3 Phase Installation
3 Phase Installation
3 Phase Installation
In industrial and commercial buildings, they need high power. So they are
connected to the three phase Delta connection (3 Phase – 3 Wire System –
No Neutral Wire) before distribution transformer and then manage the
required voltage and current according to their needs in three phase and
single phase supply.
On the other hands, buildings that need high power in three phase and
single phase, they are connected to the secondary of distribution
transformer. This way, they get three phase Star connection (3-Phase, 4
Wire System with Neutral Wire). In the Star connection, Three Phase Line
to Line (Phase to Phase) voltage are 415V AC (in US, 208V) and Single
Phase Line to Neutral (Phase to Neutral), there are 230V AC (120V in
US).
In Three Phase Supply, motors and large electric heaters can be directly
connected to the Three Phases while in in Single Phase, load (Light, fan etc)
can be connected in between Phase and Neutral through proper protective
devices.
Why We Need Three Phase Power Supply?
To operate high power equipment and appliances such as electric motors and and
high power rated air compressor etc, we need Three Phase Power supply instead of
Single Phase Power supply. In ordinary homes, we mostly use Single Phase power
supply to operate lighting load, fans, washing machines etc, but in some cases as
well as industries offices high torque motors, multi-storey & large buildings, Three
Phase power supply needs to operate and maintain the system.
In our previous posts, we did it for Single Phase electrical wiring installation in
home and already know that what are MDB, DB, Final Sub Circuit, MCB, MCCB,
CB and RCD etc.
Requirements for Three Phase Wring Installation
In this tutorial, we need the following wiring accessories to wire three phase power
in home.
Circuit breakers are installed and used for safety purposes in both residential as
well as commercial and industrial areas. In power distribution, we need circuit
breakers at different levels. Depending on the current carrying capacity, breaking
capacity and other functions, we select a suitable circuit breaker according to our
needs i.e. VCB, ACB (Air Circuit Breaker), MCCB and then MCB , this is common
hierarchy being followed in power distribution system.
Air Circuit Breaker
.
Moulded Case Circuit Breaker (MCCB)
both MCB and MCCB are classified as low voltage circuit breakers and the
operation principle is based on thermo-magnetic for both devices.
The following table shows the difference and comparison between MCB and
MCCB.
IEC60898-1
It defines behaviour of circuit breaker having rated operational voltage not
exceeding than 440V (between Phases), Rated current not exceeding than 125A
(We have range 0.5A-125A) and rated short circuit capacity not exceeding than
25KA (Usually it is 10KAin MCB). This is designed for unskilled user (or say
uninstructed user) and for devices not being maintained consequently. Also
pollution degree covered is zero pollution to maximum pollution (degree 2). These
are the circuit breakers we find in residential homes, shops, school & offices
electrical distribution switchboards.
IEC60947-2
This standard applies to circuit-breakers, the main contacts of which are intended
to be connected to circuits, the rated voltage of which does not exceed 1000 V a.c.
or 1500 V d.c. It also contains additional requirements for integrally fused circuit-
breakers. It covers very high range of standard current carrying capacity (We have
range of 6A-6300A) and meant for skilled user. The device is also supposed to be
maintained properly. Also pollution degree is to be 3 or more. These circuit
breakers are industrial applications and protect the power distribution of up to
1000 volts AC. and 1500 volts DC. (For MCBs, MCCBs & ACBs)
So it is clear that these items are different in their fundamentals. An MCB designed
for indoor, pollution-free conditions and would not be suitable for harsh, outdoor
applications that require pollution degree 3.
Typically, IEC 60898-1 certified Circuit Breakers meet minimally required
performance to proof proper protection of household installations: Pollution
degree 2, impulse voltage 4kV, isolation voltage is the same as nominal voltage
440V. That is the reason why usually we meet limited number of technical
information printed on Circuit Breakers.
It is not necessary that Circuit breakers certified with IEC 60898-1 can’t be
certified with IEC 60947-2, but for sure any manufacturer need to obtain
certification. Rating of same MCB can be different for different standards, so, it is
highly recommended to check the data properly printed on it.
So, the application and needs will decide that which device is to be used or
selected.
Comparison Between IEC 69896-1 & IEC 60947-2
ICS as a % from ICU. (See Difference between ICS & ICU in term of Circuit
Breakers)
Maximum Operating Voltage
Insulation voltage
Mechanical operation ( endurance and durability)
Breaking Capacity for each Operating Voltage
Below are types of MCBs which shows the magnetic fault protection. Also, to
prevent the accidental overloading of the cable at no fault, there is a thermal device
in MCB to eliminate the chances of unwanted tripping operation of MCB. For
short circuit protection in home appliances, the current rating is about to 6kA
while for heavy and industrial operation, it is above the 10kA.
What is an RCD?
An RCD, or residual current device, is a life-saving device which is designed to
prevent you from getting a fatal electric shock if you touch something live, such as
a bare wire. It can also provide some protection against electrical fires. RCDs offer
a level of personal protection that ordinary fuses and circuit-breakers cannot
provide.
We have used Red for Live or Phase, Black for Neutral and Green for
Earth Wire.
You may use the specific area codes i.e. IEC – International Electro-
technical Commission (UK, EU etc) or NEC (National Electrical
Code [US & Canada] where;
Wiring Colour Code:
NEC
Single Phase 120V AC:
Black = Phase or Line, White = Neutral and Green/Yellow = Earth Conductor
Three Phase 208 AC:
Black = Phase 1 or Line1, Red = Line 2, Blue = Line 3,
White /Gray = Neutral and Green/Yellow= Earth Conductor
IEC:
Single Phase 230V AC:
Brown = Phase or Line, Blue = Neutral and Green = Earth Conductor