0% found this document useful (0 votes)
1K views23 pages

Daikin - VRV III Installation Manual

The document is an installation manual for Daikin air conditioning units. It provides instructions for installing single units and units connected in series. It outlines piping connection patterns and spacing requirements between indoor and outdoor units depending on the type and number of units being installed. Diagrams illustrate the different piping connection and installation spacing patterns.

Uploaded by

Phyo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views23 pages

Daikin - VRV III Installation Manual

The document is an installation manual for Daikin air conditioning units. It provides instructions for installing single units and units connected in series. It outlines piping connection patterns and spacing requirements between indoor and outdoor units depending on the type and number of units being installed. Diagrams illustrate the different piping connection and installation spacing patterns.

Uploaded by

Phyo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 23

DAIKIN

INSTALLATION MANUAL

RXYQSPY1 RXQSPY1
RXYQ8PY1 RXQ8PY1
RXYQ10PY1 RXQ10PY1
RXYQ12PY1 RXQ12PY1
RXYQ14PY1 RXQ14PY1
( RXYQ16PY1 RXQ16PY1
RXYQ18PY1 RXQ18PY1
RXYQ20PY1 RXQ20PY1
RXYQ22PY1 RXQ22PY1
RXYQ24PY1 RXQ24PY1
RXYQ26PY1 RXQ26PY1
RXYQ28PY1 RXQ28PY1
RXYQ30PY1 RXQ30PY1
RXYQ32PY1 RXQ32PY1
RXYQ34PY1 RXQ34PY1
RXYQ36PY1 RXQ36PY1
RXYQ38PY1 RXQ38PY1
RXYQ40PY1 RXQ40PY1
RXYQ42PY1 RXQ42PY1
RXYQ44PY1 RXQ44PY1
RXYQ46PY1 RXQ46PY1
RXYQ48PY1 RXQ48PY1
RXYQSOPY1 RXQSOPY1
RXYQS2PY1 RXQS2PY1
RXYQS4PY1 RXQS4PY1
I

I
I
<If installed as a single unit> <When installed in serial>
[Q5· 8 ·10 type] (Pattern 1) i--i.=J
>300 (Pattern 1) i----------:.=J ~300
:0: I
-4
I iOOOi 4
~10iL1 'i~ ~5003
L __ ...J
:1:0111 II _J ~10 [
~10 ~ :l:l#~! ~58°
.[j
c::::L:J (Pattern 2) i ---
OR
~100
4 (Pattern 2) !tiifDR ~1g0
D [
I I

[Q12 ·14 ·16·16 type] ~50 i_~~ _I j~50 [ ~5g0 ~50:I.


'~ I 11~:
- :~50
~_____________
~500
3
7
2

~---------
1,2,3
r-------~-.L::::---
(Pattern 3) i-~o-o~ (Pattern 3 ) I >300
:0 - 0
fu J11 ~oo l ~ 1 ~200[ I ~1 ~

figure 1 ~~ ---, figure 2 figure 3

figure 4 figure 5 figure 6

A
B 1/
/7­
I I -
M !"'L< __;:;L ---------v~./~ ....
<:0
co <.0
(OID ""
""'LO
/\1 ~ ~ ~2
77 --F.:\-------- --------------17-777 ....

figure 7 figure 8 figure 9

figure 10 figure 11 _ _~ ...J figure 12 figure 13

( 1 ) ( 2 ( 1 ) ( 2 )
3 4 3 4
6 7 6 6
6 5 5
5
8
10 11
10

16
~~-~"
18·1
~ ~->
C~~2 ~O
1-~2 0:'
1

A ,," ~~~3
A-arrow view 3 4
«tX0
(C-arrow view)
figure 16

g,-~ ~
f~~~
1

B-arrow view 18·2 (O-arrow view) 18·3

figure 17 figure 18

figure 19 figure 20

2
2 3
.' ASP AlP

3
(

"
A

'-"
F1F2F1F21

_
..
ilMllHllnM.oOOlDlUIIOO

....... .. / "
AlP
lOW)lIITKlOJlOOOJJlIWllll"
Fl F2Fl F2 01 02

[g]
@] rn rn
4 6
5

figure 21 figure 22

9 --3

figure 23 figure 24

2
7
[In case of 5-10HP type] [In case of 12-18HP type]

figure 27

)
3

figure 28 figure 29 figure 30_ _~ ~ _'

3
4

figure 31 figure 32

r:t--------it6J
11

(, 3
7

8 I I: : :: 9 !
L~======ld:k:===~~:::=::=::========1~
IS
L -=----<9_----lf) 4
:12
=<> :13

figure 33 figure 34
RXYQ5PY1 RXYQ16PYl RXYQ26PYl RXYQ36PY1 RXYQ46PY1 RXQ5PYI RXQ16PVl RXQ26PYl RXQ36PYl RX046PYI
RXYQ8PY1 RXYQ18PY1 RXYQ28PYl RXYQ38PYI RXYQ46PY1 RXOBPY1 RXQ18PYI RXQ28PYI RXQ38PYl RX048PYl Installation
RXYQ10PYl RXYQ20PY1 RXYQ30PYl RXY040PYl RXYQ50PYl RXQ10PYl RXQ2QPVl RX030PYI RX040PYl RXQ50PYl
VRVlII System
RXYQ12PYl RXYQ22PY1 RXYQ32PYI RXY042PYl RXYQ52PYl RXQ12PYI RXQ22PYl RX032PYI RX042PYl RXQ52PYl air conditioner manual
RXYQ14PYl RXYQ24PY1 RXYQ34PYl RXYQ44PYl RXYQ54PYl RXQ14PYI RXQ24PYl RXQ34PY1 RXQ44PYl RXQ54PYl

CONTENTS & Warning Failur~ to observe a warning may result in death


or serious Injury.
1. FIRST OF ALL 1
1-1 . Safety considerations 1 & Caution Failure to observe a caution may result in injury
or damage to the unit.
1-2. Special notice of product...
2
1-3. Disposal requirements
, 2 These too might lead to serious injury depending
2. INTRODUCTION 2 on the circumstances.
2-1. Combination ,
2-2. Standard supplied accessories
2
3
-& Warning
2-3. Option accessory 3 • Ask your dealer or qualified personnel to carry out installation

2-4. Technical and Electrical specifications 3 work. Do not try to insta.ll the machine yourself.

2-5. Main components


3 Improper installation may result in water leakage, electric

2-6. Installation Process


3 shocks or fire.

3. SELECTION OF LOCATION 3 • Perform installation work in accordance with this installation man­

uaL

4. INSPECTING AND HANDLING THE UNIT .4 Improper installation may result in water leakage, electric shocks

5. PLACING THE UNIT 4 or fire.

6. REFRIGERANT PIPING 5 • When installing the unit in a small room, take measures against to

keep refrigerant concentration from exceeding allowable safety

6-1 . Selection of piping material and Refrigerant


limits in the event of refrigerant leakage.

branching kit... 5
Contact your dealer for more information. Excessive refrigerant in

6-2. Protection against contamination when installing pipes 5 a closed ambient can lead to oxygen deficiency.

6-3. Pipe connection 5 • Be sure to use only the specified accessories and parts for instal­
6-4. Connecting the refrigerant piping 5 lation work.
6-5. Example of connection 8 Failure to use the specified parts may result in water leakage,
7. FIELD WIRING 10 electric shocks, fire or the unit falling.
7-1. Power circuit, safety device, and cable requirements 10 • Install the air conditioner on a foundation strong enough to with­

7-2. Wiring Connection Example for Whole System 10 stand the weight of the unit.

7-3. Leading wire Procedure 11 A foundation of insufficient strength may result in the unit falling

and causing injuries.

7-4. Transmission Wiring Connection Procedure 11


• Carry out the specified installation work after taking into account

7-5. Power Wiring Connection Procedure 11 strong winds, typhoons or earthquakes.

7-6. Procedure for Wiring Inside Units 12 Improper installation work may result in the unit falling and caus­

8. AIR TIGHT TEST AND VACUUM DRYING 12 ing accidents.

8-1. Preparations 12 • Make sure that a separate power supply circuit is provided for this
8-2. Air tight test and vacuum drying method 13 unit and that all electrical work is carried out by qualified personnel
9. PIPE INSULATION 13 according to local and national regulations and this installation man­
uaL
10. CHECKING OF DEVICE AND INSTALLATION
An insufficient power supply capacity or improper electrical con­
CONDITIONS 13 struction may lead to electric shocks or fire.
11. ADDITIONAL REFRIGERANT CHARGE AND • Make sure that all wiring is secured, the specified wires are used,

and no external forces act on the terminal connections or wires.

CHECK OPERATION 13
Improper connections or installation may result in the terminals

11-1.Before working 13 overheating or fire.

11-2. Procedure of Adding Refrigerant charging and • When wiring the power supply and connecting the remote control­
check operation 15 ler wiring and transmission wiring, position the wires so that the
12. ONSITE SETTINGS 17 EL.COMPO.BOX lid can be securely fastened.
12-1.0nsite Settings With the Power Off
17 Improper positioning of the EL.COMPO.BOX lid may result in
electric shocks or fire.
12-2.0nsite Settings With the Power On
17
• If the refrigerant gas leaks during installation, ventilate the area
13. TEST RUN 17 immediately.
13-1.Before test run 17 Toxic gas may be produced if the refrigerant gas comes into con­
13-2.Test Run
17 tact with fire. "
13-3.Checks After Test Run
17 • After completing the installation work, check that the refrigerant ~.
14. CAUTION FOR REFRIGERANT LEAKS 17 gas does not leak.
Toxic gas may be produced if the refrigerant gas leaks into the
room and comes into contact with a source of fire, such as a fan
heater, stove or cooker.
1. FIRST OF ALL • Do not directly touch the refrigerant leaked from refrigerant piping

connections.

• This document is an installation manual for the Daikin RX(Y)Q-P


Frostbite may be caused.

Series VRV Inverter. Before installing the unit, read this manual • Before touching electrical parts, turn off the power.
thoroughly, and following the instructions contained in it. After • Do not allow children to mount on the outdoor unit, or avoid

installation, do a test run to make sure the unit runs properly, and placing any object on it. Falling or tumble may result in injury.

then explain how to operate and take care of the unit to the cus­ • Be sure to establish an earth. •

tomer, using the operation manual, Do not earth the unit to a utility pipe, arrester or tele­
• Lastly, make sure the customer keeps this manual, along with the phone earth.

Incomplete earth may cause electrical shock or fire.

operation manual, in a safe place.


A high surge current from lightning or other sources may cause

• This manual does not describe how to install the indoor unit. damage to the air conditioner.

Refer to the installation manual included with the indoor unit for that. • Be sure to install an earth leakage breaker.

Failure to install an earth leakage breaker may result in electric

1·1 Safety considerations shocks or fire.

Please read these "Safety considerations" carefully before installing

air conditioning unit and be sure to install it correctly. The safety pre­

cautions listed here are divided into two categories.


- & Caution - - - - - - - - - - - - - - - - - ­
In either case, important safety information is listed which must be
• While following the instructions in this installation manual, install
read carefully.
drain piping in order to ensure proper drainage and insulate piping
in order to prevent condensation.
Improper drain piping may result in water leakage and property
damage.
• Install the indoor and outdoor units, power supply wiring and con­
necting wiring at least 1 meter away from televisions or radios in
2. INTRODUCTION
order to prevent image interference or noise. • RX(Y)Q-P series are designed for outdoor installation and used for
(Depending on the radio waves, a distance of 1 meter may not be cooling and heatpump (except RXQ-P) applications. Outdoor units
sufficient enough to eliminate the noise.)
come in three standard sizes, and with a single system through a
The indoor unit should be installed as far away from fluorescent
lighting as possible. multi system combining up to three outdoor units, rated cooling
Remote controller (wireless kit) transmitting distance can result capacity from 14.0 kW to 147 kW and rated heating capacity from
shorter than expected in rooms with electronic fluorescent lamps 16.0 kW to 170 kW (except RXQ-P) can be achieved.
(inverter or rapid start types). • The RX(Y)Q-P units can be combined with Daikin VRV series
Do not install the air conditioner in the following locations: indoor units for air conditioning purposes. Always use appropriate
(a) where a mineral oil mist or an oil spray or vapor is produced, indoor units compatible with R410A. To lean which models of
for example in a kitchen.
indoor units are compatible with R410A, refer to the product cat­
Plastic parts may deteriorate and fall off or result in water leakage.
(b) where corrosive gas, such as sulfurous acid gas, is produced. alogs.
Corroding copper pipes or soldered parts may result in refrig­ To combine with other refrigerant indoor unit will cause malfunc­
erant leakage. tion.
(c) near machinery emitting electromagnetic waves.
Electromagnetic waves may disturb the operation of the con­ 2-1 Combination
trol system and result in a malfunction of the unit. The indoor units can be installed in the following range.
(d) where flammable gas may leak, where there are carbon fiber (The total number of indoor units cannot exceed 64 units.)
or ignitable dust suspensions in the air, or where volatile flam­
mables such as thinner or gasoline are handled. (Outdoor unit) (Total capacity of indoor units)
Operating the unit in such conditions may result in fire. RX(Y)Q5PY1 62.5 -162.5
(e) Locations where small animals might build nests inside the RX(Y)Q8PY1 100 -260
unit. RX(Y)Q10PY1 125 -325
If small animals enter and come in contact with electrical parts, RX(Y)Q12PY1 150 -390
this can cause malfunctions, smoke, and fire.
RX(Y)Q14PY1 175 -455
RX(Y)Q16PY1 200 -520
1-2 Special notice of product
RX(Y)Q18PY1 225 -585
[CLASSIFICATION]
RX(Y)Q20PY1 250 -650
This air conditioner comes under the term "appliances not accessible RX(Y)Q22PY1 275 -715
to the general public". RX(Y)Q24PY1 300 -780
[EMC CHARACTERISTICS] RX(Y)Q26PY1 325 -845
VRVrn System is a class A product. In a domestic environment this RX(Y)Q28PY1 350 -910
product may cause radio interference in which case the user may be RX(Y)Q30PY1 375 -975
required to take adequate measures. RX(Y)Q32PY1 400 -1040
[REFRIGERANT]
RX(Y)Q34PY1 425 -1105
VRVIII System use R410A refrigerant.
RX(Y)Q36PY1 .450 -1170
• The refrigerant R41 OA requires strict cautions for keeping the sys­ RX(Y)Q38PY1 475 -1235
tem clean, dry and tight. RX(Y)Q40PY1 500 -1300
Read the chapter "REFRIGERANT PIPING" carefully and follow RX(Y)Q42PY1 525 -1365
these procedures correctly. RX(Y)Q44PY1 550 -1430
AClean and dry RX(Y)Q46PY1 575 -1495
Foreign materials (including mineral oils such as SUNISO oil RX(Y)Q48PY1 600 -1560
or moisture) should be prevented from getting mixed into the RX(Y)Q50PY1 625 -1625
system. RX(Y)Q52PY1 650 -1690
B.Tight
RX(Y)Q54PY1 675 -1755
Take care to keep the system tight when installing.
R41 OA does not contain any chlorine, does not destroy the Note-~
ozone layer, and does not reduce the earth's protection • Be sure to connect an R410A indoor unit.
against harmful ultraviolet radiation. See the catalog for indoor unit models which can be connected.
R41 OA can contribute slightly to the greenhouse effect if it is • At above is the total capacity and total number of units of the
released.
indoor units when configured in a standard combination. See the
• Since R410A is a mixed refrigerant, the required additional refrig­
technical reference for details on total capacity and total number

c
erant must be charged in its liquid state. If the refrigerant is
of indoor units when using a configuration other than the standard
charged in a state of gas, its composition changes and the system
combination. The standard combination are as follows.
will not work properly.
Limit by the total maximum refrigerant charge <Combination unit> <Independent unit>
The total maximum refrigerant charge of a VRVrn system must be RXYQ5PY1 RXYQ5PY1
below 1OOkg, this to be in accordance with CE requirement RXYQ8PY1 RXYQ8PY1
(EN60335-2-40 standard). RXYQ10PY1 RXYQ10PY1
This means that in case the total maximum refrigerant charge of the RXYQ12PY1 RXYQ12PY1
system (factory and additional charge) is equal to or more than RXYQ14PY1 RXYQ14PY1
100kg you must divide your mUltiple outdoor system into smaller RXYQ16PY1 RXYQ16PY1
independent systems, each containing less than 100kg refrigerant RXYQ18PY1 RXYQ18PY1
RXYQ20PY1 RXYQ8PY1+ RXYQ12PY1
charge.
RXYQ22PY1 RXYQ10PY1+ RXYQ12PY1
For factory charge, refer to the unit name plate.
RXYQ24PY1 RXYQ8PY1+ RXYQ16PY1
[DESIGN PRESSURE]
RXYQ26PY1 RXYQ8PY1+ RXYQ18PY1
Since design pressure is 4.0MPa or 40bar (for R407C units: 3.3MPa
RXYQ28PY1 RXYQ10PY1+ RXYQ18PY1
or 33bar),the wall thickness of pipes should be more carefully
RXYQ30PY1 RXYQ12PY1+ RXYQ18PY1
selected in accordance with the relevant local and national regula­ RXYQ32PY1 RXYQ16PY1+ RXYQ16PY1
tions. RXYQ34PY1 RXYQ16PY1 + RXYQ18PY1
1-3 Disposal requirements RXYQ36PY1 RXYQ18PY1+ RXYQ18PY1
RXYQ38PY1 RXYQ8PY1+ RXYQ12PY1 + RXYQ18PY1
Dismantling of the unit, treatment of the refrigerant, oil and eventual RXYQ40PY1 RXYQ8PY1+ RXYQ16PY1 + RXYQ16PY1
other parts, should be done in accordance with the relevant local and RXYQ42PY1 RXYQ8PY1+ RXYQ16PY1+ RXYQ18PY1
national regulations. RXYQ44PY1 RXYQ8PY1+ RXYQ18PY1+ RXYQ18PY1
RXYQ46PY1 RXYQ1 OPY1 + RXYQ18PY1 + RXYQ18PY1
RXYQ48PY1 RXYQ12PY1+ RXYQ18PY1+ RXYQ18PY1
RXYQ50PY1 RXYQ14PY1+ RXYQ18PY1+ RXYQ18PY1
RXYQ52PY1 RXYQ16PY1+ RXYQ18PY1+ RXYQ18PY1
RXYQ54PY1 RXYQ18PY1 + RXYQ18PY1 + RXYQ18PY1
<Combination unit> <Independent unit>
QS-Q18 type
RXQSPY1 RXQSPY1
RXQ8PY1 RXQ8PY1 Gas side Liquid side Liquid side
RXQ10PY1 RXQ10PY1 Name accessory accessory accessory Others
RXQ12PY1 RXQ12PY1 pipe (2) pipe (1) pipe (2)
RXQ14PY1 RXQ14PY1 Quantity 1 pc. 1 pc. 1 pc. • Operation
RXQ16PY1 RXQ16PY1 manual
RXQ18PY1 RXQ18PY1 • Installation

~ ~ r ~ ~
RXQ20PY1 RXQ8PY1+ RXQ12PY1 manual
RXQ22PY1 RXQ10PY1+ RXQ12PY1 • "REQUEST
RXQ24PY1 RXQ8PY1+ RXQ16PY1 FOR THE
Shape
RXQ26PY1 RXQ8PY1+ RXQ18PY1 5-10, INDICA­
RXQ28PY1 RXQ1 OPY1 + RXQ18PY1 5-10 12-18 1416 12,18 TION" label
RXQ30PY1 RXQ12PY1+ RXQ18PY1 HP type HP type HP ~pe HP type (Installation
RXQ32PY1 RXQ16PY1+ RXQ16PY1
records)
RXQ34PY1 RXQ16PY1+ RXQ18PY1
RXQ36PY1 RXQ18PY1+ RXQ18PY1
RXQ38PY1 RXQ8PY1+ RXQ12PY1 + RXQ18PY1
RXQ40PY1 RXQ8PY1+ RXQ16PY1 + RXQ16PY1
RXQ42PY1 RXQ8PY1+ RXQ16PY1+ RXQ18PY1
RXQ44PY1 RXQ8PY1+ RXQ18PY1+ RXQ18PY1
RXQ46PY1 RXQ10PY1+ RXQ18PY1+ RXQ18PY1
RXQ48PY1 RXQ12PY1+ RXQ18PY1+ RXQ18PY1
RXQSOPY1 RXQ14PY1+ RXQ18PY1+ RXQ18PY1
RXQS2PY1 RXQ16PY1+ RXQ18PY1+ RXQ18PY1
RXQS4PY1 RXQ18PY1+ RXQ18PY1+ RXQ18PY1

• If the total capacity of the connected indoor units exceeds the


capacity of the outdoor unit, cooling and heating performance
may drop when running the indoor units. See the capacity table in
the Engineering Data Book for details.
• There are restrictions on the refrigerant pipe connecting order
between outdoor unit in the case of the multi system.
Install so that the following restrictions are satisfied.
<Restrictions>
The capacities of outdoor units A, Band C must fulfill the following
conditions.
A~B~C

Outdoor Outdoor Outdoor


unit A unit B unitC

to indoor unit
2-4 Technical and Electrical specifications

Outdoor unit
Refer to the Engineering Data Book for the complete list of specifica­

multi connection

tions.

piping kit

(first branch)
2-5 Main components
For main components and function of the main components, refer to
2-2 Standard supplied accessories the Engineering Data Book.
The following accessories are included. The storage location of the 2-6 Installation Process
accessories is shown in figure 1.
Figure 2 shows the installation process. Install in the order of the
QS-Q18 type steps shown.
Gas side
(Refer to figure 2)
Name Clamp (1) Clamp (2) Clamp (3) accessory 1. "3. SELECTION OF LOCATION"
pipe (1) 2. "4. INSPECTING AND HANDLING THE UNIT"
Quantity 9 pcs. 2 pcs. 1 pc. 1 pc. 3. "S. PLACING THE UNIT"
4. "6. REFRIGERANT PIPING"
5. "7. FIELD WIRING"

I I
-
Shape
/
Small
Large
[ 6.
7.
8.

9.
"8. AIR TIGHT TEST AND VACUUM DRYING"
"9. PIPE INSULATION"
"10. CHECKING OF DEVICE AND INSTALLATION
CONDITIONS"
"11. ADDITIONAL REFRIGERANT CHARGE AND
CHECK OPERATION"
10. "13. TEST RUN"
11. Operations which require the power to be turned on.

3. SELECTION OF LOCATION
Select a location for installation that meets the following conditions.
Get the customer's permission.
1. There is no danger of fire due to leakage of inflammable gas.
2. Select the location of the unit in such a way that neither the dis­
charged air nor the sound generated by the unit disturb anyone.
3. The foundation is strong enough to support the weight of the unit
and the floor is flat to prevent vibration and noise generation.
4. The piping length between the outdoor unit and the indoor unit
may not exceed the allowable piping length. (Refer to
"6. REFRIGERANT PIPING")
5. Locations where the unit's suction vent and outlet vent do not gen­ 4. INSPECTING AND HANDLING THE UNIT
erally face the wind.
Wind blowing directly into the suction or outlet vents will interfere • At delivery, the package should be checked and any damage

with the unit's operation. should be reported immediately to the carrier claims agent.

If necessary, install some kind of obstruction to block the wind. • When handling the unit, take into account the following:
6. The space around the unit is adequate for servicing and the min­
1. [I] Fragile, handle the unit with care.
imum space for air inlet and air outlet is available.
(See the "Installation Space Examples" for the minimum space III] Keep the unit upright in order to avoid compressor damage.
requirements.) 2. Decide on the transportation route.
Installation Space Examples 3. If a forklift is to be used, pass the forklift arms through the large
• The installation space requirement shown in figure 3 is a refer­ openings on the bottom of the unit. (Refer to figure 5)
ence for cooling operation when the outdoor temperature is 35°C. 4. If hanging the unit, use a cloth sling to prevent damaging the unit.
If the design outdoor temperature exceeds 35°C or the heat load Keeping the following points in mind, hang the unit following the
exceeds maximum capacity in all the outdoor unit, take an even procedure shown in figure 6.
large space on the intake shown in figure 3. • Use a sling sufficiently strong to hold the mass of the unit.
• During installation, install the units using the most appropriate of • Use 2 belts of at least 8m long.
the patterns shown in figure 3 for the location in question, taking • Place extra cloth or boards in the locations where the casing
into consideration human traffic and wind. comes in contact with the sling to prevent damage.
• If the number of units installed is more than that shown in the pat­ • Hoist the unit making sure it is being lifted at its center of gravity.
tern in figure 3, install the units so there are no short circuits. 5. After installation, remove the transportation clasp attached to the
• As regards space in front of the unit, consider the space needed large openings. (Refer to figure 6)

for the local refrigerant piping when installing the units. (Refer to figure 5)

• If the work conditions in figure 3 do not apply, contact your dealer 1. Fork
or Daikin directly. 2. Hole (large)
3. Transportation clasp (yellow)
(Refer to figure 3) 4. Fixed screws of transportation clasp
1. Front side
2. No limit to wall height (Refer to figure 6)
3. Service space of front side 1. Belt sling
4. Service space of suction side 2. Board
3. Hole (large)
For Patterns 1 and 2 in figure 3: 4. Hole (small)
5. For 5 HP type, carry the belt sling through the hole
• Wall height for front side no higher than 1500 mm. (large)
• Wall height on the suction side no higher than 500 mm.
• Wall height for sides - no limit.
• If the height is exceeded the above, calculate h1 and h2 shown 5. PLACING THE UNIT
in the figure below, and add h1/2 to the service space of front
side and h2/2 to the service space of suction side. • Make sure the unit is installed level on a sufficiently strong base to
prevent vibration and noise. (Refer to figure 7) .
• The base should be bigger around than the width of the unit's legs
(66 mm), and should support the unit. (Refer to figure 8)
If protective rubber is to be attached, attach it to the whole face of
the base.
• The height of the base should be at least 150mm from the floor.
• Secure the unit to its base using foundation bolts. (Use four com­
mercially available M12-type foundation bolts, nuts, and washers.)
h1 = A (Actual height) -1500J • The foundation bolts should be inserted 20 mm.
[ h2 = B (Actual height) - 500 (Refer to figure 7 ) ~
1. In the case of 8HP type or more, the ~
Note -a­ product cannot be supported with
four corners.
1. An inverter air conditioner may cause electronic noise gener­ In the case of 5HP type, the product can be supported
ated from AM broadcasting. Examine where to install the main with four corners.
air conditioner and electric wires, keeping proper distances 2. It is need in the case of 8HP type or more
away from stereo equipment, personal computers, etc. 3. Center of the product
Particularly for locations with weak reception, ensure there is
a distance of at least 3 meters for indoor remote controllers, (Refer to figure 8)
place power wiring and transmission wiring in conduits, and 1. Foundation bolt point (li>15 dia. : 4 positions)
ground the conduits. 2. Depth of product
3. Width of support leg
(Refer to figure 4)
1. Indoor unit Model A B
2. Branch switch, overcurrent breaker
3. Remote controller 5HP type 635 497
4. COOUHEAT selector (except RXQ-P) 8· 10HP type 930 792
5. Personal computer or radio 12·14·16 ·18HP type 1240 1102
2. When installing in a locations where there is heavy snowfall,
implement the following snow measures. Note-a­
• Ensure the base is high enough that intakes are not clogged • There are restrictions on the refrigerant pipe connecting order
by snow. between outdoor unit in the case of the multi system.
• Remove the rear intake grille to prevent snow from accumu­ See the Note in "2-1 Combination" for detail.
lating on the fins. • When installing on a roof, make sure the roof floor is strong
enough and be sure to water-proof all work.
3. If condensate may drip on downstairs (or walkway) depending
• Make sure the area around the machine drains properly by setting
on the floor condition, take a measure such as the installation of up drainage grooves around the foundation.
central drain pan kit (sold separately). Drain water is sometimes discharged from the outdoor unit when
4. The refrigerant R41 OA itself is nontoxic, nonflammable and is it is running.
safe. If the refrigerant should leak however, its concentration
may exceed the allowable limit depending on room size. DUE;) to
this it could be necessary to take measures against leakage.
See "14. CAUTION FOR REFRIGERANT LEAKS" for details.
6. REFRIGERANT PIPING (Refer to figure 10)
1. Refrigerant pipe
Note -a­ 2. Location to be brazed
3. Nitrogen
• All field piping must be installed by a licensed refrigeration tech­ 4. Taping
nician and must comply with relevant local and national regula­ 5. Handy valve
tions. 6. Regulator
• After piping work is complete, do not under any circumstances • The pressure regulator for the nitrogen released when doing
open the shutoff valve until "7. FIELD WIRING" and "10. CHECK­ the brazing should be set to 0.02 MPa (about 0.2kg/
ING OF DEVICE AND INSTALLATION CONDITIONS" are com­ cm':Enough to feel a slight breeze on your cheek).
plete.
• Do not use flux when brazing the refrigerant piping. Use the phos­ Note -a-
phor copper brazing filler metal (BCuP-2: JIS Z 3264/B-Cu93P­ Do not use anti-oxidants when brazing the pipe joints.
7101795: ISO 3677) which does not require flux. Residue can clog pipes and break equipment.
(Flux has extremely harmful influence on refrigerant piping sys­
tems. For instance, if the chlorine based flux is used, it will
6-4 Connecting the refrigerant piping
cause pipe corrosion or, in particular, if the flux contains fluo­ 1. Derection to bring out the pipes
rine, it will damage the refrigerant oil.) The local interunit piping can be connected either forward or to
6-1 Selection of piping material and Refrigerant the sides (taken out through the bottom) as shown in the figure 11.
(When passing out through the bottom, use the knock hole in the
branching kit bottom frame.)
• Use only pipes which are clean inside and outside and which do (Refer to figure 11)
not accumulate harmful sulfur, oxidants, dirt, cutting oils, mois­ 1. Left-side connection
ture, or other contamination. (Foreign materials inside pipes 2. Front connection
including oils for fabrication must be 30mg/10m or less.) 3. Right-side connection
• Use the following items for the refrigerant piping.
Precautions when knocking out knock holes
Material: Jointless phosphor-deoxidized copper pipe
• Open knock hole in the base frame by drilling the 4 concave
Size: See "6-5 Example of connection" to determine the cor­
around it with a 6mm bit. (Refer to figure 12)

rect size.
(Refer to figure 12)

Thickness: Select a thickness for the refrigerant piping which 1. Knock hole
complies with national and local laws. 2. Drill
For R410A, the design pressure is 4.0 MPa (40-bar). 3. Concave section
The minimum thickness of piping according to Japan's High­ • Be sure to avoid damaging the casing
Pressure Gas Safety Law (as of January 2003) is shown • After knocking out the holes, we recommend you remove any

below. burrs and paint them using the repair paint to prevent rusting.

Temper grade (0 type, 1/2H type) in the table indicate the • When passing electrical wiring through the knock holes, protect

material types specified in JIS H 3300. the wiring with a conduit or bushings, making sure not to damage

(unit: mm) the wiring.

Temper grade o type 2. Removing Pinch Piping


• When connecting refrigerant piping to an outdoor unit, remove
outer diameter ~6.4 I <1>9.5 I<1>12.71 ~15.9 the pinch piping. (Refer to figure 13)
smallest thickness 0.80 I 0.80 I 0.80 I 0.99 • Pinch piping should be removed using the'procedure in the fig­
(unit· mm) ure 13.

Temper grade 1/2H type (Refer to figure 13)

1. Shutoff valve (liquid side· gas side)


outer diameter I
~19.1 I~22.21 <1>25.41 ~28.61 ~31.81 <1>34.91 ~38.1 ~41.3 2. Service port
smallest thickness 0.8010.80 I 0.881 0.9911.10 11.21 11.3211.43 3. Pinch piping
4. Procedure 1:

Confirm the shutoff valve is closed.

• For piping work, follow the maximum tolerated length, difference 5. Procedure 2:
in height, and length after a branch indicated in the "6-5 Example Connect a charge hose to the service port of the liquid
of connection". side and gas side shutoff valves and remove the gas
• A refrigerant branching kit (sold separately) is needed for piping from the pinch piping.
branches and connection of piping between outdoor unit (in case 6. Procedure 3:
of multi system). After removing the gas from the pinch piping, dissolve
Use only separately sold items selected specifically according to the brazing using a burner and remove the pinch piping. (
the refrigerant branch kit selection in the "6-5 Example of con­
nection".
- & Caution - - - - - - - - - - - - - - - - - ­
After removing the gass, remove the pinch piping. .

Any gas remaining inside may blow off the pinch piping when you dis­

6-2 Protection against contamination solve the brazing, causing damage.

when installing pipes


Protect the piping to prevent moisture, dirt, dust, etc. from 3. Connecting refrigerant piping to outdoor units
entering the piping.
<In case of single system: 5-18HP type>

Place Installation period Protection method (Refer to figure 14)

More than a month Pinch the pipe 1. If connected to the front


Outdoor 2. When connected at lateral side (bottom)
Less than a month
Pinch or tape the pipe 3. Remove the shutoff valve cover to connect.
Indoor Regardless of the period
4. Remove the knock hole on the bottom frame and route
Note-a- the piping under the bottom frame.
Exercise special caution to prevent dirt or dust when passing pip­ 5. Gas side shutoff valve
ing through holes in walls and when passing pipe edges to the 6. Liquid side shutoff valve
exterior. 7. Refrigerant charge port
8. Brazing
6-3 Pipe connection 9. Liquid side accessory pipe (1)
• Be sure to perform nitrogen permutation or nitrogen blow 10. Gas side accessory pipe (1)
when brazing. (Refer to figure 10) 11. Gas side accessory pipe (2)
12. Liquid side accessory pipe (2)
Brazing without performing nitrogen permutation or nitrogen
13. Knockout hole
blow into the piping will create large quantities of oxidized film
14. Punch the knock hole.
on the inside of the pipes, adversely affecting valves and com­ 15. Gas side piping (field supply)
pressors in the refrigerating system and preventing normal 16. Liquid side piping (field supply)
operation.
Processing the Gas side accessory pipe (2) 4. Precautions when connecting piping betweemn outdoor units (In
Only in case of connecting at lateral side, cut the Gas side acces­ case of multi system)
sory pipe (2) referring the figure below. The Outdoor unit multi connection piping kit (sold separately) is
needed to connect piping between outdoor units in multi system.
Gas side
Only proceed with piping work after considering the limitations on
accessory
installation listed here and in "5. Branching the refrigerant piping",
pipe (2)
always referring to the kit's installation manual.
(1) The piping between outdoor units must be installed level
(Pattern 1) or with a rise (Pattern 2). Otherwise oil may pool
in the pipes.
CLitting
location
Pattern 1 Front connections

~
Level

Gas side accessory pipe (2)


o
Side (bottom) connections

Gas side piping


(field supply) o
()

o
(» co Pattern 2
Rise
Front connections m ml
()
o
l!l
~

Base
o
to indoor unit

So. (botton) "'0"";0"'


~
Fi9_F99
~
(mm)
Model A B C D to indoor unit
5HP type 166 16 199 246
{ ) Change to pattern 1 or pattern 2
8HP type 156 17 188 247 r--------------------,----------------------------------­
: Prohibited pattern J:
~-

10HP type 156 23 192 247


12HP type 150 29 192 247 i Downward inclination Front connections

14·16·18HP type 150 29 192 251 i to indoor unit '1O:::~F=-4~l....J-

<In case of multi system: RX(Y)Q20-S4P>

(Refer to figure 15)

iX
I
I
,
I
Side (bottom) connections flF9 m
~
1. If connected to the front I
I
2. When connected at lateral side (bottom) I
I to indoor unit
3. Remove the shutoff valve cover to connect. I
I ~ '--,
4. Remove the knock hole on the bottom frame and route I
I Downward inclination
the piping under the bottom frame.
5. Gas side shutoff valve
i
I
Oil remains in piping :
1
._-------------------------------------------------------~
6. Liquid side shutoff valve
7. Refrigerant charge port (2) To avoid the risk of oil detention in the stopping unit, always
8. Brazing connect the shutoff valve and the piping between outdoor
9. Liquid side accessory pipe (1) units as shown in the figure A or figure B.
.(~
#' . 10. Gas side accessory pipe (1)
11. Gas side accessory pipe (2)
12. Liquid side accessory pipe (2)
13. Knockout hole
14. Punch the knock hole.

Note -£'II

<Connecting Refrigerant Piping>

• When connecting the piping on site, be sure to use the accessory


piping.
• Make sure the onsite piping does not come into contact with other Front connections Side (bottom) connections
piping or the bottom frame or side panels of the unit.

<Multi Systems>

• The 5HP type cannot be used as an independent unit in a multi


system.
• The Outdoor unit multi connection piping kit (sold separately) is
needed when connecting piping between outdoor units.
Refer to the installation manual that comes with the kit when
doing this piping work.
<Outdoor unit multi connection piping kit>
r--------------------r---------------------------------­ Install the joint horizontally so that the attached warning label
:L Prohibited pattern:J
faces strait up, and the tilt is within ±15°. (Refer to figure 18-1)
I
I
I
Do not install vertically. (Refer to figure 18-2)
I
I
Front connections Maintain a straight portion of 500 mm or more until the split of
I
I
I
the joint without wrapping any onsite piping around this area.
I
I to indoor unit )------tt---.----tt------it---th Over 500 mm of straight area can be maintained by connect­
I
I ing at least 120 mm of onsite pipe (straight) to the joint.
I
I (Refer to figure 18-3)
Side (bottom) connections (Refer to figure 18)
1. Warning label
2. Horizontal surface
to indoorunit \------.-11----+1----11------,
3. ±15° or less
4. Ground
Oil remains in the stopping outdoor unit. 5. Onsite pipe (120mm length or more)
6. Straight part of 500mm or more

_?~-~~~:!~-~~~~~~-~~!_~~~~~~-~-------------------------~
Unit A X Unit A X
Unit B

Oil remains in the outdoor unit B when the system stops.


Change as shown in the figure below.
Rising height:
200 mm or more

to indoor
unit
o
(3) If the piping length between the outdoor units exceeds 2 m,
create a rise of 200 mm or more in the gas line under a length
of 2 m 'from the outdoor unit multi connection piping kit.

If less than 2m

Outdoor unit gas pipe

o to indoor unit "\-­ ---'--"""'----_------J

I Less than 2~ I

If 2 m or more

5. Branching the refrigerant piping


Heed the restrictions below when installing the refrigerant branch­
ing kit and read the installation instruction manual with the kit.
(Improper installation could lead to mal'functioning or breakdown
of the outdoor unit.)
<REFNET joint>
Install the REFNET joint so it splits horizontally or vertically.
(Refer to figure 16)
1. Horizontal surface
2. ±30° or less
3. Horizontal
4. Vertical

<REFNET header>

Install the REFNET header so it splits horizontally.

(Refer to 'figure 17)

1. Horizontal surface
~ .. ~
~~

~ ~
.-­ .-. .111'-­ .-­ en
Example of connection I
(J1
(Connection of 8 indoor units)
(*1) "-.=" indicate the Outdoor unit multi m
I. ..
Single outdoor
connection piping kit
(*2) In case of multi outdoor system, re-read to the first
system
H11 REFNET header u • • •
><
Q)
Outdoor unit multi connection piping kit as seen
from the indoor unit.
3
"'C
Ci
....
o
Multi outdoor n
o
~
system Cdefg H1
-7-7-7-7-E-7-~--~
::::J
First Outdoor \ h i j kim n Ip ::::J
unit multi connection 1 2 3 4 5 6
CD
piping kit Indoor units <[I]-ffi]) n
....
Between outdoor (*2)
Actual pipe length
Pipe length between outdoor (*2) and indoor units ~ 165m
Example unit [ID : a + b + c + d + e + f + g + p ~ 165m I
Example unit ffiJ : a + b + h ~ 165m, unit [ID : a + i + k ~ 165m Example unit rnJ : a + i ~ 165m I o·
Maximum and indoor units Equivalent length EqUivalent pipe length between outdoor (*2) and indoor units ~ 190m (assume equivalent pipe length of REFNET joint to be 0.5m, that of REFNET header to be 1m, calculation purposes) (See Note 1 - Next page) ::::J
allowable
Total extension lenath Total pipe length from outdoor unit (*2) to all indoor units ~ 1000m
length

J'ft rr
Between outdoor unit and Outdoor unit multi Actual pipe length
Pipe length between outdoor unit and Outdoor unit multi connection piping kit ~ 10m, Equivalent length between outdoor unit and Outdoor unit multi connection piping kit ~ 13m
connection piping kit (Only for multi system) Equivalent length
r 10m (Equivalent length: 13m)
Between outdoor and indoor units Difference in height Difference in height between outdoor and indoor units (H1) ~ 50m ( ~ 90m if the outdoor unit is below)
Allowable s 10m (Equivalent length: 13m)
height Between indoor and indoor units Difference in height Difference in height between indoor units (H2) ~ 15m r It
length S I t 10m (Equivalent length: 13m)
Between outdoor and outdoor units Difference in heiaht Difference in heiaht between outdoor unit (H3) ~ 5m ------
Pipe length from first refrigerant branch kit (either REFNET joint or REFNET header) to indoor unit ~ 40m (See Note 2 - Next page)
Allowable length after the branch Actual pipe length
Example unit [ID : b + c + d + e + f + g + p ~ 40m I Example unit ffiJ : b + h ~ 40m, unit 1m :i + k ~ 40m
Refrigerant branch kit selection How to select the REFNET joint How to select the REFNET header
• When using REFNET joint at the first branch counted from the outdoor unit side. • Choose from the following table in accordance with the total capacity index of all the indoor units connected below the REFNET header.
Choose from the following table in accordance with the outdoor unit capacity type. • Note: 250 type indoor unit cannot be connected below the REFNET header.
Refrigerant branch kits can only be
(Example: REFNET joint A)
used with R410A.

<200 KHRP26M22H (Max. 4 branch)

5HP type KHRP26A22T KHRP26M33H (Max. 8 branch)

& • When multi outdoor system are installed, be sure to 200 ~ x< 290
8, 10HP type KHRP26A33T KHRP26M72H (Max. 8 branch) (See Note 3 - Next page)

use the special separately sold Outdoor unit multi 290 ~x< 640
connection piping kit. 12-22HP type KHRP26A72T KHRP26M73H (Max. 8 branch) + KHRP26M73HP

640 ~
The table at right shows how to select the proper kit. 24HP type­ KHRP26A73T + KHRP26M73TP
• Choose the REFNET joints other than that for the first branch from the following table in accordance with the total
How to select the Outdoor unit multi connection piping kit (This is required when the system is multi outdoor unit system.)
capacity index of all the indoor units connected below the REFNET joint.
• Choose from the following table in accordance with the number of outdoor units.

<200 KHRP26A22T r'MfflMIffllI€H.IIImRW g.I.i,I44iI.j,i!L3IIi!1M1.@i"j·


'200 ~ x< 290 2 un~ts ~ BHFP22P100
KHRP26A33T
3 units BHFP22P151
290 ~ x< 640 KHRP26A72T
640~ KHRP26A73T + KHRP26M73TP

Example REFNET joint B: indoor units !1J+1m


Example for indoor units connected downstream Example REFNET joint C: indoor units @]+@]+[§]+ffiJ+!1J+[ID Example REFNET header: indoor units [I]+[g]+@]+@]+[§]+[§]
Example REFNET header: indoor units [I]+[g]+@]+@]+[§]+[§]+!1J+[ID

Pipe size selection Temper grade and wall thickness for pipes. Piping between Outdoor unit and first refrigerant branch kit Piping between refrigerant branch kits
(Temper grade, 0 type and 1/2H type indicate the material types specified in JIS Piping between first Outdoor unit multi connection piping kit and first refrigerant • Choose from the following table in accordance with the total capacity index of
& Caution H 3300.) (Unitmm),
branch kit. (Part A) all the indoor units connected below this.
The thickness of the pipes in the table shows the requirements of Japanese
• Choose from the following table in accordance with the outdoor unit capacity type. • Do not let the connection piping exceed the main refrigerant piping size. (Unitmm)

Copper tube w.T.


High Pressure Gas Control low. (As of Jan. 2003)

The thickness and material shall be selected in accordance with local code.

Copper tube 0.0.


(Minimum reqUirement)
Temper grade
Piping between Outdoor unit multi connection piping kits. (Part B)

Piping between outdoor unit and Outdoor unit multi connection piping kit. (Part C)
_a'!l11l!i1UiW
• Choose from the following table in accordance with the total capacity type of all @!ll.I- MIIM!f@ffflj
<1>6.4 0.80 <1>15.9
For the multi outdoor unit system, select in accordance with the following figure.
the outdoor units connected above Outdoor unit multi connection piping kit.
<1>9.5 0.80
o type (Unitmm) <1>19.1 <1>9.5
<1>12.7 0.80 200 ~ x< 290 <1>22.2
<1>15.9 0.99 Outdoor unit capacity type <1>12.7
290 ~ x< 420
<1>28.6
<1>19.1 0.80 420 ~ x< 640 <1>15.9
5HP type <1>15.9
<1>22.2 0.80 640 ~ x< 920 <1>34.9
8HP type <1>19.1 <1>9.5 <1>19.1
<1>25.4 0.88 10HP type 920 ~ <1>41.3
<1>22.2
<1>28.6 0.99 Piping between refrigerant branch kit and indoor unit
1.10
1/2H type I 12-16HP type
<1>28.6
<1>12.7
• Match to the size of the connection piping on the indoor unit.
<1>31.8 18-22HP type (Unitmm)
<1>34.9 1.21 <1>15.9
24HP type
<1>38.1 1.32 <1>34.9
26-34HP type
<1>41.3 1.43 <1>19.1
36-54HP type
<1>41.3
(See Note 1 - Next page)

How to calculate the additional refrigerant to be Total length (m)] (Total length (m)] (Total length (m)] (Total length (m)) (Total length (m))

charged R= I of liquid piping xO.37 + of liquid piping xO.26 + of liquid piping xO.18 + of liquid piping xO.12 + of liquid piping xO.059

(
size at <1>22.2 size at <1>19.1 size at <1>15.9 size at <1>12.7 size at <1>9.5

Additional refrigerant to be charged R (kg)

(R should be rounded off in units of 0.1 Kg.)

Total length (m))

+ I of liquid piping xO.022


(
size at <1>6.4
*Note 1
When the equivalent pipe length between outdoor and indoor units is 90m or more, the size of main pipes (both gas-side and liquid-side) must be increased.
Depending on the length of the piping, the capacity may drop, but even in such case it is able to increase the size of main pipes.

(Refer to figure 9)
1. Outdoor unit
2. Main pipes
3. Increase
4. The first refrigerant branch kit
5. Indoor unit
• Diameter of above case
Model Gas Liquid Model Gas Liquid Model Gas Liquid Model Gas Liquid

RX(Y)Q5 Type <1>19.1 Not RX(Y)Q20 Type <1>31.8* <1>19.1 RX(Y)Q34 Type <1>38.1* <1>22.2 RX(Y)Q48 Type Not <1>22.2
Increased Increased
RX(Y)Q8 Type <1>22.2 <1>12.7 RX(Y)Q22 Type <1>31.8* <1>19.1 RX(Y)Q36 Type Not <1>22.2 RX(Y)Q50 Type Not <1>22.2
Increased Increased
RX(Y)Q10 Type <1>25.4* <1>12.7 RX(Y)Q24 Type Not <1>19.1 RX(Y)Q38 Type Not <1>22.2 RX(Y)Q52 Type Not <1>22.2
Increased Increased Increased
RX(Y)Q12 Type Not <1>15.9 RX(Y)Q26 Type <1>38.1 * <1>22.2 RX(Y)Q40 Type Not <1>22.2 RX(Y)Q54 Type Not <1>22.2
Increased Increased Increased
RX(Y)Q14 Type Not <1>15.9 RX(Y)Q28 Type <1>38.1 * <1>22.2 RX(Y)Q42 Type Not <1>22.2 *If available on the site, use this size.
Increased Increased
Otherwise, it can not be increased.
RX(Y)Q 16 Type <1>31.8* <1>15.9 RX(Y)Q30 Type <1>38.1* <1>22.2 RX(Y)Q44 Type Not <1>22.2
Increased
RX(Y)Q18 Type <1>31.8* <1>19.1 RX(Y)Q32 Type <1>38.1 * <1>22.2 RX(Y)Q46 Type Not <1>22.2
Increased
*Note 2

Allowable length after the first refrigerant branch kit to indoor units is 40 m or less, however it can be extended up to 90 m if all the following conditions are satisfied. (In case of" Branch with REFNET joint")

Required Conditions I Example Drawings


1. It is necessary to increase the pipe size between the first branch kit [ID b+c+d+e+f+g+p~ 90 m Increase the pipe size as follows
and the final branch kit. (Reducers must be procured on site) increase the pipe size of b, c, d, e, f, g <I> 9.5 ~ <1>12.7 <1>15.9 ~ <1>19.1 <1>22.2 ~ <1>25.4* <1>34.9 ~ <1>38.1 *
However, the pipes that are same pipe size with main pipe must not <1>12.7 ~ <1>15.9 <1>19.1 ~ <1>22.2 <1>28.6 ~ <1>31.8*
be increased.
2. For calculation of Total extension length, the actual length of a+bx2+cx2+dx2+ex2+fx2+gx2
above pipes must be doubled. (except main pipe and the pipes +h+i+j+k+l+m+n+p~1000 m
Outdoor unit REFNET joint (A-G)
that are not increased)

3. Indoor unit to the nearest branch kit ~ 40 m h, i, j....... P ~ 40 m __ L_f1__tlndfm__mm-1 :1


4. The difference between
The farthest indoor unit [ID
[Outdoor unit to the farthest indoor unit] and [Outdoor unit
The nearest indoor unit [I]
to the nearest indoor unit]
( a + b + c + d + e +f + g+ p ) - (a + h ) ~ 40 m
~40 m
*If available on the site, use this size. Otherwise it can not be increased.
*Note 3
If the pipe size above the REFNET header is <1>34.9 or more, KHRP26M73HP is required.
/~,
7. FIELD WIRING • Specifications for local wiring are in compliance with IEC60245.
• Use wire type H05VV when protected pipes are used.

- & Caution - - - - - - - - - - - - - - - - - ­
Use wire type H07RN-F when protected pipes are not used.

Phase and Minirrum RecOin-


Voltage mended
• All field wiring and components must be installed by a licensed frequency circuit amp. fuses
electrician and must comply with relevant local and national reg­
RX(Y)Q5PY1 <\>3,50Hz 380-415V 11.9A 15A
ulations.
RX(y)Q8PY1 <\>3,5OHz 380-415V 18.5A 25A
• Be sure to use a dedicated power circuit. Never use a power sup­
ply shared by another appliance. RX(Y)Q10PY1 <\>3,50Hz 380-415V 21.6A 25A
• Never install a phase advancing capacitor. As this unit is equipped RX(Y)Q12PY1 <\>3,5OHz 38D-415V 22.7A 25A
with an inverter, installing a phase advancing capacitor will not only RX(Y)Q14PY1 <\>3,5OHz 38D-415V 31.5A 35A
deteriorate power factor improvement effect, but also may cause RX(y)Q16PY1 <\>3,5OHz 380-415V 31.5A 35A
capacitor abnormal heating accident due to high-frequency waves. RX(y)Q18PY1 <\>3,5OHz 38D-415V 32.5A 40A
• Only proceed with wiring work after blocking off all power. RX(y)Q20PY1 <\>3,5OHz 380-415V 41.2A 50A
• Always ground wires in accordance with relevant local and RX(y)Q22PY1 <\>3,50Hz 380-415V 44.3A 50A
national regulations.
RX(y)Q24PY1 <\>3,5OHz 380-415V 50.0A 60A
• This machine includes an inverter device. Connect earth and
RX(Y)Q26PY1 <\>3,50Hz 380-415V 51.0A 60A
leave charge to eliminate the impact on other devices by reducing
noise generated from the inverter device and to prevent leaked RX(Y)Q28PY1 <\>3,50Hz 38D-415V 54.1A 60A
current from being charged in the outer hull of the product. RX(y)Q30PY1 <\>3,5OHz 38D-415V 55.2A 70A
• Do not connect the ground wire to gas pipes, sewage pipes, light­ RX(Y)Q32PY1 <\>3,5OHz 380-415V 63.0A 70A
ning rods, or telephone ground wires. RX(y)Q34PY1 <\>3,5OHz 380-415V 64.0A BOA
Gas pipes: can explode or catch fire if there is a gas leak. RX(Y)Q36PY1 <\>3,5OHz 380-415V 65.0A 80A
Sewage pipes: no grounding effect is possible if hard plastic pip­ RX(Y)Q38PY1 <\>3,5OHz 380-415V 73.7A goA
ing is used. RX(y)Q40PY1 <\>3,50Hz 3BO-415V 81.5A goA
Telephone ground wires and lightning rods: dangerous when
RX(y)Q42PY1 <\>3,50Hz 38D-415V 82.5A 100A
struck by lightning due to abnormal rise in electrical potential in
RX(y)Q44PY1 <\>3,50Hz 38D-415V 83.5A 100A
the grounding.
RX(Y)Q46PY1 <\>3,50Hz 380-415V 86.6A 100A
'(./: • Be sure to install an earth leakage circuit breaker.
This unit uses an inverter, so install the earth leakage circuit RX(y)Q48PY1 <\>3,50Hz 380-415V 87.7A 100A
breaker that be capable of handling high harmonics in order to RX(Y)Q5OPY1 <\>3,50Hz 380-415V 96.5A 110A
prevent malfunctioning of the earth leakage circuit breaker itself. RX(Y)Q52PY1 <\>3,5OHz 38D-415V 96.5A 110A
• Earth leakage circuit breaker which are especially for protecting RX(y)Q54PY1 <\>3,5OHz 380-415V 97.5A 110A
ground-faults should be used in conjunction with main switch or
Note-a.
fuse for use with wiring. The above table indicates power specifications for standard combi­
nations (see 2. INTRODUCTION).
Note "1:~ If using anything other than the above combinations in a multi sys­
• Electrical wiring must be done in accordance with the wiring dia­ tem, calculate using the following procedure.
grams and the description herein. Minimum circuit amp value: add the minimum circuit amp values
• Do not operate until refrigerant piping work is completed. for each independent unit
(If operated before complete the piping work, the compressor may Recommended fuse capacity: select the fuse capacity with the next
be broken down.) higher value of the calculated minimum circuit amp. multiplied by 1.1.
• Never remove thermistor, sensor or etc. when connecting power Ex: Combining the RXYQ30PY1 using RXYQ8PY1 ,
wiring and transmission wiring. RXYQ10PY1, and RXYQ12PY1.
(If operated with thermistor, sensor or etc. removed, the compres­ Minimum circuit amp. of the RXYQ8PY1 in table above = 18.5 A
sor may be broken down.) Minimum circuit amp. of RXYQ10PY1 in table above = 21.6 A
• This product have reversed phase protection detector that only Minimum circuit amp. of RXYQ12PY1 in table above = 22.7 A
works when the power is turned on. If there exists black out or the Accordingly, the minimum circuit amp. of the RXYQ30PY1 = 18.5
power goes on and off which the product is operating, attach a + 21.6 + 22.7= 62.8 A
reversed phase protection circuit locally. Running the product in Multiplying the result above by 1.1 (62.8 x 1.1) = 69.1 A, so the
reversed phase may break the compressor and other parts. recommended fuse capacity would be 70 A.
• Attach the power wire securely. Introducing power with a missing
{ N-phase or with a mistaken N-phase will break the unit.
• Never connect the power supply in reversed phase.
7-2 Wiring Connection Example for Whole
System
The unit can not operate normally in reversed phase.
(Refer to figure 19)
If you connect in reversed phase, replace two of the three phases.
1. Power supply
• Make sure the electrical unbalance ratio is no greater than 2%. If 2. Main switch
it is larger than this, the unit's lifespan will be reduced. 3. Earth leakage circuit breaker
If the ratio exceeds 4%, the unit will shut down and an malfunction 4. Fuse
code will be displayed on the indoor remote controller. 5. Outdoor unit
• Connect the wire securely using designated wire and fix it with 6. COOUHEAT selector (except RXQ-P)
attached clamp without applying external pressure on the termi­ 7. Remote controller
nal parts (terminal for power wiring, terminal for transmission wir­ 8. Indoor unit

ing and earth terminal). Note "1:~

• Make sure the weak electric wiring (i.e. for the remote control­
7-1 Power circuit, safety device, and cable
ler, between units, etc.) and the power wiring do not pass near
each other, keeping them at least 50 mm apart.
requirements
Proximity may cause electrical interference, malfunctions, and
• A power circuit (see the following table) must be provided for con­ breakage.
nection of the unit. This circuit must be protected with the required • Be sure to connect the power wiring to the power wiring termi­
safety devices, i.e. a main switch, a slow blow fuse on each phase nal block and secure it as described in "7-5 Power Wiring
and an earth leakage circuit breaker. Connection Procedure".
• Transmission wiring should be secured as described in "7-4
• When using residual current operated circuit breakers, be sure to
Transmission Wiring Connection Procedure".
use a high-speed type (1 second or less) 200mA rated residual • Secure wiring with clamp such as insulation lock ties to avoid
operating current. contact with piping.
• Use copper conductors only. • Shape the wires to prevent the structure such as the EL.
• Use insulated wire for the power cord. COMPO. BOX lid deforming. And close the cover firmly.
• Select the power supply cable type and size in accordance with • 5HP type can not compose multi system.
relevant local and national regulations.
7-3 Leading wire Procedure [2J Between outdoor unit and outdoor unit of same system

• The power wiring and ground wiring are passed out from the (Only for multi system)

power wiring hole on the sides, the front (knock hole) or the bot­ Max. wiring length : 30 m

tom frame (knock hole) . ~ Transmission wiring to COOUHEAT selector

• The transmission wiring is passed out from the wiring hole (knock Max. wiring length : 500 m

hole) on the front of the unit or from a piping hole.

(Refer to figure 20)


• The transmission wiring inside the EL.COMPO.BOX should be

1. Electrical wiring diagram secured using the clamp (1) as shown in figure 24.

2. On the back of the EL .COMPO. BOX lid.


3. Power wiring, ground wiring (inside conduit) (Refer to figure 24)
4. (When the wiring is routed out through the side paneL) 1. In the EL.COMPO.BOX
5. Transmission wiring 2. Retain to the EL.COMPO.BOX with the accessory clamp
6. Pipe opening (1 ).
7. Conduit • Outside the units, the transmission wiring must be finished simul­

8. For power wiring and ground wiring taneously with the local refrigerant piping, and wound with tape

9. Through cover (field supply) as shown in figure 25.

10. Cut off the shaded zones before use. (Refer to figure 25)
11. Burr 1. liqUid pipe
12. Knockout hole 2. Gas pipe
13. For transmission wiring 3. Transmission wiring
Note-~ 4. Insulation material
• Open the knock holes with a hammer or the like. 5. Finishing tape
• After knocking out the holes, we recommend you remove any
• For multi system:
burrs and paint them using the repair paint to prevent rusting.
1. Transmission wiring between outdoor units in the same piping
• When passing wiring through the knock holes, remove burrs
system must be connected to terminals Q1 and Q2 (TO MULTI
around the knock holes and protect the wiring with protective
UNIT).
tape. (Refer to figure 20)
Connecting the wires to the F1, F2 (TO OUT/D UNIT) termi­
• If small animals might enter the unit, block off any gaps (hatching nals results in system malfunction.
parts in figure 20) with material (field supply). 2. Wiring to other systems should be connected to terminals F1
and F2 (TO OUT/D UNIT) on the PC-board of the master unit. (
7-4 Transmission Wiring Connection Procedure The outdoor unit that connected transmission wiring to indoor ~.
• Referring to figure 21 , 22 connect the transmission wiring between unit is the master unit. The others are sub unit.
outdoor unit and indoor unit, outdoor unit and outdoor unit of other
system, outdoor unit and outdoor unit of same system (only multi - ~ Caution - - - - - - - - - - - - - - - - - ­
system) or to COOUHEAT selector (except RXQ-P).
(Refer to figure 21) • Do not connect the power wiring to terminals for the transmission

1. Connection example for single system wiring. Doing so would destroy the entire system.

2. Outdoor unit • When connecting wires to the terminal block on the PC-board, too

3. COOUHEAT selector (except RXQ-P) much heat or tightening could damage the PC-board. Attach with

4. To outdoor unit of other system care.

5. Match up terminal symbols. (Has polarity) See the table below for the tightening torque of the transmission

6. Use duplex wires wiring terminals.

7. Indoor unit
8. Never connect the power wire Screw size Tightening torque (N . m)
(Refer to figure 22) M3 (A5P) 0.53 - 0.63
1. Connection example for multi system
M3.5 (A1P) 0.80 -0.96
2. Outdoor unit A (Master unit)
3. Outdoor unit B (Sub unit)
4. COOUHEAT selector (except RXQ-P)
5. To indoor unit 7-5 Power Wiring Connection Procedure

6. To outdoor unit of other system Be sure to connect the power supply wiring to the power supply ter­

• All transmission wiring is to be procured on site. All wiring should minal block and hold it in place using the included clamp as shown in

the figure 26.

use sheathed vinyl cord 0.75-1.25 mm' or cable (duplex). (Triplex


only for the COOUHEAT selector.) (Refer to figure 26)
• Transmission wiring (About the symbol m- ~,see figure 21,22) 1. Power supply (3N-50Hz 380-415V)
2. Earth leakage circuit breaker
6
\.
should be done within the following limitations.
3. Branch switch, Overcurrent breaker
If they are exceeded, transmission problems may occur. 4. Ground wire
mBetween outdoor unit and indoor unit 5. Attach insulation sleeves
Between outdoor unit and outdoor unit of other systems 6. Power supply terminal block
Max. wiring length : 1,000 m 7. Ground terminal
Max. total wiring length : 2,000 m 8. Clamp (1) (accessory)
Max. no. of branches : 16 • The L1, L2, L3 and N phases of the power wiring should be

[Note]
secured separately to the hook using the included clamp (1).

No branch is allowed
• The ground wiring should be bound to the power wiring using the

after branch
included clamp (1) to prevent outside force from being applied to

(See figure 23)


the terminal area.

Max. no. of outdoor units of other system


• Wire so that the ground wiring does not come into contact with the

that can be connected


compressor lead wiring. If they touch, this may have an adverse

:10
effect on other devices.

(Refer to figure 23) - ~ Caution - - - - - - - - - - - - - - - - - ­


1. Outdoor unit
2. Indoor unit • Be sure to use crimp-style terminal with insulating sleeves for

3. Branch line 1 connections. (See the figure below.)

4. Branch line 2
5. No branch is allowed after branch Power wire
6. Main line Crimp-style terminal
7. Central remote controller, etc. /
8. Branch line 3
9. Transmission wiring between outdoor unit and indoor unit
10. Transmission wiring between outdoor unit and outdoor unit
'f

• For wiring, use the designated power wire and connect firmly, 8. AIR TIGHT TEST AND VACUUM DRY­
then secure to prevent outside pressure being exerted on the ter­
minal board. ING
• Use an appropriate screwdriver for tightening the terminal screws.
A screwdriver with a small head will strip the head and make Note-~
• Always use nitrogen gas for the airtightness test.
proper tightening impossible.
• Over-tightening the terminal screws may break them. • Absolutely do not open the shutoff valve until the main power ciruit
See the following table for the tightening torque of the terminal insulation measurement has been completed. (measuring after
screws. the shutoff valve is opened will cause the insulation value to drop.)

Screw size Tightening torque (N·m)


8-1 Preparations
<Needed tools>
M8 Power terminal, ground terminal 5.5 -7.3
• To prevent entry of any impurities and insure suffi­
• When pulling the ground wire out, wire it so that it comes through cient pressure resistance, always use the special
Gauge manifold
the cut out section of the cup washer. (See the figure below.) An tools dedicated for R41 OA.
Charge hose
improper ground connection may prevent a good ground from • Use charge hose that have pushing stick for con-
valve
being achieved. necting to service port of shutoff valves or refriger­
ant charge port.
Cup washer
• The vacuum pump for vacuum drying should be
able to lower the pressure to -100.7kPa

Crimp-style terminal Vacuum pump


(5 Torr -755mm Hg).
• Take care the pump oil never flow backward into the
refrigerant pipe during the pump stops.
Cut out section
<The system for air tight test and vacuum drying>
• When two wires are connected to a single terminal, connect them Referring to figure 28, connect an nitrogen tank, refrigerant tank,
so that the rear sides of the crimp contacts face each other. Also, and a vacuum pump to the outdoor unit.
make sure the thinner wire is on top, securing the two wires simul­ The refrigerant tank and the charge hose connection to refrigerant
taneously to the resin hook using the included clamp (1). charge port or the valve A, C in figure 28 are needed in "11. ADDI­
Terminal Crip style TIONAL REFRIGERANT CHARGE AND CHECK OPERATION".
block terminal Wire: narrow The shutoff valve and valve A-C in figure 28 should be open or
Wire: thick closed as shown in the table below.
(Refer to figure 28)
1. Gauge manifold
2. Nitrogen
3. Measuring device
4. R410A tank (with siphon)
5. Vacuum pump
6. Charge hose
7. Liquid side shutoff valve
7-6 Procedure for Wiring Inside Units 8. Gas side shutoff valve
• Referring to figure 27, secure and wire the power and transmis­ 9. Shutoff valve service port
sion wiring using the included clamp (1), (2), and (3). 10. Valve B
11. Valve C
(Refer to figure 27) 12. Valve A
1. Retain with accessory clamp (3). 13. Outdoor unit
2. Electric conduit 14. Refrigerant charge port
3. When routing out the power/ground wires from the left 15. To indoor unit
side. 16. Interunit pipings
4. When routing out the transmission wiring from the open­ 17. Refrigerant flow
ing for piping.
5. When routing out the power/ground wires from the front. Valve shutoff valve
6. Clear over 50 mm. State of valve A, Band C and
7. When routing out the transmission wiring from the shutoff valves Liquid Gas
A B C
( knockout hole.
8. Retain to the back of the column support with the acces­ Air tight test, Vacuum drying
side side

sory clamp (2). (Close valve A and shutoff valves


Close Open Open Close Close
9. When routing out the power/ground wires from the right certainly. Otherwise the refrigerant
side. in the unit are released.)
10. Power wiring
11. Transmission wiring Note-~
12. Ground wire The airtightness test and vacuum drying

13. Secure to the back side of the support beam using the should be done using the liquid side and

accessory clamp (1). gas side shutoff valve service ports.

14. Retain to the back of the column support with the acces­ See the [R410A] Label attached to the front

sory clamp (2). plate of the outdoor unit for details on the

15. When wiring, exercise sufficient caution not to detach the location of the service port (see figure at

acoustic insulators from the compressor. right).

See [Shutoff valve operation procedure] in

-& Caution - - - - - - - - - - - - - - - - - ­ "11-1 Before working" for details on handling


[R410A] Label
the shutoff valve.

• The transmission wiring must be at least 50 mm away from the


The refrigerant charge port is connected to

power wiring.
unit pipe.

• Make sure all wiring do not contact to the pipes (hatching parts in
When shipped, the unit contains the refrigerant, so use caution

the figure 27).


when attaching the charge hose.

• After wiring work is completed, check to make sure there are no


loose connections among the electrical parts in the
EL.COMPO.BOX.
8-2 Air tight test and vacuum drying method 10. CHECKING OF DEVICE AND INSTAL­
After finished piping work, carry out air tight test and vacuum drying.
LATION CONDITIONS
<Air tight test>
Pressurize the liquid and gas pipes to 4.0MPa (40bar) (do not Be sure to check the followings.
pressurize more than 4.0MPa (40bar». If the pressure does not For those doing electrical work
drop within 24 hours, the system passes the test. 1. Make sure there is no faulty transmission wiring or loosing of a
If there is a pressure drop, check for leaks, make repairs and per­ nut.
form the airtight test again. See "7-4 Transmission Wiring Connection Procedure".
<Vacuum drying> 2. Make sure there is no faulty power wiring or loosing of a nut.
Evacuate the system from the liquid and gas pipes by using a vac­ See "7-5 Power Wiring Connection Procedure".
uum pump for more than 2 hours and bring the system to
-100.7kPa or less. After keeping the system under that condition
3. Has the insulation of the main power circuit deteriorated?
for more than 1 hour, check if the vacuum gauge rises or not. If it Measure the insulation and check the insulation is above regular
value in accordance with relevant local and national regulations.
rises, the system may either contain moisture inside or have
leaks. For those doing pipe work
1. Make sure piping size is correct.
Note-~ See "6-1 Selection of piping material and Refrigerant branch­
If moisture might enter the piping, follow belows.
ing kit".
(I.e., if doing work during the rainy season, if the actual work
2. Make sure insulation work is done.
takes long enough that condensation may form on the inside of
See "9. PIPE INSULATION".
the pipes, if rain might enter the pipes during work, etc.)

(1) After performing the vacuum drying for two hours, pressurize to
3. Make sure there is no faulty refrigerant piping.
See "6. REFRIGERANT PIPING".
0.05 MPa (i.e., vacuum breakdown) with nitrogen gas, then
depressurize down to -100.7 kPa for an hour using the vacuum
pump (vacuum drying).
11. ADDITIONAL REFRIGERANT
(2) If the pressure does not reach -100.7 kPa even after depressur­ CHARGE AND CHECK OPERATION
izing for at least two hours, repeat the vacuum breakdown - vac­
The outdoor unit is charged with refrigerant when shipped from the

uum drying process.


factory, but depending on the size and length of the piping when r'

After vacuum drying, maintain the vacuum for an hour and make sure
the pressure does'not rise by monitoring with a vacuum gauge.
installed, it may require additional charging. ~

For charging the additional refrigerant, follow the procedure in this

9. PIPE INSULATION chapter.

And then carry out the check operation.

• Insulation of pipes should be done after performing "8. AIR TIGHT


TEST AND VACUUM DRYING". 11-1 Before working

• Always insulate the liquid side piping and gas side piping in the [About the refrigerant tank]

interunit piping and refrigerant branching kit. Failing to insulate Check whether the tank has a siphon pipe before charging and place

the pipes could cause leaking or burns. (The gas side piping can the tank so that the refrigerant is charged in liquid form. (See the fig­

reach temperatures of 120°C. Be sure the insulation used can ure below.)

, withstand such temperatures.) With siphon pipe


• Reinforce the insulation on the refrigerant piping according to the
installation environment. Condensation might form on the surface Stand the tank upright and charge.
of the insulation. (The siphon pipe goes all the way inside,
• Ambient temperature: 30°C, humidity: 75% to 80% RH: min.
thickness: 15 mm.
• If the ambient temperature exceeds 30°C and the humidity
UJ
Other tanks
so the tank does not need be put
upside-down charge in liquid form.)

80% RH, then the min. thickness is 20 mm.

V
• If there is a possibility that condensation on the shutoff valve
might drip down into the indoor unit through gaps in the insulation Stand the tank upside-down and charge.
and piping because the outdoor unit is located higher than the
indoor unit, etc., this must be prevented by caulking the connec­
tions, etc. (Refer to figure 29)
• The piping lead-out hole lid should be attached after opening a
knock hole. (Refer to figure 30) -&C~~ (
• If small animals and the like might enter the unit through the pip­ • Always use the proper refrigerant (R410A). If charged with the

ing lead-out hole, close the hole with blocking material (procured refrigerant containing an improper material, it may cause an

on site) after completion of "11. ADDITIONAL REFRIGERANT explosion or accident.

CHARGE AND CHECK OPERATION". (Refer to figure 30) • R410A is a mixed refrigerant, so charging it as a gas will cause

(Refer to figure 29) the refrigerant composition to change, which may prevent normal

1. Liquid side shutoff valve operation.

2. Gas side shutoff valve


3. Indoor interunit piping [Shutoff valve operation procedure]

4. Insulation material When operating the shutoff valve, follow the procedure instructed

5. Coking, etc. below.

6. Refrigerant charge port


Note-~
(Refer to figure 30) • Do not open the shutoff valve until "10. CHECKING OF DEVICE

1. Piping lead-out hole lid AND INSTALLATION CONDITIONS" are completed. If the shutoff

2. Open a knock hole at "WZI". valve is left open without turning on the power, it may cause refrig­

3. Block "~". erant to buildup in the compressor, leading insulation degrada­

4. Liquid side piping tion.

5. Gas side piping • Be sure to use the correct tools.

Note-~ The shutoff valve is not a back-seat type. If forced it to open, it

• After knocking out the holes, we recommend you remove burrs in might break the valve body.

the knock holes (see figure 30) and paint the edges and areas • When using a service port, use the charge hose.
around the edges using the repair paint. • After tightening the cap, make sure no refrigerant gas is leaking.
[Tightening torque]
(Refer to figure 34)
The sizes of the shutoff valves on each model and the tightening
1. Service port
torque for each size are listed in the table below.
2. Cap
3. Hex holes
<Size of Shutoff Valve>
4. Shaft (valve body)
5HP type I I I
8HP type 10HPtype 12HPtype 14HP type 16HP type 18HP type 5. Seal section

l\> 9.5 l\> 12.7


Liquid The 12HP type corresponds to the The 18HP type corre­ [To open]
side shut­ 12.7-diameter onsite piping using sponds to the 15.9-diame­ 1. Remove the cap and turn the shaft counterclockwise with the
off valve the included piping. ter onsite piping using the hexagon wrench (JISB4648).
accessory pipe. 2. Turn it until the shaft stops.
l\> 25.4 3. Make sure to tighten the cap securely.
The 1OHP type corresponds to the (For the tightening torque, refer to the item <Tightening Torque>.)
Gas side 22.2-diameter onsite piping using the acces­
shutoff l\> 15.9 l\> 19.1 sory pipe. [To close]
valve The 12 ­ 18HP type corresponds to the 28.6­ 1. Remove the cap and turn the shaft clockwise with the hexagon
diameter onsite piping using the accessory wrench (JISB4648).
pipe. 2. Securely tighten the valve until the shaft contacts the main body
<Tightening torque> seal.
3. Make sure to tighten the cap securely.
Tightening torque N·m (Turn clockwise to close) (For the tightening torque, refer to the item <Tightening Torque>.)
Shutoff
valve size Cap
Shaft (valve body) Service port
(valve lid)

l\> 9.5 5.4 - 6.6 Hexagonal 13.5-16.5


wrench
l\> 12.7 8.1 - 9.9 4mm 18.0 - 22.0


l\> 15.9

l\> 19.1
13.5 - 16.5

27.0 - 33.0
Hexagonal
wrench
6mm
Hexagonal
wrench
22.5 - 27.5
11.5 - 13.9

l\> 25.4 8mm

[How to Check How Many Units are Connected]


It is possible to find out how many indoor or outdoor unit in the system are turned on by operating the push button on the PC-board (A1P) of out­

door unit (In case of multi system master unit).

Follow the procedure below to check how many indoor or outdoor units are turned on.

LED display
(LED display: •...OFF 0- ... ON -l) ... Blinking * ... Uncertain)
H1P H2P H3P H4P H5P H6P H7P
(1) Press the MODE button (BS1) once, and set the MONITOR MODE (H1 P: Blinking). -l)
• • • • • •
(2) Press the SET button (BS2) the number of times until the For checking the number of
LED display matches that at right. outdoor units: eight times
-l)
• • 0­ • • •
For checking the number of
indoor units: five times
-l)
• • • 0­ • 0­
(3) Press the RETURN button (BS3) and read the number of units from the display of
H2P through H7P.
[Reading Method] -l)
The display of H2P through H7P should be read as a binary number, with 1:) standing
* * * * * *
for "1" and. standing for "0".

Ex: For the LED display at right, this would be "0 1 011 0 ",
which would mean 22 units are conne~ \~

32 x 0 + 16 x 1 + 8 x 0 + 4 x 1 + 2 x 1 + 1 x 0 =22 units
-l)
• -l)
• -l) -l)

Note: "000000" indicates 64 units.

(4) Press the MODE button (881) once. This returns to Setting Mode 1 (default).
• • 0­ • • • •
Note -=".
Press the "MODE button" (BS1) if you get confused while operating.
This returns to Setting Mode 1 (default).
11-2 Procedure of Adding Refrigerant charging 3. Open the valve C (See the figure 31. The valve A, B and the liquid
and check operation and gas side shutout valve must be left closed), and charge the
refrigerant of the "additional charging amount" from the liquid side
-& Warning ~ Electric Shock Warning - - - - ­ shutout valve service port.
If the "additional charging amounf' was charged fully, close the
• Make sure to close the EL. COMPO. BOX lid before turning on
valve C and go to step 5.
the power when performing the refrigerant charging operation.
If the "additional charging amounf' was not charged fully, go to
• Perform the setting on the PC-board (A1P) of the outdoor unit and step 4.
check the LED display after the power is on via the inspection (Refer to figure 31)
door which is in the EL. COMPO. BOX lid. 1. Measuring device
• Use an insulated rod to operate the push buttons via the EL. 2. R410A tank (with siphon)
COMPO. BOX's inspection door. 3. Charge hose
There is a risk of electric shock if you touch any live parts, since 4. Liquid side shutoff valve
this operation must be performed with the power on. 5. Gas side shutoff valve
6. Shutoff valve service port

-& Caution - - - - - - - - - - - - - - - - ­
7. Valve B
8. Valve C
9. Valve A
• Make sure to use the protect tool (protective groves and gog­
10. Outdoor unit
gles) when charging the refrigerant.
11. Refrigerant charge port
• Due to a danger of liquid hammer, the refrigerant must not be 12. To indoor unit
charged over the allowable maximum amount when charging the 13. Field pipings
refrigerant. 14. Refrigerant flow
• Do not perform the refrigerant charging operation under working 4. Perform the refrigerant charging operation following [Refrigerant
for the indoor unit. charging operation procedure] as shown below, and charge the
• When opening the front panel, make sure to take caution to the fan remaining refrigerant of the "additional charging amount". For per­
rotation during the working. forming the refrigerant charging operation the push button on the
After the outdoor unit stops operating, the fan may keep rotation PC-board (A1P) of outdoor unit (Incase of multi system master
for a while. unit) are use. (See the figure 32) In addition, the refrigerant are
charged from the refrigerant charge port via the valve A.
Note -gJI (See the figure 33) (
• If operation is performed within 12 minutes after the indoor and For operating the push button and opening and closing the valve,
outdoor units are turned on, H2P will be lit on and the compressor follow the work procedure.
will not operate.
Note -gJI

• In order to ensure uniform refrigerant distribution, it may take up to


The refrigerant will be charged about 22kg in one hour at outdoor

around 10 minutes for the compressor to start up after the unit


temp. 30°C DB (6kg at O°C DB).

starting operating. This is not a malfunction.


If you need to speedup in case of multi system, connect the refriger­

<About refrigerant charging>


ant tanks to each outdoor unit as shown in the figure 33.

• The refrigerant charge port is connected to the piping inside the


unit. (Refer to figure 32)
When the unit is shipped from the factory, the unit's internal piping 1. EL.COMPO.BOX lid
is already charged with refrigerant, so be careful when connecting 2. Pipe intake
the charge hose. 3. Inspection door
• After adding the refrigerant, make sure to close the lid of the
4. Label "Service Precaution"
5. LED (H1-8P)
refrigerant charging port.

6. Push button (BS1-5)


The tightening torque for the lid is 11.5 to 13.9 Nm.
7. Lift the protruding part to open the cover
• See [Shutoff valve operation procedure] in chapter 11-1 for details
on how to handle shutoff valves. (Refer to figure 33)
1. Measuring device
• When done or when pausing the refrigerant charging operation,
2. R410A tank (with siphon)
close the valve of the refrigerant tank immediately. If the tank is
3. Charge hose
left with the valve open, the amount of refrigerant which is prop­ 4. Liquid side shutoff valve
erly charged may be off the point. More refrigerant may be 5. Gas side shutoff valve
charged by any remaining pressure after the machine is stopped. 6. Shutoff valve service port
<About check operation> 7. Valve B
• Make sure to perform the check operation after installation. Oth­ 8. Valve C ~
erwise, the malfunction code "U3" will be displayed and normal 9. Valve A
operation cannot be performed. 10. Outdoor unit
And the failure of "Check of miswiring" may also cause abnormal 11. Refrigerant charge port
operation. Performance may drop due to the failure of "Judgment 12. Field piping
of piping length". 13. Refrigerant flow
• Check operation must be performed for each refrigerant piping 14. To indoor unit
system. 15. In case of multi system if you need to speedup.
Checking is impossible if plural systems are being done at once.
• The individual problems of indoor units can not be checked.
About these problems check by test run after the check operation
is completed. (See chapter 13)
• The check operation cannot be performed in recovery or other

service modes.

1. Make sure the following works are complete in accordance with


the installation manual.
• Piping work
• Wiring work
• Air tight test
• Vacuum drying
• Installation work for indoor unit
2. Calculate the "additional charging amount" using "How to calcu­
late the additional refrigerant to be charged" in "6-5 Example of
connection".
[Refrigerant Charging Operation Procedure] [Check Operation Procedure]
(1) Open the liquid and gas side shutoff valves (The valve A-C must (1) Make the onsite setting as needed using the dip switches on the
be closed. The valve A-C means the valves in the figure 33.) outdoor unit PC-board (A1P) with the power off (See "12-1 Onsite
Settings With the Power Off")
[Display of normal system]
(2) Close the EL. COMPO. BOX lid and all front panels except as the
SERVo C/H SELECTOR side of the EL. COMPO. BOX and turn on the power to the out­
LED display TESTI DEMA·
MONI· MODE LN.D.P MULTI
(Default status HWL IND MASTER SLAVE NO door unit and all connected indoor units. (Be sure to turn the
TOR power on at least 6 hours before operation in order to have power
of shipped)
HAP H1P H2P H3P H4P H5P H6P H7P Hap running to the crank case heater.)
Single system {)
• • vv • • • • v• (3) Check the LED display on the outdoor unit PC-board (A1P) is as
shown in the table below and transmission is normal.
Multi
Master unit {)
• • • • • • SERV. C/H SELECTOR
system Sub unit 1 {)
• • • • • • • {) LED display MONI· MODE
TESTI
HWL IND MASTER SLAVE
L.N.O.P
DEMA·
NO
MULTI
(')
Sub unit 2
LED display: ....OFF,
{)

v... • • •
ON, {) ...Bllnklng
• • • • (Default status
of shipped)
TOR
HAP H1P H2P H3P H4P H5P H6P H7P Hap
(*)How to distinguish the master unit, sub unit 1, and sub unit 2 in the
multi system.
Single system {)
• • vv • • • • v•
Method 1: By the Hap (MULTI) LED display Multi
Master un~ {)
• • • • • •
Iv (ON): Master unit I{) (Blinking): Sub unit 1[ • (OFF): Sub unit 2
system Sub unit 1 {)
• • • • • • • {)

Method 2: By the transmission wiring to indoor unit


('j
Sub unit 2
LED display: ....OFF,
{)

v... • • •
ON, {) ... Bllnklng
• • • •
Transmission wiring is connected: Master unit
(*)How to distinguish the master unit, sub unit 1, and sub unit 2 in the
Transmission wiring is not connected: Sub unit 1 or Sub unit 2 multi system.

(2) If necessary, set the field setting by using the dip switch on the

outdoor unit PC-board (A1Pl.

(For how to set, see "12-1 Onsite Settings With the Power Off")

Method 1: By the Hap (MULTI) LED display


Iv (ON): Master unit 1-{)-(B-li-nk-in-g-):-s-ub-un-'-it-1'1.-(-0-F-F)-:-S-ub-u-n-it-2­

(3) • Close the EL. COMPO. BOX lid and all front panel except on Method 2: By the transmission wiring to indoor unit
the side of the EL. COMPO. BOX (*1) and turn the power to the Transmission wiring is connected: Master unit
outdoor unit and all connected indoor units. (*2)
Transmission wiring is not connected: Sub unit 1 or Sub unit 2
• After H2P stop blinking (about 12 minutes after turning on the
power), check LED displays as shown in the table [Display of
normal system] and the system is normal state. (4) Make the onsite settings as needed using the push button (BS1­
If H2P is blinking, check the malfunction code in the remote BS5) on the outdoor unit PC-board (A1P) with the power on. (See
controller, and correct the malfunction in accordance with "12-2 Onsite Settings With the Power On")
[Remote controller display malfunction code] in step 5. (5) Perform the check operation following the Check Operation
(*1) Lead the refrigerant charge hose etc from the pipe intake. All Method of the [Service Precautions] label on the EL. COMPO.

front panels must be closed at the procedure (9). BOX I·id. The system operation for about 40 minutes and automat­

(*2). If you perform the refrigerant charging operation within the ically stops the check operation.

refrigerant system that have the power off unit, the operation If the malfunction code is not displayed in the remote controller

cannot finish properly. after the system stop, check operation is completed. Normal oper­

For confirming the number of the outdoor and indoor units with ation will be possible after 5 minutes. If the malfunction code is

the power on, see [How to check how many units are con­ displayed in the remote controller, correct the malfunction follow­

nected] in chapter 11-1. In case of a multi system, turn on the


ing [Remote controller displays malfunction code] and perform the

power to all outdoor units in the refrigerant system.


check operation again .

• To energize the crankcase heater, make sure to turn on for 6


hours before starting operation. [Remote controller displays malfunction code]
(4) Start the additional refrigerant charge operation. Malfunc­
(About the system settings for additional refrigerant charge oper­ Installation error Remedial action
tion code
ation, refer to the [Service Precaution] label attached on the EL. E3, E4 The shutoff valve of the out­
COMPO. BOX lid in the outdoor unit.) F3,F6 Open the shutoff valve.
Open valve A immediately after starting the compressor. door unit is left closed.
UF
(5) Close the valve A if the "additional charging amount" of refrigerant The phases of the power to the Exchange two of the three phases (L1,
U1
was charged, and push the RETURN button (BS3) once. outdoor unit is reversed. L2, L3) to make aproper connection.
(6) Record the charging amount on the accessory "REQUEST FOR U1 No power is supplied to an out· Make sure the power source wire is prop­
THE INDICATION" label and attach it to the back side of the front U4 door or indoor unit (including erly connected to the outdoor unit and
panel. LC phase interruption). revise if necessary.
5. After completing the additional refrigerant charging perform the There is conflict on the con­ Check if the refrigerant piping line and the
check operation following below. UF nection of transmission wiring transmission wiring are consistent with
in the system. each other.
Note-~
Recalculate the additional amount refrig­
• For check operation, the following work will be performed. E3 erant from the piping length and correct
• Check of shutoff valve opening F6 Refrigerant overcharge. the refrigerant charge level by recovering
• Check of miswiring UF any excessive refrigerant with a refriger·
• Judgment of piping length ant recovery machine.
• Check of refrigerant overcharge • Check if the additional refrigerant
• It takes about 40 minutes to complete the check operation. charge has been finished correctly.
E4
Insufficient refrigerant. • Recalculate the add~ional amount
F3
refrigerant from the piping length and
add the adequate amount.
If the outdoor unit terminal is
U7, U4 Remove the line from the outdoor muiti
connected when there is one
UF,UH terminals (01 and 02).
outdoor unit installed.
If any malfunction codes other than the above are displayed, check
the service manual for how to respond.
12. ONSITE SETTINGS • The outdoor unit fan may rotate at low speeds if the Night-time low

noise setting or the External low noise level setting is made, but

Note-~ this is not a malfunction.

In the case of a multi system, all onsite settings should be made 13-3 Checks After Test Run

on the master unit. Settings made on sub units are invalid.


The outdoor unit to which the indoor unit transmission wire are Perform the following checks after the test run is complete.

connected is the master unit, and all other units are sub units. • Record the contents of field setting.
~ Record them on the accessory "REQUEST FOR THE INDI­
12-1 Onsite Settings With the Power Off CATION" label.
If the COOUHEAT selector was And attach the label on the back side of the front panel.
connected to the outdoor unit in • Record the installation date.
"7. FIELD WIRING", set the dip Inspection ~ Record the installation date on the accessory "REQUEST
door
switch (DS1) on the outdoor unit FOR THE INDICATION" label in accordance with the
[SeNicePrecautioosl IEC60335-2-40.
PC-board (A1P) to "ON" (it is set label
to "OFF" when shipped from the And attach the label on the back side of the front panel.
factory). Note-~

For the position of the dip switch After the test run, when handing the unit over to the customer, make

(DS1), see the "Service Precau­ sure the EL.COMPO.BOX lid, the inspection door, and the unit casing

tions" label (see at right) which is attached to the EL. COMPO. BOX are all attached.

lid.

-& Warning ~ Electric Shock Warning 14. CAUTION FOR REFRIGERANT LEAKS
Never perform with the power on.
(Points to note in connection with refrigerant leaks)
There is a serious risk of electric shock if any live part is touched.

Introduction
The installer and system specialist shall secure safety against
12-2 Onsite Settings With the Power On leakage according to local regulations or standards. The following
Use the push button switches (BS1 through BS5) on the outdoor unit standards may be applicable if local regulations are not available.
PC-board (A1P) to make the necessary onsite settings. The VRV System, like other air conditioning systems, uses R41 OA as
refrigerant. R410A itself is an entirely safe non-toxic, non-combusti- '.:

See the "Service Precautions" label on the EL. CONPO. BOX lid for
ble refrigerant. Nevertheless care must be taken to ensure that air '{.

details on the positions and operating method of the push button conditioning facilities are installed in a room which is sufficiently

switches and on the onsite setting. large. This assures that the maximum concentration level of refriger­

Make sure to record the setting on the accessory "REQUEST FOR ant gas is not exceeded, in the unlikely event of major leak in the sys­

THE INDICATION" label. tem and this in accordance to the local applicable regulations and

standards.

-& Warning ~ Electric Shock Warning Maximum concentration level

Use an insulated rod to operate the push buttons via the inspection
The maximum charge of refrigerant and the calculation of the maxi­

door of EL. COMPO. BOX lid.


mum concentration of refrigerant is directly related to the humanly

There is a risk of electric shock if you touch any live parts, since this
occupied space in to which it could leak.

3
operation must be performed with the power on:
The unit of measurement of the concentration is kg/m ( the weight in

3
kg of the refrigerant gas in 1m volume of the occupied space).

Compliance to the local applicable regulations and standards for the

13. TE;ST RUN maximum allowable concentration level is required.

In Australia the maximum allowed concentration level of refrigerant to

13-1 Before test run 3 3


a humanly space is limited to O.35kg/m for R407C and 0.44kg/m for

• Make sure the following works are completed in accordance with R410A.

the installation manual.


• Piping work
• Wiring work
• Air tight test
• Vacuum drying
• Additional refrigerant charge
• Check that all work for the indoor unit are finished and there are
1. direction of the refrigerant flow (
no danger to operate.
2. room where refrigerant leak has occurred (outflow of all
13-2 Test Run the refrigerant from the system)
Pay a special attention to the place, such as a basement, etc.
After check operation is completed, operate the unit normally and where refrigerant can stay, since refrigerant is heavier than air.
check the following.
Procedure for checking maximum concentration
(1) Make sure the indoor and outdoor units are operating normally.
(2) Operate each indoor unit one by one and make sure the corre­ Check the maximum concentration level in accordance with steps 1
to 4 below and take whatever action is necessary to comply.
sponding outdoor unit is also operating.
(3) Check to see if cold (or hot, except RXQ-P) air is coming out from 1. Calculate the amount of refrigerant (kg) charged to each system
the indoor unit. separately.
(4) Push the fan direction and strength buttons on the remote control­ amount of refriger- additional charging total amount
ler to see if they operate properly. ant in a single unit + amount (amount of of refriger­
system (amount of refrigerant added ant (kg) in
Note-~ refrigerant with locally in accordance
the system
• Heating is not possible if the outdoor temperature is 24°C or
which the system with the length or

higher. Refer to the Operation manual.


is charged before diameter of the refrig­

• If a knocking sound can be heard in the liquid compression of the leaving the factory) erant piping)

compressor, stop the unit immediately and then energize the Note-~
crank case heater for a sufficient length of time before restarting • Where a single refrigerant facility is divided into 2 entirely inde­

the operation. pendent refrigerant systems then use the amount of refrigerant

• Once stopping, the compressor will not restart in about 5 minutes with which each separate system is charged.

even if the On/Off button of the remote controller is pushed.


• When the system operation is stopped by the remote controller,
the outdoor units may continue operating for further 5 minutes at
maximum.
3
2. Calculate the sma.llest room volume (m )
Incase like the following, calculate the volume of (A), (8) as a sin­
gle room or as the smallest room.
A. Where there are no smaller room divisions

B.Where there is a room division but there is a.n opening


between the rooms sufficiently large to permit a free flow of
ai r back and forth.

1. opening between rooms


2. partition
(Where there is an opening without a .door or where there are
openings above and below the door which are each equivalent in
size to 0.15% or more of the floor area.)
3. Calculating the 'refrigerant density using the results of the calcu­
lations in steps 1 and 2 above.
total volume of refrigerant in the
refrigerant system maximum concen­
size (m') of smallest room in which ~ tration level (kg/m')
there is an indoor unit installed

If the result of the above calculation exceeds the maximum con­


centration level then make similar calculations for the second then
third smallest room and so until the result falls short of the maxi­
mum concentration.
4. Dealing with the situations where the result exceeds the maxi­
mum concentration level.
Where the installation of a facility results in a concentration in
excess of the maximum concentration level then it will be neces­
sary to revise the system. Please consult your Daikin supplier.

You might also like