Relay Output Module: Technical Data
Relay Output Module: Technical Data
Relay Output Module: Technical Data
Page 1 of 2
XP95A
Relay Output Module
Technical data
All data is supplied subject to change without notice.
Specifications are typical at 24V, 73°F and 50% RH unless
otherwise stated.
Working Voltage 17 - 28 V dc
Modulation voltage 5-9 V peak to peak
Digital communication XP95
Temperature range 32 ºF to 120 ºF
Humidity (no condensation) 10% to 93% RH
Standards and Approvals UL, ULC, CSFM
Dimensions 4½ in. (114 mm) x 4½ in. (114 mm)
x 1 in. (25 mm)
Weight 1.05 0z
Product overview Material White flame-retardant
polycarbonate
Product Relay Output Module
Part No. 55000-863
Signal Line Circuit (SLC) Supervised
Digital Communication XP95 - see Protocol Wiring styles Supervised power limited Class A
Compatibilty below or Class B
Supervisory current 0.85 mA
Compliance Surge current 2.5 mA
Maximum alarm current 3.5 mA (LED on)
Maximum line impedance 50 � max
Analog value (Normal) 16
MANAGEMENT
SYSTEMS
MANAGEMENT
SYSTEMS
PRODUCT
CERTIFICATION
© Apollo Fire Detectors Ltd 2019
Assessed to ISO 9001:2015 Assessed to ISO 14001:2015 Cert/LPCB ref. 010
Cert/LPCB ref. 010 Cert/LPCB ref. 010 EMS
PP2603/2018/Issue1
Page 2 of 2