Data Sheet 6ES7151-8AB01-0AB0: General Information

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

Data sheet 6ES7151-8AB01-0AB0

SIMATIC DP, IM151-8 PN/DP CPU f. ET200S, 192 KB work memory, int.
PROFINET interface (with three RJ45 ports) as IO controller,without battery
MMC required

General information
Product function
● Isochronous mode No
Engineering with
● Programming package STEP 7 V5.5 or higher
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes; against destruction
external protection for power supply lines 2 A min.
(recommendation)
Mains buffering
● Mains/voltage failure stored energy time 5 ms
Input current
Inrush current, typ. 1.8 A
I²t 0.13 A²·s
from supply voltage 1L+, max. 352 mA; 426 mA with DP master module
Output current
for backplane bus (5 V DC), max. 700 mA
Power loss
Power loss, typ. 5.5 W
Memory
Work memory
● integrated 192 kbyte
● expandable No
Load memory
● Plug-in (MMC) Yes
● Plug-in (MMC), max. 8 Mbyte
● Data management on MMC (after last 10 y
programming), min.
Backup
● present Yes; Ensured by SIMATIC Micro Memory Card (maintenance-free)
CPU processing times
for bit operations, typ. 0.06 µs
for word operations, typ. 0.12 µs
for fixed point arithmetic, typ. 0.16 µs

6ES71518AB010AB0 Subject to change without notice


3.26.2021
Page 1/9 © Copyright Siemens
for floating point arithmetic, typ. 0.59 µs
CPU-blocks
Number of blocks (total) 1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can
be reduced by the MMC used.
DB
● Number, max. 1 024; Number range: 1 to 16000
● Size, max. 64 kbyte
FB
● Number, max. 1 024; Number range: 0 to 7999
● Size, max. 64 kbyte
FC
● Number, max. 1 024; Number range: 0 to 7999
● Size, max. 64 kbyte
OB
● Number, max. See S7-300 operation list
● Size, max. 64 kbyte
● Number of free cycle OBs 1; OB 1
● Number of time alarm OBs 1; OB 10
● Number of delay alarm OBs 2; OB 20, 21
● Number of cyclic interrupt OBs 4; OB 32, 33, 34, 35
● Number of process alarm OBs 1; OB 40
● Number of DPV1 alarm OBs 3; OB 55, 56, 57
● Number of isochronous mode OBs 1; OB 61; only for PROFINET
● Number of startup OBs 1; OB 100
● Number of asynchronous error OBs 6; OB 80, 82, 83, 85, 86, 87 (OB83 only for centralized I/O and
PROFINET IO)
● Number of synchronous error OBs 2; OB 121, 122
Nesting depth
● per priority class 16
● additional within an error OB 4
Counters, timers and their retentivity
S7 counter
● Number 256
Retentivity
— adjustable Yes
— lower limit 0
— upper limit 255
— preset Z 0 to Z 7
Counting range
— adjustable Yes
— lower limit 0
— upper limit 999
IEC counter
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
S7 times
● Number 256
Retentivity
— adjustable Yes
— lower limit 0
— upper limit 255
— preset No retentivity
Time range
— lower limit 10 ms
— upper limit 9 990 s
IEC timer
● present Yes
● Type SFB

6ES71518AB010AB0 Subject to change without notice


3.26.2021
Page 2/9 © Copyright Siemens
● Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max. 64 kbyte
Flag
● Size, max. 256 byte
● Retentivity available Yes
● Retentivity preset MB 0 to MB 15
● Number of clock memories 8; 1 memory byte
Data blocks
● Retentivity adjustable Yes; via non-retain property on DB
● Retentivity preset Yes
Local data
● per priority class, max. 32 768 byte; Max. 2048 bytes per block
Address area
I/O address area
● Inputs 2 048 byte
● Outputs 2 048 byte
of which distributed
— Inputs 2 048 byte
— Outputs 2 048 byte
Process image
● Inputs, adjustable 2 048 byte
● Outputs, adjustable 2 048 byte
● Inputs, default 128 byte
● Outputs, default 128 byte
Subprocess images
● Number of subprocess images, max. 1; With PROFINET IO, the length of the user data is limited to 1600
bytes
Digital channels
● Inputs 16 336
— of which central 496
● Outputs 16 336
— of which central 496
Analog channels
● Inputs 1 021
— of which central 124
● Outputs 1 021
— of which central 124
Hardware configuration
Number of modules per system, max. 63; Centralized
Mounting rail
● Number of mounting rails that can be used 1
● Length of mounting rail, max. Station width: ≤ 1 m or < 2 m
Time of day
Clock
● Hardware clock (real-time) Yes
● retentive and synchronizable Yes
● Backup time 6 wk; At 40 °C ambient temperature, typically
● Deviation per day, max. 10 s; Typ.: 2 s
● Behavior of the clock following POWER-ON Clock continues running after POWER OFF
● Behavior of the clock following expiry of backup Clock continues to run with the time at which the power failure occurred
period
Operating hours counter
● Number 1
● Range of values 0 to 2^31 hours (when using SFC 101)
● Granularity 1h
● retentive Yes; Must be restarted at each restart
Clock synchronization

6ES71518AB010AB0 Subject to change without notice


3.26.2021
Page 3/9 © Copyright Siemens
● supported Yes
● to MPI, master No
● to MPI, slave No
● to DP, master Yes; With DP master module
● to DP, slave Yes; With DP master module
● in AS, master No
● in AS, slave No
● on Ethernet via NTP Yes; As client
Interfaces
Interfaces/bus type 1x PROFINET (3 RJ45 ports)
1. Interface
Isolated Yes
automatic detection of transmission rate Yes
Autonegotiation Yes
Autocrossing Yes
Change of IP address at runtime, supported Yes
Interface types
● RJ 45 (Ethernet) Yes
● Number of ports 3
● integrated switch Yes
Protocols
● MPI No
● PROFINET IO Controller Yes; Also simultaneously with IO-Device functionality
● PROFINET IO Device Yes; Also simultaneously with IO Controller functionality
● PROFINET CBA Yes
● PROFIBUS DP master No
● PROFIBUS DP slave No
● Open IE communication Yes; Via TCP/IP, ISO on TCP, and UDP
● Web server Yes
● Point-to-point connection No
PROFINET IO Controller
● Transmission rate, max. 100 Mbit/s; full duplex
Services
— PG/OP communication Yes
— Routing Yes; With DP master module
— S7 communication Yes; with loadable FBs
— Isochronous mode Yes; OB 61; only for PROFINET IO
— IRT Yes
— Shared device Yes
— Prioritized startup Yes
— Number of IO devices with prioritized startup, 32
max.
— Number of connectable IO Devices, max. 128
— Of which IO devices with IRT, max. 64
— of which in line, max. 64
— Number of IO Devices with IRT and the option 128
"high flexibility"
— of which in line, max. 61
— Number of connectable IO Devices for RT, 128
max.
— of which in line, max. 128
— Activation/deactivation of IO Devices Yes
— Number of IO Devices that can be 8
simultaneously activated/deactivated, max.
— IO Devices changing during operation (partner Yes
ports), supported
— Number of IO Devices per tool, max. 8
— Device replacement without swap medium Yes
— Send cycles 250 μs, 500 μs,1 ms; 2 ms, 4 ms (not in the case of IRT with "high

6ES71518AB010AB0 Subject to change without notice


3.26.2021
Page 4/9 © Copyright Siemens
flexibility" option)
— Updating time Minimum value depends on communication share set for PROFINET
I/O, on the number of I/O devices, and on the number of configured user
data items.
— Updating times 250 µs to 512 ms (depends on operating mode; for more details, refer to
Operating Instructions, "Interface Module IM151-8 PN/DP CPU")
Address area
— Inputs, max. 2 kbyte
— Outputs, max. 2 kbyte
— User data consistency, max. 1 024 byte; with PROFINET I/O
PROFINET IO Device
Services
— PG/OP communication Yes
— Routing Yes
— S7 communication Yes; with loadable FBs
— Isochronous mode No
— IRT Yes
— PROFIenergy Yes; With SFB 73 / 74 prepared for loadable PROFIenergy standard FB
for I-Device
— Shared device Yes
— Number of IO Controllers with shared device, 2
max.
Transfer memory
— Inputs, max. 1 440 byte; Per IO Controller with shared device
— Outputs, max. 1 440 byte; Per IO Controller with shared device
Submodules
— Number, max. 64
— User data per submodule, max. 1 024 byte
PROFINET CBA
● acyclic transmission Yes
● cyclic transmission Yes
Open IE communication
● Number of connections, max. 8
● Local port numbers used at the system end 0, 20, 21, 23, 25, 80, 102, 135, 161, 443, 8080, 34962, 34963, 34964,
65532, 65533, 65534, 65535
2. Interface
Interface type External interface via master module 6ES7138-4HA00-0AB0
Isolated Yes
Interface types
● RS 485 Yes
● Output current of the interface, max. No
Protocols
● MPI No
● PROFINET IO Controller No
● PROFINET IO Device No
● PROFINET CBA No
● PROFIBUS DP master Yes
● PROFIBUS DP slave No
● Open IE communication No
● Web server No
PROFIBUS DP master
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 32; Per station
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication Yes; I blocks only
— S7 communication Yes
— S7 communication, as client No

6ES71518AB010AB0 Subject to change without notice


3.26.2021
Page 5/9 © Copyright Siemens
— S7 communication, as server Yes
— Equidistance Yes
— Isochronous mode No
— SYNC/FREEZE Yes
— Activation/deactivation of DP slaves Yes
— Number of DP slaves that can be 8
simultaneously activated/deactivated, max.
— Direct data exchange (slave-to-slave Yes
communication)
— DPV1 Yes
Address area
— Inputs, max. 2 048 byte
— Outputs, max. 2 048 byte
User data per DP slave
— Inputs, max. 244 byte
— Outputs, max. 244 byte
Protocols
Redundancy mode
Media redundancy
— MRP Yes
— Switchover time on line break, typ. 200 ms; PROFINET MRP
— Number of stations in the ring, max. 50
Open IE communication
● TCP/IP Yes; via integrated PROFINET interface and loadable FBs
— Number of connections, max. 8
— Data length for connection type 01H, max. 1 460 byte
— Data length for connection type 11H, max. 32 768 byte
— several passive connections per port, Yes
supported
● ISO-on-TCP (RFC1006) Yes; via integrated PROFINET interface and loadable FBs
— Number of connections, max. 8
— Data length, max. 32 768 byte
● UDP Yes; via integrated PROFINET interface and loadable FBs
— Number of connections, max. 8
— Data length, max. 1 472 byte
Web server
● supported Yes
● User-defined websites Yes
● Number of HTTP clients 5
Communication functions
PG/OP communication Yes
Data record routing Yes; With DP master module
Global data communication
● supported No
S7 basic communication
● supported Yes; I blocks
● User data per job, max. 76 byte
● User data per job (of which consistent), max. 76 byte
S7 communication
● supported Yes
● as server Yes
● as client Yes; via integrated PROFINET interface and loadable FBs
● User data per job, max. See online help of STEP 7 (shared parameters of the SFBs/FBs and of
the SFCs/FCs of S7 Communication)
PROFINET CBA (at set setpoint communication load)
● Setpoint for the CPU communication load 50 %
● Number of remote interconnection partners 32
● Number of functions, master/slave 30
● Total of all master/slave connections 1 000

6ES71518AB010AB0 Subject to change without notice


3.26.2021
Page 6/9 © Copyright Siemens
● Data length of all incoming connections 4 000 byte
master/slave, max.
● Data length of all outgoing connections 4 000 byte
master/slave, max.
● Number of device-internal and PROFIBUS 500
interconnections
● Data length of device-internal und PROFIBUS 4 000 byte
interconnections, max.
● Data length per connection, max. 1 400 byte
Remote interconnections with acyclic transmission
— Sampling interval, min. 500 ms
— Number of incoming interconnections 100
— Number of outgoing interconnections 100
— Data length of all incoming interconnections, 2 000 byte
max.
— Data length of all outgoing interconnections, 2 000 byte
max.
— Data length per connection, max. 1 400 byte
Remote interconnections with cyclic transmission
— Transmission frequency: Transmission interval, 1 ms
min.
— Number of incoming interconnections 200
— Number of outgoing interconnections 200
— Data length of all incoming interconnections, 2 000 byte
max.
— Data length of all outgoing interconnections, 2 000 byte
max.
— Data length per connection, max. 450 byte
HMI variables via PROFINET (acyclic)
— Number of stations that can log on for HMI 3; 2x PN OPC/1x iMap
variables (PN OPC/iMap)
— HMI variable updating 500 ms
— Number of HMI variables 200
— Data length of all HMI variables, max. 2 000 byte
PROFIBUS proxy functionality
— supported Yes
— Number of linked PROFIBUS devices 16
— Data length per connection, max. 240 byte; Slave-dependent
iPAR server
● supported Yes
Number of connections
● overall 12
● usable for PG communication 11
— reserved for PG communication 1
— adjustable for PG communication, min. 1
— adjustable for PG communication, max. 11
● usable for OP communication 11
— reserved for OP communication 1
— adjustable for OP communication, min. 1
— adjustable for OP communication, max. 11
● usable for S7 basic communication 10
— reserved for S7 basic communication 0
— adjustable for S7 basic communication, min. 0
— adjustable for S7 basic communication, max. 10
● usable for S7 communication 10; with loadable FBs
— adjustable for S7 communication, max. 10
● total number of instances, max. 32
● usable for routing 4; With DP master module
S7 message functions
Number of login stations for message functions, max. 12; Depending on the configured connections for PG/OP and S7 basic
communication

6ES71518AB010AB0 Subject to change without notice


3.26.2021
Page 7/9 © Copyright Siemens
Process diagnostic messages Yes; ALARM_S, ALARM_SC, ALARM_SQ, ALARM_D, ALARM_DQ
simultaneously active Alarm-S blocks, max. 300
Test commissioning functions
Status block Yes; Up to 2 simultaneously
Single step Yes
Number of breakpoints 4
Status/control
● Status/control variable Yes
● Variables Inputs, outputs, memory bits, DB, times, counters
● Number of variables, max. 30
— of which status variables, max. 30
— of which control variables, max. 14
Forcing
● Forcing Yes
● Forcing, variables I/O
● Number of variables, max. 10
Diagnostic buffer
● present Yes
● Number of entries, max. 500
— adjustable No
— of which powerfail-proof 100; Only the last 100 entries are retained
Interrupts/diagnostics/status information
Alarms Yes
Diagnostics function Yes
Diagnostics indication LED
● for maintenance Yes; MT
● Bus fault BF (red) Yes; BF-PN
● Group error SF (red) Yes
● Monitoring 24 V voltage supply ON (green) Yes
● Bus activity PROFINET (green) Yes; P1-/P2-/P3-Link
Potential separation
between PROFIBUS DP and all other circuit components Yes
Isolation
Isolation tested with 500 V DC
Configuration
Configuration software
● STEP 7 Yes; V5.5 or higher
Programming
● Command set see instruction list
● Nesting levels 8
● System functions (SFC) see instruction list
● System function blocks (SFB) see instruction list
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes; Optional
— CFC Yes; Optional
— GRAPH Yes; Optional
— HiGraph® Yes; Optional
Know-how protection
● User program protection/password protection Yes
● Block encryption Yes; With S7 block Privacy
Cycle time monitoring
● lower limit 1 ms
● upper limit 6 000 ms
● adjustable Yes
● preset 150 ms

6ES71518AB010AB0 Subject to change without notice


3.26.2021
Page 8/9 © Copyright Siemens
Dimensions
Width 120 mm; DP master module: 35 mm
Height 119.5 mm
Depth 75 mm
Weights
Weight, approx. 320 g; DP master module: Approx. 100 g

last modified: 3/25/2021

6ES71518AB010AB0 Subject to change without notice


3.26.2021
Page 9/9 © Copyright Siemens

You might also like