This document provides the design specifications for a reinforced concrete column designated C1. The column has dimensions of 300mm x 300mm and is subject to a 24 ton compressive load. It requires a concrete grade of M20, 415 N/sq mm reinforcement bars distributed across 4 faces, and link spacing of Ø8mm bars at 256mm centers with a 40mm cover. The column has an axial capacity of 58.32 tons and uses 4 #16mm main reinforcement bars with a total area of 8.04sqcm. A minimum cement content of 300kg/m3 and maximum water-cement ratio of 0.55 are also specified.

Uploaded by

nirmal suthar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
53 views1 page

Reinforced Concrete Column Design

This document provides the design specifications for a reinforced concrete column designated C1. The column has dimensions of 300mm x 300mm and is subject to a 24 ton compressive load. It requires a concrete grade of M20, 415 N/sq mm reinforcement bars distributed across 4 faces, and link spacing of Ø8mm bars at 256mm centers with a 40mm cover. The column has an axial capacity of 58.32 tons and uses 4 #16mm main reinforcement bars with a total area of 8.04sqcm. A minimum cement content of 300kg/m3 and maximum water-cement ratio of 0.55 are also specified.

Uploaded by

nirmal suthar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Design Of Reinforced Concrete Column

Column Designation C1

Applied Load [t] 24

Nature of Load COMPRESSIVE


Longer Column Dimension [mm] 300
Shorter Column Dimension [mm] 300
Eff.Length along Longer COl. Dimension [M] 3
Eff.Length along Shorter COl. Dimension [M] 3
BM along Longer Column Dimension [M] 0
BM along Shorter Column Dimension [M] 0
Reinforcement % 0.8
Reinforcement Distribution on Faces 4 FACES
Applied Load Factor 1.5
Concrete Grade Required M 20
Char. Reinforcement Strength (f y) [N/sq mm] 415
Exposure Condition MILD
Fire Rating 0.50 Hour.
Axial Column Capacity [ton] 58.32
Area Of Main Tensile Reinforcement [sq cm] 8.04
Number of main bars required 4Ø16 MM
Spacing of Links [mm] Ø8 MM @ 256 c/c
Cover to Links (Nominal Cover) [mm] 40
Minimum Cement content Required in Concrete [kg/m3] 300
Maximum Water to Cement Ratio 0.55