62.9 62.9 22.69 67.8 55.7 23.41 71.7 36.5 23.84 59.4 59.4 23.98 64.0 54.2 24.74 67.6 35.5 25.20 55.0 55.0 25.06 59.3 51.7 25.85 62.7 33.9 26.33
4154
29.4 65.3 65.3 22.76 68.8 67.1 23.48 71.5 50.5 23.91 61.6 61.6 24.05 65.0 65.0 24.81 67.5 49.1 25.27 57.1 57.1 25.14 60.2 60.2 25.93 62.5 46.9 26.41
32.2 67.4 67.4 22.83 69.6 69.6 23.55 71.0 61.5 23.98 63.6 63.6 24.12 65.6 65.6 24.88 67.0 59.8 25.35 58.9 58.9 25.21 60.8 60.8 26.01 62.1 57.1 26.49
23.9 61.1 60.6 22.78 67.5 45.9 23.50 72.6 20.3 23.94 57.6 57.6 24.07 63.7 44.7 24.83 68.5 19.7 25.29 53.4 53.4 25.15 59.0 42.6 25.94 63.4 18.8 26.42
26.7 63.7 63.7 22.85 68.7 57.5 23.57 72.6 37.6 24.01 60.1 60.1 24.14 64.8 55.9 24.90 68.5 36.6 25.37 55.7 55.7 25.23 60.1 53.4 26.02 63.5 35.0 26.50
4531
29.4 66.1 66.1 22.92 69.7 69.2 23.64 72.4 52.1 24.08 62.4 62.4 24.21 65.8 65.8 24.98 68.3 50.7 25.44 57.8 57.8 25.30 60.9 60.9 26.10 63.3 48.3 26.58
32.2 68.3 68.3 22.99 70.5 70.5 23.71 72.0 63.4 24.15 64.4 64.4 24.29 66.5 66.5 25.05 67.9 61.7 25.52 59.7 59.7 25.38 61.6 61.6 26.18 62.9 58.9 26.66
Notes:
1. All capacities are gross, evaporator fan motor heat is not deducted. To obtain net cooling capacity, subtract evaporator fan motor heat.
2. DB = Dry Bulb Temperature (°C), WB = Wet Bulb Temperature (°C)
3. l/s = Liters per second
4. TGC = Total Gross Cooling Capacity(Unit : kW)
5. SHC = Sensible Heat Capacity(Unit : kW)
6. PI = Power Input(kW), Sum of Compressor & Outdoor Fan Power Input

28 Single Package 50Hz, R410A


5CUK0-01B Performance data

Heating Capacity AK-H1208C00 (SI)


Indoor Outdoor WB(°C)
-10 -5 0 2 4 6 10 15
AFR(l/s) DB(°C) TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16 20.8 9.2 24.5 10.0 28.4 10.9 29.8 11.2 31.3 11.6 33.0 11.8 35.7 12.4 39.5 13.3
18 20.2 9.5 23.8 10.4 27.5 11.3 28.9 11.6 30.3 12.0 32.0 12.2 34.6 12.8 38.2 13.7
1397 20 19.6 9.8 23.1 10.7 26.7 11.7 28.0 12.0 29.4 12.4 30.8 12.6 33.6 13.2 37.1 14.2
22 18.9 10.1 22.2 11.0 25.7 12.0 27.0 12.4 28.3 12.8 29.9 13.0 32.4 13.7 35.7 14.6
24 18.2 10.4 21.5 11.4 24.8 12.4 26.1 12.8 27.3 13.2 28.9 13.4 31.3 14.1 34.5 15.1
16 21.2 8.4 24.9 9.2 28.9 10.0 30.3 10.3 31.8 10.6 33.6 10.8 36.3 11.3 40.1 12.2
18 20.5 8.7 24.2 9.5 27.9 10.3 29.4 10.6 30.8 11.0 32.5 11.1 35.2 11.7 38.8 12.6
1746 20 19.9 9.0 23.4 9.8 27.1 10.7 28.5 11.0 29.8 11.3 31.3 11.5 34.1 12.1 37.7 13.0
22 19.2 9.2 22.6 10.1 26.1 11.0 27.4 11.3 28.8 11.7 30.4 11.9 32.9 12.5 36.3 13.4
24 18.5 9.5 21.8 10.4 25.2 11.3 26.5 11.7 27.8 12.0 29.4 12.2 31.8 12.9 35.1 13.8
16 21.6 8.0 25.5 8.7 29.4 9.5 30.9 9.8 32.4 10.1 34.2 10.3 37.1 10.8 40.9 11.6
18 20.9 8.3 24.6 9.0 28.5 9.8 29.9 10.2 31.4 10.5 33.2 10.6 35.9 11.2 39.6 12.0
2095 20 20.3 8.5 23.9 9.3 27.7 10.2 29.1 10.5 30.4 10.8 32.0 11.0 34.8 11.6 38.4 12.4
22 19.6 8.8 23.0 9.6 26.7 10.5 28.0 10.8 29.3 11.1 31.0 11.3 33.6 11.9 37.0 12.8
24 18.9 9.1 22.3 9.9 25.7 10.8 27.0 11.2 28.3 11.5 29.9 11.7 32.4 12.3 35.8 13.2

Heating Capacity AK-H1808C00/EK-H1808C00 (SI)


Indoor Outdoor WB(°C)
-10 -5 0 2 4 6 10 15
AFR(l/s) DB(°C) TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16 35.0 13.6 41.3 14.8 47.8 16.1 50.2 16.6 52.6 17.1 55.5 17.4 60.1 18.3 66.4 19.6
18 33.9 14.0 40.0 15.3 46.3 16.7 48.6 17.2 50.9 17.7 53.8 18.0 58.2 19.0 64.3 20.3
2001 20 32.9 14.5 38.8 15.8 44.9 17.2 47.1 17.8 49.4 18.3 51.9 18.6 56.5 19.6 62.4 21.0
22 31.7 14.9 37.4 16.3 43.3 17.8 45.4 18.3 47.6 18.9 50.3 19.2 54.5 20.2 60.1 21.6
24 30.6 15.4 36.1 16.8 41.8 18.3 43.9 18.9 46.0 19.5 48.6 19.8 52.6 20.8 58.0 22.3
16 35.6 12.4 42.0 13.5 48.5 14.8 51.0 15.2 53.4 15.7 56.4 15.9 61.1 16.8 67.4 18.0
18 34.5 12.8 40.6 14.0 47.0 15.3 49.4 15.7 51.7 16.2 54.7 16.5 59.2 17.3 65.3 18.6
2501 20 33.5 13.2 39.4 14.5 45.6 15.8 47.9 16.2 50.2 16.7 52.7 17.0 57.4 17.9 63.4 19.2
22 32.3 13.7 38.0 14.9 44.0 16.3 46.2 16.8 48.4 17.3 51.1 17.6 55.3 18.5 61.1 19.8
24 31.1 14.1 36.7 15.4 42.5 16.8 44.6 17.3 46.7 17.8 49.4 18.1 53.4 19.1 59.0 20.4
16 36.3 11.8 42.8 12.9 49.5 14.1 52.0 14.5 54.5 15.0 57.6 15.2 62.3 16.0 68.8 17.1
18 35.2 12.2 41.5 13.4 48.0 14.6 50.4 15.0 52.8 15.5 55.8 15.7 60.4 16.6 66.6 17.7
3001 20 34.1 12.6 40.2 13.8 46.5 15.0 48.9 15.5 51.2 16.0 53.8 16.2 58.6 17.1 64.6 18.3
22 32.9 13.0 38.8 14.2 44.9 15.5 47.1 16.0 49.4 16.5 52.2 16.8 56.5 17.6 62.3 18.9
24 31.8 13.4 37.4 14.7 43.3 16.0 45.5 16.5 47.7 17.0 50.4 17.3 54.5 18.2 60.2 19.5

Correction Factor for Heating Capacity due to Frost on Heat Exchanger and Defrosting Operation.
The heating capacity in the "Heating Capacity Table" above indicates the actual heating capacity excluding the effect of frost on the heat
exchanger and the defrosting operation. Therefore, use the following factor to calculate the average heating capacity including capacity
reduction by frost on the exchanger and defrosting operation.

Correction Factor

Outdoor Air Temperature (°CWB, RH=85%) 10 -6 -4 -2 0 2 4 6


Correction Factor 0.95 0.95 0.89 0.87 0.87 0.89 0.91 1.00

Notes:
1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Outdoor air : 85%RH. However, the condition on nominal capacity is 7°CDB/6°CWB.
3. TC=Total heating capacity(Unit : kW)
4. PI=Power Input(Comp.+indoor fan motor+outdoor fan motor) (kW)
5. AFR=Air flow rate(l/s).

50Hz, R410A Single Package 29


Performance data 5CUK0-01B

Heating Capacity AK-H2408C00/EK-H2408C00 (SI)


Indoor Outdoor WB(°C)
-10 -5 0 2 4 6 10 15
AFR(l/s) DB(°C) TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16 48.7 22.1 57.3 24.2 66.3 26.4 69.7 27.2 73.0 28.0 77.1 28.5 83.5 30.0 92.2 32.1
18 47.1 22.9 55.5 25.0 64.2 27.3 67.5 28.1 70.7 28.9 74.7 29.4 80.9 31.0 89.3 33.2
3020 20 45.7 23.6 53.9 25.8 62.3 28.2 65.5 29.0 68.6 29.9 72.1 30.4 78.5 32.0 86.6 34.3
22 44.1 24.4 51.9 26.7 60.1 29.0 63.1 29.9 66.1 30.8 69.9 31.4 75.6 33.0 83.5 35.4
24 42.6 25.2 50.1 27.5 58.0 29.9 60.9 30.9 63.8 31.8 67.5 32.3 73.0 34.0 80.6 36.5
16 49.5 20.3 58.3 22.1 67.4 24.1 70.8 24.9 74.2 25.6 78.4 26.0 84.9 27.4 93.7 29.4
18 47.9 20.9 56.4 22.9 65.3 24.9 68.6 25.7 71.8 26.5 75.9 26.9 82.2 28.3 90.7 30.4
3775 20 46.5 21.6 54.8 23.6 63.3 25.7 66.5 26.5 69.7 27.3 73.2 27.8 79.7 29.3 88.0 31.3
22 44.8 22.3 52.8 24.4 61.1 26.6 64.1 27.4 67.2 28.2 71.0 28.7 76.9 30.2 84.8 32.3
24 43.3 23.0 51.0 25.1 59.0 27.4 61.9 28.2 64.9 29.1 68.6 29.6 74.2 31.1 81.9 33.3
16 50.5 19.3 59.5 21.1 68.8 23.0 72.2 23.7 75.7 24.4 80.0 24.8 86.6 26.2 95.6 28.0
18 48.9 20.0 57.6 21.8 66.6 23.8 70.0 24.5 73.3 25.3 77.5 25.7 83.8 27.0 92.5 29.0
4530 20 47.4 20.6 55.9 22.6 64.6 24.6 67.9 25.3 71.1 26.1 74.7 26.5 81.3 27.9 89.8 29.9
22 45.7 21.3 53.8 23.3 62.3 25.4 65.4 26.1 68.6 26.9 72.4 27.4 78.4 28.8 86.5 30.9
24 44.1 22.0 52.0 24.0 60.2 26.1 63.2 26.9 66.2 27.7 70.0 28.2 75.7 29.7 83.6 31.8

Correction Factor for Heating Capacity due to Frost on Heat Exchanger and Defrosting Operation.
The heating capacity in the "Heating Capacity Table" above indicates the actual heating capacity excluding the effect of frost on the heat
exchanger and the defrosting operation. Therefore, use the following factor to calculate the average heating capacity including capacity
reduction by frost on the exchanger and defrosting operation.

Correction Factor

Outdoor Air Temperature (°CWB, RH=85%) 10 -6 -4 -2 0 2 4 6


Correction Factor 0.95 0.95 0.89 0.87 0.87 0.89 0.91 1.00

Notes:
1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Outdoor air : 85%RH. However, the condition on nominal capacity is 7°CDB/6°CWB.
3. TC=Total heating capacity(Unit : kW)
4. PI=Power Input(Comp.+indoor fan motor+outdoor fan motor) (kW)
5. AFR=Air flow rate(l/s).

30 Single Package 50Hz, R410A


5CUK0-01B Performance data

Gross Cooling Capacity (MBH) 10 ton AK-H1208C00 (English)


Outdoor DB(°F) 85 95
Indoor WB(°F) 61 67 73 61 67 73
CFM DB(°F) TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI
75 106.0 84.5 12.80 117.2 63.5 13.20 126.0 28.3 13.45 98.8 80.8 14.01 109.2 60.8 14.45 117.5 27.1 14.72
80 110.6 96.8 12.84 119.3 80.1 13.24 126.1 52.2 13.49 103.1 92.6 14.05 111.2 76.6 14.50 117.5 50.0 14.76
2960
85 114.8 106.1 12.88 121.0 95.8 13.28 125.7 72.4 13.53 107.0 101.5 14.09 112.8 91.7 14.54 117.2 69.3 14.81
90 118.6 112.1 12.92 122.3 106.9 13.32 125.0 88.6 13.57 110.5 107.3 14.14 114.0 102.3 14.58 116.5 84.8 14.85
75 110.5 93.1 12.91 122.1 70.0 13.32 131.3 31.2 13.57 102.9 89.1 14.13 113.8 67.0 14.58 122.4 29.8 14.85
80 115.2 106.7 12.95 124.3 88.2 13.36 131.3 57.6 13.61 107.4 102.1 14.18 115.9 84.4 14.63 122.4 55.1 14.89
3330
85 119.6 117.0 12.99 126.1 105.6 13.40 131.0 79.8 13.65 111.5 111.5 14.22 117.5 101.1 14.67 122.1 76.4 14.94
90 123.5 123.5 13.03 127.5 117.8 13.44 130.2 97.6 13.69 115.1 115.1 14.26 118.8 112.7 14.71 121.3 93.4 14.98
75 113.8 101.3 13.05 125.8 76.2 13.46 135.2 33.9 13.71 106.0 97.0 14.29 117.2 72.9 14.74 126.0 32.5 15.01
80 118.7 116.1 13.09 128.1 96.0 13.51 135.3 62.7 13.75 110.6 110.6 14.33 119.4 91.9 14.78 126.1 60.0 15.05
3700
85 123.2 123.2 13.13 129.9 114.9 13.54 134.9 86.8 13.79 114.8 114.8 14.37 121.1 110.0 14.82 125.8 83.1 15.10
90 127.2 127.2 13.17 131.3 128.2 13.58 134.1 106.3 13.84 118.6 118.6 14.41 122.4 122.4 14.87 125.0 101.7 15.14
75 115.9 108.5 13.12 128.2 81.6 13.54 137.8 36.3 13.79 108.1 103.8 14.36 119.5 78.1 14.82 128.4 34.7 15.09
80 121.0 121.0 13.16 130.5 102.8 13.58 137.9 67.1 13.83 112.7 112.7 14.41 121.6 98.4 14.86 128.5 64.2 15.14
4070
85 125.5 125.5 13.20 132.4 123.0 13.62 137.5 92.9 13.87 117.0 117.0 14.45 123.4 117.7 14.91 128.1 88.9 15.18
90 129.7 129.7 13.24 133.8 133.8 13.66 136.6 113.7 13.91 120.8 120.8 14.49 124.7 124.7 14.95 127.4 108.8 15.23
75 117.0 114.9 13.20 129.3 86.4 13.61 139.1 38.4 13.86 109.0 109.0 14.44 120.5 82.7 14.90 129.6 36.8 15.18
80 122.1 122.1 13.24 131.7 108.9 13.65 139.1 71.0 13.91 113.8 113.8 14.49 122.7 104.2 14.95 129.7 68.0 15.22
4440
85 126.7 126.7 13.28 133.6 130.3 13.69 138.7 98.4 13.95 118.1 118.1 14.53 124.5 124.5 14.99 129.3 94.2 15.27
90 130.8 130.8 13.32 135.0 135.0 13.74 137.9 120.4 13.99 121.9 121.9 14.57 125.8 125.8 15.03 128.5 115.2 15.31

Outdoor DB(°F) 105 115 125


Indoor WB(°F) 61 67 73 61 67 73 61 67 73
CFM DB(°F) TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI
75 89.4 76.0 15.38 98.8 57.1 15.86 106.3 25.4 16.16 75.5 69.8 17.05 83.4 52.5 17.59 89.7 23.3 17.91 83.3 81.5 16.68 92.1 61.7 17.21 99.0 27.3 17.53
80 93.3 87.0 15.42 100.6 72.0 15.91 106.3 47.0 16.21 78.7 78.7 17.10 84.9 66.1 17.64 89.7 43.1 17.97 86.9 86.9 16.73 93.7 77.3 17.26 99.0 50.6 17.58
2960
85 96.8 95.5 15.47 102.1 86.2 15.96 106.0 65.1 16.25 81.7 81.7 17.15 86.2 79.1 17.69 89.5 59.8 18.02 90.2 90.2 16.78 95.1 93.1 17.31 98.7 70.0 17.64
90 100.0 100.0 15.52 103.2 96.1 16.01 105.4 79.7 16.30 84.4 84.4 17.20 87.1 87.1 17.75 89.0 73.1 18.07 93.1 93.1 16.84 96.1 96.1 17.37 98.1 85.3 17.69
75 93.1 83.8 15.52 103.0 63.0 16.00 110.7 28.0 16.30 78.6 76.9 17.20 86.9 57.8 17.74 93.5 25.7 18.07 87.1 87.0 16.79 96.3 65.9 17.32 103.6 29.1 17.65
80 97.2 95.9 15.56 104.8 79.4 16.05 110.8 51.8 16.35 82.0 82.0 17.25 88.5 72.9 17.80 93.5 47.5 18.13 90.9 90.9 16.84 98.1 82.5 17.38 103.6 54.0 17.70
3330
85 100.8 100.8 15.61 106.3 95.0 16.10 110.4 71.8 16.40 85.1 85.1 17.30 89.8 87.2 17.85 93.2 65.9 18.18 94.4 94.4 16.90 99.5 99.3 17.43 103.3 74.7 17.75
90 104.2 104.2 15.66 107.5 106.0 16.15 109.8 87.8 16.45 87.9 87.9 17.36 90.7 90.7 17.90 92.7 80.6 18.23 97.4 97.4 16.95 100.6 100.6 17.48 102.7 91.0 17.80
75 95.9 91.2 15.68 106.1 68.6 16.18 114.0 30.5 16.48 81.0 81.0 17.38 89.5 62.9 17.93 96.3 28.0 18.27 89.5 89.5 16.90 98.9 70.7 17.44 106.3 31.2 17.76
80 100.1 100.1 15.73 108.0 86.4 16.23 114.1 56.4 16.52 84.5 84.5 17.44 91.2 79.3 17.99 96.3 51.7 18.32 93.3 93.3 16.96 100.7 88.6 17.49 106.4 58.0 17.81
3700
85 103.9 103.9 15.78 109.5 103.4 16.27 113.8 78.1 16.57 87.7 87.7 17.49 92.5 92.5 18.04 96.0 71.7 18.38 96.9 96.9 17.01 102.1 102.1 17.54 106.1 80.2 17.87
90 107.3 107.3 15.82 110.7 110.7 16.32 113.1 95.6 16.62 90.6 90.6 17.54 93.5 93.5 18.09 95.5 87.7 18.43 100.0 100.0 17.06 103.2 103.2 17.59 105.4 97.7 17.92
75 97.8 97.6 15.77 108.1 73.4 16.26 116.2 32.7 16.57 82.5 82.5 17.48 91.2 67.4 18.03 98.1 30.0 18.37 91.0 91.0 17.01 100.6 74.1 17.55 108.1 32.7 17.88
80 102.0 102.0 15.81 110.0 92.5 16.32 116.3 60.3 16.62 86.1 86.1 17.53 92.9 84.9 18.09 98.1 55.4 18.42 94.9 94.9 17.07 102.4 92.7 17.60 108.2 60.7 17.93
4070
85 105.9 105.9 15.86 111.6 110.7 16.36 115.9 83.6 16.67 89.4 89.4 17.59 94.2 94.2 18.14 97.9 76.7 18.48 98.5 98.5 17.12 103.9 103.9 17.66 107.9 84.0 17.98
90 109.3 109.3 15.91 112.8 112.8 16.41 115.2 102.3 16.72 92.3 92.3 17.64 95.2 95.2 18.19 97.3 93.9 18.53 101.7 101.7 17.17 105.0 105.0 17.71 107.2 102.3 18.04
75 98.7 98.7 15.85 109.1 77.7 16.35 117.3 34.6 16.66 83.3 83.3 17.58 92.1 71.3 18.13 99.0 31.7 18.47 92.2 92.2 17.12 101.9 76.4 17.66 109.5 33.7 17.99
80 102.9 102.9 15.90 111.0 97.9 16.41 117.3 63.9 16.71 86.9 86.9 17.63 93.7 89.9 18.19 99.0 58.6 18.52 96.1 96.1 17.18 103.7 95.7 17.72 109.6 62.7 18.05
4440
85 106.8 106.8 15.95 112.6 112.6 16.45 117.0 88.5 16.76 90.2 90.2 17.68 95.1 95.1 18.24 98.8 81.3 18.58 99.8 99.8 17.23 105.2 105.2 17.77 109.3 86.7 18.10
90 110.3 110.3 16.00 113.8 113.8 16.50 116.3 108.3 16.81 93.1 93.1 17.74 96.1 96.1 18.30 98.2 98.2 18.63 103.1 103.1 17.28 106.3 106.3 17.82 108.6 105.5 18.15

Notes:
1. All capacities are gross, evaporator fan motor heat is not deducted. To obtain net cooling capacity, subtract evaporator fan motor heat.
2. DB = Dry Bulb Temperature (°F), WB = Wet Bulb Temperature (°F)
3. CFM = Cubic Feet per minute
4. TGC = Total Gross Cooling Capacity(Unit : MBH = kBtu/h)
5. SHC = Sensible Heat Capacity(Unit : MBH = kBtu/h)
6. PI = Power Input(kW), Sum of Compressor & Outdoor Fan Power Input

50Hz, R410A Single Package 31


Performance data 5CUK0-01B

Gross Cooling Capacity (MBH) AK-H1808C00, EK-H1808C00 (English)


Outdoor DB(°F) 85 95
Indoor WB(°F) 61 67 73 61 67 73
CFM DB(°F) TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI
75.0 146.6 123.5 15.94 162.1 93.6 16.45 174.3 41.3 16.75 141.4 125.9 17.59 156.4 95.4 18.14 168.1 42.1 18.48
80.0 153.0 141.9 15.99 165.0 117.2 16.49 174.3 76.7 16.80 147.6 144.6 17.64 159.2 119.4 18.19 168.2 78.2 18.53
4400
85.0 158.7 155.5 16.04 167.4 141.1 16.54 173.8 106.1 16.85 153.1 153.1 17.69 161.5 143.8 18.25 167.7 108.2 18.59
90.0 163.9 163.7 16.09 169.2 156.8 16.59 172.8 129.2 16.90 158.2 158.2 17.74 163.2 159.8 18.30 166.7 131.7 18.64
75.0 153.4 131.8 16.08 169.6 99.8 16.59 182.4 44.1 16.90 148.0 134.3 17.72 163.6 101.7 18.28 175.9 44.9 18.62
80.0 160.1 151.4 16.13 172.7 125.0 16.64 182.4 81.9 16.95 154.4 154.3 17.78 166.6 127.4 18.34 176.0 83.4 18.68
4950
85.0 166.1 165.9 16.18 175.2 150.6 16.69 181.9 113.2 17.00 160.3 160.3 17.83 169.0 153.4 18.39 175.5 115.4 18.73
90.0 171.6 171.6 16.23 177.0 167.3 16.74 180.8 137.9 17.05 165.5 165.5 17.88 170.8 170.5 18.45 174.4 140.5 18.79
75.0 157.5 141.5 16.22 174.1 107.2 16.73 187.2 47.3 17.04 151.9 144.3 17.93 168.0 109.2 18.49 180.6 48.2 18.84
80.0 164.3 162.5 16.27 177.3 134.2 16.78 187.3 87.9 17.09 158.5 158.5 17.98 171.0 136.8 18.55 180.7 89.6 18.89
5500
85.0 170.5 170.5 16.32 179.8 161.7 16.83 186.8 121.6 17.14 164.5 164.5 18.04 173.5 164.8 18.61 180.2 123.9 18.95
90.0 176.1 176.1 16.36 181.7 179.6 16.88 185.6 148.1 17.19 169.9 169.9 18.09 175.3 175.3 18.66 179.1 150.9 19.01
75.0 160.2 148.2 16.36 177.1 112.2 16.87 190.4 49.5 17.18 154.5 151.0 18.00 170.9 114.4 18.57 183.7 50.5 18.91
80.0 167.1 167.1 16.40 180.3 140.5 16.92 190.5 92.0 17.24 161.2 161.2 18.05 173.9 143.2 18.62 183.8 93.8 18.97
6050
85.0 173.4 173.4 16.45 182.9 169.3 16.97 190.0 127.3 17.29 167.3 167.3 18.11 176.4 172.5 18.68 183.3 129.7 19.03
90.0 179.1 179.1 16.50 184.9 184.9 17.02 188.8 155.0 17.34 172.8 172.8 18.16 178.3 178.3 18.73 182.1 158.0 19.08
75.0 162.2 152.9 16.49 179.4 115.8 17.01 192.8 51.1 17.33 156.5 155.8 18.14 173.0 118.0 18.71 186.0 52.1 19.06
80.0 169.3 169.3 16.54 182.6 145.0 17.07 192.9 94.9 17.38 163.3 163.3 18.19 176.2 147.7 18.77 186.1 96.8 19.11
6600
85.0 175.7 175.7 16.59 185.2 174.6 17.12 192.4 131.3 17.43 169.5 169.5 18.25 178.7 177.9 18.82 185.6 133.8 19.17
90.0 181.4 181.4 16.64 187.2 187.2 17.17 191.2 159.9 17.49 175.0 175.0 18.30 180.6 180.6 18.88 184.5 163.0 19.23

Outdoor DB(°F) 105 115 125


Indoor WB(°F) 61 67 73 61 67 73 61 67 73
CFM DB(°F) TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI
75.0 136.5 122.7 18.92 150.9 92.9 19.51 162.2 41.0 19.87 128.8 119.4 20.01 142.4 90.4 20.65 153.1 39.9 21.03 119.3 114.0 20.94 131.9 86.3 21.60 141.8 38.1 22.00
80.0 142.4 140.9 18.97 153.6 116.4 19.57 162.3 76.2 19.93 134.4 134.4 20.07 145.0 113.2 20.71 153.2 74.2 21.09 124.5 124.5 21.00 134.3 108.1 21.66 141.9 70.8 22.06
4400
85.0 147.8 147.8 19.03 155.8 140.1 19.63 161.9 105.4 19.99 139.5 139.5 20.13 147.1 136.4 20.77 152.7 102.6 21.16 129.2 129.2 21.06 136.2 130.2 21.73 141.5 97.9 22.13
90.0 152.6 152.6 19.09 157.5 155.7 19.69 160.9 128.4 20.05 144.0 144.0 20.20 148.6 148.6 20.83 151.8 124.9 21.22 133.4 133.4 21.13 137.7 137.7 21.79 140.6 119.2 22.20
75.0 142.8 130.9 19.05 157.9 99.1 19.65 169.8 43.8 20.02 134.8 127.4 20.15 149.0 96.5 20.79 160.2 42.6 21.17 124.9 121.6 21.08 138.0 92.1 21.74 148.4 40.6 22.14
80.0 149.0 149.0 19.11 160.8 124.2 19.71 169.9 81.3 20.08 140.6 140.6 20.21 151.7 120.8 20.85 160.3 79.1 21.24 130.3 130.3 21.14 140.5 115.3 21.81 148.5 75.5 22.21
4950
85.0 154.7 154.7 19.17 163.1 149.5 19.77 169.4 112.5 20.14 145.9 145.9 20.27 153.9 145.5 20.91 159.8 109.4 21.30 135.2 135.2 21.20 142.6 138.9 21.87 148.1 104.5 22.28
90.0 159.7 159.7 19.23 164.8 164.8 19.83 168.4 137.0 20.20 150.7 150.7 20.33 155.6 155.6 20.98 158.9 133.3 21.36 139.6 139.6 21.27 144.1 144.1 21.94 147.2 127.2 22.34
75.0 146.6 140.6 19.19 162.1 106.5 19.80 174.3 47.0 20.16 138.4 136.8 20.29 153.0 103.6 20.93 164.5 45.7 21.32 128.2 128.2 21.21 141.7 98.9 21.88 152.3 43.6 22.29
80.0 153.0 153.0 19.25 165.0 133.3 19.86 174.4 87.3 20.22 144.4 144.4 20.35 155.7 129.7 20.99 164.6 85.0 21.38 133.7 133.7 21.28 144.3 123.8 21.95 152.4 81.1 22.36
5500
85.0 158.8 158.8 19.31 167.4 160.6 19.92 173.9 120.8 20.29 149.8 149.8 20.41 158.0 156.3 21.06 164.1 117.5 21.45 138.8 138.8 21.34 146.3 146.3 22.01 152.0 112.2 22.42
90.0 164.0 164.0 19.36 169.2 169.2 19.98 172.8 147.1 20.35 154.7 154.7 20.47 159.7 159.7 21.12 163.1 143.1 21.51 143.3 143.3 21.40 147.9 147.9 22.08 151.1 136.6 22.49
75.0 149.1 147.2 19.33 164.9 111.5 19.94 177.3 49.2 20.31 140.7 140.7 20.43 155.6 108.5 21.07 167.3 47.9 21.46 130.4 130.4 21.35 144.1 103.5 22.02 155.0 45.7 22.43
80.0 155.6 155.6 19.39 167.8 139.6 20.00 177.4 91.4 20.37 146.8 146.8 20.49 158.4 135.8 21.14 167.4 89.0 21.53 136.0 136.0 21.42 146.7 129.6 22.09 155.0 84.9 22.50
6050
85.0 161.5 161.5 19.45 170.3 168.1 20.06 176.9 126.4 20.43 152.4 152.4 20.55 160.7 160.7 21.20 166.9 123.0 21.59 141.1 141.1 21.48 148.8 148.8 22.16 154.6 117.4 22.57
90.0 166.8 166.8 19.50 172.1 172.1 20.12 175.8 154.0 20.49 157.4 157.4 20.61 162.4 162.4 21.26 165.9 149.8 21.66 145.8 145.8 21.54 150.4 150.4 22.22 153.6 143.0 22.64
75.0 151.1 151.1 19.47 167.0 115.0 20.08 179.5 50.7 20.45 142.6 142.6 20.57 157.6 111.9 21.21 169.4 49.4 21.61 132.0 132.0 21.49 146.0 106.8 22.17 156.9 47.1 22.58
80.0 157.6 157.6 19.53 170.0 144.0 20.14 179.6 94.3 20.52 148.7 148.7 20.63 160.4 140.1 21.28 169.5 91.8 21.67 137.8 137.8 21.55 148.6 133.7 22.23 157.0 87.6 22.65
6600
85.0 163.6 163.6 19.58 172.5 172.5 20.20 179.1 130.4 20.58 154.3 154.3 20.69 162.8 162.8 21.34 169.0 126.9 21.74 143.0 143.0 21.62 150.7 150.7 22.30 156.6 121.1 22.71
90.0 168.9 168.9 19.64 174.3 174.3 20.26 178.0 158.8 20.64 159.4 159.4 20.75 164.5 164.5 21.41 168.0 154.6 21.80 147.6 147.6 21.68 152.4 152.4 22.37 155.6 147.5 22.78

Notes:
1. All capacities are gross, evaporator fan motor heat is not deducted. To obtain net cooling capacity, subtract evaporator fan motor heat.
2. DB = Dry Bulb Temperature (°F), WB = Wet Bulb Temperature (°F)
3. CFM = Cubic Feet per minute
4. TGC = Total Gross Cooling Capacity(Unit : MBH = kBtu/h)
5. SHC = Sensible Heat Capacity(Unit : MBH = kBtu/h)
6. PI = Power Input(kW), Sum of Compressor & Outdoor Fan Power Input

32 Single Package 50Hz, R410A


5CUK0-01B Performance data

Gross Cooling Capacity (MBH) AK-H2408C00, EK-H2408C00 (English)


Outdoor DB(°F) 85 95
Indoor WB(°F) 61 67 73 61 67 73
CFM DB(°F) TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI
75.0 202.2 168.3 18.66 223.6 127.5 19.25 240.4 56.3 19.60 195.1 171.5 20.58 215.7 129.9 21.23 231.9 57.3 21.62
80.0 211.0 193.3 18.71 227.6 159.6 19.30 240.5 104.5 19.66 203.6 197.0 20.64 219.6 162.7 21.29 232.0 106.5 21.69
6400
85.0 219.0 211.8 18.77 230.9 192.2 19.36 239.8 144.6 19.72 211.2 211.2 20.70 222.8 195.9 21.36 231.4 147.3 21.75
90.0 226.2 223.1 18.83 233.4 213.6 19.42 238.4 176.1 19.78 218.2 218.2 20.77 225.1 217.6 21.42 230.0 179.4 21.82
75.0 211.7 179.6 18.82 234.0 136.0 19.41 251.6 60.0 19.77 204.2 183.0 20.74 225.7 138.6 21.40 242.7 61.2 21.79
80.0 220.8 206.2 18.88 238.2 170.3 19.47 251.7 111.5 19.83 213.0 210.2 20.80 229.8 173.6 21.46 242.8 113.7 21.86
7200
85.0 229.2 226.0 18.93 241.6 205.1 19.53 251.0 154.3 19.89 221.1 221.1 20.87 233.1 209.0 21.53 242.1 157.2 21.92
90.0 236.7 236.7 18.99 244.2 227.9 19.59 249.5 187.9 19.95 228.3 228.3 20.93 235.6 232.2 21.59 240.7 191.4 21.99
75.0 217.3 192.8 18.98 240.2 146.0 19.58 258.3 64.5 19.94 209.6 196.5 20.98 231.7 148.8 21.64 249.1 65.7 22.05
80.0 226.7 221.4 19.04 244.5 182.9 19.64 258.4 119.8 20.00 218.7 218.7 21.05 235.9 186.4 21.71 249.3 122.1 22.11
8000
85.0 235.2 235.2 19.09 248.1 220.2 19.70 257.6 165.6 20.06 226.9 226.9 21.11 239.3 224.4 21.78 248.6 168.8 22.18
90.0 243.0 243.0 19.15 250.7 244.7 19.76 256.1 201.7 20.12 234.4 234.4 21.17 241.9 241.9 21.84 247.0 205.6 22.25
75.0 221.0 201.9 19.14 244.3 152.9 19.75 262.7 67.5 20.11 213.2 205.7 21.07 235.7 155.8 21.73 253.4 68.8 22.13
80.0 230.6 230.6 19.20 248.7 191.5 19.81 262.8 125.4 20.17 222.4 222.4 21.13 239.9 195.1 21.80 253.5 127.8 22.20
8800
85.0 239.3 239.3 19.26 252.3 230.6 19.86 262.0 173.4 20.23 230.8 230.8 21.19 243.4 235.0 21.86 252.8 176.7 22.27
90.0 247.1 247.1 19.31 255.0 255.0 19.92 260.5 211.2 20.29 238.4 238.4 21.26 246.0 246.0 21.93 251.3 215.2 22.33
75.0 223.8 208.2 19.30 247.5 157.7 19.91 266.0 69.6 20.28 215.9 212.2 21.23 238.7 160.7 21.90 256.7 70.9 22.30
80.0 233.5 233.5 19.36 251.9 197.5 19.97 266.2 129.3 20.34 225.3 225.3 21.29 243.0 201.3 21.96 256.8 131.8 22.37
9600
85.0 242.3 242.3 19.42 255.5 237.8 20.03 265.4 178.9 20.40 233.8 233.8 21.35 246.5 242.4 22.03 256.1 182.3 22.44
90.0 250.3 250.3 19.48 258.3 258.3 20.09 263.8 217.9 20.46 241.5 241.5 21.42 249.2 249.2 22.09 254.5 222.0 22.50

Outdoor DB(°F) 105 115 125


Indoor WB(°F) 61 67 73 61 67 73 61 67 73
CFM DB(°F) TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI
75.0 188.3 167.2 22.14 208.2 126.6 22.84 223.8 55.9 23.26 177.7 162.7 23.42 196.5 123.2 24.16 211.2 54.4 24.61 164.6 155.2 24.50 182.0 117.6 25.28 195.6 51.9 25.75
80.0 196.4 192.0 22.20 211.9 158.5 22.90 223.9 103.8 23.33 185.4 185.4 23.49 200.0 154.3 24.24 211.3 101.0 24.69 171.7 171.7 24.58 185.2 147.2 25.35 195.7 96.4 25.82
6400
85.0 203.9 203.9 22.27 215.0 190.9 22.97 223.3 143.6 23.40 192.4 192.4 23.56 202.9 185.8 24.31 210.7 139.7 24.76 178.2 178.2 24.65 187.9 177.3 25.43 195.2 133.4 25.90
90.0 210.6 210.6 22.34 217.3 212.1 23.04 221.9 174.9 23.47 198.7 198.7 23.64 205.1 205.1 24.38 209.4 170.2 24.83 184.0 184.0 24.73 189.9 189.9 25.51 194.0 162.4 25.98
75.0 197.1 178.3 22.30 217.9 135.1 23.00 234.2 59.6 23.43 186.0 173.6 23.59 205.6 131.4 24.33 221.0 58.0 24.78 172.2 165.6 24.67 190.4 125.4 25.44 204.7 55.4 25.92
80.0 205.6 204.8 22.37 221.8 169.1 23.07 234.3 110.8 23.50 194.0 194.0 23.66 209.3 164.6 24.40 221.1 107.8 24.86 179.7 179.7 24.74 193.9 157.1 25.52 204.8 102.9 25.99
7200
85.0 213.4 213.4 22.43 225.0 203.7 23.14 233.7 153.2 23.57 201.3 201.3 23.73 212.3 198.2 24.48 220.5 149.1 24.93 186.5 186.5 24.81 196.7 189.2 25.60 204.3 142.3 26.07
90.0 220.4 220.4 22.50 227.4 226.3 23.21 232.2 186.6 23.64 207.9 207.9 23.80 214.6 214.6 24.55 219.2 181.6 25.00 192.6 192.6 24.89 198.8 198.8 25.67 203.0 173.3 26.15
75.0 202.3 191.5 22.46 223.6 145.0 23.17 240.4 64.0 23.60 190.9 186.4 23.75 211.1 141.1 24.50 226.9 62.3 24.95 176.8 176.8 24.83 195.5 134.7 25.61 210.2 59.5 26.09
80.0 211.0 211.0 22.53 227.7 181.6 23.24 240.5 118.9 23.67 199.2 199.2 23.82 214.8 176.7 24.57 227.0 115.8 25.03 184.5 184.5 24.90 199.0 168.7 25.69 210.3 110.5 26.16
8000
85.0 219.0 219.0 22.60 231.0 218.7 23.31 239.9 164.5 23.74 206.7 206.7 23.89 217.9 212.9 24.64 226.4 160.1 25.10 191.4 191.4 24.98 201.9 201.9 25.76 209.7 152.8 26.24
90.0 226.2 226.2 22.66 233.4 233.4 23.38 238.4 200.3 23.81 213.5 213.5 23.96 220.3 220.3 24.72 225.0 195.0 25.18 197.7 197.7 25.05 204.0 204.0 25.84 208.4 186.1 26.32
75.0 205.7 200.5 22.62 227.5 151.8 23.34 244.5 67.0 23.77 194.2 194.2 23.91 214.7 147.8 24.66 230.8 65.2 25.12 179.8 179.8 24.99 198.8 141.0 25.78 213.8 62.2 26.25
80.0 214.7 214.7 22.69 231.6 190.1 23.41 244.7 124.5 23.84 202.6 202.6 23.98 218.5 185.0 24.74 230.9 121.2 25.20 187.6 187.6 25.06 202.4 176.6 25.85 213.9 115.7 26.33
8800
85.0 222.8 222.8 22.76 234.9 229.0 23.48 244.0 172.2 23.91 210.2 210.2 24.05 221.7 221.7 24.81 230.2 167.6 25.27 194.7 194.7 25.14 205.3 205.3 25.93 213.3 160.0 26.41
90.0 230.1 230.1 22.83 237.4 237.4 23.55 242.5 209.7 23.98 217.1 217.1 24.12 224.1 224.1 24.88 228.8 204.1 25.35 201.1 201.1 25.21 207.5 207.5 26.01 212.0 194.8 26.49
75.0 208.4 206.8 22.78 230.4 156.6 23.50 247.7 69.1 23.94 196.7 196.7 24.07 217.4 152.4 24.83 233.7 67.3 25.29 182.2 182.2 25.15 201.4 145.5 25.94 216.5 64.2 26.42
80.0 217.4 217.4 22.85 234.5 196.1 23.57 247.8 128.5 24.01 205.2 205.2 24.14 221.3 190.9 24.90 233.9 125.0 25.37 190.0 190.0 25.23 205.0 182.2 26.02 216.6 119.3 26.50
9600
85.0 225.6 225.6 22.92 237.9 236.2 23.64 247.1 177.7 24.08 212.9 212.9 24.21 224.5 224.5 24.98 233.2 172.9 25.44 197.2 197.2 25.30 208.0 208.0 26.10 216.0 165.0 26.58
90.0 233.0 233.0 22.99 240.5 240.5 23.71 245.6 216.4 24.15 219.9 219.9 24.29 226.9 226.9 25.05 231.8 210.6 25.52 203.7 203.7 25.38 210.2 210.2 26.18 214.7 200.9 26.66

Notes:
1. All capacities are gross, evaporator fan motor heat is not deducted. To obtain net cooling capacity, subtract evaporator fan motor heat.
2. DB = Dry Bulb Temperature (°F), WB = Wet Bulb Temperature (°F)
3. CFM = Cubic Feet per minute
4. TGC = Total Gross Cooling Capacity(Unit : MBH = kBtu/h)
5. SHC = Sensible Heat Capacity(Unit : MBH = kBtu/h)
6. PI = Power Input(kW), Sum of Compressor & Outdoor Fan Power Input

50Hz, R410A Single Package 33


Performance data 5CUK0-01B

Heating Capacity AK-H1208C00 (English)


Indoor Outdoor WB(°F)
14.0 23.0 32.0 35.6 39.2 42.8 50.0 59.0
AFR(CFM) DB(°F) TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI
60.8 71.1 9.2 83.8 10.0 97.0 10.9 101.8 11.2 106.7 11.6 112.7 11.8 122.0 12.4 134.7 13.3
64.4 68.9 9.5 81.2 10.4 93.9 11.3 98.6 11.6 103.3 12.0 109.2 12.2 118.2 12.8 130.4 13.7
2960 68.0 66.8 9.8 78.7 10.7 91.1 11.7 95.7 12.0 100.2 12.4 105.3 12.6 114.7 13.2 126.6 14.2
71.6 64.4 10.1 75.9 11.0 87.8 12.0 92.2 12.4 96.6 12.8 102.1 13.0 110.5 13.7 122.0 14.6
75.2 62.2 10.4 73.3 11.4 84.8 12.4 89.0 12.8 93.3 13.2 98.6 13.4 106.7 14.1 117.8 15.1
60.8 72.3 8.4 85.2 9.2 98.5 10.0 103.5 10.3 108.4 10.6 114.6 10.8 124.0 11.3 136.9 12.2
64.4 70.0 8.7 82.5 9.5 95.4 10.3 100.2 10.6 105.0 11.0 111.0 11.1 120.1 11.7 132.6 12.6
3700 68.0 67.9 9.0 80.0 9.8 92.6 10.7 97.2 11.0 101.9 11.3 107.0 11.5 116.5 12.1 128.6 13.0
71.6 65.5 9.2 77.1 10.1 89.2 11.0 93.7 11.3 98.2 11.7 103.8 11.9 112.3 12.5 124.0 13.4
75.2 63.2 9.5 74.5 10.4 86.2 11.3 90.5 11.7 94.8 12.0 100.2 12.2 108.5 12.9 119.7 13.8
60.8 73.8 8.0 86.9 8.7 100.5 9.5 105.6 9.8 110.6 10.1 116.9 10.3 126.5 10.8 139.7 11.6
64.4 71.4 8.3 84.1 9.0 97.3 9.8 102.2 10.2 107.1 10.5 113.2 10.6 122.5 11.2 135.2 12.0
4440 68.0 69.3 8.5 81.6 9.3 94.4 10.2 99.2 10.5 103.9 10.8 109.2 11.0 118.9 11.6 131.2 12.4
71.6 66.8 8.8 78.7 9.6 91.0 10.5 95.6 10.8 100.2 11.1 105.9 11.3 114.6 11.9 126.5 12.8
75.2 64.5 9.1 76.0 9.9 87.9 10.8 92.3 11.2 96.7 11.5 102.2 11.7 110.7 12.3 122.1 13.2

Heating Capacity AK-H1808C00/EK-H1808C00 (English)


Indoor Outdoor WB(°F)
14.0 23.0 32.0 35.6 39.2 42.8 50.0 59.0
AFR(CFM) DB(°F) TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI
61 119.7 13.6 141.0 14.8 163.1 16.1 171.3 16.6 179.5 17.1 189.6 17.4 205.3 18.3 226.6 19.6
64 115.9 14.0 136.5 15.3 157.9 16.7 165.9 17.2 173.8 17.7 183.6 18.0 198.8 19.0 219.4 20.3
4240 68 112.4 14.5 132.4 15.8 153.2 17.2 160.9 17.8 168.6 18.3 177.1 18.6 192.9 19.6 212.9 21.0
72 108.4 14.9 127.6 16.3 147.7 17.8 155.1 18.3 162.5 18.9 171.7 19.2 185.9 20.2 205.2 21.6
75 104.6 15.4 123.3 16.8 142.6 18.3 149.8 18.9 156.9 19.5 165.8 19.8 179.5 20.8 198.1 22.3
61 121.6 12.4 143.3 13.5 165.7 14.8 174.1 15.2 182.4 15.7 192.7 15.9 208.6 16.8 230.3 18.0
64 117.8 12.8 138.7 14.0 160.5 15.3 168.5 15.7 176.6 16.2 186.6 16.5 202.0 17.3 223.0 18.6
5300 68 114.2 13.2 134.6 14.5 155.7 15.8 163.5 16.2 171.4 16.7 180.0 17.0 196.0 17.9 216.3 19.2
72 110.1 13.7 129.7 14.9 150.1 16.3 157.6 16.8 165.2 17.3 174.5 17.6 188.9 18.5 208.5 19.8
75 106.3 14.1 125.3 15.4 144.9 16.8 152.2 17.3 159.5 17.8 168.5 18.1 182.4 19.1 201.4 20.4
61 124.1 11.8 146.1 12.9 169.1 14.1 177.6 14.5 186.1 15.0 196.6 15.2 212.8 16.0 234.9 17.1
64 120.1 12.2 141.5 13.4 163.7 14.6 172.0 15.0 180.2 15.5 190.4 15.7 206.1 16.6 227.5 17.7
6360 68 116.6 12.6 137.3 13.8 158.9 15.0 166.8 15.5 174.8 16.0 183.6 16.2 200.0 17.1 220.7 18.3
72 112.3 13.0 132.3 14.2 153.1 15.5 160.8 16.0 168.5 16.5 178.1 16.8 192.7 17.6 212.7 18.9
75 108.5 13.4 127.8 14.7 147.9 16.0 155.3 16.5 162.7 17.0 171.9 17.3 186.1 18.2 205.4 19.5

Correction Factor for Heating Capacity due to Frost on Heat Exchanger and Defrosting Operation.
The heating capacity in the "Heating Capacity Table" above indicates the actual heating capacity excluding the effect of frost on the heat
exchanger and the defrosting operation. Therefore, use the following factor to calculate the average heating capacity including capacity
reduction by frost on the exchanger and defrosting operation.

Correction Factor

Outdoor Air Temperature (°FWB, RH=85%) 14 21.2 24.8 28.4 32 35.6 39.2 42.8
Correction Factor 0.95 0.95 0.89 0.87 0.87 0.89 0.91 1.00

Notes:
1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Outdoor air : 85%RH. However, the condition on nominal capacity is 7°FDB/6°FWB.
3. TC=Total heating capacity(Unit : kW)
4. PI=Power Input(Comp.+indoor fan motor+outdoor fan motor) (kW)
5. AFR=Air flow rate(CFM).

34 Single Package 50Hz, R410A


5CUK0-01B Performance data

Heating Capacity AK-H2408C00/EK-H2408C00 (English)


Indoor Outdoor WB(°F)
14.0 23.0 32.0 35.6 39.2 42.8 50.0 59.0
AFR(CFM) DB(°F) TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI
61 166.2 22.1 195.8 24.2 226.5 26.4 237.9 27.2 249.3 28.0 263.4 28.5 285.1 30.0 314.7 32.1
64 160.9 22.9 189.6 25.0 219.3 27.3 230.4 28.1 241.4 28.9 255.0 29.4 276.1 31.0 304.7 33.2
6400 68 156.1 23.6 183.9 25.8 212.8 28.2 223.5 29.0 234.2 29.9 246.0 30.4 267.9 32.0 295.7 34.3
72 150.5 24.4 177.3 26.7 205.1 29.0 215.4 29.9 225.7 30.8 238.5 31.4 258.2 33.0 285.0 35.4
75 145.3 25.2 171.2 27.5 198.1 29.9 208.0 30.9 218.0 31.8 230.3 32.3 249.3 34.0 275.2 36.5
61 168.9 20.3 199.0 22.1 230.2 24.1 241.8 24.9 253.3 25.6 267.7 26.0 289.7 27.4 319.8 29.4
64 163.5 20.9 192.7 22.9 222.9 24.9 234.1 25.7 245.3 26.5 259.2 26.9 280.6 28.3 309.7 30.4
8000 68 158.7 21.6 186.9 23.6 216.3 25.7 227.1 26.5 238.0 27.3 250.0 27.8 272.2 29.3 300.5 31.3
72 152.9 22.3 180.2 24.4 208.5 26.6 218.9 27.4 229.4 28.2 242.4 28.7 262.4 30.2 289.6 32.3
75 147.7 23.0 174.0 25.1 201.3 27.4 211.4 28.2 221.5 29.1 234.1 29.6 253.4 31.1 279.7 33.3
61 172.3 19.3 203.0 21.1 234.8 23.0 246.6 23.7 258.4 24.4 273.1 24.8 295.6 26.2 326.3 28.0
64 166.8 20.0 196.6 21.8 227.4 23.8 238.8 24.5 250.3 25.3 264.4 25.7 286.2 27.0 315.9 29.0
9600 68 161.9 20.6 190.7 22.6 220.6 24.6 231.7 25.3 242.8 26.1 255.1 26.5 277.7 27.9 306.5 29.9
72 156.0 21.3 183.8 23.3 212.7 25.4 223.3 26.1 234.0 26.9 247.3 27.4 267.7 28.8 295.5 30.9
75 150.7 22.0 177.5 24.0 205.4 26.1 215.7 26.9 226.0 27.7 238.8 28.2 258.5 29.7 285.3 31.8

Correction Factor for Heating Capacity due to Frost on Heat Exchanger and Defrosting Operation.
The heating capacity in the "Heating Capacity Table" above indicates the actual heating capacity excluding the effect of frost on the heat
exchanger and the defrosting operation. Therefore, use the following factor to calculate the average heating capacity including capacity
reduction by frost on the exchanger and defrosting operation.

Correction Factor

Outdoor Air Temperature (°FWB, RH=85%) 14 21.2 24.8 28.4 32 35.6 39.2 42.8
Correction Factor 0.95 0.95 0.89 0.87 0.87 0.89 0.91 1.00

Notes:
1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Outdoor air : 85%RH. However, the condition on nominal capacity is 7°FDB/6°FWB.
3. TC=Total heating capacity(Unit : kW)
4. PI=Power Input(Comp.+indoor fan motor+outdoor fan motor) (kW)
5. AFR=Air flow rate(CFM).

50Hz, R410A Single Package 35


Performance data 5CUK0-01B

Evaporator Fan Performance Data AK-H1208C00 (SI)


External Static Pressure(mm Aq.)
l/s 2.5 5.1 7.5 10.2 12.7 15.2 17.8 20.3 22.9 25.4 27.9 30.5
RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW

1397 - - - - - - - - - - - - - - - - 756 0.91 777 0.95 799 0.99 822 1.04


1572 - - - - - - - - - - 746 1.02 763 1.06 782 1.10 802 1.14 823 1.19 845 1.24 868 1.29
1746 - - 747 1.17 757 1.19 770 1.22 785 1.25 801 1.29 818 1.34 837 1.38 856 1.44 877 1.50 900 1.56 923 1.63
1921 802 1.47 810 1.49 821 1.52 834 1.56 848 1.60 864 1.65 882 1.71 900 1.77 920 1.84 941 1.91 963 2.00 986 2.09
2096 875 1.89 883 1.92 894 1.96 907 2.01 921 2.07 937 2.13 954 2.21 973 2.29 993 2.38 1014 2.47 1036 2.58 1059 2.70

3Hp STANDARD MOTOR & DRIVE


External Static Pressure(mm Aq.)
l/s 5Hp OVERSIZED MOTOR & DRIVE
33.0 35.6 38.1 40.6 43.2 45.7 48.3 50.8
RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW

1397 846 1.09 871 1.14 897 1.20 924 1.26 951 1.33 980 1.40 1009 1.48 1039 1.57
1572 892 1.35 917 1.42 943 1.49 970 1.57 997 1.66 1026 1.75 1055 1.85 1085 1.96
1746 947 1.71 972 1.79 998 1.88 1024 1.98 1052 2.09 1081 2.21 1110 2.34 1140 2.47
1921 1010 2.18 1035 2.29 1061 2.41 1088 2.53 1116 2.67 1144 2.82 1173 2.99 1204 3.16
2096 1083 2.82 1108 2.96 1134 3.11 1161 3.28 1188 3.45 1217 3.65 1246 3.86 - -

• Fan motor heat (KW) = 1.22 x Fan Bkw


• Test condition : Voltage : 415V
Operating Mode : Fan operation mode with clean filter, dry coil without electric heater.
• Do not operate the unit at a cooling airflow that is less then 165 l/s / 0.35 KW.
• l/s of cooling capacity test : 1605 l/s at 10.16mmAq.

36 Single Package 50Hz, R410A


5CUK0-01B Performance data

Evaporator Fan Performance Data AK-H1208C00 (English)


External Static Pressure(inches of water.)
CFM 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2960 - - - - - - - - - - - - - - - - 756 1.22 777 1.27 799 1.33 822 1.39


3330 - - - - - - - - - - 746 1.37 763 1.42 782 1.47 802 1.53 823 1.59 845 1.66 868 1.73
3700 - - 747 1.56 757 1.59 770 1.63 785 1.68 801 1.73 818 1.79 837 1.86 856 1.93 877 2.01 900 2.09 923 2.19
4070 802 1.96 810 2.00 821 2.04 834 2.09 848 2.15 864 2.21 882 2.29 900 2.37 920 2.46 941 2.56 963 2.67 986 2.80
4440 875 2.54 883 2.58 894 2.63 907 2.70 921 2.77 937 2.86 954 2.96 973 3.06 993 3.18 1014 3.31 1036 3.46 1059 3.61

3Hp STANDARD MOTOR & DRIVE


External Static Pressure(inches of water.)
CFM 5Hp OVERSIZED MOTOR & DRIVE
1.3 1.4 1.5 1.6 1.7 1.8 1.9 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2960 846 1.45 871 1.53 897 1.60 924 1.69 951 1.78 980 1.88 1009 1.99 1039 2.11
3330 892 1.81 917 1.90 943 2.00 970 2.11 997 2.22 1026 2.34 1055 2.48 1085 2.63
3700 947 2.29 972 2.40 998 2.53 1024 2.66 1052 2.80 1081 2.96 1110 3.13 1140 3.32
4070 1010 2.93 1035 3.07 1061 3.23 1088 3.40 1116 3.58 1144 3.78 1173 4.00 1204 4.24
4440 1083 3.78 1108 3.97 1134 4.17 1161 4.39 1188 4.63 1217 4.89 1246 5.17 -

• Fan motor heater (MBH) = 3.1 x Fan BHP


• Test Condition : ➊ Voltage : 415V
❷ Operating Mode : Fan operation mode with clean filter, dry coil without electric heater.
• Do not operate the unit at a cooling airflow that is less then 350CFM/1.2MBH.
• CFM of cooling capacity test : 3400 CFM at 0.4 in Aq.

Fan speed Data AK-H1208C00(rpm)


6 Turn Open 5 Turn Open 4 Turn Open 3 Turn Open 2 Turn Open 1 Turn Open 0 Turn Open
Standard Motor &
Drive Fan Speed
742 793 843 894 945 996 1046

Oversize Motor &


Drive Fan Speed 889 950 1010 1071 1132 1193 1254

• Factory set at 3 turns open.

50Hz, R410A Single Package 37


Performance data 5CUK0-01B

Evaporator Fan Performance Data AK-H1808C00, EK-H1808C00 (SI)


External Static Pressure(mm Aq.)
l/s 2.54 5.08 7.62 10.16 12.7 15.24 17.78 20.32 22.86 25.4 27.94 30.48
RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW

2077 565 0.08 591 0.32 618 0.50 644 0.65 671 0.78 697 0.91 724 1.02 750 1.12 777 1.22 803 1.31 830 1.40 856 1.48
2336 597 0.37 624 0.61 650 0.79 677 0.94 703 1.07 730 1.20 756 1.31 783 1.41 809 1.51 836 1.60 862 1.69 889 1.77
2596 636 0.72 662 0.95 689 1.13 715 1.28 742 1.42 768 1.54 795 1.65 821 1.75 848 1.85 874 1.94 901 2.03 927 2.11
2856 680 1.12 707 1.35 733 1.53 760 1.68 786 1.82 813 1.94 839 2.05 866 2.15 892 2.25 919 2.34 945 2.43 972 2.51
3115 731 1.57 758 1.81 784 1.99 811 2.14 837 2.27 864 2.40 890 2.51 917 2.61 943 2.71 970 2.80 996 2.89 1023 2.97

4Hp STANDARD MOTOR & DRIVE


External Static Pressure(mm Aq.)
l/s 4Hp STANDARD MOTOR & HIGH STATIC DRIVE
33.02 35.56 38.1 40.64 43.18 45.72 48.26 50.8
RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW 5Hp OVERSIZED MOTOR & DRIVE

2077 883 1.56 909 1.64 936 1.71 962 1.78 989 1.85 1015 1.92 1042 1.99 1068 2.05
2336 915 1.85 942 1.93 968 2.00 995 2.07 1021 2.14 1048 2.21 1074 2.28 1101 2.34
2596 954 2.19 980 2.27 1007 2.35 1033 2.42 1060 2.49 1086 2.56 1112 2.62 1139 2.69
2856 998 2.59 1025 2.67 1051 2.75 1078 2.82 1104 2.89 1131 2.95 1157 3.02 1184 3.08
3115 1049 3.05 1076 3.13 1102 3.20 1129 3.27 1155 3.34 1182 3.41 1208 3.48 1235 3.54

• Fan motor heat (kW) = 1.22 x Fan BkW


• Test condition : Voltage : 415V
Operating Mode : Fan operation mode with clean filter, dry coil without electric heater.
• Do not operate the unit at a cooling airflow that is less then 165 l/s / 0.35 kW.
• l/s of cooling capacity test : 2596 l/s at 10.16mmAq.

38 Single Package 50Hz, R410A


5CUK0-01B Performance data

Evaporator Fan Performance Data AK-H1808C00, EK-H1808C00 (English)


External Static Pressure(in. Aq.)
CFM 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

4400 565 0.11 591 0.43 618 0.67 644 0.87 671 1.05 697 1.21 724 1.36 750 1.50 777 1.63 803 1.76 830 1.87 856 1.98
4950 597 0.50 624 0.82 650 1.06 677 1.26 703 1.44 730 1.60 756 1.75 783 1.89 809 2.02 836 2.15 862 2.26 889 2.37
5500 636 0.96 662 1.28 689 1.52 715 1.72 742 1.90 768 2.06 795 2.21 821 2.35 848 2.48 874 2.61 901 2.72 927 2.84
6050 680 1.50 707 1.81 733 2.05 760 2.26 786 2.44 813 2.60 839 2.75 866 2.89 892 3.02 919 3.14 945 3.26 972 3.37
6600 731 2.11 758 2.43 784 2.67 811 2.87 837 3.05 864 3.21 890 3.36 917 3.50 943 3.63 970 3.75 996 3.87 1023 3.98

4Hp STANDARD MOTOR & DRIVE


External Static Pressure(in. Aq.)
CFM 4Hp STANDARD MOTOR & HIGH STATIC DRIVE
1.3 1.4 1.5 1.6 1.7 1.8 1.9 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5Hp OVERSIZED MOTOR & DRIVE

4400 883 2.09 909 2.20 936 2.30 962 2.39 989 2.49 1015 2.58 1042 2.66 1068 2.75
4950 915 2.48 942 2.59 968 2.69 995 2.78 1021 2.88 1048 2.97 1074 3.05 1101 3.14
5500 954 2.94 980 3.05 1007 3.15 1033 3.24 1060 3.34 1086 3.43 1112 3.52 1139 3.60
6050 998 3.48 1025 3.58 1051 3.68 1078 3.78 1104 3.87 1131 3.96 1157 4.05 1184 4.14
6600 1049 4.09 1076 4.19 1102 4.29 1129 4.39 1155 4.48 1182 4.58 1208 4.66 1235 4.75

• Fan motor heat (MBH) = 3.1 x Fan BHP


• Test Condition : ➊ Voltage : 415V
❷ Operating Mode : Fan operation mode with clean filter, dry coil without electric heater.
• Do not operate the unit at a cooling airflow that is less then 350CFM/1.2MBH.
• CFM of cooling capacity test : 5500 CFM at 0.4 in Aq.

Fan speed Data AK-H1808C00, EK-H1808C00(rpm)

6 Turn open 5 Turn open 4 Turn open 3 Turn open 2 Turn open 1 Turn open 0 Turn open
Standard Motor & Drive Fan Speed 623 665 708 751 793 836 879
Standard Motor & High Static Drive 816 872 928 983 1039 1095 1151
Oversize Motor & Drive Fan Speed 907 969 1032 1094 1156 1218 1280
• Factory set at 3 turns open.

50Hz, R410A Single Package 39


Performance data 5CUK0-01B

Evaporator Fan Performance Data AK-H2408C00, EK-H2408C00 (SI)


External Static Pressure(mm Aq.)
l/s 2.54 5.08 7.62 10.16 12.7 15.24 17.78 20.32 22.86 25.4 27.94 30.48
RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW

3021 - - 569 1.35 590 1.46 611 1.56 633 1.67 654 1.77 676 1.88 697 1.98 719 2.09 740 2.20 762 2.30 783 2.41
3398 577 1.60 598 1.71 620 1.81 641 1.92 663 2.03 684 2.13 706 2.24 727 2.34 748 2.45 770 2.55 791 2.66 813 2.76
3776 614 2.05 635 2.15 657 2.26 678 2.37 700 2.47 721 2.58 743 2.68 764 2.79 786 2.89 807 3.00 828 3.10 850 3.21
4154 659 2.59 681 2.70 702 2.81 723 2.91 745 3.02 766 3.12 788 3.23 809 3.33 831 3.44 852 3.54 874 3.65 895 3.75
4531 713 3.25 735 3.35 756 3.46 778 3.56 799 3.67 821 3.77 842 3.88 864 3.99 885 4.09 906 4.20 928 4.30 944 4.41

5Hp STANDARD MOTOR & DRIVE


External Static Pressure(mm Aq.)
l/s 5Hp STANDARD MOTOR & HIGH STATIC DRIVE
33.02 35.56 38.1 40.64 43.18 45.72 48.26 50.8
RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW 7.5Hp OVERSIZED MOTOR & DRIVE

3021 805 2.51 826 2.62 848 2.72 869 2.83 891 2.93 912 3.04 933 3.15 955 3.25
3398 834 2.87 856 2.97 877 3.08 899 3.19 920 3.29 942 3.40 963 3.50 985 3.61
3776 871 3.32 893 3.42 914 3.53 936 3.63 957 3.74 979 3.84 1000 3.95 1022 4.05
4154 917 3.86 938 3.97 960 4.07 981 4.18 1002 4.28 1024 4.39 1045 4.49 1067 4.60
4531 971 4.51 992 4.62 1014 4.72 1035 4.83 1057 4.94 1078 5.04 1100 5.15 1121 5.25

• Fan motor heat (kW) = 1.22 x Fan BkW


• Test condition : Voltage : 415V
Operating Mode : Fan operation mode with clean filter, dry coil without electric heater.
• Do not operate the unit at a cooling airflow that is less then 165 l/s / 0.35 kW.
• l/s of cooling capacity test : 3776 l/s at 8.38mmAq.

40 Single Package 50Hz, R410A


5CUK0-01B Performance data

Evaporator Fan Performance Data AK-H2408C00, EK-H2408C00 (English)


External Static Pressure(in. Aq.)
CFM 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

6400 - - 569 1.81 590 1.95 611 2.10 633 2.24 654 2.38 676 2.52 697 2.66 719 2.80 740 2.94 762 3.09 783 3.23
7200 577 2.15 598 2.29 620 2.43 641 2.57 663 2.72 684 2.86 706 3.00 727 3.14 748 3.28 770 3.42 791 3.56 813 3.71
8000 614 2.75 635 2.89 657 3.03 678 3.17 700 3.31 721 3.46 743 3.60 764 3.74 786 3.88 807 4.02 828 4.16 850 4.30
8800 659 3.48 681 3.62 702 3.76 723 3.90 745 4.04 766 4.19 788 4.33 809 4.47 831 4.61 852 4.75 874 4.89 895 5.03
9600 713 4.35 735 4.50 756 4.64 778 4.78 799 4.92 821 5.06 842 5.20 864 5.35 885 5.49 906 5.63 928 5.77 944 5.91

5Hp STANDARD MOTOR & DRIVE


External Static Pressure(in. Aq.)
CFM 5Hp STANDARD MOTOR & HIGH STATIC DRIVE
1.3 1.4 1.5 1.6 1.7 1.8 1.9 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 7.5Hp OVERSIZED MOTOR & DRIVE

6400 805 3.37 826 3.51 848 3.65 869 3.79 891 3.93 912 '4.08 933 4.22 955 4.36
7200 834 3.85 856 3.99 877 4.13 899 4.27 920 4.41 942 '4.56 963 4.70 985 4.84
8000 871 4.45 893 4.59 914 4.73 936 4.87 957 5.01 979 '5.15 1000 5.29 1022 5.44
8800 917 5.18 938 5.32 960 5.46 981 5.60 1002 5.74 1024 '5.88 1045 6.03 1067 6.17
9600 971 6.05 992 6.19 1014 6.34 1035 6.48 1057 6.62 1078 '6.76 1100 6.90 1121 7.04

• Fan motor heat (MBH) = 3.1 x Fan BHP


• Test Condition : ➊ Voltage : 415V
❷ Operating Mode : Fan operation mode with clean filter, dry coil without electric heater.
• Do not operate the unit at a cooling airflow that is less then 350CFM/1.2MBH.
• CFM of cooling capacity test : 8000 CFM at 0.33 in Aq.

Fan speed Data AK-H2408C00, EK-H2408C00(rpm)


6 Turn open 5 Turn open 4 Turn open 3 Turn open 2 Turn open 1 Turn open 0 Turn open
Standard Motor & Drive Fan Speed 550 586 623 659 696 733 769
Standard Motor & High Static Drive 739 788 837 886 935 984 1034
Oversize Motor & Drive Fan Speed 893 953 1012 1072 1131 1191 1250

• Factory set at 3 turns open.

50Hz, R410A Single Package 41


Performance data 5CUK0-01B

Accessory Static Pressure Drops

Electric Heater
Standard Filter
Unit Model No. CFM l/s 9kW 18kW 36kW
in Aq mm Aq in. Aq. mm Aq. in. Aq. mm Aq. in. Aq. mm Aq.
2960 1397 0.06 1.52 0.01 0.25 0.07 1.78 - -
AK-H1208C00 3700 1746 0.10 2.54 0.01 0.25 0.10 2.54 - -
4440 2095 0.14 3.56 0.02 0.51 0.15 3.81 - -
4400 2077 0.06 1.52 - - 0.04 1.02 0.04 1.02
AK-H1808C00
5500 2596 0.09 2.29 - - 0.06 1.52 0.07 1.78
EK-H1808C00
6600 3115 0.13 3.3 - - 0.1 2.54 0.11 2.79
6400 3021 0.07 1.78 - - - - 0.07 1.78
AK-H2408C00
8000 3776 0.10 2.54 - - - - 0.13 3.30
EK-H2408C00
9600 4531 0.14 3.56 - - - - 0.17 4.32

Electric Heating Capacity


Total Stage 1 Stage 2
MODEL No. of Stages
Input(kW) Output(MBH) Input(kW) Output(MBH) Input(kW) Output(MBH)
9 30.72 1 9 30.72 - -
AK-H1208C00
18 61.43 1 18 61.43 - -
AK-H1808C00 18 61.43 1 18 61.43 - -
EK-H1808C00 36 122.86 2 18 61.43 18 61.43
AK-H2408C00
36 122.86 2 18 61.43 18 61.43
EK-H2408C00

Note: 1. The output ratings shown above is at 415V. < Correction Coefficient>
For other voltage, Output = Capacity Multiplier x Rated Output
2. E/heater Voltage range is 380~415V. Voltage Capacity Multiplier
380 0.84

400 0.92

415 1.0

Air Temperature Rise Across Electric Heater(°F)

AK-H1208C00 AK-H1808C00, EK-H1808C00 AK-H2408C00, EK-H2408C00


Capacity Stage
(3,700CFM) (5,500CFM) (8,000CFM)
9kW 1 7.69 - -
18kW 1 15.4 10.3 -
36kW 2 - 20.7 14.2

(kW x 3413)
• Temp. Rise across Electric Heater =
(1.08 x CFM)
• If you want to take temp rise at different airflow use above equation.

42 Single Package 50Hz, R410A


5CUK0-01B Performance data

11. Electrical data


Electrical Data Unit wiring
Unit Operating Standard indoor fan motor Oversized indoor fan motor
Tons MODEL
Voltage Range *M.C.A. *M.F.S. *M.C.B. *M.C.A. *M.F.S. *M.C.B.
10 AK-H1208C00 342~456 38.2 40.0 40.0 - - -
AK-H1808C00
15 342~456 57.2 80.0 80.0 57.8 80.0 80.0
EK-H1808C00
AK-H2408C00
20 342~456 74.4 100.0 100.0 78.5 100.0 100.0
EK-H2408C00
Note: *M.C.A.: Minimum Circuit Ampacity
*M.F.S. : Maximum Fuse Size
*M.C.B.: Maximum Circuit Breaker

Electrical Data Unit wiring with electric heater + heat pump cycle
Electric Unit Operating Standard indoor fan motor Oversized indoor fan motor
MODEL
Heater (kW) Voltage Range *M.C.A. *M.F.S. *M.C.B. *M.C.A. *M.F.S. *M.C.B.
9 55.3 60.0 60.0 - - -
AK-H1208C00
18 72.4 70.0 70.0 - - -
3Ø,
AK-H1808C00 18 91.4 110.0 110.0 92.0 110.0 110.0
380-415V,
EK-H1808C00 36 125.5 140.0 140.0 126.1 140.0 140.0
50Hz
AK-H2408C00
36 142.8 150.0 150.0 146.9 150.0 150.0
EK-H2408C00

Note: Heater kW ratings are at 380/415 V unit.

Electrical Characteristics --- Evaporator Fan Motor --- 50 Hz


Standard evaporator fan motor Oversized evaporator fan motor
MODEL
No Volts Phase HP FLA LRA No Volts Phase HP FLA LRA
AK-H1208C00 3.0 5.0 31.0 - - - - - -
AK-H1808C00
4.0 6.5 26.0 1 380~415 3.0 5.0 7.1 42.0
EK-H1808C00 1 380~415 3
AK-H2408C00
5.0 7.1 42.0 1 380~415 3.0 7.5 11.2 63.0
EK-H2408C00
Note: • FLA-Full Load Amps.
• LRA-Locked Rotor Amps.

Electrical Characteristics --- Compressor and Outdoor Fan Motor --- 50 Hz


Compressor Outdoor Fan Motor
MODEL
No Volts Phase HP FLA LRA No Volts Phase HP FLA LRA
AK-H1208C00 2 7.0 10.4 74.0 1 1 0.50 3.40 10.5
AK-H1808C00
3 5.0 12.2 75.0 2 1 0.50 3.40 10.80
EK-H1808C00 380~415 3 220~240
AK-H2408C00
4 5.0 12.2 75.0 4 1 0.40 2.30 5.20
EK-H2408C00
Note: • FLA-Full Load Amps.
• LRA-Locked Rotor Amps.

50Hz, R410A Single Package 43


Performance data 5CUK0-01B

12. Piping diagrams


Model No.: AK-H1208C00

By Pass
Outdoor 1.6(I.D)*1EA Indoor
Coil Pressure Pressure Coil
3.36(I.D)*8EA Check Port Ceck Port
Th3 Th1 Capillary Tube
1.2(I.D)*9EA

High Pressure
Switch

Accum
Cooling Heating

COMP
A
Low Pressure
Switch
Th5
Capillary Tube Check
2.0(I.D)*3EA Valve
Capillary Tube
3.36(I.D)*8EA 1.2(I.D)*9EA

By Pass
1.6(I.D)*1EA
Pressure Pressure
Ceck Port Ceck Port
Th4 Th2

Capillary Tube Check High Pressure


2.0(I.D)*5EA Valve Switch Accum
Cooling Heating

COMP
B

Low Pressure
Switch

Notes
Th : Thermistor
Th1 : Thermistor Eva. For A Cycle
Th2 : Thermistor Eva. For B Cycle
Th3 : Thermistor Cond. For A Cycle
Th4 : Thermistor Cond. For B Cycle
Th5 : Outdoor Temp. Thermistor

44 Single Package 50Hz, R410A


5CUK0-01B Performance data

Model No.: AK-H1808C00, EK-H1808C00


BY PASS
OUTDOOR INDOOR
2.0(I.D)*2EA
COIL PRESSURE PRESSURE COIL
3.36(I.D)*20EA CHECK PORT CHECK PORT
CAPILLARY TUBE
1.6(I.D)*14EA

HI PRESSURE
SWITCH

ACCUM
Cooling Heating

CHECK CHECK
LOW PRESSURE
VALVE VALVE
SWITCH

COMP COMP
A-1 A-2

CAPILLARY TUBE CHECK


VALVE CAPILLARY TUBE
2.0(I.D)*4EA 3.36(I.D)*10EA OIL TUBE 1.6(I.D)*7EA

BY PASS
1.8(I.D)*1EA
PRESSURE PRESSURE
CHECK PORT CHECK PORT

HI PRESSURE
SWITCH

CAPILLARY TUBE CHECK


VALVE
2.0(I.D)*3EA ACCUM
Cooling Heating

COMP LOW PRESSURE


B SWITCH

50Hz, R410A Single Package 45


Performance data 5CUK0-01B

Model No.: AK-H2408C00, EK-H2408C00

OUTDOOR PRESSURE INDOOR


PRESSURE
COIL CHECK PORT COIL
CHECK PORT

HI PRESSURE
SWITCH

ACCUM
Cooling Heating
CHECK CHECK
VALVE VALVE
CAPILLARY TUBE

LOW PRESSURE
COMP COMP
A-1 A-2 SWITCH
CHECK
VALVE

PRESSURE PRESSURE
CHECK PORT CHECK PORT

HI PRESSURE
CAPILLARY TUBE

SWITCH

ACCUM
CHECK Cooling Heating
VALVE CHECK CHECK
VALVE VALVE LOW PRESSURE
COMP COMP SWITCH
B-1 B-2

CAPILLARY TUBE

CAPILLARY TUBE

46 Single Package 50Hz, R410A


5CUK0-01B Performance data

13. Operation range


Cooling Heating
48
Operative
43
Outdoor Unit [°C DB]

Continuous
operation

24

Outdoor Unit [°C DB]

Warming up
Operation
21 Continuous
Operative operation
-5

1
Operative
-5

18 32 10 27
Indoor Unit [°C DB] Indoor Unit [°C DB]

• Although low ambient kit is installed, in case outdoor Operative: Intermittent operation according to operation
temperature goes below 0°C, the cooling capacity can be condition (indoor/outdoor temperature, humidity,
dropped and operation characteristics can be slightly and load) the heating capacity can be drop
different.

50Hz, R410A Single Package 47


Controller 5CUK0-01B

14. Controller
1) LCD wired remote controller

AUTO SWING OPERATION SET TEMP SUB FUNCTION Heat Pump Model
Room Temp
HI
MED
AUTO Heater Preheat
JET Defrost Humidify 1
LO Filter Out door
Time ZONE 1 2 3 4
Timer Operation unit Program set
On Off
Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23

3 2
Signal receptor
98 Cooling Model
4
10
Timer Cancel 5
11
12 Program Week Holiday
6
13
14 SET/CLR 7
15
Hour Min RESET 8
16 17

1 Operation display 8 Room Temperature Checking Button


Displays the operation conditions. Used to check the room temperature.
2 On/Off Button 9 Heater Button
Operation starts when this button is pressed, and
stops when the button is pressed again. 10 Timer Cancel Button
Used to cancel the timer.
3 Set Temperature Button
Used to set the temperature when the desired tem- 11 Timer Set Button
perature is obtained. Used to set the timer when the desired time is
obtained.
4 Fan Operation Button
Used to circulate room air without cooling or heat- 12 Week Button
ing. Used to set a day of the week.
5 Fan Auto Button 13 Program Button
Used to set the weekly timer.
• Fan AUTO operation mode
Used to turn the indoor fan motor to on/auto oper- 14 Holiday Button
ation mode by alternate pressing. Used to set a holiday of the week.
• Fan ON operation mode 15 Time Set Button
6 Operation Mode Selection Button Used to set the time of the day and change the time
Used to select the operation mode. in the weekly timer Function.
• Cooling Operation Mode 16 Set and Clear Button
• Soft Dry Operation Mode Used to set and clear the weekly timer.
• Heating Operation Mode(except cooling model) 17 Reset Button
7 Humidify Button Used to set the current time and clear the setting time.

48 Single Package 50Hz, R410A


5CUK0-01B Controller

2) Wireless remote controller(Accessory)

1
1 Signal Transmitter
2 • Transmits the signals to the air conditioner
10
2 Operation Display of the Remote Control
3 • LED displays operation status(on or off) of
11 air conditioner.

3 Humidify Button
7 4
4 Cooling ON Button
8 6
5 Temperature Setting Buttons
5
6 Power ON/OFF Button
• Operation will start when this button is
pressed, and stop when the button is
pressed again.

7 Timer Set Button


• Subsequent pressing of the button,
changes the set time in the incremental
(Cooling Model) order from 1 hr to 7 hr. If you select "0:000"
the off timer function will be considered.
1
8 Indoor Fan Operation Button
2 9 Heating Button (Heat Pump Model Only)
10
10 Electric Heater ON/OFF Button(Optional)
3
11 9 11 Soft Dry Operation Button

7 4
8 6
5

(Heat pump Model)

50Hz, R410A Single Package 49


Installation guide at the seaside 5CUK0-01B

15. Installation guide at the seaside

CAUTION
1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion
on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunc-
tion or inefficient performance.
3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it
needs additional anticorrosion treatment on the heat exchanger.

Selecting the location(Outdoor Unit)


1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided.
Install the outdoor unit on the opposite side of the sea wind direction.

Sea wind Sea wind

2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.

Windbreak • It should be strong enough like concrete to prevent


the sea wind from the sea.
• The height and width should be more than 150% of
the outdoor unit.
Sea wind • It should be keep more than 70 cm of space
between outdoor unit and the windbreak for easy
air flow.

3) Select a well-drained place.

1. If you can’t meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment.
2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water

50 Single Package 50Hz, R410A


5CUK0-01B Mechanical specifications

16. Mechanical specifications


General
Factory assembled fully self contained, single piece design to operate up to 129°F and down to 14°F in cooling
with optional electric heater.
Unit shall be rated in accordance with ARI standard testing procedure, fully charged with R410A. Units shall
fully factory test before shipment.

Casing
Unit casing shall be constructed of having gauge zinc coated, galvanized steel. The cabinet shall be exterior
painted and weather resistance. The cabinet shall be design to allow maintenance from one side only.
Unit shall have a water and air tight service panels with minimum number of screws per panel for easy servic-
ing.

Filters
Washable filters shall be standard on all units (Except 6.25 Ton unit). Filter rack can be converted to one inch(bellow
71/2 ton).
Two inch filters shall be installed on all units above 7.5ton.

Compressors
LG single packaged units shall be direct drive hermetic compressor, reciprocating type with internal built in
lubricating mechanism for all moving parts. Motor shall be suction gas cooled with internal temperature and
over current sensitive motor over load, for maximum protection. Factory rubber shock mounted and internally
spring isolation for sound and vibration control.

Refrigerant Circuits
Each refrigerant circuit shall have independent fixed capillary tube devices and service pressure ports, low
pressure switches and refrigerant line filter factory-installed as standard.

Evaporator and Condenser Coils


Shall be aluminum plate fins, mechanically bonded to copper tubes.
Coil shall be factory test for leakage and pressure.

Outdoor Fans
Statically and dynamically, direct drive outdoor fan in vertical discharge position. Permanently lubricated fan
motors with built in thermal overload protection.

Indoor Fan
Direct drive indoor motor for 6.25 tons with forward curve centrifugal fans. Belt drive with adjustable motor pul-
ley for all unit above 6.25 ton. All motors shall be thermally overload protected. For higher static pressure
requirement over size motor is available.

Controls
All units shall be supplied with centralized micom-processor. Heating and cooling shall be control by micom
through input signals from indoor and outdoor temperature sensors. Micom shall provide anti-short cycle timer
and time delay between compressor.

50Hz, R410A Single Package 51


Appendix 5CUK0-01B

17. Appendix
Unit Conversion

Cooling Capacity

RT Btu/h kcal/h W

1 12,000 3024.2 3516.7

Volume

CMM CFM l/s

1 35.3 16.67

Length

m cm mm inch

1 100 1000 39.37

Power

HP W kW

1 746 0.746

Temperature

C = 5 (F - 32)
9
Where,
C is Temperature in °C
F is Temperature in °F

52 Single Package 50Hz, R410A


P/No.: 3828A20576W

Head Office:
20 Yoidodong, Youngdungpogu,
Yoido P.O.Box 355 Seoul 150-721,
Korea Phone:82-2-3777-7985
Changwon Office:
76 Seongsandong, Changwon,
Gyeongnam 641-713, Korea
Phone: 82-55-269-3506
http://www.lge.com/airconditioner

The air conditioners manufactured by LG


All rights reserved have received ISO9001 certificate for
Printed in Korea December/2006 quality assurance and ISO14001
The specifications, designs, and File No. : A8974 Certificate No. : certificate for environmental
information in this brochure are subject to Volume:1 E00626/1 management system.
change without notice.

You might also like