Schedule of Loads Motor Layout: C1 C2 C3 C4 C5 C6

This document contains a motor layout, single line diagram, schedule of loads, legend, and specifications for a proposed building project. The schedule of loads shows the total load current and required main breaker size as 1000 amps. The single line diagram shows the electrical system layout including a 1000 amp main breaker, generator set, and distribution transformer. Cable sizes of 3-400 mm2 THW in 90mm diameter RSC pipe are specified for the service entrance.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
224 views1 page

Schedule of Loads Motor Layout: C1 C2 C3 C4 C5 C6

This document contains a motor layout, single line diagram, schedule of loads, legend, and specifications for a proposed building project. The schedule of loads shows the total load current and required main breaker size as 1000 amps. The single line diagram shows the electrical system layout including a 1000 amp main breaker, generator set, and distribution transformer. Cable sizes of 3-400 mm2 THW in 90mm diameter RSC pipe are specified for the service entrance.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

MOTOR LAYOUT SCHEDULE OF LOADS

C1 C2 C3 C4 C5 C6

C7 C8
C11

C13
C10
C14 FOR MAIN BREAKER : TOTAL LOAD CURRENT + (HIGHEST MOTOR LOAD CURRENT X 1.5)
544.143 + ( 236.263 X 1.5 ) = 898.538 AMPS
C12
THEREFORE USE 1,000 AT, 3P, and 2 SETS OF 3 - 400 mm² THW IN 90 mm ø RSC PIPE

SINGLE LINE DIAGRAM LEGEND:


SPECIFICATIONS:
3 - 400 mm² THW (2 sets)
FREE AIR
F.C.O.
C.T.
CURRENT TRANSFORMER SERVICE ENTRANCE

P.T.
3 - 333 KVA
POTENTIAL TRANSFORMER
DIST. TRANSFORMER
L.A. 7620 / 13200 V TRANSFER SWITCH
220 / 440 V
LIGHTNING ARRESTER
M

3 - 400 mm² THW (2 sets)


3-Ø kWhr Meter 3" Ø PVC / RSC (2 sets)
FUSE CUTOUT
MOLDED CASE CIRCUIT BREAKER

GENSET
G M KILOWATT-HR METER
MCCB
MTS / ATS
1000 AT
3P
1000 AT
3P G GENERATOR SET

DISTRIBUTION TRANSFORMER

CONTROL SYSTEM

FROM THE OFFICE OF: PROFESSIONAL ELECTRICAL ENGINEER: SEAL: PROJECT TITLE: OWNER: SHEET CONTENTS: PREPARED BY : SHEET NUMBER:

ENGR. JOHN MICHAEL S. BOLANDRES, REE

PORFIRIO V. LOO PROPOSED RENTABLE SPACES AND - MOTOR LAYOUT


AND E
- SINGLE LINE DIAGRAM
UY CONDEV CORPORATION EXEQUIEL G. LAFUENTE

PRC NO. PEE 371 DATE ISSUED: 1962


FUNCTION HALL BUILDING - SCHEDULE OF LOADS
1
- LEGEND
CTC NO. 25920701 JAN. 16, 2020 TIN NO. 113 - 840 - 452 - SPECIFICTIONS
PTR NO. 2462363 JAN. 16, 2020 DUMAGUETE CITY L O C A T I O N : BRGY. DATAGON, PAMPLONA, NEGROS ORIENTAL ADDRESS: DATE: 11 - 07 - 2 0 20