3.1 Voltage and Current 4.Set Up 4.4 Supply System


SDM630-Modbus
Three Phase Multifunction DIN Rail Energy Meter The unit has a default setting of 3Phase 4wire (3P4).
Each successive press of the button selects a new parameter: To enter set-up mode, press the button for 3 seconds,
Use this section to set the type of electrical system.
until the password screen appears.
From the set-up menu, use
Setting up is password- MD
and buttons to
Phase to neutral voltages. protected so you must select the system option.
enter the correct password The screen will show the
(default ‘1000’) before currently selected power
processing. supply.

Current on each phase. If an incorrect password Press to enter the


is entered, the display will selection routine. The
show: current selection will flash.

PASS Err

DIN RAIL SMART METER Phase to neutral voltage To exit setting-up mode, press repeatedly until the Use MD and
THD% of 2nd to 19th. measurement screen is restored. buttons to select the
FOR SINGLE AND THREE PHASE required system option:
ELECTRICAL SYSTEMS 1P2 (W),3P3 (W),3P4 (W).

User Manual V5.0 4.1 Set-up Entry Methods


Some menu items, such as password, require a four-digits
1.Introduction Each phase Current number entry while others, such as supply system,
Press to confirm the
THD% of 2nd to 19th. require selection from a number of menu options.
selection. SET indicator
This document provides operating, maintenance and
will appear.
installation instructions.This unit measures and displays
the characteristics of single phase two wires (1p2w),three 4.1.1 Menu Option Selection
phase three wires (3p3w) and three phase four wires (3p4w)
networks.The measuring parameters include voltage (V), 1. Use the MD and buttons to scroll through the Press to exit the system selection routine and return to
frequency (Hz),current (A),power (kW/Kva/Kvar),Imported, 3.2 Frequency and Power Factor and Demand different options of the set up menu. the menu. SET will disappear and you will be returned to the
exported and total Energy (kWh/kvArh).The units can also main set-up Menu.
Each successive press of the MD
button selects a new range: 2. Press to confirm your selection
measure Maximum demand current and power, this is
measured over preset periods of up to 60 minutes. 3. If an item flashes, then it can be adjusted by the MD
and
buttons.
4.5 Backlit set-up
The unit is max 100A direction operated and does not need
to connect with external current transformers (CT).Built-in pulse, Backlit lasting time is settable,default lasting time is 60minutes
Frequency and Power 4. Having selected an option from the current layer, press
RS485 Modbus RTU outputs.Configuration is password protected. to confirm your selection. The SET indicator will appear.
Factor (total).
If it’s setted as 5,the backlit
5. Having completed a parameter setting, press to return
1.1 Unit Characteristics to a higher menu level. The SET indicator will be removed will be off in 5 minutes if
and you will be able to use the MD and buttons for there is no more further
The Unit can measure and display:
·Line voltage and THD% (total harmonic distortion) of all phases further menu selection. operation.
·Line Frequency
·Currents, Current demands and current THD% of all phases
Power Factor of each 6. On completion of all setting-up, press repeatedly until
·Power, maximum power demand and power factor phase. the measurement screen is restored. Press to enter the
·Active energy imported and exported
·Reactive energy imported and exported selection routine.The current
time interval will flash
The unit has password-protected set-up screens for: 4.1.2 Number Entry Procedure The options are:
·Changing password 0(always on)/5/10/30/60/120
·Supply system selection 1p2w, 3p3w,3p4w When setting up the unit, some screens require the entering
·Demand Interval Time(DIT) Maximum Power Demand. of a number. In particular, on entry to the setting up section, a
·Reset for demand measurements
password must be entered. Digits are set individually, from left Press MD
and to select the time interval.Then press
·Pulse output duration
to right. The procedure is as follows:
Two pulse output indicates real-time energy measurement. to confirm the set-up.
An RS485 output allows remote monitoring from another 1. The current digit to be set flashes and is set using the MD

display or a computer. and buttons


4.6 Pulse Output
Maximum Current 2. Press to confirm each digit setting. The SET indicator
1.2 RS485 Serial–Modbus RTU Demand. appears after the last digit has been set. This option allows you to configure the pulse output 1.The
RS485 serial port with Modbus RTU protocol to provide a output can be set to provide a pulse for a defined amount of
3. After setting the last digit, press to exit the number
means of remotely monitoring and controlling the Unit.Set-up energy active or reactive. Use this section to set up the
setting routine. The SET indicator will be removed.
screens are provided for setting up the RS485 port. pulse output for:
Toal kWh/Total kVArh
3.3 Power 4.2 Change Password Import kWh/Export kWh
1.3 Pulse output
Each successive press of the button select a new range: Import KVArh/Export KVArh
Two pulse outputs that pulse measured active and reactive
energy.The constant of pulse output 2 for active energy is
400imp/kWh (unconfigurable),its width is fixed at 100ms. From the set-up menu, use
The default constant of configurable pulse output 1 is Use the MD and MD and buttons
400imp/kWh,default pulse width is 100ms.The configurable Instantaneous Active to choose the change
Power in kW. to select the Pulse output
pulse output 1 can be set from the set-up menu. password option. option.

2.Start Up Screens
Press the to enter the
change password routine. Press to enter the
The first screen lights up Instantaneous Reactive The new password screen selection routine. The unit
all display segments and Power in kVAr. will appear with the first symbol will flash.
can be used as a display digit flashing.
check.
C1C2
Use MD and to set
the first digit and press Use MD and
Instantaneous Volt-Amps to confirm your buttons to choose kWh or
in KVA. selection. The next digit kVArh.
Software version information will flash.

On completion of the entry procedure, press to confirm


the setting and press to return to the main set up menu.
Repeat the procedure for
Total kW, kVArh, kVA. the remaining three digits.
The interface performs a
self-test and indicates the 4.6.1 Pulse rate
result if the test passes.
Use this to set the energy represented by each pulse.
Rate can be set to 1 pulse per
dFt/0.01/0.1/1/10/100 kWh/kVArh.
3.4 Energy Measurements After setting the last digit,
*After a short delay, the screen will display active energy interface
measurements. SET will show.
as follows:
Each successive press of the button selects a new range:

Press to exit the number setting routine and return to the


Total active energy in kWh. Imported active energy Set-up menu. SET will be removed
in kWh.
(It shows 1 pulse = 10kWh/kVArh)
4.3 DIT Demand Integration Time
3.Measurements This sets the period in minutes over which the current From the set-up menu,
and power readings are integrated for maximum demand use MD and buttons
The buttons operate as follows: Exported active energy
measurement. The options are: off, 5,10,15,30,60 minutes. to select the Pulse Rate
in kWh.
Selects the Voltage and Current display option.
screens. In Set-up Mode, this is the “Left” From the set-up menu, use
or “Back” button. MD
and buttons
to select the DIT option. Press to enter the
Select the Frequency and Power factor The screen will show selection routine. The
display screens. In Set-up Mode, this is the currently selected
Total active energy in kWh. current setting will flash.
the “Up” button. integration time. When it’s dFt (default),it
means 2.5Wh/VArh.
Select the Power display screens. In Set-
up Mode, this is the “Down” button. Press to enter the
selection routine. The Use MD
and buttons to choose pulse rate.
Select the Energy display screens. In Set- current time interval will On completion of the entry procedure, press to confirm
Imported reactive energy flash.
up mode, this is the “Enter” or “Right”
button. the setting and press to return to the main set up menu.

Use
MD
and
4.6.2 Pulse Duration
Warnings buttons to select the time The energy monitored can be active or reactive and the pulse
required. width can be selected as
Important Safety Information is contained in the Exported reactive energy
Maintenance section. Familiarize yourself with this 200,100 (default) or 60ms.
information before attempting installation or other
procedures. Symbols used in this document:

Risk of Danger: These instructions contain Press to confirm the


! important safety information. Read them before selection. SET indicator
will appear.
starting installation or servicing of the equipment.
Total reactive energy
Caution: Risk of Electric Shock
Press to exit the DIT selection routine and return to the menu. (It shows pulse width of 100ms)
4.8 CLR 5.6 Environment 8.Installation
From the set-up menu, The meter provides a function to reset the maximum demand • Operating temperature -25°C to +55°C*
use MD and buttons value of current and power. • Storage temperature -40°C to +70°C*
35
to select the Pulse width • Relative humidity 0 to 95%, non-
mm
option.
condensing
From the set-up menu, use
• Altitude Up to 3000m
MD
and buttons to
• Warm up time 1 minute
select the reset option.
Press to enter the • Vibration 10Hz to 50Hz, IEC
selection routine. The 60068-2-6, 2g
current setting will flash. • Shock 30g in 3 planes

Press to enter the * Maximum operating and storage temperatures are in the
selection routine. The MD context of typical daily and seasonal variation.
Use MD
and buttons to choose pulse width. will flash.

On completion of the entry procedure press to confirm 5.7 Mechanics


the setting and press to return to the main set up menu. • DIN rail dimensions 76 x 94.5 mm (WxH)
Press to confirm the setting and press to return to
per DIN 43880
the main set up menu. DIN Rail
• Mounting DIN rail (DIN 43880)
4.7 Communication • Sealing IP51 (indoor)
There is RS485 port can be used for communication 5.Specifications • Material Self-extinguishing
Modbus RTU protocol. For Modbus RTU, parameters are Ul94 V-0
5.1 Measured Parameters
selected from front panel.
The unit can monitor and display the following parameters of a
6.Dimensions Warnings
4.7.1 RS485 Address single phase two wire (1p2w), three phase three wire (3p3w) or
three phase four wire (3p4w) system. Important Safety Information is contained in the
Maintenance section. Familiarize yourself with this
information before attempting installation or other
5.1.1 Voltage and Current procedures. Symbols used in this document:
• Phase to neutral voltages 100 to 289V a.c. (not for 3p3w Risk of Danger: These instructions contain
supplies). ! important safety information. Read them before
• Voltages between phases 173 to 500V a.c. (3p supplies only). starting installation or servicing of the equipment.
(The range is from 001 to 247) • Percentage total voltage harmonic distortion (THD%) for
Caution: Risk of Electric Shock
each phase to N ( not for 3p3w supplies).
• Percentage voltage THD% between phases (three phase
From the set-up menu, supplies only).
MD
and buttons to • Current THD% for each phase
select the address ID.
5.1.2 Power factor and Frequency and
Max. Demand
• Frequency in Hz
Press button to enter
the selection routine. The • Instantaneous power: 7.Wiring diagram
current setting will be • Power 0 to 99999 W
flashing.
• Reactive power 0 to 99999 VAr
7.1 single phase two wires
• Volt-amps 0 to 99999 VA
• Maximum demanded power since last Demand reset
Use
MD
and Power factor 2
1
buttons to choose Modbus • Maximum neutral demand current, since the last Demand
A B
address (001 to 247). reset (for three phase supplies only)

5.1.3 Energy Measurements


8 9 10
On completion of the entry procedure, press button to • Imported active energy 0 to 999999.99 kWh 5 6 7 11 12 13

confirm the setting and press button to return the main • Exported reactive energy 0 to 999999.99 kVarh
set-up menu. • Imported active energy 0 to 999999.99 kWh
• Exported reactive energy 0 to 999999.99 kVarh
4.7.2 Baud Rate • Total active energy 0 to 999999.99 kWh
• Total reactive energy 0 to 999999.99 kVArh

From the set-up menu, 5.2 Measured Inputs


use MD and buttons
Voltage inputs through 4-way fixed connector with 25mm²
to select the Baud Rate
option. stranded wire capacity.single phase two wire (1p2w), three
phase three wire (3p3w) or three phase four wire (3p4w)
unbalanced. Line frequency measured from L1 voltage or
1 2 3 4
L3 voltage.

Press to enter the 5.3 Interfaces for External Monitoring


selection routine. The
current setting will flash. Three interfaces are provided:
• RS485 communication channel that can be programmed
via protocol remotely. L N
• Pulse output (pulse1) indicating real-time measured energy.
Use MD and (configurable)
buttons to choose Baud 7.2 three phase three wires
• Pulse output (pulse2) 400imp/kWh (not configurable)
rate.
The Modbus configuration (baud rate etc) and the pulse
relay output assignments (kW/kVArh, import/export etc) are 2

configured through the set-up screens. 1

On completion of the entry procedure, press to confirm A B

the setting and press to return to the main set up menu. 5.3.1 Pulse Output
The pulse output can be set to generate pulses to represent 8 9 10
4.7.3 Parity kWh or kVArh.
5 6 7 11 12 13
Rate can be set to generate 1 pulse per:
dFt (default) = 2.5 Wh/VArh
From the set-up menu, use 0.01 = 10 Wh/VArh
MD
and buttons to 0.1 = 100 Wh/VArh
select the parity option. 1 = 1 kWh/kVArh
10 = 10 kWh/kVArh
100 = 100 kWh/kVArh
Pulse width 200/100/60 ms.
Press to enter the Pulse output 2 is non-configurable.It is fixed up with active kWh.
selection routine. The Its constant is 400imp/kWh.
current setting will flash.
1 2 3 4
5.3.2 RS485 Output for Modbus RTU
For Modbus RTU, the following RS485 communication
parameters can be configured from the set-up menu:
MD
Use and buttons
Baud rate 2400, 4800, 9600, 19200, 38400
to choose parity (EVEN /
ODD / NONE). Parity none / odd / even
L1 L3 L2
Stop bits 1 or 2
RS485 network address nnn – 3-digit number, 001 to 247
On completion of the entry procedure, press to confirm
7.3 three phase four wires
the setting and press to return to the main set up menu. 5.4 Accuracy
• Voltage 0·5% of range maximum 2
1

4.7.4 Stop bits • Current 0·5% of nominal A B

• Frequency 0·2% of mid-frequency


• Power factor 1% of unity (0.01)
From the set-up menu, use 8 9 10
MD
and buttons to • Active power (W) ±1% of range maximum
• Reactive power (VAr) ±1% of range maximum
5 6 7 11 12 13
select the stop bit option.
• Apparent power (VA) ±1% of range maximum
• Active energy (Wh) Class 1 IEC 62053-21
• Reactive energy (VARh) ±1% of range maximum
Press to enter the
selection routine. The
current setting will flash.
5.5 Reference Conditions of Influence
Quantities
Influence Quantities are variables that affect measurement

Use MD and
errors to a minor degree. Accuracy is verified under nominal 1 2 3 4
value (within the specified tolerance) of these conditions.
buttons to choose stop bit
(2 or 1) • Ambient temperature 23°C ± 2°C
• Input frequency 50 or 60Hz ±2%
• Input waveform Sinusoidal (distortion
On completion of the entry procedure, press to confirm factor < 0·005)
the setting and press to return to the main set up menu. • Magnetic field of external origin Terrestrial flux
L1 L2 L3 N