Line Trap Standards
Line Trap Standards
Line Trap Standards
Sponsored by the
Power System Communications and Cybersecurity
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 11073-10427-2016
Health informatics—Personal health device communication
Part 10427: Device Specialization—Power Status Monitor of Personal Health Devices
Sponsor
IEEE 11073™ Standards Committee
of the
IEEE Engineering in Medicine and Biology Society
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
Abstract: Line traps inserted into a power line to provide a high impedance at power-line-carrier
frequencies (30 kHz to 500 kHz) are covered in this standard. The purpose is to isolate the carrier
signal from system impedance changes due to faults or switching behind the point of insertion, and
to guide the signal in the proper direction. The standard covers line traps in which the main coil is
designed as a single-phase, air-cooled inductor of the dry type.
Keywords: IEEE C93.3™, line trap, PLC, power line carrier, wave trap
,(((LVDUHJLVWHUHGWUDGHPDUNLQWKH863DWHQW 7UDGHPDUN2ႈFHRZQHGE\7KH,QVWLWXWHRI(OHFWULFDODQG(OHFWURQLFV(QJLQHHUV
Incorporated.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
Important Notices and Disclaimers Concerning IEEE Standards Documents
IEEE documents are made available for use subject to important notices and legal disclaimers. These
notices and disclaimers, or a reference to this page, appear in all standards and may be found under the heading
“Important Notices and Disclaimers Concerning IEEE Standards Documents.” They can also be obtained on
request from IEEE or viewed at http://standards.ieee.org/IPR/disclaimers.html.
IEEE Standards do not guarantee or ensure safety, security, health, or environmental protection, or ensure
DJDLQVWLQWHUIHUHQFHZLWKRUIURPRWKHUGHYLFHVRUQHWZRUNV,PSOHPHQWHUVDQGXVHUVRI,(((6WDQGDUGVGRF-
uments are responsible for determining and complying with all appropriate safety, security, environmental,
health, and interference protection practices and all applicable laws and regulations.
IEEE does not warrant or represent the accuracy or content of the material contained in its standards, and
expressly disclaims all warranties (express, implied and statutory) not included in this or any other document
UHODWLQJWRWKHVWDQGDUGLQFOXGLQJEXWQRWOLPLWHGWRWKHZDUUDQWLHVRIPHUFKDQWDELOLW\¿WQHVVIRUDSDUWLFXODU
SXUSRVHQRQLQIULQJHPHQWDQGTXDOLW\DFFXUDF\H൵HFWLYHQHVVFXUUHQF\RUFRPSOHWHQHVVRIPDWHULDO,Q
DGGLWLRQ,(((GLVFODLPVDQ\DQGDOOFRQGLWLRQVUHODWLQJWRUHVXOWVDQGZRUNPDQOLNHH൵RUW,(((VWDQGDUGV
documents are supplied “AS IS” and “WITH ALL FAULTS.”
Use of an IEEE standard is wholly voluntary. The existence of an IEEE standard does not imply that there
DUHQRRWKHUZD\VWRSURGXFHWHVWPHDVXUHSXUFKDVHPDUNHWRUSURYLGHRWKHUJRRGVDQGVHUYLFHVUHODWHGWR
the scope of the IEEE standard. Furthermore, the viewpoint expressed at the time a standard is approved and
issued is subject to change brought about through developments in the state of the art and comments received
from users of the standard.
,QSXEOLVKLQJDQGPDNLQJLWVVWDQGDUGVDYDLODEOH,(((LVQRWVXJJHVWLQJRUUHQGHULQJSURIHVVLRQDORURWKHU
VHUYLFHVIRURURQEHKDOIRIDQ\SHUVRQRUHQWLW\QRULV,(((XQGHUWDNLQJWRSHUIRUPDQ\GXW\RZHGE\DQ\
other person or entity to another. Any person utilizing any IEEE Standards document, should rely upon his or
her own independent judgment in the exercise of reasonable care in any given circumstances or, as appropri-
DWHVHHNWKHDGYLFHRIDFRPSHWHQWSURIHVVLRQDOLQGHWHUPLQLQJWKHDSSURSULDWHQHVVRIDJLYHQ,(((VWDQGDUG
IN NO EVENT SHALL IEEE BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL,
EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO: PROCURE-
MENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS
INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CON-
TRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN
ANY WAY OUT OF THE PUBLICATION, USE OF, OR RELIANCE UPON ANY STANDARD, EVEN
IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE AND REGARDLESS OF WHETHER SUCH
DAMAGE WAS FORESEEABLE.
3
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
Translations
The IEEE consensus development process involves the review of documents in English only. In the event that
an IEEE standard is translated, only the English version published by IEEE should be considered the approved
IEEE standard.
2ႈFLDOVWDWHPHQWV
A statement, written or oral, that is not processed in accordance with the IEEE-SA Standards Board Operations
0DQXDOVKDOOQRWEHFRQVLGHUHGRULQIHUUHGWREHWKHR൶FLDOSRVLWLRQRI,(((RUDQ\RILWVFRPPLWWHHVDQGVKDOO
not be considered to be, or be relied upon as, a formal position of IEEE. At lectures, symposia, seminars, or
HGXFDWLRQDOFRXUVHVDQLQGLYLGXDOSUHVHQWLQJLQIRUPDWLRQRQ,(((VWDQGDUGVVKDOOPDNHLWFOHDUWKDWKLVRUKHU
views should be considered the personal views of that individual rather than the formal position of IEEE.
Comments on standards
Comments for revision of IEEE Standards documents are welcome from any interested party, regardless
RI PHPEHUVKLS D൶OLDWLRQ ZLWK ,((( +RZHYHU ,((( GRHV QRW SURYLGH FRQVXOWLQJ LQIRUPDWLRQ RU DGYLFH
pertaining to IEEE Standards documents. Suggestions for changes in documents should be in the form of a
proposed change of text, together with appropriate supporting comments. Since IEEE standards represent a
consensus of concerned interests, it is important that any responses to comments and questions also receive
the concurrence of a balance of interests. For this reason, IEEE and the members of its societies and Standards
Coordinating Committees are not able to provide an instant response to comments or questions except in
those cases where the matter has previously been addressed. For the same reason, IEEE does not respond to
LQWHUSUHWDWLRQUHTXHVWV$Q\SHUVRQZKRZRXOGOLNHWRSDUWLFLSDWHLQUHYLVLRQVWRDQ,(((VWDQGDUGLVZHOFRPH
WRMRLQWKHUHOHYDQW,(((ZRUNLQJJURXS
Users of IEEE Standards documents should consult all applicable laws and regulations. Compliance with the
provisions of any IEEE Standards document does not imply compliance to any applicable regulatory require-
ments. Implementers of the standard are responsible for observing or referring to the applicable regulatory
requirements. IEEE does not, by the publication of its standards, intend to urge action that is not in compliance
with applicable laws, and these documents may not be construed as doing so
Copyrights
IEEE draft and approved standards are copyrighted by IEEE under US and international copyright laws. They
are made available by IEEE and are adopted for a wide variety of both public and private uses. These include
both use, by reference, in laws and regulations, and use in private self-regulation, standardization, and the pro-
PRWLRQRIHQJLQHHULQJSUDFWLFHVDQGPHWKRGV%\PDNLQJWKHVHGRFXPHQWVDYDLODEOHIRUXVHDQGDGRSWLRQE\
public authorities and private users, IEEE does not waive any rights in copyright to the documents.
4
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
Photocopies
Subject to payment of the appropriate fee, IEEE will grant users a limited, non-exclusive license to photocopy
portions of any individual standard for company or organizational internal use or individual, non-commercial
use only. To arrange for payment of licensing fees, please contact Copyright Clearance Center, Customer Ser-
vice, 222 Rosewood Drive, Danvers, MA 01923 USA; +1 978 750 8400. Permission to photocopy portions of
any individual standard for educational classroom use can also be obtained through the Copyright Clearance
Center.
Users of IEEE Standards documents should be aware that these documents may be superseded at any time by
the issuance of new editions or may be amended from time to time through the issuance of amendments, corri-
JHQGDRUHUUDWD$QR൶FLDO,(((GRFXPHQWDWDQ\SRLQWLQWLPHFRQVLVWVRIWKHFXUUHQWHGLWLRQRIWKHGRFXPHQW
WRJHWKHUZLWKDQ\DPHQGPHQWVFRUULJHQGDRUHUUDWDWKHQLQH൵HFW
Every IEEE standard is subjected to review at least every 10 years. When a document is more than 10 years old
and has not undergone a revision process, it is reasonable to conclude that its contents, although still of some
YDOXHGRQRWZKROO\UHÀHFWWKHSUHVHQWVWDWHRIWKHDUW8VHUVDUHFDXWLRQHGWRFKHFNWRGHWHUPLQHWKDWWKH\KDYH
the latest edition of any IEEE standard.
In order to determine whether a given document is the current edition and whether it has been amended
through the issuance of amendments, corrigenda, or errata, visit the IEEE Xplore at http://ieeexplore.ieee.org/
or contact IEEE at the address listed previously. For more information about the IEEE-SA or IEEE’s standards
development process, visit the IEEE-SA Website at http://standards.ieee.org.
Errata
Errata, if any, for all IEEE standards can be accessed on the IEEE-SA Website at the following URL: http://
VWDQGDUGVLHHHRUJ¿QGVWGVHUUDWDLQGH[KWPO8VHUVDUHHQFRXUDJHGWRFKHFNWKLV85/IRUHUUDWDSHULRGLFDOO\
Patents
Attention is called to the possibility that implementation of this standard may require use of subject matter
FRYHUHGE\SDWHQWULJKWV%\SXEOLFDWLRQRIWKLVVWDQGDUGQRSRVLWLRQLVWDNHQE\WKH,(((ZLWKUHVSHFWWRWKH
existence or validity of any patent rights in connection therewith. If a patent holder or patent applicant has
¿OHGDVWDWHPHQWRIDVVXUDQFHYLDDQ$FFHSWHG/HWWHURI$VVXUDQFHWKHQWKHVWDWHPHQWLVOLVWHGRQWKH,(((
SA Website at http://standards.ieee.org/about/sasb/patcom/patents.html. Letters of Assurance may indicate
whether the Submitter is willing or unwilling to grant licenses under patent rights without compensation or
under reasonable rates, with reasonable terms and conditions that are demonstrably free of any unfair discrim-
ination to applicants desiring to obtain such licenses.
Essential Patent Claims may exist for which a Letter of Assurance has not been received. The IEEE is not re-
sponsible for identifying Essential Patent Claims for which a license may be required, for conducting inquiries
into the legal validity or scope of Patents Claims, or determining whether any licensing terms or conditions
provided in connection with submission of a Letter of Assurance, if any, or in any licensing agreements are
reasonable or non-discriminatory. Users of this standard are expressly advised that determination of the valid-
LW\RIDQ\SDWHQWULJKWVDQGWKHULVNRILQIULQJHPHQWRIVXFKULJKWVLVHQWLUHO\WKHLURZQUHVSRQVLELOLW\)XUWKHU
information may be obtained from the IEEE Standards Association
5
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
Participants
$WWKHWLPHWKLV,(((VWDQGDUGZDVFRPSOHWHGWKH3RZHU/LQH&DUULHU/LQH7UDSV:RUNLQJ*URXSKDGWKH
following membership and corresponding members (CM):
The following members of the individual balloting committee voted on this standard. Balloters may have
voted for approval, disapproval, or abstention.
6
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
When the IEEE-SA Standards Board approved this standard on 14 February 2017, it had the following
membership:
0HPEHU(PHULWXV
7
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
Introduction
This introduction is not part of IEEE Std C93.3™-2017, IEEE Standard Requirements for Power-Line Carrier
Line Traps (30 kHz to 500 kHz).
This document was developed by the Power Line Carrier Subcommittee of the Power System
Communications and Cybersecurity Committee, responsible for Power Line Carrier Equipment and Coupling
&DSDFLWRU9ROWDJH7UDQVIRUPHUV'XULQJLWVGHYHORSPHQWWKHVWDQGDUGUHFHLYHGWKHEHQH¿WVRIDFRQVHQVXVRI
input from a balanced group representing the user, producer, government, and general-interest viewpoints.
These inputs were harmonized and integrated into the standard in its present approved form.
The Power Line Carrier Subcommittee was established to coordinate, review, and update the existing
GRFXPHQWVLQWRDQH൵HFWLYHJURXSRIVWDQGDUGVLQFOXGLQJWKLVVWDQGDUGIRUOLQHWUDSV$VHSDUDWHVWDQGDUGZLOO
be developed to cover each type of equipment described in the Subcommittee’s scope.
7KLV VWDQGDUG LQFOXGHV WHFKQLFDO GH¿QLWLRQV SHUIRUPDQFH UDWLQJV WHVWLQJ PHWKRGV DQG PDQXIDFWXULQJ
requirements for line traps.
(VVHQWLDOO\WKHFKDQJHVUHÀHFWHGLQWKLVUHYLVLRQDUHQHZGH¿QLWLRQVDGGLWLRQRILQIRUPDWLRQRQHPHUJHQF\
overload current capability of line traps with regards to Facility Rating standards, and the IEEE mandated
change from US to metric units of measure.
This Standard was previously maintained by NEMA and was last released as ANSI C93.3-1995. It has been
given over to IEEE to revise and maintain.
8
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
Contents
1. Overview ................................................................................................................................................... 10
1.1 Scope .................................................................................................................................................. 10
1.2 Purpose ............................................................................................................................................... 10
'H¿QLWLRQVDFURQ\PVDQGDEEUHYLDWLRQV ................................................................................................. 11
'H¿QLWLRQV .......................................................................................................................................... 11
3.2 Acronyms and abbreviations .............................................................................................................. 12
5. Ratings ...................................................................................................................................................... 14
5.1 General ratings ................................................................................................................................... 14
5.2 Rating for tuned type line traps ........................................................................................................... 17
6. Testing ....................................................................................................................................................... 18
6.1 General ............................................................................................................................................... 18
6.2 Design test procedures ........................................................................................................................ 20
6.3 Production test procedures ................................................................................................................. 27
7. Manufacturing/design requirements.......................................................................................................... 27
7.1 Mounting ............................................................................................................................................ 27
7.2 Terminals ............................................................................................................................................ 28
7.3 Tuning and protective device location and mounting ......................................................................... 28
7.4 Bird barriers........................................................................................................................................ 28
1DPHSODWHPDUNLQJVIRUWKHPDLQFRLO ................................................................................................ 28
1DPHSODWHPDUNLQJVIRUWKHWXQLQJGHYLFH ......................................................................................... 29
Annex A (informative) Guide for emergency overload current capability of line traps .................................. 30
9
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Standard Requirements for
Power-Line Carrier Line Traps
(30 kHz to 500 kHz)
1. Overview
1.1 Scope
This standard applies to a line trap inserted into a power line to provide a high impedance at power line carrier
IUHTXHQFLHV N+] WR N+] 7KH SXUSRVH LV WR LVRODWH WKH FDUULHU VLJQDO IURP V\VWHP LPSHGDQFH
FKDQJHV due to faults or switching behind the point of insertion, and to guide the signal in the proper
direction. The standard covers line traps in which the main coil is designed as a single-phase, air-cooled
inductor of the dry type.
1.2 Purpose
7KLVVWDQGDUGLVYLWDOWRWKHDSSOLFDWLRQRISRZHUOLQHFDUULHUV\VWHPVRQDOOSRZHUOLQHVN9DQGDERYH
Power-line carrier systems are used for protection systems and other communications. The line trap is part
of the system that allows the carrier signal to be coupled to the power line with optimal performance.
3HUIRUPDQFHUHTXLUHPHQWVZLOOEHHVWDEOLVKHGVRWKDWWKHLULQWHUDFWLRQZLWKWKHSRZHUV\VWHPLVNQRZQDQG
performance can be predicted.
2. Normative references
The following referenced documents are indispensable for the application of this document (i.e., they must
be understood and used, so each referenced document is cited in text and its relationship to this document is
explained). For dated references, only the edition cited applies. For undated references, the latest edition of
the referenced document (including any amendments or corrigenda) applies.
ANSI C84.1, American National Standard for Electric Power Systems and Equipment–Voltage Ratings
(60 Hz).1
10
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
IEEE Std C57.21™, IEEE Standard Requirements, Terminology, and Test Code for Shunt Reactors Rated
2YHUN9$
,(((6WG&,(((6WDQGDUGIRU0HWDO2[LGH6XUJH$UUHVWHUVIRU$&3RZHU&LUFXLWV!N9
'H¿QLWLRQVDFURQ\PVDQGDEEUHYLDWLRQV
'H¿QLWLRQV
)RUWKHSXUSRVHVRIWKLVGRFXPHQWWKHIROORZLQJWHUPVDQGGH¿QLWLRQVDSSO\7KHIEEE Standards Dictionary
OnlineVKRXOGEHFRQVXOWHGIRUWHUPVQRWGH¿QHGLQWKLVFODXVH5
apparent power-frequency inductance ( LP ): The reactance of the main coil divided by the angular
IUHTXHQF\DWZKLFKWKHUHDFWDQFHLVGHWHUPLQHGXQFRPSHQVDWHGIRUWKHH൵HFWVRIVHOIFDSDFLWDQFH
auxiliary protective device: A device associated with the tuning device to protect individual components by
limiting transient overvoltages.
bandwidth7KHIUHTXHQF\UDQJHZLWKLQZKLFKWKHEORFNLQJLPSHGDQFHLVQRWOHVVWKDQDVSHFL¿HGDPRXQW
blocking impedance7KHFRPSOH[LPSHGDQFHRIWKHFRPSOHWHOLQHWUDSZLWKLQDVSHFL¿HGFDUULHUIUHTXHQF\
range.
emergency overload current: A value of power frequency current, greater than the rated continuous current,
which the line traps may be required to carry for some limited period of time.
geometric mean frequency (GMF): The geometric mean frequency of the bandwidth limit frequencies,
which is the square root of their product.
GMF = FL × FH
where:
FL is Frequency Low
FH is Frequency High
line trap: A main coil with a protective device, with or without tuning device(s), series connected in a power
circuit to provide a high impedance at power line carrier frequencies, and negligible impedance at the power
frequency.
protective device: A device that protects the line trap by limiting transient overvoltages. It is shunt-connected
to the tuning device and the main coil.
3
IEEE publications are available from the Institute of Electrical and Electronics Engineers, Inc., 445 Hoes Lane, Piscataway, NJ 08854,
USA (http://standards.ieee.org/).
4
7KH,(((VWDQGDUGVRUSURGXFWVUHIHUUHGWRLQWKLVFODXVHDUHWUDGHPDUNVRIWKH,QVWLWXWHRI(OHFWULFDODQG(OHFWURQLFV(QJLQHHUV,QF
5
IEEE Standards Dictionary Online is available at: http://dictionary.ieee.org
11
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
rated continuous current ( I N ): The rms power frequency current that the line trap can carry continuously
without exceeding the maximum temperature rise for its insulation temperature index.
rated short-time current ( I KN ): The rms symmetrical value of current that a line trap is capable of carrying
IRUWZRVHFRQGVZLWKRXWH[FHHGLQJDVSHFL¿HGWHPSHUDWXUH
resistive bandwidth7KHIUHTXHQF\UDQJHZLWKLQZKLFKWKHUHVLVWLYHEORFNLQJLPSHGDQFHLVQRWOHVVWKDQD
VSHFL¿HGDPRXQW
resonant frequency: The frequency or frequencies to which the line trap is tuned.
self-capacitance ( C R ): The capacitance resulting from the turn-to-turn, layer-to-layer, and terminal-to-termi-
QDOFRQ¿JXUDWLRQRIWKHPDLQFRLO
self-resonant frequency: The frequency at which the combination of true inductance and self-capacitance
becomes resonant.
self-tuned trap: A line trap without a tuning device and for wideband operation designed such that the self-
resonant frequency is in the carrier band.
single-frequency line trap: A line trap that is tuned for parallel resonance at one selected carrier frequency.
tuning device$SDVVLYHQHWZRUNWKDWZKHQVKXQWFRQQHFWHGWRWKHPDLQFRLOSURGXFHVDUHODWLYHO\KLJKOLQH
trap impedance for one or more frequencies or frequency bands. It consists of capacitors and may include in-
ductors, resistors, and auxiliary protective devices.
tuning range: The portion of the carrier frequency band through which the geometric frequency (GMF) or
resonant frequency may be adjusted.
two-frequency line trap: A line trap that is tuned for parallel resonance at two selected carrier frequencies.
wideband line trap: A line trap that provides a greater bandwidth than a single-frequency line trap for the
same main coil inductance, resonant (or geometric mean) frequency, and impedance level.
GE General Electric
GF geometric frequency
GMF geometric mean frequency
5,9 UDGLRLQÀXHQFHYROWDJH
rms root mean square
12
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz 500 kHz)
4. Service conditions
4.1 Usual service conditions
Usual service conditions are as follows:
— Outdoor service
— Ambient temperature range: –40 °C to 45 °C. With regard to temperature range, Table 1GH¿QHVWKH
upper ambient temperature limit conditions.
— Maximum altitude: 1000 m above sea level
— Power frequency: 50 Hz or 60 Hz
— Atmosphere free of damaging fumes or excessive or abrasive dust and explosive mixtures of dust or
gases, steam, and salt spray
² &DUULHUIUHTXHQF\UDQJHN+]WRN+]
4.2.2 Altitude
Line traps may be used at altitudes greater than 1000 m provided that the current correction factors in Table 2
are applied, and that the temperature of the cooling air does not exceed the mean values given in Table 3.
13
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
When a line trap is applied at altitudes greater than (1000 m), the dielectric strength correction factors for
air-insulated components given in Table 4 shall apply.
2WKHUXQXVXDOVHUYLFHFRQGLWLRQVWREHFRQVLGHUHGZKHQVSHFL¿HGE\WKHXVHUFXVWRPHULQFOXGH
— Direct-current applications
— Seismic conditions
² :LQGORDGLQJFRQGLWLRQVWREHVSHFL¿HGE\XVHU
5. Ratings
5.1 General ratings
5.1.1 Main coil orientation
The continuous and corresponding short-time current ratings shall be in accordance with Table 5. Other
FXUUHQWUDWLQJVFRQWLQXRXVDQGVKRUWWLPHIDXOWFXUUHQWPD\EHVSHFL¿HGEDVHGRQDJUHHPHQWEHWZHHQWKH
manufacturer and purchaser. Short-time current ( I KN LVGH¿QHGDVVIRUVWDQGDUGOLQHWUDSVFXVWRPWUDSV
may have a higher rating.
14
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
There is no standard for power losses; for further information, refer to Annex B.
)RUUHIHUHQFHWKHIROORZLQJQRPLQDO+]UHDFWDQFHYDOXHVLQȍDUHJLYHQFRUUHVSRQGLQJWRWKHDERYHUDWHG
inductances as 0.1, 0.2, 0.4, 0.6, 0.8, and 1.0, respectively.
The maximum temperature rise above the 40 °C 24-h mean ambient temperature at rated continuous current
shall not exceed those values in Table 6.
7KHOLQHWUDSVKDOOZLWKVWDQGWKHKHDWLQJH൵HFWVRIWKHUDWHGVKRUWWLPHFXUUHQWIRUVZLWKRXWH[FHHGLQJWKH
temperature given in Table 7, and as determined in accordance with 6.2.3. Other short-time current durations
PD\EHVSHFL¿HGEDVHGRQDJUHHPHQWEHWZHHQWKHPDQXIDFWXUHUDQGSXUFKDVHU
7KHOLQHWUDSVKDOOEHFDSDEOHRIZLWKVWDQGLQJWKHPHFKDQLFDOIRUFHVSURGXFHGE\DQR൵VHWFXUUHQWKDYLQJD
VLQJOHSHDNZLWKDYDOXHRIWLPHVWKHUDWHGVKRUWWLPHFXUUHQW7KHWHUP³FDSDEOHRIZLWKVWDQGLQJ´VKDOO
be interpreted to mean that, if subjected to this duty, the line trap shall show no damage and shall be capable of
meeting all other requirements of this standard.
15
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
The voltage rating of the protective device shall be no less than the voltage ( V ) developed across the line trap
with rated short-time current, as determined by Equation (1):
where:
7KHSURWHFWLYHGHYLFHVKDOOPHHWWKHUHTXLUHPHQWVRI,(((6WG&IRULWVFODVVL¿FDWLRQDQGYROWDJHUDWLQJ
7KHLQVXODWLRQOHYHOIRUWKHPDLQFRLOVKDOOEHDWOHDVWDERYHWKHYDOXHRIWKHPD[LPXPN9VIURQW
RIZDYHSURWHFWLYHYROWDJHRURIWKHN$GLVFKDUJHYROWDJHRIWKHSURWHFWLYHGHYLFHZKLFKHYHULVKLJKHU
The RIV of a line trap shall not exceed the value stated in Table 8, when the line trap is applied at the stated
maximum system voltage. See also 6.2.8.
7DEOH²5DGLRLQÀXHQFHYROWDJH
System voltage (kV)a 5DGLRLQÀXHQFH Maximum RIV (μV)c
Maximum Nominal test voltage (kV)b
72.5 69 42 125
121 115 70 250
145 138 84 250
169 161 98 250
242 230 140 250
362 345 209 250
550 500 317 500
800 765 462 750
a
The maximum and nominal system voltages are from ANSI C84.1.
b
7KHUDGLRLQÀXHQFHWHVWYROWDJHLVWKHOLQHWRJURXQGYDOXHRIWKHPD[LPXPV\VWHPYROWDJH
c
7KHPD[LPXPSHUPLVVLEOHEDFNJURXQGYROWDJHOHYHOZLOOEHRIWKHUDGLRLQÀXHQFHYROWDJHUDWLQJ&RUUHFWLRQ
IRUEDFNJURXQGYROWDJHOHYHOVKDOOEHE\WKHUPVPHWKRG7KHVHPD[LPXPUDGLRLQÀXHQFHYROWDJHVDVFRQGXFWHG
radio noise, will add a negligible amount to the radio noise normally radiated from the line, even at short distances
from the line trap.
A line trap intended for vertical suspension mounting shall be capable of withstanding, without yielding, a
tensile force of not less than 13 300 N in addition to the weight of the line trap.
7KLVIUHTXHQF\VKDOODOZD\VEHKLJKHUWKDQN+]H[FHSWIRUOLQHWUDSVZKHUHLWPD\QRWEHSRVVLEOHWR
achieve such a high frequency because of the physical size and construction of the main coil. For these special
cases, the self-resonant frequency must be greater than the GMF of the operating bandwidth.
16
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
² 6LQJOHIUHTXHQF\¿HOGDGMXVWDEOHRUIDFWRU\¿[HG
² 7ZRIUHTXHQF\¿HOGDGMXVWDEOHRUIDFWRU\¿[HG
² :LGHEDQG¿HOGDGMXVWDEOHRUIDFWRU\¿[HG²VHHDOVRAnnex D for an example of typical frequency
bands
— Self-tuned wideband
5.2.2 Tuning
7XQLQJUDQJHVIRU¿HOGDGMXVWDEOHOLQHWUDSV
)RUDWZRIUHTXHQF\DGMXVWDEOHOLQHWUDSWKHIUHTXHQFLHVVKDOOEHVHSDUDWHGE\DWOHDVWN+]RURIWKH
higher frequency, whichever is greater.
7DEOH²7XQLQJUDQJHVIRUP+¿HOGDGMXVWDEOHOLQHWUDS
Type of tuning Tuning ranges (kHz)
30–90
Single-frequency 70–200
100–300
30–90
Two-frequency 70–200
100–300
50–200
Wideband
100–300
7XQLQJUDQJHIRUIDFWRU\¿[HGZLGHEDQGRUIDFWRU\¿[HGWZRIUHTXHQF\OLQHWUDS
$IDFWRU\¿[HGZLGHEDQGOLQHWUDSVKDOOKDYHDEDQGZLGWKZLWKLQWKHN+]WRN+]UDQJHZKLFKLVQRW
DGMXVWDEOHLQWKH¿HOG5HIHUWRAnnex DIRUDQH[DPSOHRIW\SLFDOEDQGVIRUIDFWRU\¿[HGZLGHEDQGWUDSVIRU
0.265 mH line traps.
)RUDIDFWRU\¿[HGWZRIUHTXHQF\OLQHWUDSWKHIUHTXHQFLHVVKDOOEHVHSDUDWHGE\DWOHDVWN+]RURIWKH
higher frequency, whichever is greater.
A single- or two-frequency line trap shall be capable of being tuned to a selected frequency or frequencies
ZLWKLQWKHVSHFL¿HGUDQJHZLWKDQDFFXUDF\RI
)RUDVLQJOHRUWZRIUHTXHQF\OLQHWUDSWKHUDWHGPLQLPXPEORFNLQJLPSHGDQFHVKDOOEH
17
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
)RUD¿HOGDGMXVWDEOHZLGHEDQGOLQHWUDSWKHUDWHGPLQLPXPEORFNLQJLPSHGDQFHVKDOOEH
RUFRQ¿JXUHGIRUDQ\RIWKHVHLPSHGDQFHVDVDJUHHGEHWZHHQWKHPDQXIDFWXUHUDQGSXUFKDVHU
)RUDIDFWRU\¿[HGZLGHEDQGOLQHWUDSWKHUDWHGPLQLPXPEORFNLQJLPSHGDQFHVKDOOEHRU
9DULDWLRQRIEORFNLQJFKDUDFWHULVWLFVZLWKFKDQJHLQDPELHQWWHPSHUDWXUHDQGFKDQJH
in continuous current
The resonant frequency shall not vary more than a total of 2% for changes in both the ambient temperature and
the continuous current within the temperature range of –40 °C to +45 °C, and from zero to rated continuous
current.
)RUWKH¿HOGDGMXVWDEOHW\SHWKHJHRPHWULFPHDQIUHTXHQF\VKDOOQRWYDU\PRUHWKDQDWRWDORIIRUFKDQJHV
in both the ambient temperature and the continuous current within the temperature range of –40 °C to +45 °C,
and from zero to rated continuous current.
)RUWKHIDFWRU\¿[HGW\SHWKHPLQLPXPEORFNLQJLPSHGDQFHRYHUWKHEDQGZLGWKVKDOOEHPDLQWDLQHGIRU
changes in both the ambient temperature and the continuous current within the temperature range of –40 °C to
+45 °C, and from zero to rated continuous current.
7KH³PDLQ´SURWHFWLYHJDSGH¿QHGLQ5.1.8, is usually for lightning or high fault currents that, in turn, develop
high voltages across the entire inductive coil of the line trap. This is typically referred to in line-trap literature
as the lightning protective device.
Any “auxiliary” devices would typically be downstream for additional protective clamping for that particular
GRZQVWUHDPGHYLFHXQOHVVWKHWUDSPDQXIDFWXUHUGHFLGHGWRDGGDGGLWLRQDOOHYHOVRISURWHFWLRQWREDFNXSWKLV
IXQFWLRQ$Q\FODPSLQJRUSURWHFWLYHGHYLFHVQHHGWREHVHOIUHVWRULQJDQGDXWRH[WLQJXLVKLQJRIDQ\VSDUN
DFWLYLW\$X[LOLDU\SURWHFWLYHJDSVVKDOOQHLWKHUVSDUNRYHUQRUFRQWLQXHWRVSDUNRYHUIROORZLQJWUDQVLHQWYROW-
age actuation, with the power frequency voltage, V as determined in 5.1.8. and 6.2.12 across the main coil.
7KHLQVXODWLRQOHYHOIRUWKHWXQLQJGHYLFHVKDOOEHDWOHDVWDERYHWKHYDOXHRIWKHPD[LPXPN9
VIURQWRIZDYHSURWHFWLYHYROWDJHRURIWKHN$GLVFKDUJHYROWDJHRIWKHSURWHFWLYHGHYLFHZKLFKHYHULV
higher.
The insulation level for the tuning device components protected by an auxiliary protective device shall be at
OHDVWDERYHWKHLPSXOVHVSDUNRYHUYROWDJHGHWHUPLQHGLQLWHPDRI6.2.13.
6. Testing
6.1 General
6.1.1 Test conditions
a) The ambient temperature range shall be from +10 °C through +50 °C.
18
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
b) The line trap for application at an unusual altitude service condition may be tested at an altitude less
than 1000 m if appropriate altitude corrections from Table 2, Table 3, and Table 4 are applied.
c) The line trap for application at a usual altitude service condition may be tested at any altitude higher
than 1000 m if appropriate attitude corrections from Table 2, Table 3, and Table 4 are applied.
d) The test units shall be new and in clean, dry condition.
e) The sequence of testing shall be optional, except where otherwise noted.
6.1.2.1 General
The following design tests shall be performed by the manufacturer on one-line trap of each current and
inductance rating to ensure that its characteristics and performance meet the requirements of this standard:
The following additional design tests shall be performed by the manufacturer on one tuned-type line trap of
each current and inductance rating to help ensure that its tuning characteristics and performance meet the
requirements of this standard:
6.1.3.1 General
The following production tests shall be performed by the manufacturer on each line trap:
19
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
c) Power-frequency test of protective device and auxiliary protective device(s) (see 6.3.3)
d) Turn-to-turn insulation test of the main coil (see 6.3.7)
Measurement of main coil power frequency losses is optional per agreement between the manufacturer and
purchaser (see Annex B).
6.1.3.2 Tuned-type
The following additional production tests shall be performed by the manufacturer on each tuned-type line trap:
D 0HDVXUHPHQWRIEORFNLQJLPSHGDQFHVHH6.3.4)
b) Measurement of tuning device component values (see 6.3.5)
c) Power-frequency dielectric withstand test on tuning device (see 6.3.6)
d) Power-frequency test of auxiliary protective device(s) (see 6.3.3)
a) The true inductance ( LT ) shall be determined, and shall be not less than the rated value in accordance
with 5.1.4 and 6.3.2. The main coil shall be parallel or series resonated at two frequencies, F1 and
F2 , with capacitors that will have values of C1 and C2 , respectively (see C.2).
E ,QROGHUYLQWDJHOLQHWUDSVWKHWXQLQJSDFNVFRQWDLQHGGLVFUHWHFDSDFLWRUVDQGSRVVLEO\UHVLVWRUVDQG
LQGXFWRUVWKDWFRXOGEHVWUDSSHGE\WKHXVHUWRREWDLQVHOHFWHGWXQLQJSDFNIUHTXHQFLHVDVZHOODVWR
allow the user to replace parts. In today’s line traps, especially for those that are factory tuned, these
FDSDFLWRUVDQGRWKHUUHVLVWRUVDQGLQGXFWRUVDUHSDUWRIWKH³WXQLQJSDFN´ZKLFKDUHGHVLJQHGDWWKH
IDFWRU\IRUJLYHQIUHTXHQFLHVDQGWHQGWREHUHSODFHGDVDXQLWSDFN7KHOLJKWQLQJDUUHVWHULVLQVLGH
DFURVVWKHPDLQLQGXFWLYHFRLO,QD¿[HGZLGHEDQGOLQHWUDSWKHWXQLQJSDFNFRPSRQHQWVDUHDOVR
in parallel with the lightning protection device across the full winding of the main inductive coil. In
DGMXVWDEOHRUWZRIUHTXHQF\WUDSVWKHWXQLQJSDFNFRPSRQHQWVPD\EHDWWDFKHGIURPDFRPPRQHQG
RIWKHOLQHWUDSWRGL൵HUHQWZLQGLQJSDUWVRIWKHPDLQFRLO
c) The true inductance is given in Equation (2) as follows:
2
⎛ F1 ⎞
⎜ ⎟ −1
LT = ⎝ F2 ⎠ (2)
( 2π F1 ) × ( C2 − C1 )
2
where:
To minimize computational errors, F1 should be considerably larger than F2 . Also, the GMF of F1 and F2
VKRXOGEHDSSUR[LPDWHO\N+]WKHUHIRUHWHVWIUHTXHQFLHVRIN+]DQGN+]DUHUHFRPPHQGHG
d) The apparent power-frequency inductance shall be measured to permit calculation of the voltage V as
required in 5.1.8.
20
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
e) When item b) of 6.3.1 is used for the production test for the main coil true inductance, the apparent
power-frequency inductance of the main coil shall be calculated by dividing the reactance by the
angular power frequency.
The ratio of the true inductance (determined in item a) above) to the apparent power-frequency inductance
(determined in item c) above) is the ratio used in item b) of 6.3.1.
All temperature rise tests shall be performed in an indoor area as free from drafts as practicable. The area shall
EHVX൶FLHQWO\ODUJHVRWKDWWKHDPELHQWWHPSHUDWXUHLVQRWDSSUHFLDEO\LQFUHDVHGE\KHDWLQJH൵HFWVRIWKHOLQH
trap being tested. The line trap shall be fully assembled and shall be tested in each of the positions in which it
is intended to operate.
7KHUHVKDOOEHVX൶FLHQWFOHDUDQFHIURPWKHOLQHWUDSWRÀRRUVZDOOVFHLOLQJVDQGRWKHUREMHFWVLQWKHWHVWDUHD
so that there will be no hindrance to free natural convection or to normal radiation cooling.
Temperature rise tests shall be performed at rated continuous current and power frequency. It is permissible to
shorten the time required for the test by the use of initial overloads or other suitable methods.
The temperature of the cooling air shall be determined from the average of the readings of at least three
thermometers or thermocouples placed uniformly around the line trap at the same level as the bottom of the
coil at a horizontal distance of one to two coil diameters from the edge of the coil. To reduce to a mini-
mum, the errors due to time lag between the temperature of the line trap and the variations in the ambient
temperature, the thermocouples or thermometers shall be placed in suitable containers. The container shall
have such proportions as will require not less than two hours for the indicated temperature within to change
6.3 °C if suddenly placed in air that has a temperature 10 °C higher, or lower, than the previous steady-state
indicated temperature within the container.
For measurements of increasing resistance of the coil, when the ambient temperature is other than 40 °C, the
winding losses will not be the same as the values that would have been obtained at 40 °C ambient conditions.
The correction factor is shown below in Equation (3):
T + 40°C
K= (3)
T + θ a °C
where:
To obtain the corrected temperature rise, the measured temperature rise shall be multiplied by the correction
factor K .
The average temperature rise of the main coil winding shall be measured by the increase in resistance method,
and shall not include contact resistance. This may be accomplished by using the double bridge method.
21
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
The maximum measurable hot spot temperature rise of the main coil winding conductor insulation, line
terminals, tuning devices, and protective devices shall be measured by thermocouples or thermometers.
The use of thermocouples is the preferred method of measuring hot spots and surface temperatures. The
WKHUPRFRXSOHVVKRXOGEHSODFHGDQGKHOG¿UPO\DQGVQXJO\DJDLQVWWKHFRQGXFWRUVXUIDFHDQGWKHUPDOO\LQVX-
lated from the surrounding cooling medium.
The temperature rise shall be considered constant when all temperatures, which can be measured at intervals
RIQRWOHVVWKDQPLQVKRZWKDWWKUHHFRQVHFXWLYHUHDGLQJVDUHZLWKLQRIWKHSUHYLRXVWKUHHUHDGLQJV
'XULQJWKLVSHULRGWKHWHVWFXUUHQWVKDOOEHWKHUDWHGFRQWLQXRXVFXUUHQWDQGVKDOOYDU\QRPRUHWKDQ
$FRUUHFWLRQVKDOOEHPDGHIRUWKHFRROLQJWKDWRFFXUVIURPWKHWLPHZKHQWKHSRZHULVVKXWR൵WRWKHWLPH
when the hot resistance is measured. The recommended method of determining the temperature of the winding
at the time of shutdown is to measure the resistance of the winding as the line trap cools immediately after
shutdown and to extrapolate to the time of shutdown. At least four measurements shall be made at intervals of
no more than three minutes.
lf the main coil winding employs an aluminum conductor, then the leads and connections for the bridge used
to measure the dc resistance shall also be of aluminum or special testing alloy system-designed to avoid
WKHUPRFRXSOHH൵HFWVWKDWFDQUHVXOWLQHUURQHRXVUHVLVWDQFHPHDVXUHPHQWV
The average temperature of the winding shall be determined by either Equation (4) or Equation (5):
Rt
θt = × (T + θo ) − T (4)
Ro
⎛ R − Ro ⎞
θt = ⎜ t ⎟ × (T + θo ) + θ 0 (5)
⎝ Ro ⎠
where:
T is 234.5 °C for copper or 225 °C for aluminum (based on values at T = 40 °C, otherwise K needs to
be applied to arrive at the corrected factor for temperature)
Tt is the temperature in °C corresponding to the resistance of the winding at time of shutdown
To is the temperature in °C corresponding to the reference resistance of the winding
Rt is the resistance of the winding at time of shutdown
Ro is the reference resistance of the winding
22
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
7KHPD[LPXPPHDVXUDEOHKRWVSRWWHPSHUDWXUHULVHLVWKHGL൵HUHQFHEHWZHHQWKHKRWWHVWWKHUPRFRXSOHRU
thermometer reading and the measured ambient temperature at the completion of the test.
The corrected maximum measurable hot spot temperature rise is the product of the hottest observable spot
temperature rise and the correction factor K (see 6.2.2.2).
In accordance with 6.2.11, the maximum measurable temperature rise of the tuning device capacitor should be
measured at this time.
If the tests are made at an altitude exceeding 1000 m above sea level, the temperature rise shall be corrected by
the following method in Equation (6):
⎡ ⎛ h − 1000 ⎞ ⎤
θ r = θ m ⎢1 − 0.005 ⎜ ⎟⎥ (6)
⎣ ⎝ 100 ⎠ ⎦
where:
6.2.3 Calculation of time to reach limiting temperature for rated short-time current
7KHDELOLW\RIWKHOLQHWUDSWRZLWKVWDQGWKHKHDWLQJH൵HFWVRIWKHUDWHGVKRUWWLPHFXUUHQWIRUVVKDOOEH
YHUL¿HGE\FDOFXODWLRQRIWKHWLPHWRUHDFKOLPLWLQJWHPSHUDWXUHEDVHGRQWKHDVVXPSWLRQWKDWDOOWKHKHDWLV
stored in the conductor.
7KHWLPHUHTXLUHGWRUHDFKDVSHFL¿HGOLPLWLQJWHPSHUDWXUHPD\EHFDOFXODWHGE\WKHIROORZLQJIRUPXODLQ
Equation (7):
t=
(T + θ s ) C × ln ⎛ 1 + θ ⎞
⎜ ⎟ (7)
Ws ⎝ T + θs ⎠
where:
23
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
The tensile strength test shall be performed prior to the mechanical strength for rated short-time current test
(see 6.2.5).
The line trap shall be vertically suspended using the suspension members and hardware normally supplied for
this purpose. An additional tensile force of 13 300 N shall be applied axially to the line trap and maintained for
a period of one hour.
Successful completion shall be determined by the absence of permanent deformation of any part of the line
trap.
The mechanical strength for rated short-time current test shall be performed subsequent to the following tests:
insulation test of the main coil (see 6.2.6) and the tensile strength test (see 6.2.4) when applicable.
The ability of a line trap to withstand the mechanical forces produced by the rated short-time current shall
EHYHUL¿HGE\DQR൵VHWFXUUHQWKDYLQJDVLQJOHSHDNZLWKDYDOXHRIWLPHVWKHUDWHGVKRUWWLPHFXUUHQW
Successful completion of the test shall be determined by the absence of visible damage and conformance to the
ratings in accordance with the production tests in 6.3.
The insulation test for the main coil shall be performed prior to and following the mechanical strength for rated
short-time current test.
The insulation test procedures for the main coil shall be performed according to the latest version of
IEEE Std C57.21 (see equivalent 10.3.3.2 of IEEE Std C57.21-1990). The insulation test level shall not be less
than that required in 5.1.9.
The following tests shall be performed on the protective devices according to IEEE Std C62.11:
The RIV test shall be performed with the line trap suitably supported to determine the RIV produced by the
line trap itself. The equipment and general method used in determining the RIV shall be in accordance with
ANSI/NEMA CC 1, Annex A. The RIV shall not exceed the value in accordance with 5.1.10.
The self-resonance of the main coil shall be determined by measuring the impedance of the coil using a
specialized instrument(s) for measuring impedance. The frequency shall be varied until the self-resonant point
is determined (maximum impedance of the coil).
24
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
7KHEDQGZLGWKWHVWIRUDOLQHWUDSVKDOOEHSHUIRUPHGE\PHDVXULQJWKHEORFNLQJLPSHGDQFHRIWKHOLQHWUDS
7KHPHDVXUHPHQWVKDOOGHWHUPLQHWKHORZHVWDQGKLJKHVWIUHTXHQFLHVDWZKLFKWKHUDWHGEORFNLQJLPSHGDQFH
in accordance with 5.2.3LVREWDLQHG6X൶FLHQWGDWDVKDOOEHWDNHQWRFKDUDFWHUL]HWKHLPSHGDQFHYDULDWLRQ
between these two extremes.
The test shall be performed at the upper, middle, and lower frequency of each rated tuning range (see Table 9).
The test shall be performed at the extremes of each rated tuning range. A test shall be performed at the lowest
IUHTXHQF\RIWKHUDQJHZLWKWKHVHFRQGIUHTXHQF\EHLQJVSDFHGVRWKDWWKHORZHVWIUHTXHQF\LVRUN+]
(whichever is greater) lower than the upper frequency. Another test shall be performed at the highest frequency
RIWKHUDQJHZLWKWKHVHFRQGIUHTXHQF\EHLQJVSDFHGVRWKDWWKHORZHUIUHTXHQF\LVRUN+]ZKLFKHYHU
is greater) lower than the upper frequency (see Table 9).
)LHOGDGMXVWDEOHZLGHEDQGOLQHWUDS
The test shall be performed at the upper, middle, and lower frequency of each rated tuning range and for each
UDWHGEORFNLQJLPSHGDQFH7KHUHVLVWLYHEORFNLQJLPSHGDQFHVKDOODOVREHPHDVXUHGVHHTable 9).
)DFWRU\¿[HGZLGHEDQGOLQHWUDS
7KH WHVW VKDOO EH SHUIRUPHG IRU WKH VSHFL¿HGE DQGZLGWKD QGE ORFNLQJL PSHGDQFH7 KHU HVLVWLYHEORFNLQJ
impedance shall also be measured.
9DULDWLRQRIEORFNLQJFKDUDFWHULVWLFVZLWKFKDQJHLQDPELHQWWHPSHUDWXUHDQGFKDQJH
in continuous current
The variation in resonant frequency(s) of a single-frequency or two-frequency line trap and the GMF of a
¿HOGDGMXVWDEOHZLGHEDQGOLQHWUDSFDXVHGE\YDULDWLRQRIWKHDPELHQWWHPSHUDWXUHIURP±&WR&
and concurrent variations of the continuous current from zero to rated continuous current shall be determined
E\PHDVXULQJWKHFDSDFLWDQFHDWN+]RIWKHWXQLQJGHYLFHVRYHULWVRSHUDWLQJWHPSHUDWXUHUDQJH7KH
resulting variation in resonant frequency or GMF shall be in accordance with 5.2.4.1 or 5.2.4.2 (whichever is
applicable) and shall be calculated as shown below in Equation (8):
V% =
( f h − f l ) × 100 (8)
( fh + fl ) 2
where:
7KHYDULDWLRQLQEORFNLQJLPSHGDQFHRIDIDFWRU\¿[HGZLGHEDQGOLQHWUDSFDXVHGE\DFKDQJHLQDPELHQW
temperature from –40 °C to +45 °C, and concurrent variations of the continuous current from zero to rated
FRQWLQXRXVFXUUHQWVKDOOEHGHWHUPLQHGE\EORFNLQJLPSHGDQFHPHDVXUHPHQWVRYHUWKHRSHUDWLQJWHPSHUDWXUH
UDQJHRIWKHWXQLQJGHYLFHV7KHPLQLPXPEORFNLQJLPSHGDQFHRYHUWKHEDQGZLGWKVKDOOEHLQDFFRUGDQFH
with 5.2.4.2.
The lower limit of the operating temperature range of the capacitor is –40 °C with zero current. The upper limit
is +45 °C, plus the temperature rise of the tuning device(s) measured in 6.2.2.6.
25
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
Because the inductance of the line trap basically does not change with variations in temperature or current, it is
VX൶FLHQWWRVXEMHFWRQO\WKHWXQLQJGHYLFHVWRWKHWHPSHUDWXUHF\FOHV
3RZHUIUHTXHQF\WHVWRISURWHFWLYHGHYLFHDQGDX[LOLDU\SURWHFWLYHGHYLFHVV
For these tests the tuning device shall not be connected to the main coil.
The requirements for the auxiliary protective device in accordance with 5.2.5VKDOOEHYHUL¿HGE\WKHIROORZ-
ing tests:
a) A power frequency voltage, V , in accordance with 5.1.9 shall be applied across the terminals of the
WXQLQJGHYLFHIRUDPLQLPXPRIVGXULQJZKLFKWLPHWKHDX[LOLDU\SURWHFWLYHGHYLFHVKDOOQRWVSDUN
over.
b) With the voltage, V , applied across the terminals of the tuning devices as in a), a 1.2 to 5.0 × 40 to
VLPSXOVHYROWDJHZLWKWKHVX൶FLHQWPDJQLWXGHWRFDXVHVSDUNRYHURIWKHDX[LOLDU\SURWHFWLYH
GHYLFH VKDOO EH DSSOLHG$W WKH ¿UVW SRZHU IUHTXHQF\ FXUUHQW ]HUR DIWHU WKH LPSXOVH WKH DX[LOLDU\
SURWHFWLYHGHYLFHVKDOOQRWFRQWLQXHWRVSDUNRYHU
6.2.13 Insulation testing of the tuning device components protected by auxiliary protective
GHYLFHV
D 7KHLPSXOVHVSDUNRYHUYROWDJHRIWKHDX[LOLDU\SURWHFWLYHGHYLFHVKDOOEHGHWHUPLQHGE\WHVWLQJZLWK
DWRîWRVZDYHIRUP7KHWHVWVVKDOOFRQVLVWRI¿YHSRVLWLYHDQG¿YHQHJDWLYHLPSXOVH
voltage waves. The setting of the auxiliary protective device shall be the maximum production setting
and shall not be less than that required in 6.2.12.
b) An impulse voltage of 1.2WRîWRVVKDOOEHDSSOLHGWRWKHWXQLQJGHYLFH7KHDX[LOLDU\
protective device shall be disconnected and the components shall be in the same physical relation
and with the same electrical connections they will have in service. Components not protected by the
DX[LOLDU\ SURWHFWLYH GHYLFH VKDOO EH GLVFRQQHFWHG 7KH WHVW VKDOO FRQVLVW RI ¿YH SRVLWLYH DQG ¿YH
QHJDWLYHLPSXOVHYROWDJHZDYHV7KHSHDNYDOXHVKDOOEHRIWKHYDOXHVSHFL¿HGLQ5.1.9.
The insulation test shall be performed on an assembled tuned-type line trap. Tuning device components and
wiring shall be connected in the operations setting, which produces a condition of maximum voltage stress on
the components and wiring, and between the live parts.
The insulation test of the assembled tuned-type line trap shall be performed by applying a 1.2 to 5.0 × 40 to 60
VLPSXOVHYROWDJHWRWKHWHUPLQDOVRIWKHOLQHWUDSZLWKWKHSURWHFWLYHGHYLFHGLVFRQQHFWHGDQGWKHDX[LOLDU\
protective device shorted. The magnitude of the voltage is determined from 5.1.9.
$VHULHVRI¿YHSRVLWLYHDQG¿YHQHJDWLYHLPSXOVHYROWDJHZDYHVVKDOOEHDSSOLHGWRWKHOLQHWUDS
To verify successful completion of the test, waveform records shall show no disruption in the 1.2 to 5.0 × 40
WRVSRVLWLYHDQGQHJDWLYHYROWDJHZDYHIRUPVDQGWKHEORFNLQJLPSHGDQFHVKDOOEHPHDVXUHGEHIRUHDQG
after the test.
These impulse/discharge tests as outlined in 5.1.9, 5.2.6, 6.2.12, and 6.2.13 shall be performed in accordance
with IEEE Std 4.
26
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
The main coil true inductance shall be obtained by either of the following methods:
The voltage/current method shall be used to determine the power frequency reactance of the main coil. The
apparent power frequency inductance of the main coil is calculated by dividing this reactance by the angular
power frequency.
3RZHUIUHTXHQF\WHVWRISURWHFWLYHGHYLFHDQGDX[LOLDU\SURWHFWLYHGHYLFHV
The protective device shall be subjected to power-frequency voltage withstand tests for metal-oxide surge
arresters according to IEEE Std C62.11. The auxiliary protective device(s) shall be given three consecutive
SRZHUIUHTXHQF\VSDUNRYHUWHVWVHDFKRIZKLFKVKDOOEHZLWKLQWKHVSDUNRYHUYROWDJHUDQJHFHUWL¿HGE\WKH
manufacturer.
7KHEORFNLQJLPSHGDQFHRIHDFKOLQHWUDSVKDOOEHPHDVXUHGXVLQJDVSHFLDOL]HGLQVWUXPHQWVIRUPHDVXULQJ
impedance and shall meet the requirements of 5.2.3.
)RUD¿HOGDGMXVWDEOHOLQHWUDSWKHPHDVXUHPHQWVKDOOEHSHUIRUPHGZLWKWKHOLQHWUDSWXQHGWRWKHVSHFL¿HG
IUHTXHQF\RUIUHTXHQFLHVRULIQRWVSHFL¿HGWRDIUHTXHQF\RUIUHTXHQFLHVWKDWUHTXLUHVDOOWXQLQJGHYLFH
components to be connected in the circuits.
The capacitance, inductance, and resistance of the tuning device capacitors, inductors, and resistors, respec-
tively, shall be measured to verify the component design values.
For the purpose of this test, the tuning device is disconnected from the main coil and a test voltage Vt = 1.3 V
applied for 5 s. The voltage V is determined in accordance with 5.1.8.
The insulation test procedures for the main coil shall be performed according to IEEE Std C57.21. The insula-
tion test level shall not be less than that required in 5.1.9.
7. Manufacturing/design requirements
7.1 Mounting
/LQHWUDSVIRUPRXQWLQJRQLQVXODWRUVVKDOOEHHTXLSSHGZLWKÀDQJHVWR¿WSUHGHWHUPLQHGEROWFLUFOHGLDPHWHUV
that could be for porcelain or composite insulators.
27
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
,QVXVSHQVLRQPRXQWLQJRIOLQHWUDSVFDUHPXVWEHWDNHQQRWWRH[FHHGWKHWHQVLOHVWUHQJWKUHTXLUHPHQWVLQ
accordance with 5.1.11.
7.2 Terminals
7.2.1 Location
The line-side and station-side terminals have been historically located at opposite ends of the line trap, but
SK\VLFDOO\OLQHWUDSVFDQKDYHWHUPLQDOVDWWKHVDPHVLGHLIXVLQJVWDQGR൵WHUPLQDOV
7.2.2 Types
7KHWHUPLQDOVRIWKHOLQHWUDSVIRUFXUUHQWV$DQGEHORZVKDOOEHÀDWSDGVDWOHDVWPPE\PP7KH
WHUPLQDOVRIWKHOLQHWUDSVIRUFXUUHQWV$DQGDERYHVKDOOEHÀDWSDGVDWPPE\PP)RXUPP
diameter holes shall be drilled symmetrically on 45 mm centers to allow connections both in line with, and at
right angles to, the coil axis.
Terminals that are an integral part of a structural member, such as a crossarm, shall conform to the above, ex-
cept it shall be permissible to allow connections only in line with the coil axis.
,WVKDOOEHSRVVLEOHWRPDNHFRQQHFWLRQWRHLWKHURUERWKVLGHVRIWKHWHUPLQDOV
Copper terminals shall be treated to allow the use of either aluminum or copper connectors.
Aluminum terminals are suitable for aluminum connectors. When copper connectors are used with aluminum
terminals, the connectors should be treated to allow an aluminum to copper joint.
28
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
29
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
Annex A
(informative)
If the short-time withstand current rating is exceeded, or the current in the line trap exceeds the continuous
current rating, then consideration should be given to utilizing a higher continuous current rated line trap so
WKDWORVVRIOLIHGRHVQRWRFFXU*HQHUDOO\VSHDNLQJDKLJKHUUDWHGFRQWLQXRXVFXUUHQWUDWLQJUHVXOWVLQDODUJHU
physical size line trap. There may be instances where a custom line trap can be provided that would provide a
line trap that still meets space requirements.
Table A.1 shows percentages of rated continuous current that should not be exceeded in order to minimize the
shortening in operating life.
The percentages in Table A.1 may be applied to all line traps covered in this standard. Exceeding these values
will generally result in some loss of life expectancy.
To avoid loss of life expectancy for the line trap it is recommended that the purchaser clearly specify the emer-
gency overload requirements at time of purchase.
30
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
The manufacturer provides the normal rating for rated continuous current for line traps. Emergency overload
current capacity is not stated within this standard other than the limited data in Table A.1. The following ex-
amples provide alternative methods when the overload falls outside the normal capacity ratings stated in Table
A.1.
A.1.2 Method 1
Ta + θ NR + θ ER ≤ TE max (A.1)
where:
Ta is the ambient air temperature: the assumed temperature of the air surrounding the line trap
measured at the station
T NR is the normal-continuous current temperature rise supplied by the manufacturer: the
temperature rise above ambient at rated continuous current in °C. (Use Table A.2 if
manufacturer’s data is unavailable.)
T ER is the emergency rating overload current capability temperature rise: the temperature rise in
°C above the rated continuous current temperature rise when operating at the emergency
overload current for the duration of the emergency
TE max is the emergency maximum allowable temperature supplied by the manufacturer: the
maximum allowable temperature under emergency conditions. (Use Table A.2 if
manufacturer’s data is unavailable.)
7DEOH$²/LQHWUDSLGHQWL¿FDWLRQREVROHWHDQGVRPHFXUUHQWH[DPSOHV
Line trap Line trap Limit of Normal Emergency maximum allowable
LGHQWL¿FDWLRQ insulation observable allowable temperature durations
class temperature maximum Greater 24 h or less
rise at rated temperature than 24 h
continuous
current
T NR TE max
Type or °C °C °C °C °C
Obsolete Traps
General Electric 130 90 130 145 160
(GE) type CF
(1954–1965) open
Table continues
31
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
Most line traps use the temperature designation rather than the B, F, or H designation.
The emergency rating overload current capability temperature rise ( T ER ) is calculated using the following
formula provided by one of the line trap manufacturers:
θ ER = ⎡( I ER I NR ) − 1⎤ × [θ NR ] × ⎡⎣1 − e( − tER τ ) ⎤⎦
2
(A.2)
⎣ ⎦
where:
(YHQZLWKLQWKHVDPHFRLOWHFKQRORJ\WKHWKHUPDOWLPHFRQVWDQWPD\YDU\VLJQL¿FDQWO\GHSHQGLQJRQWKHOLQH
WUDSUDWLQJVDQGVL]HV7KHXVHRIWKHDERYHPHQWLRQHG¿JXUHVPD\EHFRQVHUYDWLYHLQVRPHSDUWLFXODUFDVHV
The desired emergency current ( I ER ) and duration ( tER ) must be selected so that the inequality in
Equation (A.2) is true for the calculated emergency rating temperature rise T ER .
A.1.3 Method 2
The emergency overload current as a percentage of rated continuous current values from Table A.1 can be
JUDSKHGDQGDJUDSKLFDOWUHQGOLQHFDQEHGHWHUPLQHGXVLQJWKHEHVW¿WHTXDWLRQPHWKRG7KHIRUPXODIRUWKH
32
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
trend line may be used to extrapolate the emergency overload current as a percentage of rated continuous cur-
rent corresponding to durations not included in Table A.1.
In the graphical example below, the Table A.1 data for an ambient temperature of 40 °C was plotted and a trend
line was established. The trend line formula was then used to extrapolate the emergency overload current as a
percentage of rated continuous current of 153% for a 7 min duration. The trend line formula was also used to
extend the curve from 15 min to 7 min. The emergency overload current as a percentage of rated continuous
current of 148% for a 10 min duration was then determined from the extended portion of the graph.
Adding these graphically determined values to Table A.1 provides the following extended table:
This method may be used to produce extended curves and tables for other ambient temperatures in Table A.3.
These “extended values” are outside the normal test data results provided by the manufacturer unless other-
wise stated in their literature. It also assumes that the line equation holds true over the entire curve.
33
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
)LJXUH$²2YHUORDGUDWLQJRIOLQHWUDSVIURP&DPELHQWH[WUDSRODWHGIURPPLQWR
PLQXVLQJHTXDWLRQRIOLQHPHWKRG
7KHOLPLWLQJIDFWRUKHUHLVWKHLQVXODWLRQFKDUDFWHULVWLFDQGWKHKHDWLQJH൵HFWWKDWWDNHVSODFHIURPWKHORDG
current and any external temperature outside the upper temperature limit. Also, there are generally two types
of line traps, an “open” design and an “encapsulated” design.
For most applications, where the line trap is not subjected to any overload requirements, no further consider-
ations are involved. However, if there are occasional random events that need to be considered and whether the
line trap can survive the event of higher than rated continuous currents for a given time, then further evaluation
may be needed to determine if the insulation temperature will remain below the maximum limit.
Table A.1 is an overload table that can be used to remain within the design temperatures of the line trap and
avoid shortening the life of the trap. Excursions beyond these limits may still be within the maximum limita-
tions of the insulation, but may result in some loss of life of the line trap.
%HORZDUHWZRH[DPSOHVRQHRSHQDLUFRLODQGRQHHQFDSVXODWHGFRLOIRUVSHFL¿FPRGHOV
34
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
A.2.3 Examples
Given all of the above methodology, a practical question is to determine whether the line trap capabilities were
DGHTXDWHIRUWKHORVVRIRQHOLQHLQDWKUHHOLQHFRQ¿JXUDWLRQEHWZHHQWZRVWDWLRQVJLYHQWKDWWKHORDGZRXOG
be forced to automatically divide between the two remaining lines if one line tripped out. This was of special
LPSRUWDQFHZLWKDSRZHUSODQWDWRQHHQGWKDWFRXOGIRUFHWULSSLQJWKHXQLWVR൵OLQHLIWKHOLQHVZHUHQRWFDSD-
ble of carrying the line current.
For the loss of one line, the 3000 A line traps could potentially be subjected to up to 4800 A for 4 min on the
WZRUHPDLQLQJOLQHVWKDWLWZRXOGWDNHXQGHUH[LVWLQJRSHUDWLQJSURFHGXUHVWRUHGXFHWKHFXUUHQWRQWKHOLQHV
This could correlate up to 160% overload (OL) for 4 min. The line traps are pedestal mounted up high above
WKHJURXQGZKHUHWKHUHJHQHUDOO\LVVRPHZLQGÀRZWDNLQJSODFH8VHWKHDVVXPSWLRQRIPSKDVDUHDVRQDEOH
PLQLPXPLIWDNHQLQWRDFFRXQW
,QWKLVH[DPSOHWKHOLQHWUDSVRQHDFKHQGRIWKHOLQHVDUHWZRGL൵HUHQWW\SHVRQHW\SHLVHQFORVHGRUHQFDSVX-
lated and the other is an open coil design. The manufacturer indicates a normal temperature rise ( T NR ) of
115 °C for the Trench Type L and 100 °C for the General Electric (GE) Type CF. Both are rated 190 °C
( TE max ) for max temperature rating of the insulation per Trench.
— Six 3000 A - Trench Type: LTP, Rated Inductance: 265 uH, Type No.:L3000XZ0265-632PC1
— Six 3000 A - GE type 4CF02A
I NR is 3000 A
Ta is 40 °C
T NR is 100 °C, which is recommended by the manufacturer for no loss of life in this case, (note this is less
than the value in Table A.2, for a GE Type CF (after 1965) where a T NR of 115 °C is listed).
W is 15 min
The overload condition for the problem is 4 min; however, the overload will be calculated for both 4 min
and 6 min to assist in understanding boundaries for the overload capability. Substituting these values into
Equation A.2 yields:
⎡⎛ 4800 ⎞ 2 ⎤ ⎡ −( 6 ) ⎤
θ ER = ⎢⎜ ⎟ − 1⎥ × [100] × ⎢1 − e = [1.56] × [100] × [0.33] = 51.4°C temperature rise in 6 min
15
⎢⎣ ⎝ 3000 ⎠ ⎥⎦ ⎣ ⎦⎥
For 6 min, the overload caused a 51.4 °C average rise in temperature from the steady state condition. (151.4 °C
total average rise-at the end of the overload). Adding the ambient temperature results in 151.4 °C + 40 °C =
191.4 °C total average temperature for 6 min.
35
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
⎡⎛ 4800 ⎞ 2 ⎤ ⎡ −( 4 ) ⎤
θ ER = ⎢⎜ ⎟ − 1⎥ × [100] × ⎢1 − e = [1.56] × [100] × [0.234] = 36.5°C temperature rise in 4 min
15
⎢⎣⎝ 3000 ⎠ ⎥⎦ ⎣ ⎦⎥
For 4 min, the overload results in a total temp of 177 °C, and for 6 min a temperature of 191 °C as summarized
in Table A.4. The allowable maximum temperature TE max is 190 °C for 24 h or less.
T NR rise 10 100
I NR is 3000 A
Ta is 40 °C
T NR is 115 °C, which is recommended by the manufacturer for no loss of life in this case, (note this is more
than the value for a Trench encapsulated Type L in Table A.2 where a T NR of 110 °C is listed).
W is 48 min
Once again, the overload condtion for the problem is 4 min; however, the overload will be calculated for both 4
min and 6 min to assist in understanding boundaries for the overload capability. Substituting these values into
Equation A.2 for 6 min yields:
⎡⎛ 4800 ⎞ 2 ⎤ ⎡ −( 6 ) ⎤
θ ER = ⎢⎜ ⎟ − 1⎥ × [115] × ⎢1 − e ⎥⎦ [
= 1.56] × [115] × [ 0.1175] = 21.1°C temperature rise in 6 min
48
⎢⎣ ⎝ 3000 ⎠ ⎥⎦ ⎣
For 4 min, the overload results in a total temperature of 169 °C, and for 6 min a temperature of 176 °C as sum-
marized in Table A.5. The allowable maximum temperature TE max is 190 °C for 24 h or less.
After performing the calculations for both examples, the Trench and GE line traps on both ends of the lines
meet the 160% overload current criteria for 4 min.
36
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
The maximum permissible total average temperature for the various coil types of this example, with no loss of
life per the manufacturer, are:
Overloads with no loss of life should be calculated so that the rise in average temperature due to the overload
compensates for the drop in ambient temperature. In other words, overloads at rated ambient are not allowed
unless loss of life is acceptable.
Trench is the supplier of Trench Electric Line Traps. They also bought the design and support of the (out of
production) GE Line Traps and carrier equipment.
Some loss of life may occur when operated at the upper end of these extended higher overload current.
After performing the calculations in both examples, the Trench and GE line traps on both ends of the lines
meet the 160% overload current criteria for 4 min.
,QWKLVH[DPSOHWKHOLQHWUDSVDUHWZRGL൵HUHQWW\SHVRQHW\SHLVHQFORVHGRQHW\SHLVDQRSHQFRLOGHVLJQ
Both are rated 190 °C for max temperature rating of the insulation per Trench.
37
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps(30 kHz to 500 kHz)
Annex B
(informative)
Impedance bridges and current comparator bridges are frequently used to measure losses. They are generally
PRUHDFFXUDWHWKDQZDWWPHWHUPHDVXUHPHQWV:KLOHPDQ\FRQ¿JXUDWLRQVRILPSHGDQFHEULGJHQHWZRUNVDUH
SRVVLEOHWKHFKRLFHRIDSDUWLFXODUQHWZRUNVKDOOEHGHWHUPLQHGE\WKHPHDVXUHPHQWSUREOHPDWKDQGDQGWKH
testing facilities available.
If the purchaser requires the losses to be determined, this should be done by agreement with the manufacturer.
$UHTXLUHPHQWIRUORZHUSRZHUORVVHVFDQLQÀXHQFHWKHRYHUDOOH[SHQGLWXUHIRUWKHOLQHWUDS
Because line traps vary widely in design and construction, it is recommended, for comparison purposes, that
the losses be corrected for a temperature of 75 °C.
38
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
Annex C
(informative)
)LJXUH&²&RPPRQWHUPLQDORULHQWDWLRQDQGFRQVWUXFWLRQSDUW
39
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
)LJXUH&²&RPPRQWHUPLQDORULHQWDWLRQDQGFRQVWUXFWLRQSDUW
C.2 Schematic
The following schematic (see Figure C.3) is typical for an FWB trap as described in 6.2.1. L is the main power
LQGXFWLYHFRLO7KHWXQLQJSDFNFRQVLVWVRI&1, R1, C2, and L2. C1 and C2 are capacitors, where C1 forms a reso-
nance with L. C2 and L2DUHWKHVHULHVHOHPHQWVWKDWD൵HFWWKHVHULHVUHVRQDQFHDWWKHJHRPHWULFPHDQIUHTXHQF\
(GMF). R1D൵HFWVWKHPLQLPXPOLQHWUDSLPSHGDQFHDWWKH*0)
40
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
41
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
Annex D
(informative)
7\SLFDO¿[HGZLGHEDQGEDQGZLGWKUDQJHV
Refer to Table D.1IRUDOLVWLQJRIW\SLFDO¿[HGZLGHEDQGEDQGZLGWKUDQJHVIRUDQGPLQ
N+]
Table D.1—Typical bandwidth ranges for factory wideband 0.265 mH line traps
PLQ PLQ PLQ PLQ
kHz kHz kHz kHz
40.0–48.0 46.0 –53.0 60.0–68.0 70.0–79.0
42.0–52.0 50.0–58.0 65.0–75.0 74.0–84.5
45.0–57.0 54.0–64.5 70.0–82.0 78.0–90.0
50.0–66.0 58.0–70.5 75.0–89.0 82.0–95.5
54.0–73.5 62.0–76.8 80.0–97.0 86.0–101.5
58.0–81.5 66.0–83.5 85.0–104.5 90.0–107.5
62.0–89.5 70.0–90.3 90.0–113.0 94.0–113.5
66.0–98.5 74.0–97.0 95.0–121.0 98.0–119.5
70.0–108.0 78.0–104.0 100.0–130.0 102.0–126.5
74.0–117.0 82.0–112.0 105.0–139.0 106.0–132.5
78.0–128.0 86.0–120.0 110.0–148.0 110.0–139.0
82.0–139.0 90.0–128.0 115.0–158.0 114.0–146.0
86.0–153.0 94.0–136.0 120.0–168.0 118.0–152.0
90.0–166.0 98.0–144.0 125.0–178.0 122.0–159.0
94.0–181.0 102.0–154.0 130.0–191.0 126.0 –166.0
98.0–199.0 106.0–163.0 135.0–203.0 130.0–174.0
102.0–214.0 110.0–173.0 140.0–214.0 134.0–181.0
106.0–234.0 114.0 –184.0 145.0–227.0 138.0–189.0
110.0–255.0 118.0 –195.0 150.0–241.0 142.0–196.0
114.0– 278.0 122.0–208.0 155.0–254.0 146.0–204.0
118.0–306.0 126.0– 221.0 160.0–269.0 150.0–212.0
122.0–339.0 130.0–233.0 165.0–283.0 154.0–220.0
126.0–376.0 134.0–247.0 170.0–299.0 158.0–229.0
128.5–400.0 138.0–262.0 175.0–316.0 162.0–238.0
133.0–450.0 142.0–278.0 180.0–333.0 166.0–247.0
137.0 –500.0 146.0–294.0 185.0–351.0 170.0–256.0
— 150.0–311.0 190.0–370.0 175.0–270.0
— 155.0–335.0 195.0–390.0 180.0–281.0
— 160.0–361.0 200.0–410.0 185.0–294.0
— 165.0–388.0 205.0–434.0 190.0–306.0
— 170.0–416.0 210.0–458.0 195.0–321.0
— 175.0–450.0 215.0–488.0 200.0–337.0
— 180.0–486.0 217.0–500.0 205.0–351.0
— 182.0–500.0 — 210.0–368.0
Table continues
42
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
Table D.1—Typical bandwidth ranges for factory wideband 0.265 mH line traps (continued)
PLQ PLQ PLQ PLQ
kHz kHz kHz kHz
— — — 215.0–384.0
— — — 220.0–400.0
— — — 225.0–418.0
— — — 230.0–436.0
— — — 235.0–455.0
— — — 240.0–476.0
— — — 245.0–500.0
43
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C93.3-2017
IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz)
Annex E
(informative)
Bibliography
Bibliographical references are resources that provide additional or helpful material but do not need to be un-
derstood or used to implement this standard. Reference to these resources is made for informational use only.
[B1] ANSI C93.1, American National Standards Requirements for Power Line Carrier Coupling Capacitors &
Coupling Capacitor Voltage Transformers.6
[B2] ANSI/NEMA C29.8, American National Standards for Wet-Process Porcelain Insulators (Apparatus,
Cap and Pin Type).7
>%@%DJZHOO$DQG+'REVRQ³8VHRI&DUULHU/LQH7UDSV:LWK1R7XUQLQJ3DFNV´79$3DSHU7±±
36&&,(((:LQWHU0HHWLQJ>$GHPRQVWUDWLRQRIWKHLGHDRIVHOIWXQLQJZLWKRXWWXQLQJSDFNVLQOLQH
traps].
[B4] IEEE Std 693™, Recommended Practice for Seismic Design of Substations.8
6
ANSI publications are available from the Sales Department, American National Standards Institute, 25 West 43rd Street, 4th Floor, New
<RUN1<86$http://www.ansi.org/).
7
NEMA publications are available from Global Engineering Documents, 15 Inverness Way East, Englewood, CO 80112, USA (http://
global.ihs.com/).
8
IEEE publications are available from the Institute of Electrical and Electronics Engineers, Inc., 445 Hoes Lane, Piscataway, NJ 08854,
USA (http://standards.ieee.org/).
44
Copyright © 2017 IEEE. All rights reserved.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: Victoria University. Downloaded on July 21,2021 at 02:18:45 UTC from IEEE Xplore. Restrictions apply.