S5134 Ethernet IO Modules: 8 Channels Universal AI, 8 Channels AO 8 Channels DO, 3channels DI

The S5134 is an analog and digital I/O module that provides 8 universal analog inputs, 8 analog outputs, 3 digital inputs, and 8 digital outputs. It uses standard Modbus RTU and TCP/IP protocols for communication over RS485 and Ethernet. The module supports a wide range of analog signal types and has surge protection on its I/O channels. It is a low cost and high quality solution for remote data acquisition, industrial automation, and other applications.

Uploaded by

anaklurah sini
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
315 views10 pages

S5134 Ethernet IO Modules: 8 Channels Universal AI, 8 Channels AO 8 Channels DO, 3channels DI

The S5134 is an analog and digital I/O module that provides 8 universal analog inputs, 8 analog outputs, 3 digital inputs, and 8 digital outputs. It uses standard Modbus RTU and TCP/IP protocols for communication over RS485 and Ethernet. The module supports a wide range of analog signal types and has surge protection on its I/O channels. It is a low cost and high quality solution for remote data acquisition, industrial automation, and other applications.

Uploaded by

anaklurah sini
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

S5134

Ethernet IO Modules
8 Channels Universal AI, 8 Channels AO
8 Channels DO, 3Channels DI

SHJ
Sales: [email protected]

Support: [email protected]
S5134 User’s Manual Rev 1.1

S5134 is a high quality and low cost analog data acquisition module with 8 universal analog
inputs. Each input can be 0-5V,0-10V,0-20mA,thermistor,dry contact, open-collector input,8
channels 0-10V analog output,3 isolated digital input and 8 channels isolated open-collector
digital output. The digital input can be dry contact, wet contact and open-collector, each input
also can be 32-bit counter.S5134 has RS485 and rj45 two type interface,rs485 support standard
Modbus RTU protocol and RJ45 support Modbus Tcpip protocol.It can easy integrate with PLC
and labview with standard Modbus/Modbus Tcpip protocol
Highlights:
z Surge-protected analog inputs with 12-bit resolution and 100k sample speed
z Input can be any combination of 0-5V,4-20mA,0-10V,NTC 10K thermistor,
open-collector and dry contact
z The channel number is configurable, can be set up from 1 channel through 8 channels,
for analog input and set up from 1 to 6 for digital input, improve sample rate for small
count input
z 8 channels 0-10V analog output with high accurate reference chip
z Isolated digital inputs can be configured as counter input, total 32 bits,1000Hz
z Total 8 channels isolated open-collector digital output
z Standard ModBus TCPIP protocol,easy work with PLC
z Standard ModBus protocol allows for up to 254 unique devices on one RS485 network
z A lot of spare FLASH can be used to store user’s parameters
z Can update your firmware via ISP through RS485 network, can provide any hex file to
help you finish some logic control
z DIN support available

Application:
9 Remote data acquisition
9 Process monitoring
9 Industrial process control
9 Energy management
9 Supervisory control
9 Security systems
9 Laboratory automation
9 Building automation
9 Product testing
9 Direct digital control

www.SHJelectronic.com 2 [email protected]
S5134 User’s Manual Rev 1.1

Technical data:
Analog Input Resolution--------------------------------------------------------------------------------12-bit
Analog Input Channel Number------------------------------------------------------------------------------8
Analog Input range----------------------0-5V,0-10v,0-20mA, thermistor, dry contact,open-collector
Analog Input Protection---------------------------------------------------------------------Lightning,static
Analog Input Accuracy---------------------------------------------------------------------------------±0.1%
Analog Input Zero drift-----------------------------------------------------------------------------±3uV/℃
Analog Input Sample Rate-----------60 sample/second(8 channels),900 sample/second(1 channel)

Analog Output Resolution-----------------------------------------------------------------------------12-bit


Analog Output Channel Number--------------------------------------------------------------------------8
Analog Output Range----------------------------------------------------------------------------------0-10V
Analog Output Accuracy--------------------------------------------------------------------±0.2% of FSR
Analog Output Zero Drift------------------------------------------------------------------------±30uV/℃

Digital Input Channel Number----------------------------------------------------------------------------- 3


Digital Input Range-------------------------------------------------------------------------------+4V~+36V
Digital Input Signal----------------------------------------------wet contact, dry contact, open-collector
Digital Input Counter Frequency-------------------------------100Hz@3channels;1000Hz@1channel
Digital Input Counter Length---------------------------------------------------------------------------32-bit

Output channel number------------------------------------------------------------------------8


Output signal---------------------------------------------------------------------open-collector
Output current----------------------------------------------------------------maximum 40mA

Output BUS----------------------------------------------------------------------------------Ethernet/RS485
RS232/RS485 protocol--------------------------------------------------------------MODBUS/RTU
Ethernet protocol------------------------------------------------------------------MODBUS/TCPIP
Output Protection-----------------------------------------------------------------------------Lightning,static
Power input----------------------------------------------------------------------------------15~24V(AC/DC
Power consumption------------------------------------------------------------------------------------<0.6W
Ambient temperature:
Operation-------------------------------------------------------------------------- -20~85℃(-4~185℉)
Storage---------------------------------------------------------------------------------------- -40~125℃(-40~257℉)
Ambient humidity-----------------------------------------------------------------------------------------------10%~90%RH
Material,enclosure-----------------------------------------------------------------------Flame proof plastic
Enclosure rating--------------------------------------------------------------------------------------------IP31
Colour----------------------------------------------------------------------------------------------White/Black
Size---------------------------------------------------------------------------------------------115*90*43 mm
Wiring diagram and description:

www.SHJelectronic.com 3 [email protected]
S5134 User’s Manual Rev 1.1

Top view figure

Communication wiring diagram

www.SHJelectronic.com 4 [email protected]
S5134 User’s Manual Rev 1.1

Analog inputs wiring diagram

Analog outputs wiring diagram

Dry contact wiring diagram

www.SHJelectronic.com 5 [email protected]
S5134 User’s Manual Rev 1.1

WET contact wiring diagram

Isoalted digital output wiring diagram

Inputs
Each analog input can be jumper-configured in 1 of 4 ways:
— 0-5V signal
— 0-10V
— 0-20mA
— Dry contact, thermistor, open-collector. thermistor default is 10K NTC, but can custom according

www.SHJelectronic.com 6 [email protected]
S5134 User’s Manual Rev 1.1

to your sensor type


All digital inputs can be jumper-configured in 1 of 2 ways:
— Wet contact input
— Dry contact, open-collector input
PINs and LEDs
Power supply
24VAC: power supply positive input, has reverse protection, accept AC and DC input
- : Power supply negative input
RS485 Port
B: Connect to B of RS485
A: Connect to A of RS485
R: Connect to GND for RS485
Ethernet port
Connect to local Ethernet network through RJ45 cable

Inputs
Analog:
A1 ~ A8: Analog input 1 through 8
AGND: common for analog input 1 through 8,also use for analog output
Digital:
DVCC: Power source input for digital input 1 through 3,wet contact input available
D1 ~ D3: Digital input channel 1 through 3
DGND: common for digital input 1 through 3, available in dry input mode
Outputs
Analog:
AO1 ~ AO8: Analog output 1 through 8
AGND: common for analog output 1 through 8,also use for analog input
Digital:
O1~O8: Digital output channel 1 through 8
OGND: common GND for digital output 1 through 8

Leds
BEAT: Will flash when system is working
Comm: Will flash when RS485 serial port communication

Modbus register list:


Note: * means default value
Value range Proper
Address Bytes Description
Min Max ty
0-3 4 1 4294967295 Serial number,unique for each product R
4-5 2 100 65535 Firmware version number R

www.SHJelectronic.com 7 [email protected]
S5134 User’s Manual Rev 1.1

6 1 1 254 Device address,default is 254* R/W


7 2 5134 5134 Product model R
8 1 1 255 Hardware version R
Baudrate setting
Value Buadrate
12 1200
24 2400
48 4800
9 2 12 1152 96 9600 R/W
192* 19200*
384 38400
576 57600
1152 115200
For example:write 96 to register 9 to set the baudrate 9600.
10-99 - - - Reserved -
Analog reading for channel input 1 through 8,the units
100-107 2 0 4095 R
decided by register 119 through 126
Status for digital input channel 1 through 3, 0 = contact
108 1 0 255 active,1 = contact inactive.Bit0 correspond to channel R
1,bit1 correspond to channel 2 etc.
Open-collector output,0 = active,1 = inactive.Bit0
109 1 0 255 R/W
correspond to output 1,bit1 correspond to channel 2 etc.
Analog output1 voltage setting,6000 set output voltage
110 2 0 10000 R/W
6.00V
Analog output2~8 voltage setting,6000 set output voltage
111~117 2 0 10000 R/W
6.00V
Enable/disable the corresponding channel,0 = disable,1* =
enable.Bit0 correspond to channel 1 and Bit7 correspond to
118 1 0 255 R/W
channel 8.For example,enable channel 1,2 and disable
channel 3 through 8,write 0x03 to register 118.
Channel 1 through 8 units setting.0* = raw AD sample
reading,1 = 0~5V(real value = the current reading / 100,for
example, the current reading is 288,the real voltage is
288/100 = 2.88V),2 = 0~10V(real value = current reading /
119-126 1 0 8 100),3 = 4~20mA(real value = the current reading / R/W
100),4 = 0~100%,5 = ON/OFF,6 = OFF/ON,7 = 10K
thermistor,  elsius(real value = current reading / 10),8 =
10K thermistor,Fahrenheit(real value = current reading
/ 10).

www.SHJelectronic.com 8 [email protected]
S5134 User’s Manual Rev 1.1

Channel 1 through 8 Filter factor,0 = no filter,10* is


127-134 1 0 100 R/W
default.
135,137, In calibration mode, channel 1 through 8 sample data as
2 0 4095 R/W
139 … input 0 volts
136,138 In calibration mode, channel 1 through 8 sample data as
2 0 4095 R/W
140… input is full scale
The minimum reading from multimeter when calibrate
151 2 0 30000 R/W
analog output channel 1
The maximum reading from multimeter when calibrate
152 2 0 30000 analog output channel 1,multimeter is show 10.05V,then R/W
write 10050 to this register.
153,155 The minimum reading from multimeter when calibrate
2 0 30000 R/W
… analog output channel 2~8
154,156 The maximum reading from multimeter when calibrate
2 0 30000 R/W
… analog output channel 2~8
Analog input 1 through 8 in temperature units, use
167~174 2 0 1000 R/W
calibrate temperature by adjust the offset
175 2 0 65535 High word for digital input1 counter R/W
Low word for digital input1 counter, value of counter =
176 2 0 65535 R/W
(175)*65536 + (176)
177 2 0 65535 High word for digital input2 counter R/W
Low word for digital input2 counter, value of counter =
178 2 0 65535 R/W
(177)*65536 + (178)
179 2 0 65535 High word for digital input3 counter R/W
Low word for digital input3 counter, value of counter =
180 2 0 65535 R/W
(179)*65536 + (180)
181~186 Reserved -
Filter time for counter input, the units is 10us and the
187 2 1 30000 R/W
default is 200us
Disable/enable input,0 = disable and 1 = enable.Bit0
188 1 0 255 R/W
correspond to input1, Bit1 correspond to input 2 and so on.
Input status selection.0 = ON/OFF,1 = OFF/ON, default is
189 1 0 1 R/W
ON/OFF
Digital input counter will increase at rising edge or falling
190 1 0 1 R/W
edge.0 = rising edge,1 = falling edge, default is rising edge
Respond delay for serial communication, the units is ms
191 1 1 100 R/W
and default is 10ms
192-199 - - - reserved -

www.SHJelectronic.com 9 [email protected]
S5134 User’s Manual Rev 1.1

200-203 1 0 255 Device local IP address, default is 192.168.0.18 R/W

204-207 1 0 255 Gate way address, default I is 192.168.0.X R/W

208-211 1 0 255 Subnet address, default is 255.25.255.0 R/W

212-217 1 0 255 MAC address R/W


Port number, default is 502, Write this register also save
218 2 0 65535 R/W
value of register 200 to 218.
Default Settings:
Device ID: 254, 255 is broadcast address
Data Format: 1 start bit, 8 data bit, 1 stop bit, none parity
Baudrate: 19200
There are a INIT jumper inside the board,short INIT then power on S5134,parameters will go to
default settings.