3RU11161GB0 Datasheet en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Data sheet 3RU1116-1GB0

Overload relay 4.5...6.3 A For motor protection Size S00, Class 10


Contactor mounting Main circuit: screw terminal Auxiliary circuit: screw
terminal Manual-Automatic-Reset !!! Phased-out product !!! Successor is
SIRIUS 3RU2 Preferred successor type is >>3RU2116-1GB0<<

product brand name SIRIUS


product designation thermal overload relay
General technical data
size of overload relay S00
size of contactor can be combined company-specific S00
power loss [W] for rated value of the current at AC in hot 6.6 W
operating state
● per pole 2.2 W
insulation voltage with degree of pollution 3 at AC rated 690 V
value
surge voltage resistance rated value 6 kV
protection class IP on the front IP20
shock resistance 8g / 10 ms
type of protection DMT 98 ATEX G 001
reference code acc. to IEC 81346-2 F
Substance Prohibitance (Date) 01.07.2006 00:00:00
Ambient conditions
installation altitude at height above sea level maximum 2 000 m
ambient temperature
● during operation -20 ... +70 °C
● during storage -55 ... +80 °C
● during transport -55 ... +80 °C
relative humidity during operation 100 %
Main circuit
number of poles for main current circuit 3
adjustable current response value current of the 4.5 ... 6.3 A
current-dependent overload release
operating voltage at AC-3 rated value maximum 690 V
Auxiliary circuit
number of NC contacts for auxiliary contacts 1
number of NO contacts for auxiliary contacts 1
number of CO contacts for auxiliary contacts 0
operational current of auxiliary contacts at AC-15
● at 24 V 3A
● at 110 V 3A
● at 120 V 3A
● at 125 V 3A

3RU11161GB0 Subject to change without notice


7.1.2021
Page 1/5 © Copyright Siemens
● at 230 V 2A
● at 400 V 1A
operational current of auxiliary contacts at DC-13
● at 24 V 1A
● at 110 V 0.22 A
● at 125 V 0.22 A
● at 220 V 0.11 A
Protective and monitoring functions
trip class CLASS 10
Short-circuit protection
design of the fuse link
● for short-circuit protection of the auxiliary switch fuse gL/gG: 6 A, quick: 10 A
required
Installation/ mounting/ dimensions
mounting position with vertical mounting surface +/-135° rotatable, with vertical mounting
surface +/- 45° tiltable to the front and back
fastening method Contactor mounting
height 87 mm
width 45 mm
depth 78 mm
required spacing
● with side-by-side mounting
— forwards 0 mm
— backwards 0 mm
— upwards 0 mm
— downwards 0 mm
— at the side 0 mm
● for grounded parts
— forwards 0 mm
— backwards 0 mm
— upwards 0 mm
— at the side 6 mm
— downwards 0 mm
● for live parts
— forwards 0 mm
— backwards 0 mm
— upwards 0 mm
— downwards 0 mm
— at the side 6 mm
Connections/ Terminals
product component removable terminal for auxiliary and No
control circuit
type of electrical connection
● for main current circuit screw-type terminals
● for auxiliary and control circuit screw-type terminals
type of connectable conductor cross-sections
● for main contacts
— solid 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm² max.
— finely stranded with core end processing 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG cables for main contacts 2x (20 ... 16), 2x (18 ... 14), 2x 12
type of connectable conductor cross-sections
● for auxiliary contacts
— solid 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
— finely stranded with core end processing 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG cables for auxiliary contacts 2x (20 ... 16), 2x (18 ... 14)
Safety related data
touch protection against electrical shock finger-safe
Certificates/ approvals

3RU11161GB0 Subject to change without notice


7.1.2021
Page 2/5 © Copyright Siemens
General Product Approval For use in hazardous locations

Declaration of Conformity Test Certificates Marine / Shipping

Miscellaneous Special Test Certific- Type Test Certific-


ate ates/Test Report

Marine / Shipping other

Miscellaneous

other Railway

Confirmation Special Test Certific-


ate

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RU1116-1GB0
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RU1116-1GB0
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RU1116-1GB0
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RU1116-1GB0&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RU1116-1GB0/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RU1116-1GB0&objecttype=14&gridview=view1

3RU11161GB0 Subject to change without notice


7.1.2021
Page 3/5 © Copyright Siemens
3RU11161GB0 Subject to change without notice
7.1.2021
Page 4/5 © Copyright Siemens
last modified: 2/11/2021

3RU11161GB0 Subject to change without notice


7.1.2021
Page 5/5 © Copyright Siemens

You might also like