Single Package: Engineering Product Data
Single Package: Engineering Product Data
Single Package: Engineering Product Data
R-410A
Single Package
(50Hz/R410A)
5CUK0-01B
Replaces 5CUK0-01A
Introduction 5CUK0-01B
Introduction
Preface
Thank you very much for your special patronage of LG air conditioners.
LG’s "Roof Top or Single Package" is an ideal choice when we talk about high load applications.
As the name Roof Top signifies, this unit is generally installed on the top of the roof. Also the Single Package signifies that
both condenser and evaporator are enclosed in a single body(same as window type). The unit is used along with ducts and
has flexible air flow as per installation conditions. The air flow can be horizontal or vertically downward which offers wider
flexibility in the field applications.
Apart from common features, this unit offers some unique features like High & Low static driver kit, Oversize motor option,
Manual Hood for fresh air intake, Compact design etc.
This unit is ideal for Single story and Double story houses as they offer high static pressure.
With its easy installation and simple control system, this product is suitable for Factories, Shopping malls, Multiplex, Hotels
etc.
A lot of information regarding the design & installation of this system is provided in this edition. This new product series con-
tains data on the same pattern.
Please utilize all the information for conducting your business efficiently.
Make sure the specification, dimensions and other technical data are same as provided in enginering data book before you
start the project.
LG Electronics Inc.
Air Conditioning Division
Publication history
Pub. No. Frequency Category Type Product name Refrigerant Models Notes Published in
AK-H1208C00
AK-H1808C00
5CUK0-01A 50Hz CAC Single Single Package R410A AK-H2408C00 New edition of EPDB July.2006
EK-H1808C00
EK-H2408C00
5CUK0-01B 50Hz CAC Single Single Package R410A AK-H1208C00 Model Update Dec.2006
1. Model line up
1.1 Heat Pump
Nominal Capacity Model Power Supply
Ton Refrigerant Model Name Ø, V, Hz
10 AK-H1208C00
AK-H1808C00
15
R410A EK-H1808C00 3Ø, 380-415V, 50Hz
AK-H2408C00
20
EK-H2408C00
2. Nomenclature
EK-H1808C00
Development Sequence
SEER Grade
Type SEER 10 11 12 13 14 15
MICOM Control 0 1 2 3 4 5
3~5RT
Mechanical Cont. A B C D E F
6~6.5RT There is no SEER regulation for these units
so "0" is allotted to these units.
Type of Flow
C: Convertible
Heating Capacity
Model Type
H : Heat Pump
■ Reliablity
• Time delay relay is standard component
• Low pressure Switch is standard component
• LG Scroll compressor with internal high-pressure & over-
current protector
• Strainer is adopted
• Durable painting steel cabinet
• Factory charged refrigerant
• Direct-drive multi-speed PSC blower Motor.
• Direct-drive PSC condenser fan Motor
Typical Installation
Roof Jack Installation
Slab on Ground Installation
1 2 ........ 16
Group Control :
- It enables to control max of 16 units with the help of
one wired remote controller. All the units will follow
same setting of temperature & other sub functions.
........
CHILD LOCK
-Display
Defrost / Deicing :
- In the heating mode, it prevents the ice formation on the outdoor unit. The heating cycle is reversed to the
cooling cycle to defrost the evaporator pipe of the outdoor unit. While defrost cycle, the compressor is on and
indoor fan, outdoor fan and 4-way valve are off.
Weekly Program :
- It provides on / off schedule of operation for a period of one
week.
Electric Heater:(Accessory)
- Electric Heater can be used to provide heat in addition to cycle
heat. It also provides quick heating. It can also work as a stand
alone heater with only fan operation.
Conventional
After 15 days
starting to
corrode
- All single package air conditioners has soft start function i.e.
Indoor fan, outdoor fan & compressor start in sequence to pre-
vent overcurrent during starting.
4. List of functions
AK-H1808C00 AK-H2408C00
Category Function AK-H1208C00 EK-H1808C00 EK-H2408C00
Air supply outlet 1 1 1
Airflow direction control(left & right) - - -
Airflow direction control(up & down) - - -
Auto swing(left & right) - - -
Air flow Auto swing(up & down) - - -
Airflow steps(fan/cool/heat) - - -
Chaos swing - - -
Chaos wind(auto wind) - - -
Jet cool(Power wind) - - -
Swirl wind - - -
Deodorizing filter - - -
Air purifying Plasma air purifier - - -
Prefilter(washable / anti-fungus) O O O
Drain pump - - -
E.S.P. control - - -
Installation
Electric heater(operation) Accessory Accessory Accessory
High ceiling operation - - -
Hot start - - -
Self diagnosis O O O
Soft dry operation O O O
Defrost / Deicing O O O
Reliability High pressure switch O O O
Low pressure switch O O O
Phase protection O O O
Restart delay (3-minutes) O O O
Soft start - - -
Test function O O O
Auto changeover - - -
Auto cleaning - - -
Auto operation(artificial intelligence) - - -
Auto restart operation O O O
Child lock O O O
Convenience Forced operation - - -
Group control O O O
Sleep mode - - -
Timer(on/off) O O O
Timer(weekly) O O O
Two thermistor control Accessory Accessory Accessory
Standard wired remote controller O O O
Deluxe wired remote controller - - -
Individual Simple wired remote controller - - -
control Wired remote controller(for hotel use) - - -
Wireless remote controller(simple) Accessory(AUWRHS) Accessory(AUWRHS) Accessory(AUWRHS)
Wireless LCD remote control - - -
General central controller (Non LGAP) Accessory Accessory Accessory
CAC network Dry contact - - -
function Network Soluation(LGAP) - - -
PDI(power distribution indicator) - - -
Zone control - - -
Special CTIE Accessory Accessory Accessory
function kit Electro thermostat - - -
Low ambient operation - - -
Others - - - -
Note:
O : Applied, X : Not applied, – : No relation
* Option : Model name & price are different according to options, and assembled in factory with main unit.
* Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.
5. Specifications
Nominal Capacity (Ton) 10 15 20
Models AK-H1208C00 AK-H1808C00 AK-H2408C00
EK-H1808C00 EK-H2408C00
Capacity Gross Cooling Capacity kW 34.6 50.1 69.1
Btu/h 118,000 171,000 235,900
Net Cooling Capacity kW 32.8 48.6 65.9
Btu/h 112,000 166,000 225,000
Net Heating Capacity kW 32.8 52.8 73.3
Btu/h 112,000 180,000 250,000
Electrical Data Power Supply Ø / V / Hz 3/380~415/50 3/380~415/50 3/380~415/50
M.C.A Cooling A 38.2 57.2 74.4
(with Standard Motor) Heating A 38.2 57.2 74.4
Power Input Cooling W 14,400 20,000 26,500
Heating W 11,600 17,000 27,800
Performance Air Circulation(Nominal) CFM 3,700 5,500 8,000
EER Btu/h.W 7.78 8.30 8.50
SEER Btu/h.W - - -
COP W/W 2.83 3.10 2.64
Sound Rating bell 9.20 9.20 9.20
Indoor Coil Type High efficiency High efficiency High efficiency
Tube Size(O.D) mm(inch) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Rows / Column / FPI 3R / 44C / 16FPI 3R / 44C / 16FPI 3R / 52C / 16FPI
Length mm(inch) 900(35 7/16) 1,000(39 6/16) 1,000(39 6/16)
Face Area m2(sq.ft) 1.01(10.8) 1.12(12.1) 1.32(14.2)
Indoor Fan Type * No. Used Centrifugal Blower Centrifugal Blower Centrifugal Blower
Diameter mm(inch) 380(14 31/32) 380(15) 460(18)
Width mm(inch) 280(11 1/32) 380(15) 460(18)
Drive Type / Motor Step Belt / 1 Belt / 1 Belt / 1
No. Motors 1 1 1
Motor Output(Standard / Oversized) Hp 3.0 / 5.0 4.0 / 5.0 5.0 / 7.5
Motor RPM(Standard / Oversized) 1,400 / 1,430 1,380~1,400 / 1,400~1,430 2,892~2,900 / 2,870~2,900
No. of Outdoor Units - - -
Compressor Type * Quantity SCROLL * 2(Non Tropical) SCROLL * 3(Non Tropical) SCROLL * 4(Non Tropical)
Model ARA073YAA AR073YAB AR073YAB
Maker LG LG LG
Capacity Btu/h 62,000 61,000 61,000
Motor Type Three Phase Three Phase Three Phase
Motor Input W 6,020 6,289 6,289
Oil Type FVC68D(PVE) FVC68D(PVE) FVC68D(PVE)
Oil Charge cc 1,800±10 2,325±10 2,325±10
Outdoor Coil Type High efficiency High efficiency Corrugate Corrugate Corrugate Corrugate
Tube Size(O.D) mm(inch) 9.52(3/8) 9.52(3/8) 7(9/32) 7(9/32) 7(9/32) 7(9/32)
Rows / Column / FPI 2R / 32C / 17FPI 2R / 32C / 17FPI 3R / 52C / 17FPI 2R / 42C / 17FPI 3R / 46C / 17FPI 3R / 46C / 17FPI
Length mm(inch) 1,100(43 5/16) 1,100(43 5/16) 1,300(51 3/16) 1,300(51 3/16) 2,000(78 12/16) 2,000(78 12/16)
Face Area m2(sq.ft) 0.89(9.58) 0.89(9.58) 1.42(15.3) 1.15(12.3) 1.93(20.8) 1.93(20.8)
Outdoor Fan Type * No. Used Propeller * 2 Propeller * 2 Propeller * 4
Diameter inch 23.6 23.6 22
Drive Type Direct Direct Direct
Air Circulation CFM 3,125 3,125 3,125
No. Motor / Motor Output(Hp) Hp 2EA / 0.5 2EA / 0.5 4EA / 0.4
Motor RPM 910 910 950
Service Valve Liquid mm(inch) - - -
Gas mm(inch) - - -
Connecting Tube Liquid mm(inch) - - -
Gas mm(inch) - - -
Length(Standard) mm(inch) - - -
Dehumidification Rate l/h 8.10 13.3 20.0
Drain Connection Size(inch) 1 1 1
Refrigerant Refrigerant Charge kg 4.1/Circuit 4.65 2.9 5.6/Circuit
lbs 9.04/Circuit 10.25 6.39 12.35/Circuit
Type R-410A R-410A R-410A R-410A
Refrigerant Control Capillary Tube Capillary Tube Capillary Tube Capillary Tube
Dimensions Indoor Unit (W * H * D) mm - - -
inch - - -
Outdoor Unit or S/Package mm 2170 * 1244 * 1460 2,230 * 1,244 * 1,540 2,898 * 1,250 * 2,200
(W * H * D) inch 85 7/16 * 49 * 57 8/16 87 13/16 * 49 * 60 10/16 114 2/16 * 49 3/16 * 86 10/16
Net Weight Indoor Unit kg(lbs) - - -
Outdoor Unit or S/Package kg(lbs) 450(992) 550(1,212) 900(1,984)
Fliter Size * No. Used 925*418 * 1EA 1045*980 * 1EA 510*625 * 2ea
Filter Rack Thickness inch 1, 2 1, 2 1, 2
Notes:
1. Capacities are based on the following conditions: 2. Nominal CFM : Fan operation mode with clean filter, dry coil.
Cooling: - Indoor Temperature 27.0°C(80.6°F) DB/19.0°C(66.2°F) WB 3. The specification may be subject to change without notic for purpose of improvement.
- Outdoor Temperature 35°C(95°F) DB/24°C(75.2°F) WB
Heating: - Indoor Temperature 20.0°C(68°F) DB/15.0°C(59°F) WB
- Outdoor Temperature 7.0°C(44.6°F) DB/6.0°C(42.8°F) WB
- Level Difference of Zero
6. Dimensions
Model No.: AK-H1208C00
UNIT Dimensions (Figure B)
Unit: inch(mm)
UNITS 10RT
H 48 5/16 (1227)
I 54 13/16 (1392)
CLEARANCE 34"
J 85 7/16 (2170) CLEARANCE 16"
K 45 1/16 (1144)
103
Drain Connection Hole 1"
L 7 2/16 (181)
1021
M 4 (100) Figure A
K
M
L
J
I
CLEARANCE 34"
CLEARANCE 46"
Figure B
HORIZONTAL FLOW APPLICATION (Figure C)
Unit: inch(mm)
CLEARANCE 34"
UNITS 10RT CLEARANCE 16"
A 18 8/16 (470)
B 11 15/16 (303)
C 15 8/16 (393)
D F
1 8/16 (38)
E
E 3 15/16 (100)
F 35 8/16 (902) C
H D
CLEARANCE 46" B
G 4 (102) CLEARANCE 34"
A
H 30 10/16 (778) G
A B C D Figure C
DOWN FLOW APPLICATION (Figure D)
Unit: inch(mm)
E
G
F
UNITS 10RT
H
SUPPLY
RETURN
A 15 6/16 (390)
B 12 8/16 (317)
C 18 10/16 (473)
D 6 4/16 (158)
E 2 11/16 (68)
F 35 7/16 (900)
G 2 11/16 (68)
TOP VIEW Figure D
H 30 11/16 (780)
UNITS 15/17.5RT
A 49 (1244)
B 60 10/16 (1540)
C 87 13/16 (2230)
F
D 44 3/16 (1123) E
E 7 1/16 (180) A
F 3 15/16 (100)
C B CLEARANCE 34"
D
CLEARANCE 46"
Figure A
B 5 11/16 (145)
C 2 11/16 (68)
D 17 15/16 (455)
E 14 6/16 (365)
A
F 18 12/16 (476)
G 5 2/16 (130)
B
G 31 3/16 (800)
H C
D
CLEARANCE 46" E
CLEARANCE 34"
G F
Figure B
DOWN FLOW APPLICATION (Figure C)
Unit: inch(mm)
A B C D
UNITS 15/17.5RT
A 7 29/32 (455)
E
B 14 11/32 (364)
F
H 49 3/16 (1250)
I 86 10/16 (2200)
J 114 2/16 (2898) K
N H
K 7 1/16 (180)
M
L 49 1/16 (1246)
J
I
M 3 2/16 (80) L
CLEARANCE 34"
CLEARANCE 46"
N 3 2/16 (80)
Figure A
HORIZONTAL FLOW APPLICATION (Figure B)
Unit: inch(mm)
CLEARANCE 34"
UNITS 20 RT CLEARANCE 16"
A 34 12/16 (882)
B 17 (432)
C 23 11/16 (602)
F
D 3 6/16 (86)
E
E 6 10/16 (168)
F 39 7/16 (1002) C
B D
CLEARANCE 46"
G 5 6/16 (137) CLEARANCE 34"
H A
G
H 25 11/16 (652) Figure B
A B C D
DOWN FLOW APPLICATION (Figure C)
E
Unit: inch(mm)
F
UNITS 20 RT
H
SUPPLY
RETURN
A 23 5/8 (600)
B 15 5/8 (396)
C 34 12/16 (882)
D 6 10/16 (168)
E 6 9/16 (167)
F 39 6/16 (1000)
G 6 13/16 (173)
H 25 13/16 (655)
TOP VIEW Figure C
Weights
Maximum Unit and Corner Weights (lbs) and Center of Gravity Dimensions (In.)
Unit Maximum Weights (lbs) Corner Weights (lbs) Center of Gravity (mm)
Tons Model No. Shipping Net A B C D E F
10 AK-H1208C00 970 772 260 196 146 168 37 20
AK-H1808C00
15 1455 1213 411 310 228 264 40 28
EK-H1808C00
AK-H2408C00
20 2171 1808 639 438 320 411 43 31
EK-H2408C00
Note: 1.Corner weights are given for information only.
2. Weights are approximate.
A B
D C
CENTER OF GRAVITY
7. Roof Curbs
Model No.: AK-H1208C00
30
30
1304 1025
106
"A" 2080
603
83
30
30
100
Detail View "A"
30
30
2022
220
2122
30
549 1344
(Unit : mm)
40 40
1452 40 1055
250 "A"
40 2142
40
457
40
2062
2162
80
108
632
40 (Unit : mm)
1064
2020
1930 50
50 2716
230 208 2626
50
650 "A" 50
80
100 550
88
40
2626
2776
1930
2080
(Unit : mm)
8. Wiring diagrams
Model No.: AK-H1208C00
Notes:
RY RELAY EH ELECTRIC HEATER COMP COMPRESSOR
BK BLACK OR ORANGE YL YELLOW
BR BROWN RD RED BL BLUE
WH WHITE FACTORY WIRING FIELD WIRING
Notes:
RY RELAY EH ELECTRIC HEATER COMP COMPRESSOR
BK BLACK OR ORANGE YL YELLOW
BR BROWN RD RED BL BLUE
WH WHITE FACTORY WIRING FIELD WIRING
Notes:
RY RELAY EH ELECTRIC HEATER COMP COMPRESSOR
BK BLACK OR ORANGE YL YELLOW
BR BROWN RD RED BL BLUE
WH WHITE FACTORY WIRING FIELD WIRING
9. Selection procedure
Selection Procedure - Heat pump(English)
Cooling
Step 1. Based on building's cooling load calculation from ASHRAE or any approved
standard method.
a. Cooling Capacity ...................................................................200,000 Btu/h
b. Sensible Cooling Capacity.....................................................170,000 Btu/h
c. Heating Capacity ...................................................................200,000 Btu/h
d. Outdoor Entering-air Temperature ........................................95°F
e. Outdoor Air winter design Temperature(DB) .........................39.2°F
f. Indoor Air winter design Temperature(DB)............................68°F
g. Indoor Entering-air Temperature(DB/WB) .............................80°F/67°F
f. Indoor air-flow........................................................................8,000 CFM
g. Electrical Characteristics(V-Ph-Hz) .......................................380~415-3-50
h. External static pressure .........................................................0.70 in.Aq.
Verify the unit performance at the given conditions in accordance with step #3.
Step 3. From Gross Cooing Capacity(MBH) 20 ton EK-H2408C00 (English) table, at 8,000 CFM and 95
DB ambient temperature, with 80°F DB. 67°F WB air entering temperature.
Total cooling capacity= 235,900 Btu/h, Sensible capacity = 186,400 Btu/h
To find the capacity at intermediate points between any two values mentioned in the
capacity table, interpolation should be used. Extrapolation is not recommended.
Selection Procedure
Step 4. The capacity estimated at step #3 is the gross capacity of the selected unit. The generated heat
from indoor motor is a function of CFM & static pressure. The total unit static pressure is as follows:
Evaporator fan motor performance table has deducted the pressure drop for filter already in the unit.
Therefore, the actual total static pressure is 0.7 in. Aq.
With 8,000CFM and 0.7 in Aq., Evaporator Fan Performance EK-H2408C00 (English) table shows
3.6 BHP for this unit.
FAN MOTOR HEAT;
3.1 x Fan BHP = MBH
3.1 x 3.6 = 11.20 MBH
Now subtract the fan motor heat from the gross cooling capacity of the unit;
Step 5. If the selected unit performance will not meet the required load, either total or sensible cooling, the
next higher size unit should be selected.
Heating
Step 1. Calculate the building heating load using the ASHRAE calculation or from other standard accepted
method.
Step 2. From Heating Capacity EK-H2408C00 (English), The heating capacity is 238,000 Btu/h at 8,000
CFM with 39.2°F outdoor DB temperature and 68°F indoor DB temperature. The required heating
capacity is 200,000 Btu/h.
Since heating capacity 238,000 Btu/h is greater than required heating capacity 200,000 Btu/h. So
additional electric heat is not required.
Step 3. If the selected unit performance will not meet the required load. The additional electric heater should
be selected from Electric Heating Capacity table.
Cooling
Step 1. Based on building's cooling load calculation from ASHRAE or any approved
standard method.
a. Cooling Capacity ...................................................................58.6 kW
b. Sensible Cooling Capacity.....................................................49.8 kW
c. Heating Capacity ...................................................................58.6 kW
d. Outdoor Entering-air Temperature ........................................35°C
e. Outdoor Air winter design Temperature(DB) .........................4°C
f. Indoor Air winter design Temperature(DB)............................20°C
g. Indoor Entering-air Temp.(D.B/W.B) .....................................26.7°C / 19.4°C
f. Indoor air-flow........................................................................3,776 l/s
g. Electrical Characteristics(V-Ph-Hz) .......................................380~415-3-50
h. External static pressure .........................................................17.78mm Aq.
Verify the unit performance at the given conditions in accordance with step #3.
Step 3. From Gross Cooing Capacity(kW) 20 ton EK-H2408C00 (SI) table, at 3,776 l/s and 35°C out-
door ambient temperature, with 26.7°C DB. 19.4°C WB air entering temperature.
Total cooling capacity= 69.1kW, Sensible capacity = 54.6kW
To find capacity at intermediate conditions not in the table.
Interpolation should be used when design conditions are between two numbers that are in the
capacity table. Extra-polation is not recommended.
Selection Procedure
Step 4. The capacity estimated at step #3 is the gross capacity of the selected unit. The generated heat
from indoor motor is a function of l/s & static pressure. To determine the total unit static pressure.
External Static(Duct system) 17.78 mm Aq.
Standard Filter 2.54 mm Aq.
Total static pressure 20.32 mm Aq.
Evaporator fan motor performance table has deducted the pressure drop for filter already in the unit.
Therefore, the actual total static pressure is 17.78 mm Aq.
With 3,776 l/s and 17.78 mm Aq., Evaporator Fan Performance EK-H2408C00 (SI) table shows 2.68
BkW for this unit.
FAN MOTOR HEAT;
1.22 x Fan Bkw = kW
1.22 x 2.68 = 3.27kW
Now subtract the fan motor heat from the gross cooling capacity of the unit;
Net cooling capacity 69.1kW - 2.68 kW = 66.42 kW
Net sensible cooling 54.6kW - 2.68 kW = 51.92 kW
Step 5. If the selected unit performance will not meet the required load, either total or sensible cooling, the
next higher size unit should be selected.
Heating
Step 1. Calculate the building heating load using the ASHRAE calculation or from other standard accepted
method.
Step 2. From Heating Capacity EK-H2408C00 (SI) table, The heating capacity is 69.7 kW at 3,776 l/s with
4°C outdoor temperature and 20°C indoor temperature. The required heating capacity is 58.6kW.
Since heating capacity 69.7kW is greater than required heating capacity 58.6kW. So, additional elec-
tric heat is not required.
Step 3. If the selected unit performance will not meet the required load. The additional electric heater should
be selected from Electric Heating Capacity table.
Correction Factor for Heating Capacity due to Frost on Heat Exchanger and Defrosting Operation.
The heating capacity in the "Heating Capacity Table" above indicates the actual heating capacity excluding the effect of frost on the heat
exchanger and the defrosting operation. Therefore, use the following factor to calculate the average heating capacity including capacity
reduction by frost on the exchanger and defrosting operation.
Correction Factor
Notes:
1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Outdoor air : 85%RH. However, the condition on nominal capacity is 7°CDB/6°CWB.
3. TC=Total heating capacity(Unit : kW)
4. PI=Power Input(Comp.+indoor fan motor+outdoor fan motor) (kW)
5. AFR=Air flow rate(l/s).
Correction Factor for Heating Capacity due to Frost on Heat Exchanger and Defrosting Operation.
The heating capacity in the "Heating Capacity Table" above indicates the actual heating capacity excluding the effect of frost on the heat
exchanger and the defrosting operation. Therefore, use the following factor to calculate the average heating capacity including capacity
reduction by frost on the exchanger and defrosting operation.
Correction Factor
Notes:
1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Outdoor air : 85%RH. However, the condition on nominal capacity is 7°CDB/6°CWB.
3. TC=Total heating capacity(Unit : kW)
4. PI=Power Input(Comp.+indoor fan motor+outdoor fan motor) (kW)
5. AFR=Air flow rate(l/s).
Notes:
1. All capacities are gross, evaporator fan motor heat is not deducted. To obtain net cooling capacity, subtract evaporator fan motor heat.
2. DB = Dry Bulb Temperature (°F), WB = Wet Bulb Temperature (°F)
3. CFM = Cubic Feet per minute
4. TGC = Total Gross Cooling Capacity(Unit : MBH = kBtu/h)
5. SHC = Sensible Heat Capacity(Unit : MBH = kBtu/h)
6. PI = Power Input(kW), Sum of Compressor & Outdoor Fan Power Input
Notes:
1. All capacities are gross, evaporator fan motor heat is not deducted. To obtain net cooling capacity, subtract evaporator fan motor heat.
2. DB = Dry Bulb Temperature (°F), WB = Wet Bulb Temperature (°F)
3. CFM = Cubic Feet per minute
4. TGC = Total Gross Cooling Capacity(Unit : MBH = kBtu/h)
5. SHC = Sensible Heat Capacity(Unit : MBH = kBtu/h)
6. PI = Power Input(kW), Sum of Compressor & Outdoor Fan Power Input
Notes:
1. All capacities are gross, evaporator fan motor heat is not deducted. To obtain net cooling capacity, subtract evaporator fan motor heat.
2. DB = Dry Bulb Temperature (°F), WB = Wet Bulb Temperature (°F)
3. CFM = Cubic Feet per minute
4. TGC = Total Gross Cooling Capacity(Unit : MBH = kBtu/h)
5. SHC = Sensible Heat Capacity(Unit : MBH = kBtu/h)
6. PI = Power Input(kW), Sum of Compressor & Outdoor Fan Power Input
Correction Factor for Heating Capacity due to Frost on Heat Exchanger and Defrosting Operation.
The heating capacity in the "Heating Capacity Table" above indicates the actual heating capacity excluding the effect of frost on the heat
exchanger and the defrosting operation. Therefore, use the following factor to calculate the average heating capacity including capacity
reduction by frost on the exchanger and defrosting operation.
Correction Factor
Outdoor Air Temperature (°FWB, RH=85%) 14 21.2 24.8 28.4 32 35.6 39.2 42.8
Correction Factor 0.95 0.95 0.89 0.87 0.87 0.89 0.91 1.00
Notes:
1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Outdoor air : 85%RH. However, the condition on nominal capacity is 7°FDB/6°FWB.
3. TC=Total heating capacity(Unit : kW)
4. PI=Power Input(Comp.+indoor fan motor+outdoor fan motor) (kW)
5. AFR=Air flow rate(CFM).
Correction Factor for Heating Capacity due to Frost on Heat Exchanger and Defrosting Operation.
The heating capacity in the "Heating Capacity Table" above indicates the actual heating capacity excluding the effect of frost on the heat
exchanger and the defrosting operation. Therefore, use the following factor to calculate the average heating capacity including capacity
reduction by frost on the exchanger and defrosting operation.
Correction Factor
Outdoor Air Temperature (°FWB, RH=85%) 14 21.2 24.8 28.4 32 35.6 39.2 42.8
Correction Factor 0.95 0.95 0.89 0.87 0.87 0.89 0.91 1.00
Notes:
1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Outdoor air : 85%RH. However, the condition on nominal capacity is 7°FDB/6°FWB.
3. TC=Total heating capacity(Unit : kW)
4. PI=Power Input(Comp.+indoor fan motor+outdoor fan motor) (kW)
5. AFR=Air flow rate(CFM).
1397 846 1.09 871 1.14 897 1.20 924 1.26 951 1.33 980 1.40 1009 1.48 1039 1.57
1572 892 1.35 917 1.42 943 1.49 970 1.57 997 1.66 1026 1.75 1055 1.85 1085 1.96
1746 947 1.71 972 1.79 998 1.88 1024 1.98 1052 2.09 1081 2.21 1110 2.34 1140 2.47
1921 1010 2.18 1035 2.29 1061 2.41 1088 2.53 1116 2.67 1144 2.82 1173 2.99 1204 3.16
2096 1083 2.82 1108 2.96 1134 3.11 1161 3.28 1188 3.45 1217 3.65 1246 3.86 - -
2960 846 1.45 871 1.53 897 1.60 924 1.69 951 1.78 980 1.88 1009 1.99 1039 2.11
3330 892 1.81 917 1.90 943 2.00 970 2.11 997 2.22 1026 2.34 1055 2.48 1085 2.63
3700 947 2.29 972 2.40 998 2.53 1024 2.66 1052 2.80 1081 2.96 1110 3.13 1140 3.32
4070 1010 2.93 1035 3.07 1061 3.23 1088 3.40 1116 3.58 1144 3.78 1173 4.00 1204 4.24
4440 1083 3.78 1108 3.97 1134 4.17 1161 4.39 1188 4.63 1217 4.89 1246 5.17 -
2077 565 0.08 591 0.32 618 0.50 644 0.65 671 0.78 697 0.91 724 1.02 750 1.12 777 1.22 803 1.31 830 1.40 856 1.48
2336 597 0.37 624 0.61 650 0.79 677 0.94 703 1.07 730 1.20 756 1.31 783 1.41 809 1.51 836 1.60 862 1.69 889 1.77
2596 636 0.72 662 0.95 689 1.13 715 1.28 742 1.42 768 1.54 795 1.65 821 1.75 848 1.85 874 1.94 901 2.03 927 2.11
2856 680 1.12 707 1.35 733 1.53 760 1.68 786 1.82 813 1.94 839 2.05 866 2.15 892 2.25 919 2.34 945 2.43 972 2.51
3115 731 1.57 758 1.81 784 1.99 811 2.14 837 2.27 864 2.40 890 2.51 917 2.61 943 2.71 970 2.80 996 2.89 1023 2.97
2077 883 1.56 909 1.64 936 1.71 962 1.78 989 1.85 1015 1.92 1042 1.99 1068 2.05
2336 915 1.85 942 1.93 968 2.00 995 2.07 1021 2.14 1048 2.21 1074 2.28 1101 2.34
2596 954 2.19 980 2.27 1007 2.35 1033 2.42 1060 2.49 1086 2.56 1112 2.62 1139 2.69
2856 998 2.59 1025 2.67 1051 2.75 1078 2.82 1104 2.89 1131 2.95 1157 3.02 1184 3.08
3115 1049 3.05 1076 3.13 1102 3.20 1129 3.27 1155 3.34 1182 3.41 1208 3.48 1235 3.54
4400 565 0.11 591 0.43 618 0.67 644 0.87 671 1.05 697 1.21 724 1.36 750 1.50 777 1.63 803 1.76 830 1.87 856 1.98
4950 597 0.50 624 0.82 650 1.06 677 1.26 703 1.44 730 1.60 756 1.75 783 1.89 809 2.02 836 2.15 862 2.26 889 2.37
5500 636 0.96 662 1.28 689 1.52 715 1.72 742 1.90 768 2.06 795 2.21 821 2.35 848 2.48 874 2.61 901 2.72 927 2.84
6050 680 1.50 707 1.81 733 2.05 760 2.26 786 2.44 813 2.60 839 2.75 866 2.89 892 3.02 919 3.14 945 3.26 972 3.37
6600 731 2.11 758 2.43 784 2.67 811 2.87 837 3.05 864 3.21 890 3.36 917 3.50 943 3.63 970 3.75 996 3.87 1023 3.98
4400 883 2.09 909 2.20 936 2.30 962 2.39 989 2.49 1015 2.58 1042 2.66 1068 2.75
4950 915 2.48 942 2.59 968 2.69 995 2.78 1021 2.88 1048 2.97 1074 3.05 1101 3.14
5500 954 2.94 980 3.05 1007 3.15 1033 3.24 1060 3.34 1086 3.43 1112 3.52 1139 3.60
6050 998 3.48 1025 3.58 1051 3.68 1078 3.78 1104 3.87 1131 3.96 1157 4.05 1184 4.14
6600 1049 4.09 1076 4.19 1102 4.29 1129 4.39 1155 4.48 1182 4.58 1208 4.66 1235 4.75
6 Turn open 5 Turn open 4 Turn open 3 Turn open 2 Turn open 1 Turn open 0 Turn open
Standard Motor & Drive Fan Speed 623 665 708 751 793 836 879
Standard Motor & High Static Drive 816 872 928 983 1039 1095 1151
Oversize Motor & Drive Fan Speed 907 969 1032 1094 1156 1218 1280
• Factory set at 3 turns open.
3021 - - 569 1.35 590 1.46 611 1.56 633 1.67 654 1.77 676 1.88 697 1.98 719 2.09 740 2.20 762 2.30 783 2.41
3398 577 1.60 598 1.71 620 1.81 641 1.92 663 2.03 684 2.13 706 2.24 727 2.34 748 2.45 770 2.55 791 2.66 813 2.76
3776 614 2.05 635 2.15 657 2.26 678 2.37 700 2.47 721 2.58 743 2.68 764 2.79 786 2.89 807 3.00 828 3.10 850 3.21
4154 659 2.59 681 2.70 702 2.81 723 2.91 745 3.02 766 3.12 788 3.23 809 3.33 831 3.44 852 3.54 874 3.65 895 3.75
4531 713 3.25 735 3.35 756 3.46 778 3.56 799 3.67 821 3.77 842 3.88 864 3.99 885 4.09 906 4.20 928 4.30 944 4.41
3021 805 2.51 826 2.62 848 2.72 869 2.83 891 2.93 912 3.04 933 3.15 955 3.25
3398 834 2.87 856 2.97 877 3.08 899 3.19 920 3.29 942 3.40 963 3.50 985 3.61
3776 871 3.32 893 3.42 914 3.53 936 3.63 957 3.74 979 3.84 1000 3.95 1022 4.05
4154 917 3.86 938 3.97 960 4.07 981 4.18 1002 4.28 1024 4.39 1045 4.49 1067 4.60
4531 971 4.51 992 4.62 1014 4.72 1035 4.83 1057 4.94 1078 5.04 1100 5.15 1121 5.25
6400 - - 569 1.81 590 1.95 611 2.10 633 2.24 654 2.38 676 2.52 697 2.66 719 2.80 740 2.94 762 3.09 783 3.23
7200 577 2.15 598 2.29 620 2.43 641 2.57 663 2.72 684 2.86 706 3.00 727 3.14 748 3.28 770 3.42 791 3.56 813 3.71
8000 614 2.75 635 2.89 657 3.03 678 3.17 700 3.31 721 3.46 743 3.60 764 3.74 786 3.88 807 4.02 828 4.16 850 4.30
8800 659 3.48 681 3.62 702 3.76 723 3.90 745 4.04 766 4.19 788 4.33 809 4.47 831 4.61 852 4.75 874 4.89 895 5.03
9600 713 4.35 735 4.50 756 4.64 778 4.78 799 4.92 821 5.06 842 5.20 864 5.35 885 5.49 906 5.63 928 5.77 944 5.91
6400 805 3.37 826 3.51 848 3.65 869 3.79 891 3.93 912 '4.08 933 4.22 955 4.36
7200 834 3.85 856 3.99 877 4.13 899 4.27 920 4.41 942 '4.56 963 4.70 985 4.84
8000 871 4.45 893 4.59 914 4.73 936 4.87 957 5.01 979 '5.15 1000 5.29 1022 5.44
8800 917 5.18 938 5.32 960 5.46 981 5.60 1002 5.74 1024 '5.88 1045 6.03 1067 6.17
9600 971 6.05 992 6.19 1014 6.34 1035 6.48 1057 6.62 1078 '6.76 1100 6.90 1121 7.04
Electric Heater
Standard Filter
Unit Model No. CFM l/s 9kW 18kW 36kW
in Aq mm Aq in. Aq. mm Aq. in. Aq. mm Aq. in. Aq. mm Aq.
2960 1397 0.06 1.52 0.01 0.25 0.07 1.78 - -
AK-H1208C00 3700 1746 0.10 2.54 0.01 0.25 0.10 2.54 - -
4440 2095 0.14 3.56 0.02 0.51 0.15 3.81 - -
4400 2077 0.06 1.52 - - 0.04 1.02 0.04 1.02
AK-H1808C00
5500 2596 0.09 2.29 - - 0.06 1.52 0.07 1.78
EK-H1808C00
6600 3115 0.13 3.3 - - 0.1 2.54 0.11 2.79
6400 3021 0.07 1.78 - - - - 0.07 1.78
AK-H2408C00
8000 3776 0.10 2.54 - - - - 0.13 3.30
EK-H2408C00
9600 4531 0.14 3.56 - - - - 0.17 4.32
Note: 1. The output ratings shown above is at 415V. < Correction Coefficient>
For other voltage, Output = Capacity Multiplier x Rated Output
2. E/heater Voltage range is 380~415V. Voltage Capacity Multiplier
380 0.84
400 0.92
415 1.0
(kW x 3413)
• Temp. Rise across Electric Heater =
(1.08 x CFM)
• If you want to take temp rise at different airflow use above equation.
Electrical Data Unit wiring with electric heater + heat pump cycle
Electric Unit Operating Standard indoor fan motor Oversized indoor fan motor
MODEL
Heater (kW) Voltage Range *M.C.A. *M.F.S. *M.C.B. *M.C.A. *M.F.S. *M.C.B.
9 55.3 60.0 60.0 - - -
AK-H1208C00
18 72.4 70.0 70.0 - - -
3Ø,
AK-H1808C00 18 91.4 110.0 110.0 92.0 110.0 110.0
380-415V,
EK-H1808C00 36 125.5 140.0 140.0 126.1 140.0 140.0
50Hz
AK-H2408C00
36 142.8 150.0 150.0 146.9 150.0 150.0
EK-H2408C00
By Pass
Outdoor 1.6(I.D)*1EA Indoor
Coil Pressure Pressure Coil
3.36(I.D)*8EA Check Port Ceck Port
Th3 Th1 Capillary Tube
1.2(I.D)*9EA
High Pressure
Switch
Accum
Cooling Heating
COMP
A
Low Pressure
Switch
Th5
Capillary Tube Check
2.0(I.D)*3EA Valve
Capillary Tube
3.36(I.D)*8EA 1.2(I.D)*9EA
By Pass
1.6(I.D)*1EA
Pressure Pressure
Ceck Port Ceck Port
Th4 Th2
COMP
B
Low Pressure
Switch
Notes
Th : Thermistor
Th1 : Thermistor Eva. For A Cycle
Th2 : Thermistor Eva. For B Cycle
Th3 : Thermistor Cond. For A Cycle
Th4 : Thermistor Cond. For B Cycle
Th5 : Outdoor Temp. Thermistor
HI PRESSURE
SWITCH
ACCUM
Cooling Heating
CHECK CHECK
LOW PRESSURE
VALVE VALVE
SWITCH
COMP COMP
A-1 A-2
BY PASS
1.8(I.D)*1EA
PRESSURE PRESSURE
CHECK PORT CHECK PORT
HI PRESSURE
SWITCH
HI PRESSURE
SWITCH
ACCUM
Cooling Heating
CHECK CHECK
VALVE VALVE
CAPILLARY TUBE
LOW PRESSURE
COMP COMP
A-1 A-2 SWITCH
CHECK
VALVE
PRESSURE PRESSURE
CHECK PORT CHECK PORT
HI PRESSURE
CAPILLARY TUBE
SWITCH
ACCUM
CHECK Cooling Heating
VALVE CHECK CHECK
VALVE VALVE LOW PRESSURE
COMP COMP SWITCH
B-1 B-2
CAPILLARY TUBE
CAPILLARY TUBE
Continuous
operation
24
Warming up
Operation
21 Continuous
Operative operation
-5
1
Operative
-5
18 32 10 27
Indoor Unit [°C DB] Indoor Unit [°C DB]
• Although low ambient kit is installed, in case outdoor Operative: Intermittent operation according to operation
temperature goes below 0°C, the cooling capacity can be condition (indoor/outdoor temperature, humidity,
dropped and operation characteristics can be slightly and load) the heating capacity can be drop
different.
14. Controller
1) LCD wired remote controller
AUTO SWING OPERATION SET TEMP SUB FUNCTION Heat Pump Model
Room Temp
HI
MED
AUTO Heater Preheat
JET Defrost Humidify 1
LO Filter Out door
Time ZONE 1 2 3 4
Timer Operation unit Program set
On Off
Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23
3 2
Signal receptor
98 Cooling Model
4
10
Timer Cancel 5
11
12 Program Week Holiday
6
13
14 SET/CLR 7
15
Hour Min RESET 8
16 17
1
1 Signal Transmitter
2 • Transmits the signals to the air conditioner
10
2 Operation Display of the Remote Control
3 • LED displays operation status(on or off) of
11 air conditioner.
3 Humidify Button
7 4
4 Cooling ON Button
8 6
5 Temperature Setting Buttons
5
6 Power ON/OFF Button
• Operation will start when this button is
pressed, and stop when the button is
pressed again.
7 4
8 6
5
CAUTION
1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion
on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunc-
tion or inefficient performance.
3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it
needs additional anticorrosion treatment on the heat exchanger.
2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
1. If you can’t meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment.
2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water
Casing
Unit casing shall be constructed of having gauge zinc coated, galvanized steel. The cabinet shall be exterior
painted and weather resistance. The cabinet shall be design to allow maintenance from one side only.
Unit shall have a water and air tight service panels with minimum number of screws per panel for easy servic-
ing.
Filters
Washable filters shall be standard on all units (Except 6.25 Ton unit). Filter rack can be converted to one inch(bellow
71/2 ton).
Two inch filters shall be installed on all units above 7.5ton.
Compressors
LG single packaged units shall be direct drive hermetic compressor, reciprocating type with internal built in
lubricating mechanism for all moving parts. Motor shall be suction gas cooled with internal temperature and
over current sensitive motor over load, for maximum protection. Factory rubber shock mounted and internally
spring isolation for sound and vibration control.
Refrigerant Circuits
Each refrigerant circuit shall have independent fixed capillary tube devices and service pressure ports, low
pressure switches and refrigerant line filter factory-installed as standard.
Outdoor Fans
Statically and dynamically, direct drive outdoor fan in vertical discharge position. Permanently lubricated fan
motors with built in thermal overload protection.
Indoor Fan
Direct drive indoor motor for 6.25 tons with forward curve centrifugal fans. Belt drive with adjustable motor pul-
ley for all unit above 6.25 ton. All motors shall be thermally overload protected. For higher static pressure
requirement over size motor is available.
Controls
All units shall be supplied with centralized micom-processor. Heating and cooling shall be control by micom
through input signals from indoor and outdoor temperature sensors. Micom shall provide anti-short cycle timer
and time delay between compressor.
17. Appendix
Unit Conversion
Cooling Capacity
RT Btu/h kcal/h W
Volume
1 35.3 16.67
Length
m cm mm inch
Power
HP W kW
1 746 0.746
Temperature
C = 5 (F - 32)
9
Where,
C is Temperature in °C
F is Temperature in °F
Head Office:
20 Yoidodong, Youngdungpogu,
Yoido P.O.Box 355 Seoul 150-721,
Korea Phone:82-2-3777-7985
Changwon Office:
76 Seongsandong, Changwon,
Gyeongnam 641-713, Korea
Phone: 82-55-269-3506
http://www.lge.com/airconditioner